Building Regulation Part A - 1997
Building Regulation Part A - 1997
Building Regulation Part A - 1997
T echnical
Gu idance
D ocu ment
Structure
Printed on
Recycled Paper 0ç DEPARTMENT OF THE
ENVIRONMENT
r This document
contains pages
Building Regulations 1997
Structure
iTTfliiiiaitiflfl-jrijflirrriiijfl
U:UuI.iI1IiIisiI'-'QJ!jsII1I1I1.i,iIIuIju
DEPARTMENT OF THE
ENVIRONMENT
© Governmentof Ireland 1997
C—
Contents
Page
Introduction 2
The Guidance
Existing Buildings
Technical Specifications
Materials and Workmanship
Interpretation
SECTION I
STRUCTURE- LOADING AND GROUND MOVEMENT
Introduction 4
Otherapproaches 5
Definitions
(a) safely,and
Ground movement. A2 A building shall be designed and constructed, with due regard to the theory and
practiceof structural engineering, so as to ensure that movements of thesubsoil
caused by subsidence, swelling, shrinkage or freezingwill not impairthe stabilityof
any part of the building.
Disproportionate A3 (I) A multi-storey building shall be designed and constructed, with due
collapse, regard to the theory and practiceof structural engineering, so as to ensure
that in the eventof an accident the structure will not be damagedto an
extent disproportionateto the cause ofthe damage.
"wind load" means all loads due to the effect ofwind pressure or suction.
3
Section I
Structure - Loading and Ground Movement
Section I
Structure - Loading and Ground Movement
Loading Al (I) A buildingshall be designed and constructed,with due regard to the theory
and practice ofstructural engineering, so as to ensure that the combrned
dead.imposedand wind loads are sustained and transmittedto the ground -
(a) safely,and
(2) In assessing whether a building complies with sub-paragraph (I), regard shall
be had to theimposed loads and wind loads to which it is likely to be
subjected in the ordinary course ofits use for the purposefor which it is
intended.
Part I - Basic requirements for stability. Cavity width - the horizontal distance between the
two leaves of a cavitywall.
Part 2 - Sizes of certain timber floor, ceiling and roof
members in houses with not more than two floors Compartment wall - A wall constructed as a
including the ground floor. compartmentwall to meet the requirements of Part
B of the Second Scheduleto the Building Regulations
Part 3 - Thickness of masonry walls in houses with - Fire Safety.
not more than two floors including the groundfloor.
Pier - A member which forms an integral part of a
Part 4 - Proportions for masonry chimneys above wall, in the form of a thickened section, so as to
the roof surface. afford lateral support to the wall to which it is
bonded or securely tied.
Part 5 - Strip foundations of plain concrete.
Separatingwall - A wall or part of a wall which is
Part I gives general rules which must be observed in common to adjoining buildings and constructed to
using Parts 2 and 3. Parts 2 to 5 may be used meet the requirements of Part B of the Second
independently of each other. Scheduleto the Building Regulations- Fire Safety.
Sub-section 2 is relevant to all building types and Spacing - The distance between the longitudinal
lists standards for structural design and construction centres of any two adjacent members of the same
but, where these do not give precise guidance, type, measured in the plane of floor, ceiling, roof, or
regard should be had to par. I .0. I. other partof the structure of which members form a
part.
Sub-section 3 provides guidance for recovering of
existing roof structures and the structural safety of Span - The distance measured along the centre line
externalwall cladding. of a member between the centres of any two
adjacent bearings or supports.
1.0.3 Other approaches- If otherapproaches
are adopted, it is essential to have regard to par. Note: The spans given in Part 2 of sub-section I of
1.0. I and to the following:- this Section for floor joists, rafters, purlins and
ceiling joists are as defined in SR I I : I 988.
(a) The numerical values of safety factors, whether
expressed explicitly or implicitly in design Supported wall - A wall to which lateral support is
equations or design values, should be derived afforded by a combination of buttressing walls, piers
from considerations of the aspects of design and or chimneys acting in conjunction with floor(s) or
construction given in par. 1.0. I as a whole. A roof.
change in any one of these aspects may affect the
safety of the structure.
