Instrumentation Sucaco Cable
Instrumentation Sucaco Cable
Instrumentation Sucaco Cable
We produce and markets power cable upto 150 kV, optical and
cables and enamelled wires under brand name of “ SUPREME “. The Company
The company has a Quality Assurance Program and ISO 9001 certificate
PE/XLPE insulation PAGE PVC insulation PAGE
CSEV 3 ~ 4 CSVV 25 ~ 26
Single and multi pairs, PE insulation, Single and multi pairs, PVC insulation,
Overall shielded, PVC outer sheath. Overall shielded, PVC outer sheath.
CSCV-TCWB 5 ~ 6 CSVV-TCWB 27 ~ 28
Single and multi pairs, XLPE insulation, Single and multi pairs, PVC insulation,
Overall shielded, Tinned copper wire Overall shielded, Tinned copper wire
braiding, PVC outer sheath. braiding, PVC outer sheath
PSEV 7~8 PSVV 29 ~ 30
Single and multi pairs, PE insulation, Single and multi pairs, PVC insulation,
Individual and Overall shielded, Individual and Overall shielded,
PVC outer sheath. PVC outer sheath.
PSCV-TCWB 9 ~ 10 PSVV-TCWB 31 ~ 32
Single and multi pairs, XLPE insulation, Single and multi pairs, PVC insulation,
Individual and Overall shielded, Individual and Overall shielded,
Tinned copper wire braiding, Tinned copper wire braiding,
PVC outer sheath. PVC outer sheath.
CSEV-SWA 11 ~ 12 MSVV 33 ~ 34
Single and multi pairs, PE insulation, Multi cores, PVC insulation,
Overall shielded, galvanized Overall shielded, PVC outer sheath.
round steel wire armour,
PVC outer sheath. CSVV-SWA 35 ~ 36
Single and multi pairs, PVC insulation,
PSEV-SWA 13 ~ 14 Overall shielded, galvanized
Single and multi pairs, PE insulation, round steel wire armour, PVC outer sheath.
Individual and overall shielded,
galvanized round steel wire armour, PSVV-SWA 37 ~ 38
PVC outer sheath. Single and multi pairs, PVC insulation,
Individual and overall shielded,
CSEV-LS/SWA 15 ~ 16 galvanized round steel wire armour,
Single and multi pairs, PE insulation, PVC outer sheath.
Overall shielded, lead sheath,
galvanized round steel wire armour, MSVV-SWA 39 ~ 40
PVC outer sheath. Multi cores, PVC insulation,
Overall shielded, galvanized round steel
PSEV-LS/SWA 17 ~ 18 wire armour, PVC outer sheath.
Single and multi pairs, PE insulation,
Individual and overall shielded,
lead sheath, galvanized round steel
wire armour, PVC outer sheath.
CSEV ALCA 19 ~ 20
Single and multi pairs, PE insulation,
Overall shielded, aluminium
corrugated armour, PVC outer sheath.
PSEV ALCA 21 ~ 22
Single and multi pairs, PE insulation,
Individual and overall shielded,
aluminium corrugated armour,
PVC outer sheath.
CSEV
300/500 Volt
Single & multi pairs, PE insulated,
Overall shielded, PVC sheathed
BS 5308-1
0.5 ………… 1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in duct, cable
tray or conduit for control, • Conductor : Plain or tinned annealed copper wire.
communication, data Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
(analog/digital) and voice
transmission signals and • Insulation : Polyethylene (PE) type 03 to BS 6234.
service typically in industrial
project, petroleum or oil • Pairs colour code : Black, White with number printing on insulation.
and gas industry.
• Triads colour code : Black, White, Red with number printing on insulation.
• Pairs twisting : All pairs are twisted to counter electromagnetic noise.
3
csev
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Overall Approximately
shielded Standard
No of Nominal Bending
Class cross- No/Dia of Overall delivery radius ,
pairs Insulation Outer sheath Tinned Cable Weight
sectional wire copper drain diameter length min
area wire
- - pcs/mm mm mm Kg/km m mm
1 1 0.5 1/0.8 0.5 0.8 0.5 6.5 40 1,000 55
2 1 0.5 1/0.8 0.5 0.8 0.5 7 56 1,000 60
5 1 0.5 1/0.8 0.5 1.1 0.5 11 123 1,000 90
10 1 0.5 1/0.8 0.5 1.2 0.5 15 213 1,000 120
15 1 0.5 1/0.8 0.5 1.2 0.5 17.5 294 1,000 140
20 1 0.5 1/0.8 0.5 1.3 0.5 19.5 380 500 160
30 1 0.5 1/0.8 0.5 1.3 0.5 23 535 500 185
50 1 0.5 1/0.8 0.5 1.5 0.5 29 860 500 235
1 1 1.0 1/1.13 0.6 0.8 0.5 7.5 55 1,000 60
2 1 1.0 1/1.13 0.6 0.8 0.5 8.5 84 1,000 70
5 1 1.0 1/1.13 0.6 1.2 0.5 14 199 1,000 115
10 1 1.0 1/1.13 0.6 1.2 0.5 18 346 1,000 145
15 1 1.0 1/1.13 0.6 1.3 0.5 21.5 497 1,000 175
20 1 1.0 1/1.13 0.6 1.5 0.5 24.5 658 500 200
30 1 1.0 1/1.13 0.6 1.5 0.5 29 937 500 235
50 1 1.0 1/1.13 0.6 2.0 0.5 37.5 1,561 500 300
1 2 1.5 7/0.53 0.6 0.8 0.5 8.5 71 1,000 70
2 2 1.5 7/0.53 0.6 0.9 0.5 10 116 1,000 80
5 2 1.5 7/0.53 0.6 1.2 0.5 16 268 1,000 130
10 2 1.5 7/0.53 0.6 1.3 0.5 21 486 1,000 170
15 2 1.5 7/0.53 0.6 1.5 0.5 25.5 712 1,000 205
20 2 1.5 7/0.53 0.6 1.5 0.5 28.5 916 500 230
30 2 1.5 7/0.53 0.6 1.7 0.5 34.5 1,346 500 280
50 2 1.5 7/0.53 0.6 2.0 0.5 44 2,195 500 355
1 5 0.5 16/0.2 0.6 0.8 0.5 7 44 1,000 60
2 5 0.5 16/0.2 0.6 0.8 0.5 8 63 1,000 65
5 5 0.5 16/0.2 0.6 1.1 0.5 13 140 1,000 105
10 5 0.5 16/0.2 0.6 1.2 0.5 17 242 1,000 140
15 5 0.5 16/0.2 0.6 1.2 0.5 20 342 1,000 160
20 5 0.5 16/0.2 0.6 1.3 0.5 22.5 433 500 180
30 5 0.5 16/0.2 0.6 1.5 0.5 27 631 500 220
50 5 0.5 16/0.2 0.6 1.7 0.5 34 1,007 500 275
ELECTRICAL DATA
Resistance at 20 oC
4
CSCV-TCWB
300 Volt
Single & multi pairs, XLPE insulated, Overall shielded,
Tinned copper wire braiding, PVC sheathed
BS EN 50288-7
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in direct • Conductor : Plain or tinned annealed copper wire.
burried for control, Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
communication, data
(analog/digital) and voice • Insulation : XLPE to BS 7655.
transmission signals and
service typically in industrial • Pairs colour code : Black, White with number printing on insulation.
project, petroleum or oil
and gas industry. • Triads colour code : Black, White, Red with number printing on insulation.
• Pairs twisting : All pairs are twisted to counter electromagnetic noise.
5
cscv-tcwb
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor, max Insulation min
Cable Max. L/R
Class
size ratio
Plain Annealed Between any
Between
annealed tinned core or Mutual Core to core Core to shield
conductors
copper wire copper wire shield
- pF/m Volt / 1 minute
5 0.5 39 40.1 1,000 400 250 25 1,000
5 0.75 26 26.7 1,000 400 250 25 1,000
2 1.5 12.1 12.2 1,000 400 250 40 1,000
6
PSEV
300/500 Volt
Single & multi pairs, PE insulated, Individual and
overall shielded, PVC sheathed
BS 5308 - 1
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in duct, • Conductor : Plain or tinned annealed copper wire .
cable tray or conduit for Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
control, communication,
data (analog/digital) and • Insulation : Polyethylene (PE) type 03 to BS 6234.
voice transmission signals
and service typically in • Pairs colour code : Black, White with number printing on insulation.
industrial project,
petroleum or oil and gas • Triads colour code : Black, White, Red with number printing on insulation.
industry.
