Process Control Understanding The Basics

The document discusses the basics of process control. Process control involves measuring process variables like temperature and pressure, comparing the measurements to set points, and taking action to correct any deviations. This occurs through control loops that measure variables, decide what adjustments are needed, and act on that decision. Good process control requires understanding variables, tuning control loops, and using symbols like those defined by ISA to design control systems.

Uploaded by

Armand Muteb Amk
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views

Process Control Understanding The Basics

The document discusses the basics of process control. Process control involves measuring process variables like temperature and pressure, comparing the measurements to set points, and taking action to correct any deviations. This occurs through control loops that measure variables, decide what adjustments are needed, and act on that decision. Good process control requires understanding variables, tuning control loops, and using symbols like those defined by ISA to design control systems.

Uploaded by

Armand Muteb Amk
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Process Control – Understanding the Basics

The difference between good control and bad control is the difference between success and failure. Process control
begins with understanding your process variables. In manufacturing, a wide number of variables from temperature to
flow to pressure can be measured simultaneously. All of these can be interdependent variables in a single process.
Controlling each variable manually would be difficult, time-consuming, prone to
mistakes and potentially hazardous. Fortunately, process control simplifies complex
tasks, reduces variability and ensures the safety of your workers and equipment. Common process variables include:

All process control loops work in the same way, requiring three tasks to occur: Pressure
Flow
 Measure – measure the right parameters accurately and quickly Level
 Decide – what to adjust and by how much Temperature
Density
 Act – quickly act on the decision before the process goes further out
pH
of control Mass
Conductivity
Let’s look at a basic example. A level
sensor measures the level in a tank and
transmits a signal associated with the level
reading to a controller. The controller compares the reading to a pre-
determined value. If the level is low, the controller sends a signal to the valve
on the feed line. The valve opens to add product to the tank and bring the
level back to the correct position.

Many different instruments and devices may be used in control loops


(transmitters, sensors, valves, pumps, etc.) but the three basic steps are
always used.

Good control decisions are made by applying your process knowledge. The
control loop needs to be “tuned” for the best response. Too little correction
and you have no impact. Too much correction may result in damage to the
controls, the equipment or the product.

Let’s define a few other terms commonly used in process control.

Set Point – the value for a process variable that is desired to be maintained. For example, if a process temperature
needs to be kept within ±5°C of 100°C, then the set point is 100°C. Set points can also be maximum or minimum values.

Greensboro Division / Corporate Headquarters Louisville Division Nashville Division


Phone: 336.393.0100 / 800.334.0231 Phone: 502.459.7475 / 800.459.7475 Phone: 615.822.3030 / 855.749.4820
Fax: 336.393.0140 Fax: 502.459.7633 Fax: 615.822.3031

www.mgnewell.com [email protected] [email protected]


Error – the difference between the measured variable and the set point. The error can be either positive or negative. In
our example, if the measured temperature is 108°C, then the error is +8°C.

Duration – the length of time that an error condition exists

Offset – a sustained deviation of the process variable from the set point. For example, if our control system held the
temperature at 100.5°C consistently (even though the set point was 100.0°C), then an offset of 0.5°C exists.

Load Disturbance – an undesired change in one of the factors that can affect the process variable. For example, the
addition of cold water to the tank would be a load disturbance because it lowers the temperature of the process fluid.

Closed and Open Control Loops – a closed control loop exists where a process variable is measured, compared to a set
point and action taken to correct any deviation. An open control loop exists where action is taken without regard to
process variable conditions. For example, a water valve may be opened to add cooling water to a process based on a
pre-set time interval, regardless of the actual temperature of the process fluid.

ISA Symbols
The Instrumentation, Systems and Automation Society (ISA) is one of the leading
process control standards organizations. They have developed a series of
symbols for use in engineered drawings and design of control loops. Drawings
using these symbols are known as Piping and Instrumentation Drawings (P&ID).

In P&ID drawings, these symbols represent measurement instrumentation,


controls, piping, equipment and the process variable being measured. Below is a
quick reference guide for commonly used symbols:

A circle represents individual measurement instruments,


such as transmitters, sensors and detectors.

A single horizontal line indicates that the instrument is


located in a primary location (i.e. control room). A double
line indicates an auxiliary location. No line indicates that it
is field-mounted and a dotted line indicates that the
instrument is inaccessible (i.e. behind a panel board).
A square with a circle inside represents instruments that
both display readings and perform some control function.

A hexagon represents computer functions, such as those


carried out by a controller.

A square with a diamond inside represents PLC’s.

www.mgnewell.com [email protected] [email protected]


A ‘bow tie’ shape represents a valve in the piping. An
actuator is always drawn above the valve to indicate
whether it is pneumatic, manual or electric.

Pumps are represented with this symbol. Directional


arrows show the flow direction.

Piping and connections are represented with several


symbols: a heavy line for piping; a thin solid line for
process connections to instruments, etc. A full list of
piping listings can be found on the ISA site.

Identification letters indicate the variable being measure


(flow, temperature, etc) and the device function
(transmitter, sensor, valve, etc).
The tag number references the specific control loop.

The figure below is an example of several elements of these symbols being used in a P&ID.

For a complete listing of ISA symbols and identification letters, visit www.isa.org.