Fzm-1 Interface Module: Installation and Maintenance Instructions
Fzm-1 Interface Module: Installation and Maintenance Instructions
Fzm-1 Interface Module: Installation and Maintenance Instructions
I56-3504-002
12 Clintonville Road
Northford, CT 06472-1653
FZM-1 Interface Module Phone: 203.484.7161
Specifications
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 5.1 mA (LED on)
Average Operating Current: 270µA (LED flashing)
EOL Resistance: 3.9K Ohms
Maximum IDC Wiring Resistance: 25 Ohms
IDC Supply Voltage (between Terminals T10 and T11)
Regulated DC Voltage: 24 VDC power limited
Ripple Voltage: 0.1 Volts RMS maximum
Current: 90mA per module
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Non-condensing
Dimensions: 41/2˝ H × 4 W × 11/4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.)
Accessories: SMB500 Electrical Box
C1066-00
C1059-00
NO-460-008 1 I56-3504-002
Figure 3. Interface two-wire conventional detectors, NFPA Style B:
OPTIONAL BRANCH CIRCUIT )–( )–( FROM
TO NEXT INTERFACE TO NEXT PANEL OR
POWER TO THE INTERFACE MODULE. MODULE DEVICE PREVIOUS
MODULE MUST BE EXTERNALLY SUPERVISES SUPPLY )+( )+( DEVICE
SWITCED TO RESET THE VOLTAGE AND
DETECTORS. A RELAY CONTROL DETECTOR LOOP.
MODULE CAN BE USED TO SWITCH INTERFACE
MODULE SIGNAL LINE CIRCUIT (SLC)
POWER FROM A STANDARD POWER 32 VDC MAX.
SUPPLY (SEE FIGURE 5). TWISTED PAIR
IS RECOMMENDED
(–)
LISTED BATTERY-BACKUP SWITCHED )–(
REGUALTED DC POWER SUPPLY CONNECT MODULES TO
(+) LISTED COMPATIBLE
)+( CONTROL PANELS ONLY.
C1061-00
Figure 4. Interface two-wire conventional detectors, NFPA Style D:
POWER TO THE INTERFACE FROM
TO NEXT )–( )–( PANEL OR
MODULE MUST BE OPTIONAL BRANCH CIRCUIT DEVICE
EXTERNALLY SWITCED TO TO NEXT INTERFACE MODULE. PREVIOUS
)+( )+( DEVICE
RESET THE DETECTORS. A MODULE SUPERVISES SUPPLY
RELAY CONTROL MODULE CAN VOLTAGE AND
BE USED TO SWITCH POWER DETECTOR LOOP. INTERFACE
FROM A STANDARD POWER MODULE
SUPPLY (SEE FIGURE 5).
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
LISTED (–)
BATTERY-BACKUP )–(
SWITCHED REGUALTED
DC POWER SUPPLY (+)
)+(
+ +
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY
DEVICES ON THE SAME MODULE.
− − *NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT
ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. DETECTORS
MUST BE UL LISTED COMPATIBLE WITH MODULE. INSTALL DETECTORS PER MANUFACTURER’S INSTALLATION INSTRUCTIONS
C1062-00
Figure 5. Relay control module used to disconnect a power supply:
)–( )–(
FROM
TO NEXT PANEL OR
DEVICE )+( )+( PREVIOUS
DEVICE
RELAY CONTROL
MODULE
C0945-00
NO-460-008 2 I56-3504-002