• Pairs twisting : All pairs are twisted to counter electromagnetic noise.
• Individual shielding : Each pair is shielded with strand tinned annealed copper
wire and aluminium foil tape to give a maximum
protection against electrostatic noise and crosstalk
OPTIONAL : interference.
Other construction such as • Overall shielding : All pairs shields are isolated from each other. Individually
FIRE RESISTANT shielded pairs are assembled with non-hygroscopic fillers
INSTRUMENTATION CABLE (if necessary) and entire assembly is covered by polyester
with low smoke zero tape and shielded with strand tinned annealed copper
halogen (LSOH) features wire and aluminium foil tape.
and other types are
available upon request. • Outer sheath : Extruded Polyvinyl Chloride (PVC) , TM1 type to BS 6746,
Black colour.
• Cable marking : SUPREME CABLE PSEV “ SIZE “ 300/500 V
INSTRUMENTATION CABLE with interval length marking
every 1 (one) meter.
7
psev
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Ind. and Approximately
overall
Nominal shielded Standard
No of Bending
Class cross- No/Dia of Overall delivery
pairs Insulation Outer sheath Tinned Cable Weight radius ,
sectional wire diameter length min
copper drain
area wire
- - pcs/mm mm mm Kg/km m mm
2 5 0.5 1/0.8 0.5 0.9 0.5 12 100 1,000 100
5 5 0.5 1/0.8 0.5 1.2 0.5 14 187 1,000 115
10 5 0.5 1/0.8 0.5 1.2 0.5 23 349 1,000 185
15 5 0.5 1/0.8 0.5 1.3 0.5 26.5 490 1,000 215
20 5 0.5 1/0.8 0.5 1.3 0.5 29 619 500 235
30 5 0.5 1/0.8 0.5 1.5 0.5 35 902 500 280
50 5 0.5 1/0.8 0.5 2.0 0.5 45.5 1,507 500 365
2 1 1.0 1/1.13 0.6 1.1 0.5 15 146 1,000 120
5 1 1.0 1/1.13 0.6 1.2 0.5 16.5 263 1,000 135
10 1 1.0 1/1.13 0.6 1.3 0.5 27 511 1,000 220
15 1 1.0 1/1.13 0.6 1.5 0.5 31.5 737 1,000 255
20 1 1.0 1/1.13 0.6 1.7 0.5 25.5 965 500 205
30 1 1.0 1/1.13 0.6 2.0 0.5 42.5 1,417 500 340
50 1 1.0 1/1.13 0.6 2.2 0.5 55 2,265 500 440
2 2 1.5 7/0.53 0.6 0.8 0.5 17 188 1,000 140
5 2 1.5 7/0.53 0.6 0.9 0.5 18.5 345 1,000 150
10 2 1.5 7/0.53 0.6 1.2 0.5 31.5 686 1,000 255
15 2 1.5 7/0.53 0.6 1.3 0.5 36.5 986 500 295
20 2 1.5 7/0.53 0.6 1.5 0.5 40.5 1,254 500 325
30 2 1.5 7/0.53 0.6 1.5 0.5 48.5 1,848 500 390
50 2 1.5 7/0.53 0.6 1.7 0.5 62.5 2,969 500 500
2 5 0.5 16/0.2 0.6 1.1 0.5 14.5 122 1,000 120
5 5 0.5 16/0.2 0.6 1.2 0.5 15.5 208 1,000 125
10 5 0.5 16/0.2 0.6 1.3 0.5 25.5 400 1,000 205
15 5 0.5 16/0.2 0.6 1.5 0.5 30 572 1,000 240
20 5 0.5 16/0.2 0.6 1.5 0.5 33.5 718 500 270
30 5 0.5 16/0.2 0.6 1.7 0.5 39.5 1,040 500 320
50 5 0.5 16/0.2 0.6 2.2 0.5 51.5 1,725 500 415
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation , min
Max. L/R
Class Cable size
ratio
Plain Annealed
Between Between Core to
annealed tinned Unbalance Mutual Core to core shield
conductors shields
copper wire copper wire
- pF/250 m pF/m Volt / 1 minute
1 0.5 36 36.7 5 1 250 115 25 1,000
1 1.0 18.1 18.2 5 1 250 115 25 1,000
2 1.5 12.1 12.2 5 1 250 115 40 1,000
5 0.5 39 40.1 5 1 250 115 25 1,000
8
PSCV-TCWB
300 Volt
Single & multi pairs, XLPE insulated,
Individual and overall shielded,
Tinned copper wire braiding,
PVC sheathed
BS EN 50288-7
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in direct • Conductor : Plain or tinned annealed copper wire .
burried for control, Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
communication, data
(analog/digital) and voice • Insulation : XLPE to BS 7655.
transmission signals and • Pairs colour code : Black, White with number printing on insulation.
service typically in • Triads colour code : Black, White, Red with number printing on insulation.
industrial project,
petroleum or oil and gas • Pairs twisting : All pairs are twisted to counter electromagnetic noise.
industry. • Individual shielding : Each pair is shielded with strand tinned annealed copper
wire and aluminium foil tape to give a maximum
protection against electrostatic noise and crosstalk
interference.
• Overall shielding : All pairs shields are isolated from each other. Individually
OPTIONAL : shielded pairs are assembled with non-hygroscopic fillers
(if necessary) and entire assembly is covered by polyester
Other construction such as tape and shielded with strand tinned annealed copper
FIRE RESISTANT wire and aluminium foil tape.
INSTRUMENTATION CABLE
with low smoke zero • Inner sheath : Extruded Polyvinyl Chloride (PVC) , Black colour.
halogen (LSOH) features • Braid shielding : Tinned annealed copper wire to protect against
and other types are electromagnetic noise.
available upon request.
• Outer sheath : Extruded Polyvinyl Chloride (PVC) , TM1 type to BS 6746 ,
Black colour.
• Cable marking : SUPREME CABLE PSCV-TCWB “ SIZE “ 300 V
INSTRUMENTATION CABLE with interval length marking
every 1 (one) meter.
9
pscv - tcwb
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Ind. and Approximately
overall Diameter of
shielded tinned Standard
No of Nominal Bending
Class delivery
pairs cross- No/Dia of copper wire Overall radius,
Insulation Outer sheath Tinned Cable Weight length min
sectional wire braiding diameter
copper
area
drain wire
- - 2
pcs/mm mm mm2 mm mm Kg/km m mm
2 2 0.5 7/0.30 0.4 1.1 0.5 9.7 11.9 190 500 95
5 2 0.5 7/0.30 0.4 1.2 0.5 12 14.4 288 500 115
2 2 0.75 7/0.37 0.4 1.1 0.5 10.4 12.6 212 500 100
2 2 1.5 7/0.53 0.5 1.2 0.5 12.9 15.3 292 500 125
ELECTRICAL DATA
Resistance at 20 ¼C
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation , min Max.
Cable
Class L/R
size
Plain Annealed Between any ratio
Between Between
annealed tinned core or Mutual Core to core Core to shield
conductors shields
copper wire copper wire shield
- pF/m Volt / 1 minute
5 0.5 39 40.1 1,000 1 400 250 25 1,000
5 0.75 26 26.7 1,000 1 400 250 25 1,000
2 1.5 12.1 12.2 1,000 1 400 250 40 1,000
10
CSEV-SWA
300/500 Volt
Single & multi pairs, PE insulated,
Overall shielded, Armoured, PVC sheathed
BS 5308 - 1
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in direct • Conductor : Plain or tinned annealed copper wire .
burried for control, Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
communication, data
(analog/digital) and voice • Insulation : Polyethylene (PE) type 03 to BS 6234.
transmission signals and
service typically in industrial • Pairs colour code : Black, White with number printing on insulation.
project, petroleum or oil
and gas industry. • Triads colour code : Black, White, Red with number printing on insulation.
• Pairs twisting : All pairs are twisted to counter electromagnetic noise.