I
Sub-section I I .1.2.3 The guidance given in this Part assumes that:
Sizes for Certain Structural (a) the dead and imposed loads to be sustained by
elements for Houses and other the floor, ceiling or roof of which the member
small buildings forms part do not exceed the values given in SR
II: 1988,
Part I - Basic requirements for (b) the species and grade of timber are those given
stability in SR II: 1988, and
1.1.1.1 This Part must be used in conjunction with (c) floorboarding complying with BS 1297: 1987 is
Parts 2 and 3 of this sub-section. used.
Wall ties Should comply with l.S. 268: 1987 1.1.3.8 Retained earth - Differences in level of
Metal Wail Ties for Masonry ground or other solid construction between one
Wal!s. side of the wall and the other must be less than four
timesthe thickness ofthe wall.
Maximum Loads
Limitations on Building Geometry
1.1.3.6 Vertical loads - The vertical imposed
loads should not exceed the following: 1.1.3.9 Residential buildings (see Diagram 2)
Element Loading (a) No part of any wall or roof should be more than
Roof Distributed load 0.75 kN/m2. I 0 m above the lowest adjacent ground level.
Floors Distributed load 1.50 kN/m2.
Ceilings Distributed load 0.75 kNIm2. (b) The width of the building should not be less than
halfthe height of the building.
1.1.3.7 Wind loads - Diagram I shows Ireland
divided into three wind zones, A, B and C. The (c) The width of a wing should not be less than half
divisions between the zones relate roughly to the 44 the height of the wing when the projection P
m/s and 47 m/s gust speed contours of the map exceeds twicethe width W2.
issued by Met Eireann.
.1.3.10 Floors should be as described below:
The design wind speed (Vs) determined in
accordancewith CP3: Chapter V: Part 2:1972 as (a) Ground floors -
amended in 1986 should not exceed 44 m/s. This Timber floors or ground supported concrete
condition will normally be satisfied if the building site floors or suspended concretefloors of maximum
is located in: span 5 m.
Zone B: On normal or slightly sloping sites in 1.1.3.1 I The floor to floor and ceiling to ceiling
open country side with scattered heights should not exceed 2.7 m.
windbreaks or in country with many
windbreaks or in towns or cities. 1.1.3.12 The roof span should not exceed 12 m.
Zone C: In country with many windbreaks or Lateral Support and End Restraint
in towns or cities.
.1.3. I3 The ends of every load-bearing wall should
be bonded or otherwise securely tied throughout
91
Diagram 2 SIzeand proportion Par.!. L3.9 Diagram 3 Size of openings Par. 1.1.3.14
of buildings and recesses
MAXIMUM HEIGHT
Pu Wi Wi Wi
.
NottoexceedlOm
Window Thickness i
Door reducing
recess
Lowest ground level
MINIMUMWIDTH
Wu
n
KWI
K
L
I N Wi
4. Psshould be greater than or equal to Wi+ Wi
3
10
(f) the buttressing wall is properly bonded to a
Diagram4 Piers and Par. 1.1.3,15
storey height wall, pier or chimney at the
chimneys opposite side of the opening to the supported
MINIMUM DIMENSIONS wall,
(a) the opening is in the ground storey of an I . I .3.20 Openings and thickness-reducing recesses
externalbuttressing wall, in walls should not exceed 2.4 m in height (see also
par. 1.1.3.21).
(b) the opening does not exceed 2.4 m in height,
I. I .3.21 Dimensional criteria for chases -
(c) the supported wall is restrained at first floor
level or, where the building is a single storey (a) Chasesshould not impairthe stability ofthe wall.
Chases are not allowed when using hollow
building, at roof level,
blocks.
(d) the supported wall is properly bonded to the
buttressing wall belowthe ground floor level, (b) Horizontal chasesshould not be deeper than 116
of thethickness of the leaf.
(e) the supported wall is bonded to the buttressing
wall above the opening by a beam or lintel (c) Vertical chases should not be deeper than 1/3 of
spanning the opening in the buttressing wall, thethickness of the leaf.
II
Diagram S Unbuttressed wall sections Par.I.I.3.17
E
p
DEE
Unbuttressedsectionof
gable wall
EEl
i:J
Not more than 3 m
5(b)DIMENSIONALLIMITATIONSOF UNBUTTRESSED SECTIONS
LILI
Supported wall properly
bonded to the buttressing
wall below ground floor
i___
:1:::::::
5(d)BONDING OF SUPPORTED WALL BELOWGROUND FLOOR LEVEL
Supported wallbondedto
buttressing wall above
opening by beam or lintel.
