Panelview™ E Transfer Utility: (Cat. No. 2711E-Nd7)
Panelview™ E Transfer Utility: (Cat. No. 2711E-Nd7)
Transfer Utility
(Cat. No. 2711E-ND7)
User Manual
Important User Information Because of the variety of uses for the products described in this
publication, those responsible for the application and use of this
control equipment must satisfy themselves that all necessary steps
have been taken to assure that each application and use meets all
performance and safety requirements, including any applicable laws,
regulations, codes and standards.
death, property damage or economic loss
• identify a hazard
• avoid a hazard
• recognize the consequences
Preface
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P–1
Purpose of This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P–1
Contents of This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P–2
Related Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P–2
Technical Support Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P–4
Allen-Bradley Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P–4
Local Product Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P–4
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . P–4
Publication 2711E-6.16
toc–ii Table of Contents
Uploading Chapter 3
1000e/1200e/1400e Uploading PanelView 1000e/1200e/1400e Application Files . . . . . . 3–1
Application Files and Alarm Uploading the PanelView 1000e/1200e/1400e Alarm History File . . . 3–8
History Files Alarm History Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–8
Uploading the Alarm History Files . . . . . . . . . . . . . . . . . . . . . . . 3–10
Downloading Chapter 4
1000e/1200e/1400e Downloading PanelView 1000e/1200e/1400e Application Files . . . . 4–1
Application Files
Configuring Chapter 5
Communications Settings Selecting Communication Hardware and Driver Packages . . . . . . . 5–1
for 1000e/1200e/1400e Configuring Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
Application Transfers Selecting the Transfer Method . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–5
Configuring the Transfer Parameters . . . . . . . . . . . . . . . . . . . . . . . 5–5
Obtain Transfer Parameters from an Application File . . . . . . . . . . 5–5
Configure Transfer Parameters Manually . . . . . . . . . . . . . . . . . . 5–7
Serial Transfer Method — Driver Configuration . . . . . . . . . . . . 5–8
Network Transfer Method — Network and
Driver Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–10
Remote I/O Pass-Through — Network, Driver, and
Pass-Through Setup Configuration . . . . . . . . . . . . . . . . . . 5–13
Saving the Communication Settings . . . . . . . . . . . . . . . . . . . . . . . 5–16
Index
Publication 2711E-6.16
Preface
Preface
Before You Begin Before you begin you should be familiar with:
• Microsoft Windows 2000, Microsoft Windows NTt 4.0,
Microsoft Windows 95 or Microsoft Windows 3.x operating
system
Purpose of This Manual The PanelView e Transfer Utility User Manual describes the
methods of transferring application and alarm history files between
the computer and the PanelView terminal. The computer must have
the PanelView e Transfer Utility installed. This user manual also
provides step-by-step instructions for each method.
P–2 Preface
Related Publications
Technical Support If you have questions about the PanelView e Transfer Utility 32,
Services consult the online help and user documentation first. If you can’t find
the answer, take advantage of our Technical Support Fax Back
system, available 24 hours a day, 7 days a week at 1-440-646-6701.
Or, browse our technical document library on the World Wide Web
at http://www.ab.com/mem/technotes/kbhome.html
Alternatively, contact:
Allen-Bradley
Technical Support
1 Allen Bradley Drive
Mayfield Heights, Ohio 44124-6118
or call 1-440-646-5800 or fax 1-440-646-5801 for technical support
between 8 AM and 5 PM (EST), Monday to Friday.
Conventions Used in This The following conventions are used throughout this manual:
Manual • bulleted lists such as this one provide information, not
procedural steps
• numbered lists provide sequential steps or hierarchical
information
• italic type is used for emphasis
• text in this font indicates words or phrases you should type
About the PanelView e File Use the PanelView e Transfer Utility 32 to transfer PanelBuilder
Transfer Utility 32 application files between a computer and the PanelView terminal.
You can transfer application files created in PanelBuilder 1400e for
Windows. You can also use this utility to upload alarm history
information from a PanelView 1000e/1200e/1400e terminal to the
computer that the Transfer Utility runs on. Only Version 2 and later
alarm history files can be uploaded.
Types of Applications You can transfer terminal application files, whose names end in .pvd,
using the PanelView e Transfer Utility 32. The *.pvd files are created
in PanelBuilder 1400e for Windows. Files are initially created and
edited as *.pvc. You then must save the file as a *.pvd to download
it. These are PanelView enhanced 1200 (Series F and later) and
1000e/1200e/1400e terminal files.
