GENERAL NOTES :

1. ALL ELECTRICAL WORKS SHALL COMPLY WITH THESE PLANS AND SPECIFICATIONS. THE APPLICABLE
PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC), THE RULES AND
REGULATIONS OF THE LOCAL ENFORCING AUTHORITY AND THE REQUIREMENTS OF THE LOCAL
POWER COMPANY.

2. THE ELECTRICAL SERVICE POWER SHALL BE 1-PHASE,2-WIRE,230V AC, 60Hz.

3. WIRING METHOD SHALL BE AS FOLLOWS:


RIGID STEEL CONDUIT OR POLYVINYL CHLORIDE CONDUIT SCHEDULE 40 SHALL BE USED AS
SPECIFIED IN THE PLAN.

1 2 4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THHN" UNLESS OTHERWISE

450
INDICATED IN THE PLAN. THE MINIMUM SIZE WIRE FOR POWER AND LIGHTING CIRCUIT
GROUND TERMINAL BLOCK

5. ALL OUTLET BOXES SHALL BE GALVANIZED GAGE NO. 16 DEEP TYPE.

6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED FOR THE PARTICULAR
LOCATION AND USAGE.

9730 7. EQUIPMENT GROUNDING SYSTEM SHALL BE PROVIDED TO THE ELECTRICAL SYSTEM AS PER
= 33.84 AMPERES
I L= (.80)
230 (55A/33.84A)
FLUORESCENT LIGHT PHILIPPINE ELECTRICAL CODE REQUIREMENT.

3 PANEL BOARD DIAGRAM 4 FIXTURE MOUNTING DETAIL 8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS:
a. LIGHT SWITCH - 1.20M ABOVE FINISH FLOOR
b. CONVENIENCE OUTLET - 0.3M ABOVE FINISH FLOOR
EE-1 NOT TO SCALE EE-1 NOT TO SCALE
9. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A
DULY REGISTERED ELECTRICAL ENGINEER.

LEGEND

- 1-18 WATTS COMPACT FLUORESCENT LAMP WITH MEDIUM BASE,


KEYLESS TYPE PORCELAIN RECEPTACLE

1 - 1 x 36 WATTS FLUORESCENT LIGHTING FIXTURE, BOX TYPE

2
- 2 x 36 WATTS FLUORESCENT LIGHTING FIXTURE, BOX TYPE WITH
CANOPY BASE AND STEM 1.5 FT. (450mm) LENGTH SIMILAR TO AMCO
AP-1113-1.5 OR APPROVED EQUAL
I @ 85% DF
L 2
- 2 x 36 WATTS FLUORESCENT LIGHTING FIXTURE, BOX TYPE
5602
I L= 0.85 = 20.70 AMPERES
230 (40A/20.70A) WF - WALL FAN OUTLET

- SINGLE POLE WALL SWITCH

- DUPLEX SWITCH, 2 SINGLE POLE SWITCHES ON ONE-GANG SWITCH


PLATE

- THREE WAY WALL SWITCH

- FAN CONTROL SWITCH


- RACEWAY CONDUIT CONCEALED IN CEILING

- RACEWAY CONDUIT CONCEALED UNDER FLOOR

- PANELBOARD, MARKED AS "LP"

- CKT. BREAKER, RATING AS INDICATED

- DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE 15 AMPS,


240 VOLT

WP - WEATHERPROOF DUPLEX CONVENIENCE OUTLET,


GROUNDING TYPE,15 AMPS, 240 VOLT

- CIRCUIT HOMERUN
5000mm

I @ 80% DF - ENCLOSED AIR CIRCUIT BREAKER


L
1800mm

4128
I = 0.80 = 14.36 AMPERES - FIRE ALARM CONTROL PANEL
L 230 (55A/14.36A) FA

F - FIRE ALARM STATION OUTLET

B - FIRE ALARM BELL

M - SERVICE METER

1 LOAD SCHEDULE - SERVICE ENTRANCE


MDP
EE-1 NOT TO SCALE
2 ELECTRICAL RISER DIAGRAM - MAIN DISTRIBUTION PANELBOARD

EE-1 NOT TO SCALE

VARIOUS DPWH GENERAL NOTES, LEGEND,


(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET) PROPOSED PROJECTS FLUORESCENT LIGHT BOD
FIXTURE MOUNTING DETAIL, 33
NOTE : ADOPTED FROM DEPED STANDARD PLANS STANDARD FOUR-STOREY LOAD SCHEDULE, EE-1
GILBERTO S. REYES RAUL C. ASIS ROGELIO L. SINGSON 38
SCHOOL BUILDING PANEL BOARD DIAGRAM AND
OIC, BUILDINGS DIVISION DIRECTOR IV, BOD UNDERSECRETARY SECRETARY ELECTRICAL RISER DIAGRAM
( 4-CLASSROOMS )