___
Supportedwall 3 m maximum
::::::Florimr>
5(f) BONDING OF BUTTRESSINGWALLAT OTHER SIDB OF OPE
Storeyheightwall
Minimum
T
Not more than 5.5 m
13 m maximum
5(h)BEARINGLENGTHS FOR
BEAMS OR LINTELS
13 I
Interaction of Elements (a) has a pitch of less than 15°, and
(i) 90 mm bearing on the supported walls, or 1.1.3.27 Wall ties should be provided in cavity
walls. In conditions of severe exposure, austenitic
(ii) 75 mm bearing on a timber wall plateat each stainless steel or suitable non-ferrous ties should be
end, used. The minimum quantity of ties provided should
be 2.5 per square metre for cavities of 50 - 75 mm
(b) where the joists are carried on the supported width and 3 per square metre for cavities of 76 - 110
wall by joist hangers of the restraint type mm. Extra wall ties are required at the jambs of
described in l.S. 325 and shown in Diagram 6 (c), openings as shown in Diagram 9 (for definitions of
at not more than 800 mm centres, severe exposure and for use of ties in other cavity
widths, see I.S. 325: Part 2).
(c) where floors are at or about the same level on
each side of a supported wall as shown in
Diagram 6 (d) and contact between floors and
wall is continuous or at intervals not exceeding
2 m. Where contact is intermittent, the point of
contact should be in line or nearly in line.
Il*1
1
Ia
i
mm Noggingto
extend at
(c)
IIlLtr .
H+
lr
F.
FW
lN
I*
I
tk*
+
_____________________
Is
Diagram 7 Lateralsupportat roof level Par. 1.1.3.25
strap
Supportedwall
Opening
'wall
___________ — —
PLAN
Connectionprovided by timber bearing on
wall or by restrainttype joist hanger.
t more
Supportedwall
PLAN Packs
I>Packs
—Straps
PLAN
'7 I
Dtagram9 Spacingofwallties Par 11327
[
J
I
I..
I
Part 4 - Proportions for masonry Part 5 - Strip foundations of plain
chimneys above the roof surface concrete
Heightto width relationship Conditions relating to the Subsoil
1.1.4.1 Where a chimney is not supported by 1.1.5.1 There should not be -
adequate ties or otherwise made secure, its height
(H), measured from the level of the highest point of (a) made ground or wide variation in type of subsoil
intersection with the roof surface, gutter or other within the loaded area, or
part of the building and including any flue pot or
terminal, should not be more than X times W (b) weaker type of soil at such a depth below the
where: soil on which the foundation rests as could
impairthe stabilityof the structure.
X = 4.SinwindzoneA
X = 4.0 in wind zone B Design provisions
X = 3.5 in wind zone C.
1.1.5.2 The following design provisions relate to
W is the least horizontal dimension of the chimney foundations -
measured at the same point of intersection
(see Diagram I 0). (a) the foundations should be situated centrally
under the wall,
Notes:
The zones are described in Diagram I. (b) strip foundations should have minimum widths in
accordance with par. I. 1.5.3,
The proportions given in this paragraph are intended
for general application. More slender chimneys may (c) concrete should be composed of cement to
be built if they can be shown by calculation to be l.S. I: 199 I and fine and coarse aggregate
stable in the particular wind environment of the conforming to l.S. 5: 1990 and be one of the
building. followinggrades -
Foundation width
should be not less
than the appropriate
STRIP FOUNDATION dimension in Table I
30 40 50 60 70
Type ofsubsoil Condition of Field test Minimum width ofstrip foundation (mm)
subsoil applicable
rock not inferior to requiresat least a In each case the width (wt) ofwall pIus 150 mm
sandstone, pneumatic or other
limestone or mechanically operated
firm chalk pick for excavation
Ill
clay stiff cannotbe moulded withthe 400 400 500 600 650
sandy clay stiff fingers and requiresa pickor
boulder clay stiff pneumatic or othermechanically
operated spadefor its removal
IV
clay firm can be mouldedby substantial 400 450 500 600 650
sandy clay firm pressure withthe fingers
boulderclay firm and can be excavated with
a spade
V
sand loose can be excavated witha spade.
silty sand loose A wooden peg 50 mm square in
clayey sand loose cross section can be easily driven
boulderclay loose
VI Note:
silt soft
soft
irly easily mouldedin the Wherethere is any doubt as to the condition of
clay fingers and readily excavated the subsoil, and always in the case of subsoil types
sandy clay soft V, VI and VII, an appropriatesite investigation, on
silty clay soft which the foundationdesign can be based,
is essential.
