ECC-50DA Battery Calculation: Secondary Power Source Requirements

This document provides a battery calculation for an ECC-50DA fire alarm system. It lists the standby and alarm current draws for various system components and calculates the total current loads. It then determines the required standby and alarm times in hours and amp-hours. The final recommended battery based on a derated total amp-hour load of 0.00 amp-hours is the BAT-1270 7AH battery.

Uploaded by

Fire Chile
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
120 views1 page

ECC-50DA Battery Calculation: Secondary Power Source Requirements

This document provides a battery calculation for an ECC-50DA fire alarm system. It lists the standby and alarm current draws for various system components and calculates the total current loads. It then determines the required standby and alarm times in hours and amp-hours. The final recommended battery based on a derated total amp-hour load of 0.00 amp-hours is the BAT-1270 7AH battery.

Uploaded by

Fire Chile
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

ECC-50DA Battery Calculation

Secondary Power Source Requirements


Standby Current (amps) Secondary Alarm Current (amps)
Device Type Qty Current Draw Total Qty Current Draw Total
1. System
ECC-50DA (25V)* 0 X 0.0850 = 0 X 0.5250 =
ECC-50DA (70.7V)* 0 X 0.1000 = 0 X 0.5800 =
ECC-CE4 0 X 0.0200 = 0 X 0.1800 =
2. Speakers
Enter Number of Watts @ 25Vrms 0 X 0.0000 = 0 X 0.0400 =
Enter Number of Watts @ 70.7Vrms 0 X 0.0000 = 0 X 0.0450 =

Total Standby Load 0.0000 Total Alarm Load 0.0000


* Select only ONE type of Amplifier

ECC-50DA Battery Calculation


Calculation in Total Sheet
Required Standby Time in Hours
24 Hours
Standby Load Current (Amps) 0.0000 Amps X 24 = 0.000 AH
Required Alarm Time in Hours
15 Minutes
Alarm Load Current (Amps) 0.0000 Amps X 0.25 = 0.000 AH
Total Current Load 0.00 AH
*Multiply by the Derating Factor 1.2 = x 1.20

Total Ampere Hours Required 0.00 AH

Recommended Batteries: BAT-1270 - 7AH Batteries

* Derating Factor required to compensate for the non-linear discharge characteristic of a battery.

Fire-Lite Alarms Page 1 09/13/2021