Demo Modbus Server

This document describes a Modbus server demo project that allows testing Modbus slave communication via COM port or Ethernet. It provides instructions on setting up the HMI screen with option list and other objects to configure and monitor the communication parameters.

Uploaded by

Full To
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

 

                                                                                                            Modbus Server 

Modbus Server

  1 V1.00 
                                                                                                              Modbus Server 

Table of Contents
1. Overview and Operation........................................................................................................ 3

2. Setting up the Screen ............................................................................................................ 6

3. Addresses.............................................................................................................................. 9

  2 V1.00 
                                                                                                              Modbus Server 

1. Overview and Operation

Overview
This demo project is for testing Modbus slave communication when connecting
via COM Port or Ethernet.
With Option List Object the communication parameters can be updated and
tested easily and directly on HMI.

  3 V1.00 
                                                                                                              Modbus Server 

Operation
Select the COM Port to be tested and set the relevant communication
parameters:

After setting, push update button to update communication parameters.

  4 V1.00 
                                                                                                              Modbus Server 

To test Ethernet communication, set Ethernet Modbus Server station number.


Please note that the port no. here is read only and can’t be modified on HMI.

  5 V1.00 
                                                                                                              Modbus Server 

2. Setting up the Screen

1. Create 15 Option List Objects, respectively set system registers from


LW-9550 ~ LW-9564 to be monitor addresses. The following takes
LW-9550 as an example.

Option list tab:

  6 V1.00 
                                                                                                              Modbus Server 

[Source of item data] set to Predefine; [Monitor address] set to LW-9550; [Item
no.] must be set according to the range of the register, for LW-9550, the
available value range is 0 ~ 2, which means 3 states in total, therefore set to 3,
and adjust the relevant properties as required.

Mapping tab:

Since the available value range for LW-9550 is 0 ~ 2, please fill in 0, 1, 2


respectively in [Value] column. In [Item data] column, fill in the corresponding
usage: RS232, RS485 2W, RS485 4W.

Please refer to the demonstration above to set the rest 14 Options List Objects

2. Create 4 Numeric Input Objects, respectively set [Read address] to


LW-9541 ~ LW-9544, for setting Modbus Server station number.

  7 V1.00 
                                                                                                              Modbus Server 

3. Create 3 Set Bit Objects, respectively set [Write address] to LB-9030 ~


LB-9032 for updating COM port 1 ~ 3 communication parameter settings.
Set [Attribute] to Momentary.

4. Create a Numeric Display Object, set [Read address] to LW-9133 for


reading Ethernet port number.

  8 V1.00 
                                                                                                              Modbus Server 

3. Addresses

The addresses of objects used in this demonstration are listed below.


 
Object Address Object ID Description

Window 4
Option List LW-9550 OL_0 COM1 mode
LW-9555 OL_1  COM2 mode 
LW-9560 OL_2  COM3 mode 
LW-9551 OL_3  COM1 baud rate
LW-9556 OL_4  COM2 baud rate
LW-9561 OL_5  COM3 baud rate
LW-9552 OL_6  COM1 databits
LW-9557 OL_7  COM2 databits
LW-9562 OL_8  COM3 databits
LW-9553 OL_9  COM1 parity
LW-9558 OL_10  COM2 parity
LW-9563 OL_11  COM3 parity
LW-9554 OL_12  COM1 stop bits
LW-9559 OL_13  COM2 stop bits
LW-9564 OL_14  COM3 stop bits
Set Bit LB-9030 SB_0 Update COM1 com. parameters
LB-9031 SB_1 Update COM2 com. parameters
LB-9032 SB_2 Update COM3 com. parameters
Numeric LW-9541 NE_0 Modbus server sta. no. (COM1)
Input
LW_9542 NE_1 Modbus server sta. no. (COM2)
LW-9543 NE_2 Modbus server sta. no. (COM3)
LW-9544 NE_3 Modbus server sta. no. (Ethernet)
Numeric LW-9133 ND_0 Ethernet port no.
Display