VII
silt very soft naturalsample in winter
clay very soft conditionsexudes between
sandy clay very soft fingers when squeezed in
silty clay very soft fist
In no case should the widthofthe foundationbe less than the totalwidthof the wall plus 75 mm on each side.
211
Sub-section 2 Foundations - general
Design and Construction of all
BS8004: 1986
BS 6399 : Part 3 (For imposed roof loads and using SR II: 1988
the snow load map in Diagram 14) BS5268:Part2: 1991
22
Building Research Establishment Digest 366:
Structuralappraisal of existing buildings for change of
use.
23 I
Diagram 14 Basic snow load on the ground in kN/m2 Par. 1.0.!
Ground level assumed to be 100 m above mean sea level (produced on the basis of snow depth data supplied by
Met Eireann).
24
Diagram 15 Wind speeds Par. LO.I
50
45
48 46
47
Estimated maximum gust speed (mis)with return period 50 years. Validfor a height of JO m above openlevel country.
(Data supplied by Met Eireann).
25
Sub-section 3 Structural safety of external wall
Recovering of Existing Roof cladding
Structures and Structural Safety of General
External Wall Cladding
1.3.2 The remainder of this sub-section includes
guidance for the design and construction of external
Recoveringof existing roofstructures wall cladding. The guidance is applicable to cladding
which by reason of weight or height would presenta
1.3.1 Where new roof coverings would impose hazard if it became detached from the building. For
higher loads on the roofstructure or where the new the purposes of this section, cladding is deemed to
material would be lighter than the original material, include glazed curtain walling but not windows.
strengthening measures may be required. The
followingprocedure is recommended: 1.3.3 These provisions are not intended to
provide guidance concerning the weather resistance
(a) arrange for a thorough structural survey of the of wall cladding which is included in Technical
existing roof structure and the vertical restraints, Guidance DocumentC.
(b) check the dry mass per unit areaof the proposed 1.3.4 Wall cladding should be capable of safely
roof covering and compare it with that of the sustaining and transmitting to the supporting
existing roof covering, structure of the building all dead, imposed and wind
loads.
(c) make allowance for the increase in load due to
water absorption, e.g. 0.3% for oven dry slates 1.3.5 Wall cladding should be securely fixed to and
and up to 10.5% for clay plain tiles and concrete supported by the supporting structure of the
tiles, building. This should comprise both vertical support
and hold back restraint.
(d) check if the roofstructure is capable of
sustaining the increased load or if the vertical I .3.6 Provision should be made, where necessary,
restraints provided to the roof structure are to accommodate differential movement of the
adequate for the wind uplift (the uplift may result cladding and the supporting structure of the building.
due to the use of lighter roofing material and/or
provisionof new underlay), 1.3.7 The cladding and its fixings should be of
durable materials, the anticipated life of the fixings
(e) provide appropriatestrengthening measures such being not less than that of the cladding. Where the
as: fixings are not readily accessible for inspection and
maintenance, particular care will be required in the
(i) replacement of defective members and choice of materials and standard of workmanship to
vertical restraints, be achieved (see Technical Guidance DocumentD).
26
derived from a consideration of the equipment likely (b) The mean of the loads which cause a
to be used. displacement of 0. I mm under direct tension and
1.0 mm underdirectshear.
1.3.9 Where the wall cladding is required to
support other fixtures, e.g. antennae, signboards, The design of certain resin bonded fixings should
etc., full account should be taken of the loads and take account of their rapid loss of strength at
forces arising from such fixtures. temperatures above 50°C.
1.3.10 Where the wall cladding is required to The componentparts of mechanical fixings should be
function as pedestrian guarding to a stairway, ramp, lockable or be otherwise mechanicallyfixed together
vertical drop or vehicle barrier, then account should to preventunintended slippage between the parts.
be taken of the additional imposed loading, as
stipulated in Technical Guidance DocumentK.
