Realtime Monitoring Software User Manual
Realtime Monitoring Software User Manual
50
User Manual
1
1.3.1 Previous Page .......................................................................................................30
2
Real-time Monitoring Software
Title bar displays title information of the real-time monitoring software. For
example: “AdvanTrol-Pro monitoring software——XXXXX”, here, XXXXX
represents the name of current main window in real-time monitoring
1
Real-time Monitoring Software
There are 24 vivid icons of tools, which almost incorporate all functions of the
real-time monitoring software. See the following figure:
According to the function of icons, all icons can be sorted into four groups,
operating system icons, panel operation icons, page turning icons and
other icons.
Alarm message Band shows the alarm information which recently triggered
alarms. Maximum 4 pieces of alarm messages can be displayed in the
band at same time. User can view the messages of rest alarms by clicking
the scrollbar at right side of the band. Alarm messages would be ranged in
the sequence of time when alarm messages were generated. The first
alarm message is the latest one. As shown in the following figure, each
alarm message shows alarm time, tag name, tag description, current value,
alarm description and alarm type.
2
Real-time Monitoring Software
3
Real-time Monitoring Software
“Setting”. Alarm “Severity filter” and alarm “Enable/Disable” (only valid for
authorized) can be set.. The faceplate “Setting” is as shown in following
figure:
4
Real-time Monitoring Software
5
Real-time Monitoring Software
Window
pages Format Function Operation
Name
tuning 8 points Display the data and status of internal Modify parameter and
320
grouping /page instruments, test points, SC language status
tuning Variabl 1 points Display all parameters of an internal Modify parameter, status
trend e /page instrument and turning trend panel. and displaying mode
6
Real-time Monitoring Software
Click the icon “ ” on toolbar to open the window “Alarm Summary”. Alarm
1. There are 1000 pieces of latest alarm messages can be displayed in the
Alarm Summary window. The upper messages represent the latterly
generated alarms.
7
Real-time Monitoring Software
2. Two displaying modes, real-time alarm and history alarm can be chosen
for Alarm Summary display. Sequentially, based on which displaying
mode is chosen, different alarm information would be shown in the
Alarm Summary window. The items of Alarm Summary, such as “NO.”,
“Alarm time”, “Region”, “Tag name”, “Alarm Desc.”, “Type”, “Severity”,
“ACK time” and “Disappear time” are configurable,
3. The column “Region” of the window shows the name of data region
about the alarms. The name of data region is the same as the name
which defined for the data region of the system configuration.
5. Type of alarm such as ON, OFF, LO (Low limit) and HI (High limit) is
displayed in column “Type” of the window. Different statuses of alarm
messages will be presented in different colors.
6. Alarm messages list are classified into two class in real-time alarm
status. One group are current and active alarm messages and another
are alarms eliminated and unacknowledged. The amount of real-time
8
Real-time Monitoring Software
alarms is unlimited, and they are listed basing on the time they were
generated. So a latest alarm message will be listed on the top of the
window, push the old alarms down to a lower position.
Time” defines the period time in which the alarms are going to be shown on
history alarm window. At least one alarm type in column “Alarm Type”
should be selected. Either “Select Tag” or “Select Region/Group” is
available for user to search the alarms. When “Data region” is selected, the
name of data region which is defined in the system configuration is
displayed in list box. When “Select Tag” is selected, fuzzy search that
distinguishes capital or small letter can be fulfilled. Then, select the tag
name (multi-options are permitted). The selected tag will be displayed in
the right list. While, doesn’t set tag type is enable. Dialog box “Alarm
Backward” is shown as follows:
9
Real-time Monitoring Software
When searching object and time range have been defined, please click
“OK” to open history alarm display which is different from the Real-time
alarm display mentioned above. If there are too many pages of history
to the first page and “ ” to go to the last page; click “ ” to turn to the
Only the history alarm would be displayed in this window, Color of all
records are green. Status of alarm records can be told from the “Disappear
time” which is different from the status of alarms of Real-time alarm window;
it refers to the status at the time of searching. Sometimes some alarms
doesn't have “Disappear time”, the reason should be as follows: the alarm
record was not eliminated when it is quested or Real-time monitoring
system or alarm record server has exit before the alarm is eliminated.