Types of Transfers The PanelView e Transfer Utility 32 does the following types of
transfers:
• downloading an application file—Transferring an application
file from the development computer to a PanelView terminal so
the application can be run. PanelView enhanced 1200 (Series F
and later) and PanelView 1000e/1200e/1400e applications can be
downloaded.
• uploading an application file—Transferring an application file
from the PanelView terminal to the development computer that
the PanelView e Transfer Utility 32 is on so the application can
be edited or archived. PanelView enhanced 1200 (Series F and
later) and PanelView 1000e/1200e/1400e applications can be
uploaded.
• uploading alarm history files—Transferring the Alarm History
File from the PanelView terminal to the development computer so
the files can be analyzed or archived. Only PanelView enhanced
1200 (Series F and later) and 1000e/1200e/1400e V02.00.00 and
later Alarm History files can be uploaded.
Methods of Downloading There are three methods for downloading and uploading applications
and Uploading and alarm history files:
Applications and Alarm • Serial (RS-232) Upload/Download—To transfer applications serially,
History Files you need an RS-232 Serial (Upload/Download) cable (A-B Cat. no.
2706-NC13, 2711-NC13, or 2711-NC14 for PanelView 1000e/1400e
Series F and later terminals; 2711-NC1 for PanelView 1200e/1400e
terminals Series E and earlier),for connecting the computer to the terminal.
Alarm History files directly by connecting the serial ports on the
computer and PanelView terminal. This is a serial file transfer.
• Network Upload/Download—You can upload applications or
Alarm History files once you have connected the PanelView
terminal and computer to the DH+ or ControlNet network. You
can download applications between the computer running the
Transfer Utility and the PanelView terminal over the DH+ or
ControlNet network without taking the terminal out of Run mode.
Since the serial port is not used for network transfers, you can
print from the PanelView terminal without changing the serial
cabling of the terminal.
1–4 Introducing the PanelView e Transfer Utility 32
File Transfer Tips Read this section when preparing to perform an application file
transfer.
General
The PanelView 1200/1400e Transfer Utility Version 3 supports the full range
of INTERCHANGE serial and network drivers. The
INTERCHANGE drivers allow ports and communication devices to
be shared between PanelBuilder and other Allen-Bradley products
such as the 6200-series PLC-5 Programming Software and
PanelBuilder 900. INTERCHANGE drivers also support
communication cards such as the KT and PCMK for DH+
communication. Contact your Allen-Bradley representative for more
information on INTERCHANGE.
System Requirements You need the following hardware and software to install the
PanelView e Transfer Utility 32.
Publication 2711E-UM003B–EN–P
2–2 Working with the PanelView e Transfer Utility 32
PanelBuilder Applications
PanelView Terminals
To transfer files using the PanelView e Transfer Utility 32, you must
have one or more of the following PanelView terminals. Table 2.B
lists the terminal products and their catalog numbers.
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–3
Equipment Required for This section describes the equipment required to perform the
Transferring Applications following application transfers:
• serial transfer
• DH+ network transfer
• ControlNet network transfer
• Remote I/O Pass-Through transfer
Serial Upload/Download
Upload/Download Cable
2711–NC13, series F or later
2711–NC1, series E or earlier
Publication 2711E-UM003B–EN–P
2–4 Working with the PanelView e Transfer Utility 32
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–5
Publication 2711E-UM003B–EN–P
2–6 Working with the PanelView e Transfer Utility 32
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–7
Publication 2711E-UM003B–EN–P
2–8 Working with the PanelView e Transfer Utility 32
The 1200e terminals are not compatible with ControlNet. You need
the following Allen-Bradley ControlNet Interface modules installed
in the development computer to transfer applications over
ControlNet:
• 1784-KTCX (Series B or later)
• 1784-KTC
• 1770-KFC
You can transfer applications over a ControlNet network using
RSLinx drivers, or Serial 1 or Serial 2 drivers if the transfer is over a
KFC module.
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–9
Publication 2711E-UM003B–EN–P
2–10 Working with the PanelView e Transfer Utility 32
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–11
Publication 2711E-UM003B–EN–P
2–12 Working with the PanelView e Transfer Utility 32
Figures 2.8 and 2.9 show how the application file is transferred from
the development computer to the PLC and then to the PanelView
terminal.