1.3.15 Movement - Guidance is given in BS
I .3.1 I For sports stadia, imposed loading should be 8200: 1985 and l.S. 325: Part 2: 1995 on the means
that stipulated in Table 3 of BS 6180, where the wall of providing for the differential movementofthe wall
cladding is required to function as pedestrian cladding and the supporting structure ofthe building.
guarding.
27
Timber cladding
BS5268: Part2: 1991
Glass cladding
8S5516: 1991
28
Section 2
Disproportionate Collapse
Disproportionate A3 (I) A muki-storey buildingshall be designed and constructed with due regard
collapse. to thetheoryand practiceofstructural engineering,so asto ensure that in
theeventofan accidentthe structure will not be damagedto an extent
disproportionateto the causeofthe damage.
Additional information
2.2 Structuralfailure of any membernot designed as
a protected key element or member in any one
storey should not result in failure of the structure
beyond the immediately adjacent storeys or beyond
an areawithin those storeys of:
(a) 70 m2, or
29
Standards and other references
l.S. I: 1991 Portland Cement BS 5268: Structural use of timber Part 6: Code of
practice for timber frame walls Section 6.1: 1988
l.S. 5: 1990 Aggregates for Concrete Dwellings not exceeding three storeysAMD 6743
l.S. 20: 1974 Concrete Building Blocks BS5390: 1976 (1984) Code of practice for stone
masonry AMD 4272
l.S. 20: Part I: 1987 Concrete Building Blocks,
Part I Normal DensityBlocks BS 5427: 1976 Code of practice for performance
and loading criteria for profiled sheeting in building
l.S. 91: 1983 Clay Building Bricks
BS 5516: 1991 Code of practice for design and
l.S. 189: 1974 Concrete Building Bricks installation of sloping and vertical patentglazing
IS. I 90: 1974 Calcium Silicate Building Bricks BS 5628:Code of practice for use of masonry Part
2:1985 Structuraluse of reinforcedand prestressed
l.S. 193: 1986 Timber Trussed Rafters for Roofs masonry
l.S. 240: 1980 Precast Prestressed Concrete Units BS 5950: Structural use of steelwork in building Part
for use in CompositeLintels I: 1990 Code of practice for design in simple and
continuous construction: hot rolled sections
I.S. 268: 1986 Metal Wall Tiesfor Masonry Walls AMD 6972
l.S. 325:Code of Practice for Use of Masonry Part I: BS 5950: Structural use of steelwork in building Part
I 986 Structural Use of UnreinforcedMasonry 2: 1992 Specification for materials, fabricationand
erection: hot rolled sections AMD 7766
Code of Practice for Use of Masonry Part 2:
l.S. 325:
1995 Masonry Construction BS 5950: Structural use of steelwork in building
Part 3: Design in composite construction Section
IS. 326: 1995 Concrete 3.1: 1990 Code of practice for design of simple and
continuous composite beams
l.S. 406: 1987 Masonry Mortars
BS 5950: Structural use of steelwork in building Part
SR II:
1988 Structural Timber for Domestic 4: 1994 Code of practice for design of composite
Construction slabs with profiled steel sheeting
BS 1297: 1987 Specification for tongued and BS 5950: Structural use of steelwork in building
grooved softwood flooring Part 5: 1987 Code of practice for design of cold
formed sections AMD 5957
BS 4471: 1987 Specification for sizes of sawn and
processed softwood AMD 8901 BS 5950: Structural use of steelwork in building Part
6: I 995 Code of practice for design of light gauge
BS 5080: Part I: 1993 Method of test for tensile profiled steel sheeting
loading
BS 6 I 80: I 995 Code of practice for barriers in and
BS 5080: Part 2: 1986(1993) Method for about buildings
determination of resistance to loading in shear AMD
7602 Code of practice for glazing buildings
BS 6262: 1982
AMD 4063; AMD 4582; AMD 8279
BS 5268: Structural use of timber Part 2: 1991
Code of practice for permissible stress design, BS 6262: Glazing for buildings Part 4: 1994 Code of
materials and workmanship AMD 8597 practicefor safety Human impact
30
BS 6399: Loading for buildings Part I: 1984 Code
of practice for dead and imposed loads AMD 4949;
AMD 5881;AMD 6031
3'
ISBN 0-7076-3771-6
li
9 780707 637716
"(-I