History alarm window is as shown in the following figure which has the
name “History alarm track” displayed at the bottom right of the widow.
10
Real-time Monitoring Software
Click the button “ ” to display real-time alarm records. All the alarms
11
Real-time Monitoring Software
Under the status of history alarm display, click the button “ ” to export
history alarm records to the backup file folder. This button is disabled in the
Real-time alarm window. Real-time alarm record can not be saved by
clicking this button. Each clicking saves a single file which will be exported
to the folder “backup” of the project configuration folder. If it is the first time
to save backup file, a file folder named “AlmHisData” will be created in
backup file folder, in which all backup files of history alarm records will be
saved.
5. Printting button “ ”
In the window of history alarm, click the button “ ” to print the alarm
history records listed in current page using default printer of the monitoring
system. This button is disabled in the window of Real-time alarm. Real-time
alarm record can not be printed by clicking this button. It can only be printed
by the line-by-line printer. Line-by-line printer can be configured in system
setting of AdvanTrol-Pro.
12
Real-time Monitoring Software
Click the system information button “ ” on the Tool Bar to open the
“System” dialog box. A check box “Running the real time alarm printer
service” (marked with red circle) can be found as the following figure.
Check or cancel this check box to enable or disable function of real-time
print. Modification of setting takes effect only when user closes the dialog
box by clicking the button “Close”. Dialog box “System” is as shown in
following figure.
“Shift” can be used too). Clicking the button “ ” to acknowledge the alarm
which means the operator has noticed the alarm message. The button “ ”
13
Real-time Monitoring Software
Click the icon “ ” on toolbar to open the “System Overview” windowl. The
2. Each block of message can be configured for signal point (tag) and
description, the index of standard display interface (system overview,
control grouping, trend display, graphics and data view etc) and
14
Real-time Monitoring Software
description.
5. Click the block of analog tag, customized SFloat tag, or loop, etc; it
would go to relevant tuning panel. Click the block of standard display
interface; it would go to relevant standard display interface.
Click the icon “ ” on toolbar to open the “Control grouping” display. In this
window, tags and loop information are shown by faceplate of tag operation.
Information mainly involves tag name (loop name), current tag value, alarm
status, histogram, tag type and tag description etc. Click tag name (loop
name) to open relevant turning trend (exclusive of digital variables) each
control grouping display is able to display maximum eight tag operational
faceplates. Data or status of signal tags can be modified by clicking mouse
in relevant position. Control grouping display is shown as follows:
15
Real-time Monitoring Software
In the window of operation station, many tag information are shown in the
form of an interface similar to conventional instrument. These interfaces are
called operational faceplates. Including analog input operational faceplate,
PAT data operational faceplate, digital input/output operational faceplate,
loop operational faceplate, digital variable operational faceplate, SFloat
operational faceplate, description operational faceplate and integer
operational faceplate.
Operator having the required authority can revise data. Once a value is
selected the entire field will be highlighted (white font and blue background)
allowing any entry to overwrite the entire field .We can use the ‘Esc’ key to
cancel the currently selection and restore the original value. Input value and
press “Enter” to confirm the change. Value can also be changed by the key
“Up” and “Down” in operator keyboard. Button such as
manual/auto/cascade and digital output status of loop operational faceplate
can be operated by mouse clicking. SV and MV of loop faceplate and
description status of description operational faceplate are controlled by
sliding bar. Left click (don’t release the mouse) and drag the sliding bar to a
position (value) needed, then release the mouse and press “Enter” to
confirm.
