Fzm-1 Interface Module: Installation and Maintenance Instructions

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Installation And Maintenance Instructions

I56-3504-002
12 Clintonville Road
Northford, CT 06472-1653
FZM-1 Interface Module Phone: 203.484.7161

Specifications
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 5.1 mA (LED on)
Average Operating Current: 270µA (LED flashing)
EOL Resistance: 3.9K Ohms
Maximum IDC Wiring Resistance: 25 Ohms
IDC Supply Voltage (between Terminals T10 and T11)
Regulated DC Voltage: 24 VDC power limited
Ripple Voltage: 0.1 Volts RMS maximum
Current: 90mA per module
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Non-condensing
Dimensions: 41/2˝ H × 4 W × 11/4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.)
Accessories: SMB500 Electrical Box

Before Installing Wiring


This information is included as a quick reference installation guide. Refer to NOTE: All wiring must conform to applicable local codes, ordinances, and
the control panel installation manual for detailed system information. If the regulations. This module is intended for powerlimited wiring only.
modules will be installed in an existing operational system, inform the opera- 1. Install module wiring in accordance with the job drawings and appropri-
tor and local authority that the system will be temporarily out of service. Dis- ate wiring diagrams.
connect power to the control panel before installing the modules.
2. Set the address on the module per job drawings.
NOTICE: This manual should be left with the owner/user of this equipment. 3. Secure module to electrical box (supplied by installer), as shown in
General Description Figure 2.
The FZM-1 Interface Module is intended for use in intelligent, two-wire sys- Figure 2. Module mounting:
tems, where the individual address of each module is selected using the built-
in rotary switches. This module allows intelligent panels to interface and
monitor two-wire conventional smoke detectors. It transmits the status (nor-
mal, open, or alarm) of one full zone of conventional detectors back to the
control panel. All two-wire detectors being monitored must be UL compatible
with this module. The FZM-1 has a panel controlled LED indicator and can
be used to replace an MMX-2 module in existing systems. FZM-1 is capable of
handling more than one detector in alarm condition.
Compatibility Requirements
To ensure proper operation, this module shall be connected to a compatible
Notifier system control panel only (list available from Notifier). In addition,
please refer to Notifier Device Compatibility document number 15378 for the ISOLATED
compatible list of detectors. QUADRANT
Mounting
The FZM-1 mounts directly to 4-inch square electrical boxes (see Figure 2).
The box must have a minimum depth of 21/8 inches. Surface mounted electri-
cal boxes (SMB500) are available from Notifier.
Figure 1. CONTROLS AND INDICATORS:

C1066-00

C1059-00
NO-460-008 1 I56-3504-002
Figure 3. Interface two-wire conventional detectors, NFPA Style B:
OPTIONAL BRANCH CIRCUIT )–( )–( FROM
TO NEXT INTERFACE TO NEXT PANEL OR
POWER TO THE INTERFACE MODULE. MODULE DEVICE PREVIOUS
MODULE MUST BE EXTERNALLY SUPERVISES SUPPLY )+( )+( DEVICE
SWITCED TO RESET THE VOLTAGE AND
DETECTORS. A RELAY CONTROL DETECTOR LOOP.
MODULE CAN BE USED TO SWITCH INTERFACE
MODULE SIGNAL LINE CIRCUIT (SLC)
POWER FROM A STANDARD POWER 32 VDC MAX.
SUPPLY (SEE FIGURE 5). TWISTED PAIR
IS RECOMMENDED
(–)
LISTED BATTERY-BACKUP SWITCHED )–(
REGUALTED DC POWER SUPPLY CONNECT MODULES TO
(+) LISTED COMPATIBLE
)+( CONTROL PANELS ONLY.

3.9K EOL TERMINAL WIRING MUST


RESISTOR BE POWER LIMITED.
(INCLUDED)
A2143-10
+ +
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY,
OR SECURITY DEVICES ON THE SAME MODULE.
– – *NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT
ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. DETECTORS MUST
BE UL LISTED COMPATIBLE WITH MODULE. INSTALL DETECTORS PER MANUFACTURER’S INSTALLATION INSTRUCTIONS

C1061-00
Figure 4. Interface two-wire conventional detectors, NFPA Style D:
POWER TO THE INTERFACE FROM
TO NEXT )–( )–( PANEL OR
MODULE MUST BE OPTIONAL BRANCH CIRCUIT DEVICE
EXTERNALLY SWITCED TO TO NEXT INTERFACE MODULE. PREVIOUS
)+( )+( DEVICE
RESET THE DETECTORS. A MODULE SUPERVISES SUPPLY
RELAY CONTROL MODULE CAN VOLTAGE AND
BE USED TO SWITCH POWER DETECTOR LOOP. INTERFACE
FROM A STANDARD POWER MODULE
SUPPLY (SEE FIGURE 5).
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
LISTED (–)
BATTERY-BACKUP )–(
SWITCHED REGUALTED
DC POWER SUPPLY (+)
)+(

3.9K EOL RESISTOR CONNECT MODULES TO


REQUIRED AT TERMINALS LISTED COMPATIBLE
8 & 9 (INCLUDED) A2143-10 CONTROL PANELS ONLY.

TERMINAL WIRING MUST


BE POWER LIMITED.

+ +
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY
DEVICES ON THE SAME MODULE.
− − *NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT
ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. DETECTORS
MUST BE UL LISTED COMPATIBLE WITH MODULE. INSTALL DETECTORS PER MANUFACTURER’S INSTALLATION INSTRUCTIONS

C1062-00
Figure 5. Relay control module used to disconnect a power supply:
)–( )–(
FROM
TO NEXT PANEL OR
DEVICE )+( )+( PREVIOUS
DEVICE
RELAY CONTROL
MODULE

SIGNAL LINE CIRCUIT (SLC)


32 VDC MAX.
POWER LIMITED DC TWISTED PAIR
POWER SUPPLY, )+( IS RECOMMENDED
LISTED FOR FIRE
PROTECTION WITH
BATTERY BACKUP )–( )–(
)+(

CONNECT MODULES TO LISTED COMPATIBLE


)–( CONTROL PANELS ONLY.
)+(
*NOTE: ANY FAULT IN THE POWER SUPPLY IS
LIMITED TO THAT ZONE AND DOES NOT
RESULT IN A FAULT IN A SEPARATE ZONE.

C0945-00
NO-460-008 2 I56-3504-002
©2008 Notifier