11
csev - swa
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Overall Approximately
Nominal shielded
No of Dia of Standard Bending
Class
pairs cross- No/Dia of
Insulation
Outer Tinned armour wire Overall Cable Weight delivery radius,
sectional wire sheath diameter min
copper drain length
area wire
- - pcs/mm mm mm mm Kg/km m mm
1 1 0.5 1/0.8 0.5 1.3 0.5 0.9 11 219 1,000 110
2 1 0.5 1/0.8 0.5 1.3 0.5 0.9 11.5 254 1,000 115
5 1 0.5 1/0.8 0.5 1.4 0.5 0.9 16 422 1,000 160
10 1 0.5 1/0.8 0.5 1.6 0.5 1.25 20.5 747 1,000 205
15 1 0.5 1/0.8 0.5 1.6 0.5 1.25 23 905 1,000 230
20 1 0.5 1/0.8 0.5 1.7 0.5 1.6 26 1,234 500 260
30 1 0.5 1/0.8 0.5 1.8 0.5 1.6 30 1,543 500 300
50 1 0.5 1/0.8 0.5 2.0 0.5 1.6 36.5 2,146 500 365
1 1 1.0 1/1.13 0.6 1.3 0.5 0.9 12.5 277 1,000 125
2 1 1.0 1/1.13 0.6 1.4 0.5 0.9 13.5 346 1,000 135
5 1 1.0 1/1.13 0.6 1.5 0.5 1.25 20 752 1,000 200
10 1 1.0 1/1.13 0.6 1.7 0.5 1.25 25 1,118 1,000 250
15 1 1.0 1/1.13 0.6 1.8 0.5 1.6 30 1,629 1,000 300
20 1 1.0 1/1.13 0.6 1.8 0.5 1.6 33 1,972 500 330
30 1 1.0 1/1.13 0.6 2.0 0.5 1.6 38.5 2,555 500 385
50 1 1.0 1/1.13 0.6 2.2 0.5 2 48.5 4,108 500 485
1 2 1.5 7/0.53 0.6 1.4 0.5 0.9 13 302 1,000 130
2 2 1.5 7/0.53 0.6 1.4 0.5 0.9 14.5 381 1,000 145
5 2 1.5 7/0.53 0.6 1.6 0.5 1.25 21.5 814 1,000 215
10 2 1.5 7/0.53 0.6 1.8 0.5 1.6 28 1,413 1,000 280
15 2 1.5 7/0.53 0.6 1.9 0.5 1.6 32.5 1,835 1,000 325
20 2 1.5 7/0.53 0.6 2.0 0.5 2 36.5 2,445 500 365
30 2 1.5 7/0.53 0.6 2.1 0.5 2 42.5 3,177 500 425
50 2 1.5 7/0.53 0.6 2.4 0.5 2.5 53.5 5,045 500 535
1 5 0.5 16/0.2 0.6 1.3 0.5 0.9 11.5 237 1,000 115
2 5 0.5 16/0.2 0.6 1.3 0.5 0.9 12.5 281 1,000 125
5 5 0.5 16/0.2 0.6 1.5 0.5 0.9 17.5 481 1,000 175
10 5 0.5 16/0.2 0.6 1.6 0.5 1.25 22.5 841 1,000 225
15 5 0.5 16/0.2 0.6 1.7 0.5 1.6 26.5 1,215 1,000 265
20 5 0.5 16/0.2 0.6 1.8 0.5 1.6 29.5 1,420 500 295
30 5 0.5 16/0.2 0.6 1.9 0.5 1.6 34 1,818 500 340
50 5 0.5 16/0.2 0.6 2.1 0.5 2 42.5 2,834 500 425
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation min Max.
Class Cable L/R
size ratio
Plain Annealed
Between Core to
annealed tinned Unbalance Mutual Core to core
conductors shield
copper wire copper wire
- pF/250 m pF/m Volt / 1 minute
1 0.5 36 36.7 5 250 115 25 1,000
1 1.0 18.1 18.2 5 250 115 25 1,000
2 1.5 12.1 12.2 5 250 115 40 1,000
5 0.5 39 40.1 5 250 115 25 1,000
12
PSEV-SWA
300/500 Volt
Single & multi pairs, PE insulated, Individual and
overall shielded, Armoured, PVC sheathed
BS 5308 - 1
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in direct • Conductor : Plain or tinned annealed copper wire .
burried for control, Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
communication, data
(analog/digital) and voice • Insulation : Polyethylene (PE) type 03 to BS 6234.
transmission signals and • Pairs colour code : Black, White with number printing on insulation.
service typically in industrial • Triads colour code : Black, White, Red with number printing on insulation.
project, petroleum or oil
and gas industry. • Pairs twisting : All pairs are twisted to counter electromagnetic noise.
• Individual shielding : Each pair is shielded with strand tinned annealed copper
wire and aluminium foil tape to give a maximum
protection against electrostatic noise and crosstalk
interference.
OPTIONAL :
• Overall shielding : All pairs shields are isolated from each other. Individually
Other construction such as shielded pairs are assembled with non- hygroscopic fillers
FIRE RESISTANT (if necessary) and entire assembly is covered by polyester
INSTRUMENTATIO CABLE tape and shielded with strand tinned annealed copper
with low smoke zero wire and aluminium foil tape.
halogen (LSOH) features
and other types are • Inner sheath : Extruded Polyvinyl Chloride (PVC) , Black colour.
available upon request. • Armouring : Galvanized round steel wire.
• Outer sheath : Extruded Polyvinyl Chloride (PVC) , TM1 type to BS 6746,
Blue colour.
• Cable marking : SUPREME CABLE PSEV-SWA “ SIZE “ 300/500 V
INSTRUMENTATION CABLE with interval length marking
every 1 (one) meter.
• Operating temperature maximum 70 ̊C
13
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Ind. and Approximately
overall
shielded Standard Bending
No of Dia of
Class Nominal delivery radius,
pairs cross- No/Dia of armour wire Overall min
Insulation Outer sheath Tinned Cable Weight length
sectional wire diameter
area copper drain
wire
- - pcs/mm mm mm mm Kg/km m mm
2 5 0.5 16/0.2 0.6 1.7 0.5 0.9 20.5 526 1,000 205
5 5 0.5 16/0.2 0.6 1.7 0.5 1.25 24.5 905 1,000 245
10 5 0.5 16/0.2 0.6 1.8 0.5 1.6 34.5 1,545 1,000 345
15 5 0.5 16/0.2 0.6 1.8 0.5 1.6 38.5 1,909 500 385
20 5 0.5 16/0.2 0.6 1.9 0.5 1.6 42.5 2,221 500 425
30 5 0.5 16/0.2 0.6 2.1 0.5 2 50.5 3,198 500 505
50 5 0.5 16/0.2 0.6 2.4 0.5 2.5 64.5 5,194 300 645
2 5 0.75 24/0.2 0.6 1.5 0.5 0.9 21.5 575 1,000 215
5 5 0.75 24/0.2 0.6 1.6 0.5 1.25 29 977 1,000 290
10 5 0.75 24/0.2 0.6 1.8 0.5 1.6 38.5 1,711 1,000 385
15 5 0.75 24/0.2 0.6 1.9 0.5 1.6 38.5 1,909 500 385
20 5 0.75 24/0.2 0.6 2 0.5 2 46.5 2,853 500 465
30 5 0.75 24/0.2 0.6 2.2 0.5 2 54.5 3,720 500 545
50 5 0.75 24/0.2 0.6 2.5 0.5 2.5 59 5,865 300 590
2 2 1.5 7/0.53 0.6 1.6 0.5 1.25 23 812 1,000 230
5 2 1.5 7/0.53 0.6 1.7 0.5 1.6 30 1,334 1,000 300
10 2 1.5 7/0.53 0.6 1.9 0.5 1.6 40 2,092 500 400
15 2 1.5 7/0.53 0.6 2 0.5 2 46.5 2,948 500 465
20 2 1.5 7/0.53 0.6 2.1 0.5 2 51 3,462 500 510
30 2 1.5 7/0.53 0.6 2.4 0.5 2.5 61 5,108 500 610
50 2 1.5 7/0.53 0.6 2.7 0.5 2.5 76 7,225 300 760
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation , min Max.