16
Real-time Monitoring Software
17
Real-time Monitoring Software
Item Specification
Data to be
Related to tag or loop type
displayed
18
Real-time Monitoring Software
Click the icon “ ” on toolbar to open turning trend. Tuning trend mainly
19
Real-time Monitoring Software
HH Analog input
HI Analog input
LO Analog input
LL Analog input
DZ Analog input
To be displayed when
Signal cutting Analog input evolution is
configured.
To be displayed when
Accumulate Analog input accumulative variable
is configured.
Revisable in the
MV Loop
manual status
DV Loop
Deviation Loop
P Loop
20
Real-time Monitoring Software
I Loop
D Loop
Executor Loop
Adjuster(Positive/
Loop
negative)
Cascade variable
Ratio signal ratio-multiplication
calculator
Cascade variable
Zoom coef. ratio-multiplication
calculator
Cascade variable
Offset ratio-multiplication
calculator
21
Real-time Monitoring Software
Cascade variable
Const ratio ratio-multiplication
calculator
Cascade variable
Multiplication
ratio-multiplication
calculator (Y/N)
calculator
Click the icon “ ” on toolbar to open trend display. The data would be
22
Real-time Monitoring Software
Click the button to stabilize the trend display, making it easy to view for
users. Click the button once again to restore the refreshing of trend pane.
These two buttons are used to display trend display of a previous page
or the next page.
3. Paging proportion “ ”.
dropdown box of “ ”.
The two buttons are used for enlarging or shortening the trend length of one
page. The more shortened the longer length of trend can be displayed on
one page.
23
Real-time Monitoring Software
Click the button “ ” to open a dialog box “Time and tag setting”. Within
effective range (Starting time shall be at least 100s earlier than ending time),
user can choose time range that is to be covered. Once the time range is
determined, a section of trend curve in this time period will be displayed in
trend display. Data number varies from 100 to 1200. “Location” can be
defined as inside or outside of the curve panel. “Display” (Interval for
displaying) shall be any integer from 1 to 10. And maximum eight tags can
be set in tab “Set tag”.
with which the display setting of the trend panel can be done.
24
Real-time Monitoring Software
Set Curve Chare: Set color, grid line and grid of curve.
8. Refreshing button “ ”
9. Print button “ ”
following figure:
25
Real-time Monitoring Software
In tab “Set Time”, user can set proper “Starting time”, “Ending time”, “Time
interval”, “Total data”, “Amount/page” to be printed; maximum 8 tags can be
set in the tab “Set Tag”; click the button “Print Description” to set printer
based on actual needs.
1.2.8 GRAPHICS
26
Real-time Monitoring Software
27
Real-time Monitoring Software
3. Right click the dynamic data; maximum five tag faceplate would be
visible in a graphics panel.
Real-time data including important system data and field data is presented
in the form of report in the report view to help engineers examine the
28
Real-time Monitoring Software
1. Report: The report displayed can be selected from the dropdown list by.
5. Input text: Click any cell in report page to input text. To delete all
contents in a cell, please select a cell (including configuration contents
contained in report), then press the key “Delete”. Texts of many cells
can not be deleted at a time. Please save text by clicking the button
“Save” when text is input, otherwise, input of text will be void.
following figure.
29
Real-time Monitoring Software
With the icon “ ”, user can turn to the next page among many pages of
the same type. With SCKey, many pages can be configured for each
standard panel. In operation, user can turn to the next page by clicking the
icon “Next page”.
30
Real-time Monitoring Software
Click the “Next page” button “ ” to turn to a next page among many
pages of the same type. Left click the icon “ ” to display page No. of all
pages of the type. Then, click the page to be turned to. Left click the icon
"Page Turn” as shown in the following figure:
If right click the icon “Page Turn”, name of all standard panels and graphics
will be displayed. When the mouse points at the name of any panel, all
pages in the panel will be shown. Click a page number to turn to the
relevant panel. Right click the icon “page tuning” as shown in the following
figure:
System operation icons are mainly for relevant operation of the system
including “Fault Diagnose”, “login password”, ”ACK alarm”, ”alarm sound
muting”, ”Exit System”, “Load configuration file” and “Operation record” etc.