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–13
Publication 2711E-UM003B–EN–P
2–14 Working with the PanelView e Transfer Utility 32
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–15
Publication 2711E-UM003B–EN–P
2–16 Working with the PanelView e Transfer Utility 32
General Installation You can install the PanelView e Transfer Utility 32 software using
Information the CD-ROM provided in the PanelBuilder 1400e software kit (A-B
Catalog Number 2711E-ND1) or using the CD provided in the
Transfer Utility software package (A-B Catalog Number
2711E-ND7).
You can also create your own floppy disks of the PanelView e
Transfer Utility 32 software from the CD this manual was on. For
instructions on how to create floppy disks of the software from the
CD, refer to the Floppies.txt file, in the root directory of the CD.
The CD-ROM includes two install versions for the Transfer Utility
software:
• Version 3—This version offers you the PanelView 1200/1400e
Transfer Utility (FTU) on an operating system that uses Windows
3.x, or Windows 95. Version 3 supports INTERCHANGE and
WINtelligent LINX drivers for PanelView 1000e, 1200, 1200e,
and 1400e file transfers.
• Version 5—This version offers you the PanelView e Transfer
Utility 32 (FTU32) software on an operating system that uses
Windows 95 or Windows NT. Version 5 supports RSLinx drivers
for PanelView 1000e, 1200e, and 1400e file transfers.
If your operating system is Windows 3.x, the CD-ROM will install
FTU Version 3. If your operating system is Windows 95, you have a
choice of installing FTU Version 3 or Version 5. If your operating
system is Windows NT, the CD-ROM will install FTU Version 5,
also called FTU32.
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–17
You can also create your own floppy disks of the PanelView e
Transfer Utility 32 software from the CD this manual was on. For
instructions on how to create floppy disks of the software from the
CD, refer to the Floppies.txt file, in the root directory of the CD.
To install FTU32:
1. Start Windows 2000(SP2)/NT/95. If you’re already in Windows,
close all open Windows applications.
2. Insert the CD-ROM in the drive.
The CD-ROM begins to run automatically.
If the install does not start automatically, choose Run from the
Start button and select setup.exe from the CD-ROM drive; or
select setup.exe from Windows Explorer.
3. In the Welcome dialog box, choose Next.
4. If you are installing on Windows 95, the Select Version dialog
box appears.
Publication 2711E-UM003B–EN–P
2–18 Working with the PanelView e Transfer Utility 32
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–19
Publication 2711E-UM003B–EN–P
2–20 Working with the PanelView e Transfer Utility 32
11. Choose the program folder (program group) in which you want to
install the FTU32’s icons, which includes a Readme file icon, the
Transfer Utility icon, and an Uninstall icon. By default, the icons
are installed in the PanelBuilder 1400e program folder. Then
choose Next.
12. Choose whether the installation utility will modify the
AUTOEXEC.BAT file.
If you are installing on Windows 95, the entry
C:\Progra~1\Rockwe~1\RDM;%Path%
is required in the PATH variable for the FTU32 to work correctly.
If you are installing on Windows NT, the entry
C:\Program Files\Rockwell Software\RDM
is required in the PATH variable in the Environment tab of the
System Properties dialog box.
Choose Next to approve the changes and continue.
13. The setup utility shows a summary of the choices you made in the
preceding dialog boxes. To make any changes, choose the Back
button. Otherwise, choose Next to begin the installation.
14. After all the applications have completed installing, you are
prompted to reboot your computer. You can reboot immediately
or later, but you must reboot before you can run the Transfer
Utility or other applications successfully.
If you want to upload or download PanelView files over the PLC
networks, you also need to install RSLinx Lite software, Version
2.0 or later. See the RSLinx user documentation provided for
installation procedures.
Do not cancel the installation while it is in progress. If you want to
undo the installation, let the installation finish, then use Uninstall
PanelView e Transfer Utility to remove all the installed files and to
update the Windows registry.
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–21
Installing the FTU from PanelView 1200/1400e Transfer Utility (FTU) Version 3 is provided
PanelBuilder 1400e on the PanelBuilder 1400e CD-ROM. The software installation
CD-ROM on Windows 95 program creates a directory on your hard drive for the FTU and
or Windows 3.x copies all necessary files to it. By default, the drive and directory is
C:\AB\PB1400E\FTU. You can change this default.