Cable
Class L/R
size
Plain Annealed Between any ratio
Between Between
annealed tinned core or Mutual Core to core Core to shield
conductors shields
copper wire copper wire shield
- pF/m Volt / 1 minute
5 0.5 39 40.1 25 1 7 250 25 1,000
5 0.75 26 26.7 25 1 7 250 25 1,000
2 1.5 12.1 12.2 25 1 7 250 40 1,000
14
CSEV-LS/SWA
300/500 Volt
CSEV-LS/SWA 300/500 Volt
Single & multi pairs, PE insulated,
Overall shielded, Lead sheathed, Armoured,
PVC sheathed
BS 5308 - 1
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in direct • Conductor : Plain or tinned annealed copper wire.
burried for control, Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
communication, data
(analog/digital) and voice • Insulation : Polyethylene (PE) type 03 to BS 6234.
transmission signals and • Pairs colour code : Black, White with number printing on insulation.
service typically in
industrial project, • Triads colour code : Black, White, Red with number printing on insulation.
petroleum or oil and gas • Pairs twisting : All pairs are twisted to counter electromagnetic noise.
industry chemical plant
and in area in which • Overall shielding : Twisted pairs are assembled with non-hygroscopic fillers
ground water contains (if necessary) and entire assembly is covered by polyester
waste oils or sulfides. tape and shielded with strand tinned annealed copper
wire and aluminium foil tape.
15
csev - LS/swa
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Approximately
Overall
shielded
No of Nominal Dia of Standard Bending
Class cross- No/Dia of
pairs Insulation Lead sheath Outer sheath Tinned armour wire Overall Cable delivery radius,
sectional wire diameter Weight length min
area copper drain
wire
- - pcs/mm mm mm mm Kg/km m mm
1 1 0.5 1/0.8 0.5 1.1 1.4 0.5 0.9 15 634 1,000 150
2 1 0.5 1/0.8 0.5 1.1 1.4 0.5 0.9 15.5 702 1,000 155
5 1 0.5 1/0.8 0.5 1.1 1.6 0.5 1.25 21 1,184 1,000 210
10 1 0.5 1/0.8 0.5 1.1 1.7 0.5 1.6 25.5 1,738 1,000 255
15 1 0.5 1/0.8 0.5 1.2 1.8 0.5 1.6 28.5 2,113 1,000 285
20 1 0.5 1/0.8 0.5 1.3 1.8 0.5 1.6 31 2,489 500 310
30 1 0.5 1/0.8 0.5 1.4 1.9 0.5 1.6 35 3,092 500 350
50 1 0.5 1/0.8 0.5 1.5 2.1 0.5 2 42.5 4,491 500 425
1 1 1.0 1/1.13 0.6 1.1 1.4 0.5 0.9 16.5 756 1,000 165
2 1 1.0 1/1.13 0.6 1.1 1.5 0.5 0.9 17.5 871 1,000 175
5 1 1.0 1/1.13 0.6 1.1 1.7 0.5 1.6 25.5 1,745 1,000 255
10 1 1.0 1/1.13 0.6 1.2 1.8 0.5 1.6 30.5 2,426 1,000 305
15 1 1.0 1/1.13 0.6 1.3 1.9 0.5 1.6 34.5 3,082 1,000 345
20 1 1.0 1/1.13 0.6 1.4 2.0 0.5 2 39.5 4,015 500 395
30 1 1.0 1/1.13 0.6 1.5 2.1 0.5 2 45 5,086 500 450
50 1 1.0 1/1.13 0.6 1.8 2.4 0.5 2.5 56.5 7,928 500 565
1 2 1.5 7/0.53 0.6 1.1 1.5 0.5 0.9 17 804 1,000 170
2 2 1.5 7/0.53 0.6 1.1 1.5 0.5 1.25 19 1,054 1,000 190
5 2 1.5 7/0.53 0.6 1.2 1.7 0.5 1.6 27 1,942 1,000 270
10 2 1.5 7/0.53 0.6 1.3 1.9 0.5 1.6 32.5 2,748 1,000 325
15 2 1.5 7/0.53 0.6 1.4 2.0 0.5 2 38.5 3,814 500 385
20 2 1.5 7/0.53 0.6 1.5 2.1 0.5 2 42.5 4,488 500 425
30 2 1.5 7/0.53 0.6 1.7 2.3 0.5 2.5 50.5 6,401 500 505
50 2 1.5 7/0.53 0.6 2.0 2.6 0.5 2.5 61 9,130 300 610
1 5 0.5 16/0.2 0.6 1.1 1.4 0.5 0.9 15.5 687 1,000 155
2 5 0.5 16/0.2 0.6 1.1 1.4 0.5 0.9 16.5 764 1,000 165
5 5 0.5 16/0.2 0.6 1.1 1.6 0.5 1.25 22.5 1,304 1,000 225
10 5 0.5 16/0.2 0.6 1.2 1.8 0.5 1.6 28 2,040 1,000 280
15 5 0.5 16/0.2 0.6 1.3 1.8 0.5 1.6 31.5 2,495 1,000 315
20 5 0.5 16/0.2 0.6 1.3 1.9 0.5 1.6 34 2,829 500 340
30 5 0.5 16/0.2 0.6 1.5 2.1 0.5 2 41 4,051 500 410
50 5 0.5 16/0.2 0.6 1.7 2.3 0.5 2.5 50 6,039 500 500
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation min
Max. L/R
Class Cable size
ratio
Plain Annealed
Between
annealed tinned Unbalance Mutual Core to core Core to shield
conductors
copper wire copper wire
- pF/250 m pF/m Volt / 1 minute
1 0.5 36 36.7 5 250 115 25 1,000
1 1.0 18.1 18.2 5 250 115 25 1,000
2 1.5 12.1 12.2 5 250 115 40 1,000
5 0.5 39 40.1 5 250 115 25 1,000
16
PSEV-LS/SWA
300/500 Volt
Single & multi pairs, PE insulated,
Individual and overall shielded,
Lead sheathed, Armoured, PVC sheathed
BS 5308 - 1
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in direct • Conductor : Plain or tinned annealed copper wire .
burried for control, Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
communication, data
(analog/digital) and voice • Insulation : Polyethylene (PE) type 03 to BS 6234.
transmission signals and • Pairs colour code : Black, White with number printing on insulation.
service typically in • Triads colour code : Black, White, Red with number printing on insulation.
industrial project, • Pairs twisting : All pairs are twisted to counter electromagnetic noise.
petroleum or oil and gas
industry, chemical plant • Individual shielding : Each pair is shielded with strand tinned annealed copper
and in area in which wire and aluminium foil tape to give a maximum
ground water contains protection against electrostatic noise and crosstalk
waste oils or sulfides. interference.
• Overall shielding : All pairs shields are isolated from each other. Individually
shielded pairs are assembled with non-hygroscopic fillers
(if necessary) and entire assembly is covered by polyester
OPTIONAL : tape and shielded with strend tinned annealed copper
wire and aluminium foil tape.
Other construction such as
FIRE RESISTANT • Bedding/filler : Extruded Polyvinyl Chloride (PVC) filler.
INSTRUMENTATION CABLE • Lead sheath : Lead alloy “E” grade.
with low smoke zero • Inner sheath : Extruded Polyvinyl Chloride (PVC) , Black colour.
halogen (LSOH) features • Armouring : Galvanized round steel wire.
and other types are • Outer sheath : Extruded Polyvinyl Chloride (PVC) , TM1 type to BS 6746,
available upon request. Black colour.
• Cable marking : SUPREME CABLE PSEV-LS/SWA “ SIZE “ 300/500 V
INSTRUMENTATION CABLE with interval length marking
every 1 (one) meter.
