Basic Air Conditioning Formulas
Basic Air Conditioning Formulas
Figure 5
Formulas
Basic Air Conditioning Formulas
Application
EXPRESSED
TO DETERMINE AS COOLING HEATING and/or HUMIDIFYING
NT V NT V
Guide
Total Airflow CFMT 1. CFMT = 1. CFMT =
60 min./hr. 60 min./hr.
NO V No V
Infiltration or Ventilation CFMo 2. CFMo = 2. CFMo =
60 min./hr. 60 min./hr.
Total Heat (HT) Btuh 5. HT = CFMT x 4.5 x (h1 – h2) = Btuh 6. HT = CFMT x 4.5 x (h2 – h1) = Btuh
Sensible Heat (HS) Btuh 7. HS = CFMT x 1.08 x (T1 – T2) = Btuh 8. HS = CFMT x 1.08 x (T2 – T1) = Btuh
Latent Heat (HL) Btuh 9. HL = CFMT x .68 x (W1 – W2) = Btuh 10. HL = CFMT x .68 x (W2 – W1) = Btuh
CFMo CFMo
Entering Air Temperature (T1) °F. D.B. 11. T1 = t1 + x (t2 – t1) = °F.D.B. 1 12. T1 = t1 – x (t1 – t2) = °F.D.B. 2
CFMT CFMT
(Mixed Air)
1 If duct heat gain is a factor, add to T1: 2 If duct heat loss is a factor, subtract from T1:
Duct Heat Gain (Btuh) Duct Heat Loss (Btuh)
CFMT x 1.08 CFMT x 1.08
Btu/lb. HT HT
Enthalpy – Leaving Air (h2) 17. h2 = h1 – = Btu/lb. dry air 18. h2 = h1 + = Btu/lb. dry air
dry air CFMT x 4.5 CFMT x 4.5
19. Refer to Enthalpy Table and read W.B. temperature 20. Refer to Enthalpy Table and read W.B. temperature
Leaving Air W.B. Temperature °F.W.B.
corresponding to enthalpy of leaving air (h2) (see #17). corresponding to enthalpy of leaving air (h2) (see #18).
Heat Required to Evaporate
Water Vapor Added to Btuh 21. HL = CFMo x .68 (W3 – Wo) = Btuh 22. HL = CFMo x .68 (W3 – Wo) = Btuh
Ventilation Air
Excess Latent Capacity
( ) ( )
Lbs. Make up = of System x % Run Time HL loss Btuh (see #22)
Humidification Requirements 23. = lbs./hr. 24. Make up = = lbs./hr.
water/hr. Moisture 1060 Btu/lb. Moisture 1060 Btu/lb.
(Industrial Process Work)
* See Enthalpy of air (Total Heat Content of Air) Table for exact values.