31
Real-time Monitoring Software
System status of both hardware and software for control station is shown in
diagnosis display so as to determine the faults of the control station timely
32
Real-time Monitoring Software
3. Diagnosis of controller
To view detail information of the control station, user can double click “02”
icon, a message box would be popup in the Diagnosis Display. See
following figure:
33
Real-time Monitoring Software
34
Real-time Monitoring Software
redundant with each other; both of the two modules are out of operation.
User can view detail information of the data transmission module by double
click the icon shown above.
As viewed from the above figure, 02# data transmission module itself works
well and is in working status, 03# data transmission module itself works well
and is on standby.
Serial number (0#~15#) for I/O modules can be found on racks. “&”
represents two redundant I/O modules. See following figure, eight pairs of
redundant I/O modules have been configured.
35
Real-time Monitoring Software
Five indicators are shown in each I/O module, which from top to bottom
indicates operation status (blinking red indicator indicates operation failure
of module), work status (when the indicator is alight, the module is in work
status), standby status (when the indicator is alight, the module is on
standby), channel condition (when the indicator is alight, the channel is in
normal status, and when the indicator dims out, the channel is in failure)
and type matching (indicator being alight indicates module type matches
configuration, and being dark indicates module type doesn't match
configuration). Five indicators being dark indicate interruption of data
36
Real-time Monitoring Software
User can search history diagnosis information by time or control station. Set
starting time, ending time and control station, then click the button “Display”
to start searching. As shown in following figure:
37
Real-time Monitoring Software
30 records are listed in one page. To view more alarms, please click the
paging button at the bottom of the dialog box; click the button “Print” can
print diagnosis records. Diagnosis records can be classified into four types:
Notice, I/O, system and cleanup.
System failure refers to general faults of the control system, which includes
faults in configuration of the controller, clock, stack; communication port
self-test failure; memory data self-test error; mismatch of configuration for
two modules redundant with each other; communication controller software
version No. verification; fault in user programs, user stack, SCL language
program status; network bus failure; ROM self-test failure, standby
redundant module data copy failure; host cycle time overflow; dial failure;
network connection failure and default in data transmission module etc.
1.4.2 PASSWORD
monitoring software and set relevant options. Click the button “ ” to open
1. Name and level of current user are displayed in the dialog box
38
Real-time Monitoring Software
2. To change current user, please select user name from the dropdown list
of “Name” by click the drop down arrow symbol and then input correct
password.
3. Click the button “Option” to open a dialog box “Password Option”: (1)
used to define the default user upon the monitoring software was
started up; (2) select the user authority which is allowed to switch to
observe of the software, observe means no operation would be accept
in the monitoring interface .
4. Switch to observe: when current user has this authority (which can be
set in “Password option”), click the button “Switch to observe” to switch
any operation status to status of observe.
summary window.
1.4.4 MUTING
sounds of alarms would announce again, upon new alarm generated later .
39
Real-time Monitoring Software
Input current user password in the text box “Password”, then click the
button “Ok” to exit the AdvanTrol-Pro monitoring software.
To load and open a new operation team file, please click the “Load
figure.
40
Real-time Monitoring Software
Operation record dialog box consists two parts, one is record display area
at the top, and the other is tool bar at the bottom. For each type of operation
record, maximum 100,000 records can be saved. When there are more
than 100,000 records, the firstly generated 10,000 records will be deleted
so as to leave space for newly generated record information.
41
Real-time Monitoring Software
1. Advanced Search
42
Real-time Monitoring Software
Select different items in the dialog box shown above would get different
result..
43
Real-time Monitoring Software
2. Refresh
The second icon is the refresh icon “ ”. Click this button to refresh the
The third button “ ” is to find the latest record. Click this button, and one
page (100 records) of the latest record would be gotten from the database
and shown in the list.
