Basic Air Conditioning Formulas

1. The document provides formulas for calculating key metrics related to basic air conditioning, including: airflow, number of air changes per hour, heat transfer rates, temperatures, enthalpy, and humidification requirements. 2. Formulas are given to calculate total airflow, infiltration/ventilation, sensible heat, latent heat, entering/leaving air temperatures, enthalpy, and humidification needs for both cooling and heating applications. 3. Key variables in the formulas include airflow, temperature differences, enthalpy, and heat transfer rates which are used to determine system requirements and specifications.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
98 views

Basic Air Conditioning Formulas

1. The document provides formulas for calculating key metrics related to basic air conditioning, including: airflow, number of air changes per hour, heat transfer rates, temperatures, enthalpy, and humidification requirements. 2. Formulas are given to calculate total airflow, infiltration/ventilation, sensible heat, latent heat, entering/leaving air temperatures, enthalpy, and humidification needs for both cooling and heating applications. 3. Key variables in the formulas include airflow, temperature differences, enthalpy, and heat transfer rates which are used to determine system requirements and specifications.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Basic Air Conditioning

Figure 5
Formulas
Basic Air Conditioning Formulas

Application
EXPRESSED
TO DETERMINE AS COOLING HEATING and/or HUMIDIFYING
NT V NT V

Guide
Total Airflow CFMT 1. CFMT = 1. CFMT =
60 min./hr. 60 min./hr.

NO V No V
Infiltration or Ventilation CFMo 2. CFMo = 2. CFMo =
60 min./hr. 60 min./hr.

Number of Air Changes CFMT (60 min./hr.) CFMT (60 min./hr.)


NT 3. NT = 3. NT =
Per Hour – Total V V

Number of Air Changes CFMo (60 min./hr.) CFMo (60 min./hr.)


Per Hour – Outdoor Air No 4. No = 4. No =
V V

Total Heat (HT) Btuh 5. HT = CFMT x 4.5 x (h1 – h2) = Btuh 6. HT = CFMT x 4.5 x (h2 – h1) = Btuh

Sensible Heat (HS) Btuh 7. HS = CFMT x 1.08 x (T1 – T2) = Btuh 8. HS = CFMT x 1.08 x (T2 – T1) = Btuh

Latent Heat (HL) Btuh 9. HL = CFMT x .68 x (W1 – W2) = Btuh 10. HL = CFMT x .68 x (W2 – W1) = Btuh

CFMo CFMo
Entering Air Temperature (T1) °F. D.B. 11. T1 = t1 + x (t2 – t1) = °F.D.B. 1 12. T1 = t1 – x (t1 – t2) = °F.D.B. 2
CFMT CFMT
(Mixed Air)
1 If duct heat gain is a factor, add to T1: 2 If duct heat loss is a factor, subtract from T1:
Duct Heat Gain (Btuh) Duct Heat Loss (Btuh)
CFMT x 1.08 CFMT x 1.08

Leaving Air D.B. HS HS


°F. D.B. 13. T2 = T1 – = °F.D.B. 14. T2 = T1 + = °F.D.B.
Temperature (T2) CFMT x 1.08 CFMT x 1.08
HS (total) HS
Required Airflow CFMT 15. CFMT = = CFM 16. CFMT = = CFM
1.08 x (T1 – T2) 1.08 x (T2 – T1)
OR
HS (internal)3
CFMT = = CFM
1.08 x (t1 – T2)
3 Sensible load of outside air not included

Btu/lb. HT HT
Enthalpy – Leaving Air (h2) 17. h2 = h1 – = Btu/lb. dry air 18. h2 = h1 + = Btu/lb. dry air
dry air CFMT x 4.5 CFMT x 4.5

19. Refer to Enthalpy Table and read W.B. temperature 20. Refer to Enthalpy Table and read W.B. temperature
Leaving Air W.B. Temperature °F.W.B.
corresponding to enthalpy of leaving air (h2) (see #17). corresponding to enthalpy of leaving air (h2) (see #18).
Heat Required to Evaporate
Water Vapor Added to Btuh 21. HL = CFMo x .68 (W3 – Wo) = Btuh 22. HL = CFMo x .68 (W3 – Wo) = Btuh
Ventilation Air
Excess Latent Capacity

( ) ( )
Lbs. Make up = of System x % Run Time HL loss Btuh (see #22)
Humidification Requirements 23. = lbs./hr. 24. Make up = = lbs./hr.
water/hr. Moisture 1060 Btu/lb. Moisture 1060 Btu/lb.
(Industrial Process Work)

LEGEND DERIVATION OF AIR CONSTANTS


CFMT = Total airflow cubic feet/min. The air constants below apply specifically to standard air which is
CFMo = Outdoor air cubic feet/min. defined as dry air at 70°F and 14.7 P.S.I.A. (29.92 in. mercury column).
NT = Total air changes per hour They can, however, be used in most cooling calculations unless extremely
No = Outdoor air, air changes per hour precise results are desired.
V = Volume of space cubic feet 4.5 (To convert CFM to lbs./hr.)
HT = Total heat Btuh
HS = Sensible heat Btuh 60 min./hr.
4.5 = or 60 X .075
HL = Latent heat Btuh 13.33
* h1 = Enthalpy or total heat of entering air Btu/lb. Where 13.33 is the specific volume of standard air (cu.ft./lb.) and
* h2 = Enthalpy or total heat of leaving air Btu/lb. .075 is the density (lbs./cu.ft.)
T1 = Temperature of entering air .24 X 60
T2 = Temperature of leaving air 1.08 = or .24 X 4.5
13.33
Tadp = Apparatus dewpoint °F.D.B.
.24 BTU = specific heat of standard air (BTU/LB/°F)
t1 = Indoor design temperature °F.D.B.
t2 = Outdoor design temperature °F.D.B. 60 1060 1060
.68 = X or 4.5 X
W1 = Grains of water/lb. of dry air at entering condition Grains/lb. 13.33 7000 7000
W2 = Grains of water/lb. of dry air at leaving condition Grains/lb.
Where: 1060 = Average Latent Heat of water vapor (BTU/LB.).
W3 = Grains of water/lb. of dry air at indoor design conditions Grains/lb.
Wo = Grains of water/lb. of dry air at outdoor design conditions Grains/lb. 7000 = Grains per lb.

* See Enthalpy of air (Total Heat Content of Air) Table for exact values.