Condensadora TSA 3 - 5 Guia Tecnica LENNOX
Condensadora TSA 3 - 5 Guia Tecnica LENNOX
Condensadora TSA 3 - 5 Guia Tecnica LENNOX
TS
T−CLASS™ SPLIT SYSTEM UNITS
Standard Efficiency - R-410A - 60 HZ
Bulletin No. 210461
P R O D U C T S P E C I F I C AT I O N S March 2016
Supersedes August 2015
SEER up to 14.50
3 to 5 Tons
Cooling Capacity - 33,400 to 92,000 Btuh
MODEL NUMBER IDENTIFICATION
T S A 036 S 4 N 4 1 Y
Brand/Family Voltage
T = T-Class™ Product Line Y = 208/230V-3 phase-60hz
G = 460V-3 phase-60hz
J = 575V−3 phase−60hz
Unit Type
S = Split System Air Conditioner
Minor Design Sequence
1 = 1st Revision
Major Design Sequence 2 = 2nd Revision
A = 1st Generation 3 = 3rd Revision
B = 2nd Generation
Coil Type
Nominal Cooling Capacity − Tons 4 = Four-Sided
036 = 3 Tons
042 = 3.5 Tons
048 = 4 Tons Part Load Capability
060 = 5 Tons N = No part load, Single Circuit
CONTENTS
AHRI System Matches............................................... 10
Dimensions................................................................... 7
Electrical Data.............................................................. 6 E
Features....................................................................... 2
Installation Clearances................................................. 8
Model Number Identification......................................... 1 B
Optional Accessories.................................................... 6
Optional Conventional Temperature Control Systems.. 5
Sound Data................................................................... 8 C
Specifications............................................................... 6
WARRANTY D
Compressor - Limited warranty for five years.
All other covered components - One year.
Refer to Lennox Equipment Limited Warranty certificate
included with unit for specific details.
F
APPROVALS
Certified in Accordance with the USE certification
program, which is based on AHRI Standard 210/240-
2008.
Sound rated in Lennox reverberant sound test room
in Accordance with test conditions included in AHRI
Standard 270-2008.
Tested in the Lennox Research Laboratory
environmental test room. REFRIGERATION SYSTEM
Rated According to U.S. Department of Energy (DOE) R-410A Refrigerant
test procedures. Non-chlorine, ozone friendly, R-410A.
Units and components within bonded for grounding to Unit pre-charged with refrigerant.
meet safety standards for servicing required by UL, See Specification table.
NEC and CEC.
Units are ETL certified for the U.S. and Canada. B Outdoor Coil Fan
Direct drive fan moves large air volumes uniformly
ISO 9001 Registered Manufacturing Quality System. through entire condenser coil for high refrigerant cooling
APPLICATIONS capacity.
SEER up to 14.50. Vertical air discharge minimizes operating sounds and
eliminates damage to lawn and shrubs.
3 through 5 ton.
Fan motor has ball bearings and is inherently protected.
Three-phase power supply.
Motor totally enclosed for maximum protection from
Sound levels as low as 76 dB.
weather, dust and corrosion.
Vertical air discharge allows concealment behind shrubs
Rain shield on motor provides additional protection from
at grade level or out of sight on a roof.
moisture.
Matching add-on furnace indoor coils or air handlers
Louvered steel top fan guard furnished as standard.
provide a wide range of cooling capacities and
applications. See AHRI System Matches. Fan service access accomplished by removal of top
panel.
See Indoor Coils and Air Handlers sections for data.
Units shipped completely factory assembled, piped and High Pressure Switch
wired. Each unit test operated at the factory ensuring Protects the system from high pressure conditions that
proper operation. can be a result of fan failure or a blocked/dirty coil.
Installer must set air conditioner, connect refrigerant Automatic reset.
lines and make electrical connections to complete job.
For expanded ratings, see www.lennoxcommercial.com
Optional Accessories
Outdoor temperature sensor C0SNSR04AE1- X2658
Optional wall mounting plate C0MISC17AE1- X2659
4-3/8 4-3/8
INLET AIR (111) (111)
4-3/8 4-3/8
(111) (111)
6-3/8
(162) 4-3/8
SUCTION LINE (111)
CONNECTION
A
A
DISCHARGE AIR
CONDENSER
COIL FAN
COMPRESSOR
C B
SUCTION &
LIQUID LINE
CONNECTIONS
ELECTRICAL
INLETS
2-3/4 (70)
2 (51)
A B C
Model No.
inches mm inches mm inches mm
TSA036S4 24-1/4 616 29-1/4 743 28-1/2 724
TSA042S4 28-1/4 718 29-1/4 743 28-1/2 724
TSA048S4 28-1/4 718 37-1/4 946 36-1/2 927
TSA060S4 28-1/4 718 33-1/4 845 32-1/2 826
See NOTES
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on
one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in.
See See (914 mm)
NOTES NOTES Clearance to one of the remaining two sides may be 12 in.
(305 mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.
CONTROL
See NOTES BOX
SOUND DATA
Unit
1 Octave Band Linear Sound Power Levels dB, re 10-12 Watts Center Frequency - HZ 1
Sound Rating
Model No. 125 250 500 1000 2000 4000 8000 Number (dB)
TSA036S4 70.5 67.5 69.5 72.5 69.5 63 59 76
TSA042S4 74 76.5 76.5 75.5 72 68 63.5 80
TSA048S4 73.5 76 76 76.5 72.5 69.5 64.5 80
TSA060S4 73.5 74.5 77 75 72 69 64.5 80
NOTE - the octave sound power data does not include tonal correction.
1
Tested according to AHRI Standard 270-2008 test conditions.
Cooling or heating capacities are net values, including Units which do not have an indoor air-circulating blower
the effects of blower motor heat, and do not include furnished as part of the model, i.e., split system with
supplementary heat. Power input is the total power input indoor coil only, is established by subtracting from the
to the compressor(s) and fan(s), plus any controls and total cooling capacity 1250 Btu/h per 1,000 cfm, and by
other items required as part of the system for normal adding the same amount to the heating capacity. Total
operation. power input for both heating and cooling is increased by
365 W per 1,000 cfm of indoor air circulated.
Visit us at www.lennox.com
For the latest technical information, www.lennoxcommercial.com
Contact us at 1-800-4-LENNOX
NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency. ©2016 Lennox Industries, Inc.