Click the button “ ” to backup current search result. The system would
5. Print
The fifth button “ ” on the operation record toolbar is used for printing.
When there is more than one record searched out, this button would be
available. Click it to open a dialog box to set print range involved in search
result. Then, the selected records will be printed by system default printer.
6. Paging
The seventh, eighth, ninth and tenth buttons on the operation record toolbar
is used for paging, include “Go to the first page”, “Go to the previous page”,
“go to the next page” and “Go to the last page”. Operation records searched
out are displayed page by page with 300 records displayed in one page.
There are two message boxes in the operation record toolbar. The left one
is page number message box which shows the page number of the record.
44
Real-time Monitoring Software
The message box on the right side shows the status of operation records. It
indicates the total number of records searched out and status of operation
record function. If search of records is under processing, the message of
“Records X” (X is current number of the records) and “Search under
processing” will be shown; if search is completed, the message of “Records
X” and “Search ended” will be shown; if search is paused, the message
“Records X” and “Search paused” will be shown.
45
Real-time Monitoring Software
use right (Equipment name and user name) of the software. Besides,
system setting can be modified here. Dialog box “System “is as shown in
following figure.
If this item is selected, report will be printed based on the report output
setting in SCFormEx.
If this item is selected, newly generated alarm records will be printed one by
one.
Click the button “Alarm sound modify” to open a dialog box “Alarm Sound”.
Herein, user can set the amount of mixed sounds, the maximum amount is
ten. The volume can be adjusted by mouse drag operation, . Dialog box
“Alarm Sound“ is as shown in following figure.
46
Real-time Monitoring Software
Notes: the modification of mixed sound would valid after restart the
monitoring software.
Click the button “Open system service” to pop up the dialog box which
mainly to be used to show the information “System environment”,
“Real-time Browse”, “Trend records”, “Network info.”, and set “Time
synchronization”, “Close system” , “Shield HOTKEY”, “Print setting”, “User
management”, “Strategy management” and “Log on”.
47
Real-time Monitoring Software
1) System environment
2) Real-time browse
User can view configuration and real-time information of tags, events and
tasks. It qualifies user to assign value to tags, set writing switch and
alarm-enabling switch etc. See following figure.
48
Real-time Monitoring Software
3) Trend records
4) Network information
49
Real-time Monitoring Software
Click the button “Network info.” to open the interface “Operation Network
Management”, as shown in following figure.
50
Real-time Monitoring Software
In the above figure, name of data group is listed in the column “Data group”,
and addresses of operation nodes that function as corresponding roles of a
data group (column "Disconnect" shows address of corresponding
operation nodes of a data group) are listed in the column “Local
connection”, column “Client”, column “Server” and column “Disconnection”.
Notes: a master server is identified by a sign of “(master)” followed the IP,
and others are all redundant servers. As operation log relates to operation
node rather than data group, column “data group name” isn’t showing here.
51
Real-time Monitoring Software
“166” is the IP for the operation station, it functions as the real-time data
client end. For the moment, data from “165” is sending to “166”.There are
1952 tags whose data group numbered as 1, 2, 3, 4, 5, 6……
52
Real-time Monitoring Software
5) Time synchronization:
53
Real-time Monitoring Software
(1) Client
54
Real-time Monitoring Software
Note1: DCS can be connected to GPS Clock source, and the time of all
the operation nodes can be synchronized by SNTP (simple network
time protocol).
c) synchronizing period
The synchronizing period is optional as 3S, 5S, 30S, 2min, 5min and auto.
Software would self-adjust the synchronizing period basing on the time
deviation. When auto mode is configured as the synchronizing period, if
there is more time deviation, the smaller synchronizing period would be
automatic adjusted to shorten the deviation. Vice versa, if the less time
deviation, the bigger synchronizing period would be self-adjusted. The
self-adjusted scope is the same as mentioned above.
d) synchronizing precision
55
Real-time Monitoring Software
(2) Sever
56
Real-time Monitoring Software
When the sever is set as "control network", the clients which need to
synchronize the time with the sever must be set as "control network"
After the synchronizing sever is started up, the other clients can apply for
the time synchronization, the synchronizing precision would be less than 1S.
