411UDAC Battery Calculation: Secondary Power Source Requirements

The document is a battery calculation for a fire alarm system that includes a main circuit board and notification appliances. It lists the current draw of different components in both standby and alarm modes. It then calculates the total standby and alarm load currents. Based on the required standby and alarm times, it determines the total amp-hours required is 3.62 amp-hours. It recommends using a 7AH battery and notes the batteries can be charged and housed in the specified equipment cabinet.

Uploaded by

Fire Chile
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
64 views1 page

411UDAC Battery Calculation: Secondary Power Source Requirements

The document is a battery calculation for a fire alarm system that includes a main circuit board and notification appliances. It lists the current draw of different components in both standby and alarm modes. It then calculates the total standby and alarm load currents. Based on the required standby and alarm times, it determines the total amp-hours required is 3.62 amp-hours. It recommends using a 7AH battery and notes the batteries can be charged and housed in the specified equipment cabinet.

Uploaded by

Fire Chile
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

411UDAC Battery Calculation

Secondary Power Source Requirements


Standby Current (amps) Secondary Alarm Current (amps)
Device Type Qty Current Draw Total Qty Current Draw Total
1. System
Main Circuit Board 1 x 0.125000 = 0.125000 1 x 0.180000 = 0.180000
2. Notification Appliances
NAC Device 1 0 x 0.000000 = 0 x 0.000000 =
NAC Device 2 0 x 0.000000 = 0 x 0.000000 =
NAC Device 3 0 x 0.000000 = 0 x 0.000000 =
NAC Device 4 0 x 0.000000 = 0 x 0.000000 =
NAC Device 5 0 x 0.000000 = 0 x 0.000000 =
NAC Device 6 0 x 0.000000 = 0 x 0.000000 =
NAC Device 7 0 x 0.000000 = 0 x 0.000000 =
NAC Device 8 0 x 0.000000 = 0 x 0.000000 =
NAC Standby Draw 0.000000 NAC Alarm Draw 0.000000
3. Resettable Power
4-Wire Detectors 0 x 0.000000 = 0 x 0.000000 =
Additional Draw 12VDC Resettable 0 x 0.000000 = 0 x 0.000000 =
Resettable Standby Draw 0.000000 Resettable Alarm Draw 0.000000
4. Additional Devices
EOLR-1 0 x 0.020000 = 0 x 0.020000 =
Auxiliary Device 1 0 x 0.000000 = 0 x 0.000000 =
Auxiliary Device 2 0 x 0.000000 = 0 x 0.000000 =
Auxiliary Device 3 0 x 0.000000 = 0 x 0.000000 =
Auxiliary Device 4 0 x 0.000000 = 0 x 0.000000 =
Auxiliary Device 5 0 x 0.000000 = 0 x 0.000000 =

Total Standby Load 0.125000 Total Alarm Load 0.180000

411UDAC Battery Calculation


Calculation in Total Sheet
Required Standby Time in Hours
24 Hours
Standby Load Current 0.12500 Amps x 24 = 3.000 AH
Required Alarm Time in Minutes
5 Minutes
Alarm Load Current (Amps) 0.18000 Amps x 0.084 = 0.015 AH
Total Current Load 3.015 AH
Multiply by the Derating Factor 1.2 = x 1.20

Total Ampere Hours Required 3.62 AH


Recommended Batteries: BAT-1270 - 7AH Battery

Battery Check
The batteries can be charged by the 411UDAC Charger.
The batteries can be housed in the 411UDAC Cabinet.

Current Draw Check


NAC#1 current is within the limitations of the circuit.
411UDAC Control Panel:
The output current is within the panel's limitations.

Fire-Lite Alarms Page 1 09/13/2021