17
psev LS swa
DIMENSIONAL & MECHANICAL DATA
- - pcs/mm mm mm mm Kg/km m
2 1 0.5 1/0.8 0.5 1.1 1.5 0.5 1.25 22 1,245 1,000 220
5 1 0.5 1/0.8 0.5 1.1 1.6 0.5 1.25 23.5 1,437 1,000 235
10 1 0.5 1/0.8 0.5 1.2 1.7 0.5 1.6 34 2,609 1,000 340
15 1 0.5 1/0.8 0.5 1.3 1.9 0.5 1.6 38 3,208 500 380
20 1 0.5 1/0.8 0.5 1.4 1.9 0.5 2 42 4,082 500 420
30 1 0.5 1/0.8 0.5 1.5 2.0 0.5 2 48.5 5,089 500 485
50 1 0.5 1/0.8 0.5 1.8 2.3 0.5 2.5 61.5 8,073 300 615
2 1 1.0 1/1.13 0.6 1.1 1.6 0.5 1.25 25.5 1,564 1,000 255
5 1 1.0 1/1.13 0.6 1.2 1.7 0.5 1.6 28 2,085 1,000 280
10 1 1.0 1/1.13 0.6 1.3 1.9 0.5 1.6 40.5 3,531 500 405
15 1 1.0 1/1.13 0.6 1.5 2.1 0.5 2 47 4,940 500 470
20 1 1.0 1/1.13 0.6 1.6 2.2 0.5 2 52 5,840 500 520
30 1 1.0 1/1.13 0.6 1.7 2.4 0.5 2.5 61.5 8,085 300 615
50 12 1.0 1/1.13 0.6 2.0 2.7 0.5 2.5 76 11,589 250 760
2 2 1.5 7/0.53 0.6 1.1 1.7 0.5 1.6 28 1,896 1,000 280
5 2 1.5 7/0.53 0.6 1.2 1.8 0.5 1.6 29.5 2,253 1,000 295
10 2 1.5 7/0.53 0.6 1.5 2.1 0.5 2 45 4,523 500 450
15 2 1.5 7/0.53 0.6 1.6 2.2 0.5 2 50.5 5,636 500 505
20 2 1.5 7/0.53 0.6 1.7 2.3 0.5 2.5 56.5 7,029 500 565
30 2 1.5 7/0.53 0.6 1.9 2.5 0.5 2.5 65 9,067 300 650
50 2 1.5 7/0.53 0.6 2.2 2.9 0.5 2.5 81 13,032 250 810
2 5 0.5 16/0.2 0.6 1.1 1.6 0.5 1.25 24 1,403 1,000 240
5 5 0.5 16/0.2 0.6 1.1 1.7 0.5 1.6 26.5 1,763 1,000 265
10 5 0.5 16/0.2 0.6 1.3 1.9 0.5 1.6 37.5 3,049 500 375
15 5 0.5 16/0.2 0.6 1.4 2.0 0.5 2 43 4,103 500 430
20 5 0.5 16/0.2 0.6 1.5 2.1 0.5 2 47 4,761 500 470
30 5 0.5 16/0.2 0.6 1.6 2.2 0.5 2 53.5 5,947 500 535
50 5 0.5 16/0.2 0.6 1.9 2.6 0.5 2.5 68.5 9,382 300 685
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation , min
Cable Max. L/R
Class
size ratio
Plain Annealed
Between Between
annealed tinned Unbalance Mutual Core to core Core to shield
conductors shields
copper wire copper wire
- pF/250 m pF/m Volt / 1 minute
1 0.5 36 36.7 5 1 250 115 25 1,000
1 1.0 18.1 18.2 5 1 250 115 25 1,000
2 1.5 12.1 12.2 5 1 250 115 40 1,000
5 0.5 39 40.1 5 1 250 115 25 1,000
18
CSEV ALCA
300/500 Volt
Single & multi pairs,
PE insulated, Overall shielded,
Corrugated armoured, PVC sheathed
BS 5308 - 1
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in direct • Conductor : Plain or tinned annealed copper wire .
burried for control, Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
communication, data
(analog/digital) and voice • Insulation : Polyethylene (PE) type 03 to BS 6234.
transmission signals and
service typically in • Pairs colour code : Black, White with number printing on insulation.
industrial project,
petroleum or oil and gas • Triads colour code : Black, White, Red with number printing on insulation.
industry.
• Pairs twisting : All pairs are twisted to counter electromagnetic noise.
19
csev alca
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Approximately
Overall
shielded
Nominal Standard Bending
No of Dia of
Class cross- No/Dia of delivery radius,
pairs Insulation Outer sheath corrugated Overall Cable
min
sectional wire Tinned armour diameter Weight length
area copper drain
wire
- - pcs/mm mm mm mm Kg/km m mm
1 1 0.5 1/0.8 0.5 1.3 0.5 21 24 495 500 240
2 1 0.5 1/0.8 0.5 1.3 0.5 21 24 501 500 240
5 1 0.5 1/0.8 0.5 1.4 0.5 21 24 501 500 240
10 1 0.5 1/0.8 0.5 1.6 0.5 22 25.5 599 500 255
15 1 0.5 1/0.8 0.5 1.6 0.5 25 28.5 725 500 285
20 1 0.5 1/0.8 0.5 1.7 0.5 27 30.5 853 500 305
30 1 0.5 1/0.8 0.5 1.8 0.5 31 35 1,012 500 350
50 1 0.5 1/0.8 0.5. 2.0 0.5 37 41.5 1,428 500 415
1 1 1.0 1/1.13 0.6 1.3 0.5 21 24 499 500 240
2 1 1.0 1/1.13 0.6 1.4 0.5 21 24 528 500 240
5 1 1.0 1/1.13 0.6 1.5 0.5 22 25 599 500 250
10 1 1.0 1/1.13 0.6 1.7 0.5 27 30.5 903 500 305
15 1 1.0 1/1.13 0.6 1.8 0.5 31 35 1,099 500 350
20 1 1.0 1/1.13 0.6 1.8 0.5 34 38 1,429 500 380
30 1 1.0 1/1.13 0.6 2.0 0.5 39 43 1,907 500 430
50 1 1.0 1/1.13 0.6 2.2 0.5 48 52.5 2,696 500 525
1 2 1.5 7/0.53 0.6 1.4 0.5 21 24 506 500 240
2 2 1.5 7/0.53 0.6 1.4 0.5 21 24 526 500 240
5 2 1.5 7/0.53 0.6 1.6 0.5 24 27.5 661 500 275
10 2 1.5 7/0.53 0.6 1.8 0.5 29 33 1,002 500 330
15 2 1.5 7/0.53 0.6 1.9 0.5 33 37 1,315 500 370
20 2 1.5 7/0.53 0.6 2.0 0.5 36 40.5 1,588 500 405
30 2 1.5 7/0.53 0.6 2.1 0.5 42 46.5 2,143 500 465
50 2 1.5 7/0.53 0.6 2.4 0.5 52 57 3,242 500 570
1 5 0.5 16/0.2 0.6 1.3 0.5 21 24 490 500 240
2 5 0.5 16/0.2 0.6 1.3 0.5 21 24 495 500 240
5 5 0.5 16/0.2 0.6 1.5 0.5 21 24 495 500 240
10 5 0.5 16/0.2 0.6 1.6 0.5 25 28.5 674 500 285
15 5 0.5 16/0.2 0.6 1.7 0.5 28 31.5 835 500 315
20 5 0.5 16/0.2 0.6 1.8 0.5 30 34 969 500 340
30 5 0.5 16/0.2 0.6 1.9 0.5 35 39 1,263 500 390
50 5 0.5 16/0.2 0.6 2.1 0.5 42 46.5 1,804 500 465
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor, max Insulation min
Max. L/R
Class Cable size
ratio
Plain Annealed
Between
annealed tinned Unbalance Mutual Core to core Core to shield
conductors
copper wire copper wire
- pF/250 m pF/m Volt / 1 minute
1 0.5 36 36.7 5 250 115 25 1,000
1 1.0 18.1 18.2 5 250 115 25 1,000
2 1.5 12.1 12.2 5 250 115 40 1,000
5 0.5 39 40.1 5 250 115 25 1,000
17
20
PSEV ALCA
300/500 Volt
Single & multi pairs, PE insulated,
Individual and overall shielded,
Corrugated armoured,
PVC sheathed
BS 5308 - 1
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in direct • Conductor : Plain or tinned annealed copper wire.
burried for control, Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
communication, data
(analog/digital) and voice • Insulation : Polyethylene (PE) type 03 to BS 6234.
transmission signals and • Pairs colour code : Black, White with number printing on insulation.
service typically in industrial • Triads colour code : Black, White, Red with number printing on insulation.
project, petroleum or oil • Pairs twisting : All pairs are twisted to counter electromagnetic noise.
and gas industry.
• Individual shielding : Each pair is shielded with strand tinned annealed copper
wire and aluminium foil tape to give a maximum
protection against electrostatic noise and crosstalk
interference.
• Overall shielding : All pairs shields are isolated from each other. Individually
OPTIONAL : shielded pairs are assembled with non-hygroscopic fillers
(if necessary) and entire assembly is covered by polyester
Other construction such as tape and shielded with strand tinned annealed copper
FIRE RESISTANT wire and aluminium foil tape.
INSTRUMENTATION CABLE • Inner sheath : Extruded Polyvinyl Chloride (PVC) , Black colour.
with low smoke zero • Armouring : Corrugated aluminium tape.
halogen (LSOH) features
and other types are • Outer sheath : Extruded Polyvinyl Chloride (PVC) , TM1 type to BS 6746,
available upon the Orange colour.
customer request.
• Cable marking : SUPREME CABLE PSEV ALCA “ SIZE “ 300/500 V
INSTRUMENTATION CABLE with interval length marking
every 1 (one) meter.