After the success of first synchronization, the synchronizing period of next
synchronization might be 5min, 2min, or the less period, lies on the
deviation of last synchronization.
The node wouldn't synchronize the time, if the disable time synchronization
57
Real-time Monitoring Software
is selected.
Note1: If user doesn't set anyone of the Client, Sever and Disable
synchronizing function, the following interface would pop up.
58
Real-time Monitoring Software
The function associate with the Clients and Sever function, it's suitable for
the structure which operation stations connected together and control
stations divided.
59
Real-time Monitoring Software
6) Close system
Click the button “Close system” to pop up a dialog box “System close”. To
exit the monitoring system, please input correct password.
7) Shielding HOTKEY
8) Print setting
Report printer is exclusively used for printing report. Bigger size paper
can be used for printing report, a line printer is suggested.
60
Real-time Monitoring Software
Trend printer is exclusively used for printing tend chart. To distinguish the
curves from each other easily, please use color printer.
Screen save printer is exclusively used for printing screen chart. In order to
ensure higher resolution of screen copy chart, please use color printer with
higher resolution.
9) User management
61
Real-time Monitoring Software
11) Log on
Click this button to Login the system, see the following figure.
62
Real-time Monitoring Software
The “Find tag icon” button “ ” is used to search I/O tag in the monitoring
Select “All types” in the column “Tag type”, and select corresponding control
station from the dropdown list beside “Controller”. When settings are
completed, click the button “Search” to display all search results in the list
box. Double click the tag name, it would be shown in control grouping
display (digital variable) or tuning trend (analog variable). The dialog box
“Find IO Tags” is as shown in following figure.
Select “Select types” in the column “Tag type” to display all tag types.
Select tag types (multiple choices) t, click the button “Find”, then the tags
which satisfy the search condition will be displayed in the list box. Double
63
Real-time Monitoring Software
click the name of the tag, it would be shown in control grouping display
(digital variable) or tuning trend (analog variable).
If input the name of tag in the text box “Tag”, only the tag with this name will
be displayed in the list box. Double click it to open the control grouping
display or tuning trend to view the search result.
Notes: If the tag searched for is analog input tag, loop tag or SCX
language analog variable tag, it will be displayed in the form of tuning
trend.
start straightly as soon as the button is clicked without any dialog box
popped up. Therefore, special attention is required when clicking this button
against improper operation.
64
Real-time Monitoring Software
The operator keyboard has 96 keys, which can be roughly grouped into
customizing key, function key, panel control key, screen control key, loop
control key, numeric key, alarm managing key and cursor movement key
etc, and redundancy is considered for some of important keys.
Function
F1~F12 Fn
key
System
Introduction
Panel Alarms
control overview
Chapter 1
System Profiles
Control
grouping
Tuning trend
Trend display
Graphics
Report
65
Real-time Monitoring Software
Data view
Password
Diagnosis
Turn page
Panel
Page up
control
Page down
Screen copy →
Screen
Save screen →
Dump
Recurrence of →
panels
Auto
Manual
Digital Up
Increase
Decrease
Fast Decreases
Up
Down
Cursor
movement
Left
Right
66
Real-time Monitoring Software
Alarms
acknowledgeme
Alarm nt
Operation
Muting
Cancel
Delete
Soft keyboard
Enter
0 0 Figure “0”
1 1 Figure “1”
2 2 Figure “2”
3 3 Figure “3”
Modify
parameter
4 4 Figure “4”
5 5 Figure “5”
7 7 Figure “7”
8 8 Figure “8”
9 9 Figure “9”
. . Characters “.”
- - Characters “-”
Custom
UD1~UD24
keys
67