01-15456 STS-1 Installation Instructions

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

STS-1 Security Tamper Switch

PRODUCT INSTALLATION DRAWING


Document 15456 Rev. C
ECN 98-473 11/16/98

Figure 1: Installing STS-1 Switch and Magnet in CAB-3 Series Enclosure

1) Install the Security Tamper Switch (STS-1) on the side of the


cabinet backbox opposite the placement of the door hinge. To
install, push switch through the opening in backbox until it
snaps into place.
Security Tamper 2) Install the magnet on the same side of the cabinet door as the
Switch (STS-1) lock. To install, push magnet through opening in door until it
snaps into place.

Install an R-47K End-of-Line


Resistor into the circuit as shown
yellow
Figure 2: Connecting an Security Tamper
STS-1 Switch to an Switch (STS-1)
purple
MMX-101 Monitor Module

red

black
SLC loop MMX-101

SLC loop out


Install an R-47K End-of-Line
Resistor into the circuit.
Connect wires with wire nuts.
Figure 3: Connecting an
STS-1 Switch to Security Tamper
an MMX-1 Monitor Module Switch (STS-1)

SLC loop in

One Fire-Lite Place


Northford, CT 06472
(203) 484-7161
Fax: (203) 484-7118

1
Figure 4: Connecting an STS-1 Switch to an XP5-M Module

SLC loop out

SLC loop
in

Figure 5: Connecting an STS-1 Switch to an MPS-400

Wire the STS-1 to the MPS-400:


1) Remove the jumper from J5 on the
MPS-400. AFP-400 in
a CAB-A3
2) Connect cable 75148 to J5.

MPS-400

Cable 75148
Security Tamper
connected to
Switch (STS-1)
J5

Cable 75148
J5

For further information on the STS-1, refer to the AM2020/AFP1010 Installation Manual, Document 15088 or the
AFP-400 Installation Manual, Document 50253.

2 Document # 15456 Rev. C 11/16/98