21
psev alca
DIMENSIONAL & MECHANICAL DATA
- - pcs/mm mm mm mm Kg/km m mm
2 1 0.5 1/0.8 0.5 1.4 0.5 20 23 422 500 230
5 1 0.5 1/0.8 0.5 1.5 0.5 21 24.5 526 500 245
10 1 0.5 1/0.8 0.5 1.7 0.5 30 34 843 500 340
15 1 0.5 1/0.8 0.5 1.7 0.5 34 38 1,048 500 380
20 1 0.5 1/0.8 0.5 1.8 0.5 37 41 1,227 500 410
30 1 0.5 1/0.8 0.5 1.9 0.5 42.5 46.5 1,619 500 465
50 1 0.5 1/0.8 0.5 2.2 0.5 53 58 2,463 500 580
2 1 1.0 1/1.13 0.6 1.5 0.5 23 26.5 521 500 265
5 1 1.0 1/1.13 0.6 1.6 0.5 24 27.5 656 500 275
10 1 1.0 1/1.13 0.6 1.8 0.5 35 39 1,093 500 390
15 1 1.0 1/1.13 0.6 1.9 0.5 39 43 1,402 500 430
20 1 1.0 1/1.13 0.6 2.0 0.5 43 47.5 1,706 500 475
30 1 1.0 1/1.13 0.6 2.2 0.5 50 55 2,322 500 550
50 1 1.0 1/1.13 0.6 2.5 0.5 62.5 68 3,456 300 680
2 2 1.5 7/0.53 0.6 1.6 0.5 25 28.5 599 500 285
5 2 1.5 7/0.53 0.6 1.7 0.5 26 30 787 500 300
10 2 1.5 7/0.53 0.6 1.9 0.5 39 43 1,351 500 430
15 2 1.5 7/0.53 0.6 2.0 0.5 44 48 1,747 500 480
20 2 1.5 7/0.53 0.6 2.1 0.5 48 53.5 2,095 500 535
30 2 1.5 7/0.53 0.6 2.5 0.5 56 61.5 2,923 500 615
50 2 1.5 7/0.53 0.6 2.7 0.5 70 76 4,363 250 760
2 5 0.5 16/0.2 0.6 1.5 0.5 22 25.5 479 500 255
5 5 0.5 16/0.2 0.6 1.6 0.5 23 26.5 594 500 265
10 5 0.5 16/0.2 0.6 1.8 0.5 33 37 955 500 370
15 5 0.5 16/0.2 0.6 1.8 0.5 38 42 1,200 500 420
20 5 0.5 16/0.2 0.6 1.9 0.5 41 45 1,411 500 450
30 5 0.5 16/0.2 0.6 2.1 0.5 47 51.5 1,872 500 515
50 5 0.5 16/0.2 0.6 2.4 0.5 59 64 2,805 300 640
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation , min
Cable Max. L/R
Class
size ratio
Plain Annealed
Between Between
annealed tinned Unbalance Mutual Core to core Core to shield
conductors shields
copper wire copper wire
- pF/250 m pF/m Volt / 1 minute
1 0.5 36 36.7 5 1 250 115 25 1,000
1 1.0 18.1 18.2 5 1 250 115 25 1,000
2 1.5 12.1 12.2 5 1 250 115 40 1,000
5 0.5 39 40.1 5 1 250 115 25 1,000
22
CSVV
300/500 Volt
Single & multi pairs, PVC insulated,
Overall shielded, PVC sheathed
BS 5308 - 2
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in duct, • Conductor : Plain or tinned annealed copper wire.
cable tray or conduit for Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
control, communication,
data (analog/digital) and • Insulation : Polyvinyl Chloride (PVC) type T1 to BS 7655.
voice transmission signals
and service typically in • Pairs colour code : Black, White with number printing on insulation.
industrial project,
petroleum or oil and gas • Triads colour code : Black, White, Red with number printing on insulation.
industry.
• Pairs twisting : All pairs are twisted to counter electromagnetic noise.
25
csvv
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Approximately
Overall
shielded
Nominal Standard Bending
No of
Class cross- No/Dia of Overall delivery radius,
pairs Insulation Outer sheath Tinned Cable Weight length min
sectional wire diameter
area copper drain
wire
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation min Max.
Cable
Class L/R
size
Plain Annealed Between any ratio
Between
annealed tinned core or Mutual Core to core Core to shield
conductors
copper wire copper wire shield
- pF/m Volt / 1 minute
5 0.5 39 40.1 25 400 250 25 1,000
5 0.75 26 26.7 25 400 250 25 1,000
2 1.5 12.1 12.2 25 400 250 40 1,000
26
CSVV-TCWB
300 Volt
Single & multi pairs,
PVC insulated, Overall shielded,
Tinned copper wire braiding,
PVC sheathed
BS EN 50288-7
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in direct • Conductor : Plain or tinned annealed copper wire .
burried for control, Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
communication, data
(analog/digital) and voice • Insulation : Polyvinyl Chloride (PVC) type T1 to BS 7655.
transmission signals and • Pairs colour code : Black, White with number printing on insulation.
service typically in industrial • Triads colour code : Black, White, Red with number printing on insulation.
project, petroleum or oil
and gas industry. • Pairs twisting : All pairs are twisted to counter electromagnetic noise.
27
csvv-tcwb
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Approximately
Overall
shielded Diameter of
Standard
No of Class Nominal tinned Bending
delivery radius,
pairs cross- No/Dia of copper wire Overall
Insulation Outer sheath Tinned Cable Weight length min
sectional wire braiding diameter
area copper drain
wire
- - pcs/mm mm mm mm Kg/km m mm
1 2 0.5 7/0.3 0.4 0.9 0.5 6.3 8.5 94 500 70
2 2 0.5 7/0.3 0.4 1.0 0.5 10 12 172 500 100
5 2 0.5 7/0.3 0.4 1.1 0.5 12.4 15 255 500 120
1 2 0.75 7/0.37 0.4 0.9 0.5 6.8 9 118 500 75
2 2 0.75 7/0.37 0.4 1.1 0.5 10.8 13.5 201 500 110
1 2 1.5 7/0.53 0.5 1.0 0.5 8.2 10.5 159 500 85
2 2 1.5 7/0.53 0.5 1.1 0.5 13.6 16 279 500 130
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation min
Cable Max. L/R
Class
size ratio
Plain Annealed Between any
Between
annealed tinned core or Mutual Core to core Core to shield
copper wire conductors
copper wire shield
- pF/m Volt / 1 minute
5 0.5 39 40.1 10 400 250 25 1,000
5 0.75 26 26.7 10 400 250 25 1,000
2 1.5 12.1 12.2 10 400 250 40 1,000
28
PSVV
300/500 Volt
Single & multi pairs, PVC insulated,
Individual and overall shielded,
PVC sheathed
BS 5308 - 2
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in duct, cable • Conductor : Plain or tinned annealed copper wire .
tray or conduit for control, Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
communication, data • Insulation : Polyvinyl Chloride (PVC) type T1 to BS 7655.
(analog/digital) and voice • Pairs colour code : Black, White with number printing on insulation.
transmission signals and
service typically in industrial • Triads colour code : Black, White, Red with number printing on insulation.
project, petroleum or oil • Pairs twisting : All pairs are twisted to counter electromagnetic noise.
and gas industry.
• Individual shielding : Each pair is shielded with strand tinned annealed copper
wire and aluminium foil tape to give a maximum
protection against electrostatic noise and crosstalk
interference.
OPTIONAL : • Overall shielding : All pairs shields are isolated from each other. Individually
shielded pairs are assembled with non-hygroscopic fillers
Other construction such as
(if necessary) and entire assembly is covered by polyester
FIRE RESISTANT
tape and shielded with strand tinned annealed copper
INSTRUMENTATION CABLE
wire and aluminium foil tape.
with low smoke zero
• Outer sheath : Extruded Polyvinyl Chloride (PVC) , TM1 type to BS 6746,
halogen.
Black colour.
• Cable marking : SUPREME CABLE PSVV “ SIZE “ 300/500 V
INSTRUMENTATION CABLE with interval length marking
every 1 (one) meter.
29
psvv
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Ind. and Approximately
overall
shielded Standard Bending
No of Nominal radius,
Class delivery
pairs cross- No/Dia of Overall min
Insulation Outer sheath Tinned Cable Weight length
sectional wire diameter
area copper drain
wire
- - pcs/mm mm mm Kg/km m mm
2 5 0.5 16/0.2 0.6 1.1 0.5 12.5 130 1,000 100
5 5 0.5 16/0.2 0.6 1.2 0.5 15 235 1,000 120
10 5 0.5 16/0.2 0.6 1.3 0.5 21 429 1,000 170
15 5 0.5 16/0.2 0.6 1.5 0.5 24.5 620 1,000 200
20 5 0.5 16/0.2 0.6 1.5 0.5 28 814 500 225
30 5 0.5 16/0.2 0.6 1.7 0.5 33.5 1,196 500 270
50 5 0.5 16/0.2 0.6 2.2 0.5 42.5 1,916 500 340
2 5 0.75 24/0.2 0.6 1.1 0.5 13.5 156 1,000 110
5 5 0.75 24/0.2 0.6 1.2 0.5 17.5 309 1,000 140
10 5 0.75 24/0.2 0.6 1.3 0.5 25 571 1,000 200
15 5 0.75 24/0.2 0.6 1.5 0.5 29 830 1,000 235
20 5 0.75 24/0.2 0.6 1.7 0.5 33 1,083 500 265
30 5 0.75 24/0.2 0.6 2.0 0.5 39.5 1,609 500 320
50 5 0.75 24/0.2 0.6 2.2 0.5 50.5 2,592 500 405
2 2 1.5 7/0.53 0.6 1.2 0.5 15.5 208 1,000 125
5 2 1.5 7/0.53 0.6 1.3 0.5 20 419 1,000 160
10 2 1.5 7/00.53 0.6 1.5 0.5 28.5 730 1,000 230
15 2 1.5 7/0.53 0.6 1.7 0.5 33 1,151 1,000 265
20 2 1.5 7/0.53 0.6 1.7 0.5 37 1,480 500 300
30 2 1.5 7/0.53 0.6 2.0 0.5 44.5 2,187 500 360
50 2 1.5 7/0.53 0.6 2.2 0.5 57 3,543 500 460
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor, max Insulation, min
Cable Max. L/R
Class
size ratio
Plain Annealed Between any Core
Between Between
annealed tinned core or Mutual Core to core to
conductors shields shield
copper wire copper wire shield
- pF/m Volt / 1 minute
5 0.5 39 40.1 25 1 400 250 25 1,000
5 0.75 26 26.7 25 1 400 250 25 1,000
2 1.5 12.1 12.2 25 1 400 250 40 1,000
30
PSVV-TCWB
300 Volt
Single & multi pairs, PVC insulated,
Individual and overall shielded,
Tinned copper wire braiding, PVC sheathed
BS EN 50288-7
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in direct • Conductor : Plain or tinned annealed copper wire.
burried for control, Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
communication, data
(analog/digital) and voice • Insulation : Polyvinyl Chloride (PVC) type T1 to BS 7655
transmission signals and • Pairs colour code : Black, White with number printing on insulation.
service typically in industrial • Triads colour code : Black, White, Red with number printing on insulation.
project, petroleum or oil • Pairs twisting : All pairs are twisted to counter electromagnetic noise.
and gas industry.
• Individual shielding : Each pair is shielded with strand tinned annealed copper
wire and aluminium foil tape to give a maximum
protection against electrostatic noise and crosstalk
interference.
• Overall shielding : All pairs shields are isolated from each other. Individually
OPTIONAL : shielded pairs are assembled with non-hygroscopic fillers
(if necessary) and entire assembly is covered by polyester
Other construction such as tape andshielded with strand tinned annealed copper
FIRE RESISTANT wire and aluminium foil tape.
INSTRUMENTATION CABLE
with low smoke zero • Inner sheath : Extruded Polyvinyl Chloride (PVC) , Black colour.
halogen (LSOH) features
and other types are • Braid shielding : Tinned annealed copper wire to protect against
available upon request. electromagnetic noise.
31
psvv- tcwb
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Ind. and Approximately
overall
Diameter of
shielded Standard Bending
No of tinned
Class Nominal delivery radius,
pairs cross- No/Dia of copper wire Overall min
Insulation Outer sheath Tinned Cable Weight length
sectional wire braiding diameter
area copper drain
wire
- - pcs/mm mm mm Kg/km m mm
2 2 0.5 7/0.30 0.4 1.1 0.5 9.7 11.9 193 500 95
5 2 0.5 7/0.30 0.4 1.2 0.5 12 14.4 297 500 115
2 2 0.75 7/0.37 0.4 1.1 0.5 10.4 12.6 216 500 100
2 2 1.5 7/0.53 0.5 1.2 0.5 12.9 15.3 299 500 125
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation , min
Cable Max. L/R
Class
size ratio
Plain Annealed Between any
Between Between
annealed tinned core or Mutual Core to core Core to shield
conductors shields
copper wire copper wire shield
- pF/m Volt / 1 minute
5 0.5 39 40.1 10 1 400 250 25 1,000
5 0.75 26 26.7 10 1 400 250 25 1,000
2 1.5 12.1 12.2 10 1 400 250 40 1,000
32
MSVV
300/500 Volt
Multicores, PVC insulated,
Overall shielded, PVC sheathed
BS 5308 - 2
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in duct, cable • Conductor : Plain or tinned annealed copper wire .
tray or conduit for control, Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
communication, data
(analog/digital) and voice • Insulation : Polyvinyl Chloride (PVC) type T1 to BS 7655.
transmission signals and
service typically in industrial • Identification of cores : Black with white number printing on insulation.
project, petroleum or oil
and gas industry. • Cores lay-up : All cores are concentrically laid-up to counter electro
magnetic noise.
33
msvv
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Approximately
Overall
shielded
Nominal Standard Bending
No of
Class cross- No/Dia of Overall delivery radius,
cores Insulation Outer sheath Tinned Cable Weight length min
sectional wire diameter
area copper drain
wire
- - pcs/mm mm mm Kg/km m mm
2 5 0.5 16/0.2 0.6 0.8 0.5 7.5 49 1,000 60
3 5 0.5 16/0.2 0.6 0.8 0.5 8 59 1,000 65
4 5 0.5 16/0.2 0.6 0.8 0.5 8.5 71 1,000 70
6 5 0.5 16/0.2 0.6 0.9 0.5 10 99 1,000 80
10 5 0.5 16/0.2 0.6 1.1 0.5 12.5 156 1,000 100
20 5 0.5 16/0.2 0.6 1.2 0.5 15.5 270 500 125
40 5 0.5 16/0.2 0.6 1.3 0.5 20.5 487 500 165
2 5 0.75 24/0.2 0.6 0.8 0.5 8 57 1,000 65
3 5 0.75 24/0.2 0.6 0.8 0.5 8.5 69 1,000 70
4 5 0.75 24/0.2 0.6 0.8 0.5 9 86 1,000 75
6 5 0.75 24/0.2 0.6 0.9 0.5 10.5 121 1,000 65
10 5 0.75 24/0.2 0.6 1.1 0.5 13.5 192 1,000 110
20 5 0.75 24/0.2 0.6 1.2 0.5 17 339 500 140
40 5 0.75 24/0.2 0.6 1.3 0.5 22 620 500 180
2 2 1.5 7/0.53 0.6 0.8 0.5 9 78 1,000 75
3 2 1.5 7/0.53 0.6 0.9 0.5 9.5 105 1,000 80
4 2 1.5 7/0.53 0.6 0.9 0.5 10 129 1,000 80
6 2 1.5 7/0.53 0.6 1.1 0.5 12.5 189 1,000 100
10 2 1.5 7/0.53 0.6 1.2 0.5 15 294 1,000 120
~ 2 1.5 7/0.53 0.6 1.3 0.5 19 533 500 155
40 2 1.5 7/0.53 0.6 1.5 0.5 25 1,007 500 200
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation min
Cable Max. L/R
Class
size ratio
Plain Annealed Between any
Between
annealed tinned core or Mutual Core to core Core to shield
conductors
copper wire copper wire shield
- pF/m Volt / 1 minute
5 0.5 39 40.1 25 400 250 250 1,000
5 0.75 26 26.7 25 400 250 250 1,000
2 1.5 12.1 12.2 25 400 250 40 1,000
34
CSVV-SWA
300/500 Volt
Single & multi pairs, PVC insulated,
Overall shielded, Armoured, PVC sheathed
BS 5308 - 2
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
35
csvv-swa
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Approximately
Overall
shielded
Nominal Standard Bending
No of Dia of
Class cross- No/Dia of Overall delivery radius,
pairs Insulation Outer sheath Tinned armour wire Cable Weight min
sectional wire diameter length
area copper drain
wire
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation min
Cable Max. L/R
Class
size ratio
Plain Annealed Between any
Between
annealed tinned core or Mutual Core to core Core to shield
conductors
copper wire copper wire shield
- pF/m Volt / 1 minute
5 0.5 39 40.1 25 400 250 25 1,000
5 0.75 26 26.7 25 400 250 25 1,000
2 1.5 12.1 12.2 25 400 250 40 1,000
36
PSVV-SWA
300/500 Volt
Single & multi pairs, PVC insulated,
Individual and overall shielded,
Armoured, PVC sheathed
BS 5308 - 2
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
Suitable used in direct • Conductor : Plain or tinned annealed copper wire .
burried for control, Class 1 , 2 or 5 based on IEC 60228 or BS 6360.
communication, data
(analog/digital) and voice • Insulation : Polyvinyl Chloride (PVC) type T1 to BS 7655
transmission signals and • Pairs colour code : Black, White with number printing on insulation.
service typically in industrial • Triads colour code : Black, White, Red with number printing on insulation.
project, petroleum or oil • Pairs twisting : All pairs are twisted to counter electromagnetic noise.
and gas industry.
• Individual shielding : Each pair is shielded with strand tinned annealed copper
wire and aluminium foil tape to give a maximum
protection against electrostatic noise and cross talk
interference.
OPTIONAL : • Overall shielding : All pairs shields are isolated from each other. Individually
shielded pairs are assembled with non-hygroscopic fillers
Other construction such as (if necessary) and entire assembly is covered by polyester
FIRE RESISTANT tape and shielded with strand tinned annealed copper
INSTRUMENTATION CABLE wire and aluminium foil tape.
with low smoke zero
halogen (LSOH) features • Inner sheath : Extruded Polyvinyl Chloride (PVC) , Black colour.
and other types are • Armouring : Galvanized round steel wire.
available upon request. • Outer sheath : Extruded Polyvinyl Chloride (PVC) , TM1 type to BS 6746,
Blue colour.
• Cable marking : SUPREME CABLE PSVV-SWA “ SIZE “ 300/500 V
INSTRUMENTATION CABLE with interval length marking
every 1 (one) meter.
• Operating temperature maximum 70 ̊C
37
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Ind. and Approximately
overall
shielded Standard Bending
No of Dia of
Class Nominal delivery radius,
pairs cross- No/Dia of armour wire Overall min
Insulation Outer sheath Tinned Cable Weight length
sectional wire diameter
area copper drain
wire
- - pcs/mm mm mm mm Kg/km m mm
2 5 0.5 16/0.2 0.6 1.7 0.5 0.9 20.5 526 1,000 205
5 5 0.5 16/0.2 0.6 1.7 0.5 1.25 24.5 905 1,000 245
10 5 0.5 16/0.2 0.6 1.8 0.5 1.6 34.5 1,545 1,000 345
15 5 0.5 16/0.2 0.6 1.8 0.5 1.6 38.5 1,909 500 385
20 5 0.5 16/0.2 0.6 1.9 0.5 1.6 42.5 2,221 500 425
30 5 0.5 16/0.2 0.6 2.1 0.5 2 50.5 3,198 500 505
50 5 0.5 16/0.2 0.6 2.4 0.5 2.5 64.5 5,194 300 645
2 5 0.75 24/0.2 0.6 1.5 0.5 0.9 21.5 575 1,000 215
5 5 0.75 24/0.2 0.6 1.6 0.5 1.25 29 977 1,000 290
10 5 0.75 24/0.2 0.6 1.8 0.5 1.6 38.5 1,711 1,000 385
15 5 0.75 24/0.2 0.6 1.9 0.5 1.6 38.5 1,909 500 385
20 5 0.75 24/0.2 0.6 2 0.5 2 46.5 2,853 500 465
30 5 0.75 24/0.2 0.6 2.2 0.5 2 54.5 3,720 500 545
50 5 0.75 24/0.2 0.6 2.5 0.5 2.5 59 5,865 300 590
2 2 1.5 7/0.53 0.6 1.6 0.5 1.25 23 812 1,000 230
5 2 1.5 7/0.53 0.6 1.7 0.5 1.6 30 1,334 1,000 300
10 2 1.5 7/0.53 0.6 1.9 0.5 1.6 40 2,092 500 400
15 2 1.5 7/0.53 0.6 2 0.5 2 46.5 2,948 500 465
20 2 1.5 7/0.53 0.6 2.1 0.5 2 51 3,462 500 510
30 2 1.5 7/0.53 0.6 2.4 0.5 2.5 61 5,108 500 610
50 2 1.5 7/0.53 0.6 2.7 0.5 2.5 76 7,225 300 760
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation , min Max.
Cable
Class L/R
size
Plain Annealed Between any ratio
Between Between
annealed tinned core or Mutual Core to core Core to shield
conductors shields
copper wire copper wire shield
- pF/m Volt / 1 minute
5 0.5 39 40.1 25 1 7 250 25 1,000
5 0.75 26 26.7 25 1 7 250 25 1,000
2 1.5 12.1 12.2 25 1 7 250 40 1,000
38
MSVV-SWA
300/500 Volt
Multicores, PVC insulated, Overall shielded,
Armoured, PVC sheathed
BS 5308 - 2
0.5 …………1.5 mm2
APPLICATION : CONSTRUCTION :
39
DIMENSIONAL & MECHANICAL DATA
CONDUCTOR Nominal thickness Approximately
Overall
shielded Bending
Nominal Standard
No of Dia of radius,
Class cross- No/Dia of Overall delivery
cores Insulation Outer sheath Tinned armour wire Cable Weight min
sectional wire diameter length
area copper drain
wire
- - pcs/mm mm mm mm Kg/km m mm
2 5 0.5 16/0.2 0.6 1.3 0.5 0.9 12 239 1,000 120
3 5 0.5 16/0.2 0.6 1.3 0.5 0.9 12.5 257 1,000 125
4 5 0.5 16/0.2 0.6 1.3 0.5 0.9 13 283 1,000 130
6 5 0.5 16/0.2 0.6 1.4 0.5 0.9 14.5 352 1,000 145
10 5 0.5 16/0.2 0.6 1.5 0.5 0.9 17.5 477 1,000 175
20 5 0.5 16/0.2 0.6 1.6 0.5 1.25 21.5 790 500 215
40 5 0.5 16/0.2 0.6 1.7 0.5 1.6 27 1,296 500 270
2 5 0.75 24/0.2 0.6 1.3 0.5 0.9 12.5 255 500 125
3 5 0.75 24/0.2 0.6 1.3 0.5 0.9 13 282 1,000 130
4 5 0.75 24/0.2 0.6 1.4 0.5 0.9 14 318 1,000 140
6 5 0.75 24/0.2 0.6 1.4 0.5 0.9 15.5 396 1,000 155
10 5 0.75 24/0.2 0.6 1.5 0.5 0.9 18.5 545 1,000 185
20 5 0.75 24/0.2 0.6 1.6 0.5 1.25 23 927 500 230
40 5 0.75 24/0.2 0.6 1.8 0.5 1.6 29.5 1,534 500 295
2 2 1.5 7/0.53 0.6 1.4 0.5 0.9 13.5 302 1,000 135
3 2 1.5 7/0.53 0.6 1.4 0.5 0.9 14.5 351 1,000 145
4 2 1.5 7/0.53 0.6 1.4 0.5 0.9 15 390 1,000 150
6 2 1.5 7/0.53 0.6 1.4 0.5 0.9 17 503 1,000 170
10 2 1.5 7/0.53 0.6 1.6 0.5 1.25 21.5 907 500 215
20 2 1.5 7/0.53 0.6 1.7 0.5 1.6 26 1,316 500 260
40 2 1.5 7/0.53 0.6 1.9 0.5 1.6 32.5 2,068 500 325
ELECTRICAL DATA
Resistance at 20 oC
Max. capacitance at 1 kHz AC voltage test
Conductor , max Insulation min
Cable Max. L/R
Class
size ratio
Plain Annealed Between any
Between
annealed tinned core or Mutual Core to core Core to shield
conductors
copper wire copper wire shield
- pF/m Volt / 1 minute
5 0.5 39 40.1 25 400 250 25 1,000
5 0.75 26 26.7 25 400 250 25 1,000
2 1.5 12.1 12.2 25 400 250 40 1,000
40
Notes