You can create your own 3.5-inch floppy disks from the CD. For
instructions on how to create floppy disks of the software from the
CD, refer to the Floppies.txt file, in the root directory of the CD.
Publication 2711E-UM003B–EN–P
2–22 Working with the PanelView e Transfer Utility 32
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–23
13. After all the applications have completed installing, you are
prompted to reboot your computer. You can reboot immediately
or later, but you must reboot before you can run the Transfer
Utility or other applications successfully.
If you want to upload or download PanelView files over the PLC
networks after you finish installing the Transfer Utility, you also
need to install INTERCHANGE or WINtelligent LINX software.
If you do not have this software, contact Allen-Bradley Technical
Support for assistance.
Do not cancel the installation while it is in progress. If you want to
undo the installation, let the installation finish, then use Uninstall
Transfer Utility to remove all the installed files and to update the
Windows registry.
Installing the FTU32 from PanelView e Transfer Utility 32 (FTU32) Version 5 is provided in
the “PanelView 1200/1400e the Transfer Utility kit (A-B Catalog Number 2711E-ND7) on CD.
Transfer Utilities” CD on
Windows NT or You can create your own 3.5-inch floppy disks from the CD. For
Windows 95 instructions on how to create floppy disks of the software from the
CD, refer to the Floppies.txt file, in the root directory of the
PanelBuilder 1400e CD.
To install the FTU32:
1. Start Windows NT or Windows 95. If you’re already in Windows,
close all open Windows applications.
2. Insert the CD in the drive.
3. Browse the CD for file “FTU_V5”. Browse Disk 1. Run
“SETUP.EXE”.
4. The Welcome dialog box for the Transfer Utility recommends
that you close all open Windows applications. If you have done
that, choose Next.
5. In the registration window, enter registration information about
your copy of the FTU32. Registration information is on the
software registration card in your PanelBuilder 1400e or Transfer
Utility package.
6. Choose the drive and directory in which the FTU32 will be
installed. By default, this is C:\AB\PB1400E\FTU32. To change
the destination drive or directory, type the new drive and/or
directory in the Program Files box. Then choose Next.
Publication 2711E-UM003B–EN–P
2–24 Working with the PanelView e Transfer Utility 32
Installing the FTU from the PanelView 1200/1400e Transfer Utility (FTU) Version 3 is provided
“PanelView 1200/1400e in the PanelView 1200/1400e Transfer Utility kit (2711E-ND7) on
Transfer Utilities” CD on CD.
Windows 95 or
Windows 3.x You can create your own 3.5-inch floppy disks from the CD. For
instructions on how to create floppy disks of the software from the
CD, refer to the Floppies.txt file, in the root directory of the CD.
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–25
Publication 2711E-UM003B–EN–P
2–26 Working with the PanelView e Transfer Utility 32
For information on how to start and exit from the PanelView 1200
Transfer Utility, see the PanelView 1200 Transfer Utility User
Manual (Publication Number 2711-UM010B–EN–P).
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–27
If you have problems running the Transfer Utility and you have
had previous versions of the Transfer Utility on your computer,
we recommend you select “Uninstall PanelView e Transfer
Utility 32” in the PanelBuilder 1400e folder. The “Uninstall
PanelView e Transfer Utility 32” program deletes any of the
shared files and windows system file conflicts that may exist
from earlier installations. You will then have to reinstall the
Transfer Utility software. If problems still exist, contact
Allen-Bradley Technical Support. For information about
obtaining Technical Support, see the Preface in this manual.
Publication 2711E-UM003B–EN–P
2–28 Working with the PanelView e Transfer Utility 32
Exiting the PanelView e When you have finished transferring applications, exit the Transfer
Transfer Utility 32 Utility.
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–29
Starting the PanelView The PanelView 1200/1400e Transfer Utility Version 3 (FTU) includes
1400e Transfer Utility two utilities that can be accessed from the same icon:
Version 3 (FTU) • the Transfer Utility for the PanelView 1000e/1200e/1400e
terminals that is activated from toolbar buttons.
• the PanelView 1200 Transfer Utility that can be selected from the
Transfer menu bar.
This section describes how to start the program from Windows 3.x
and Windows 95. Screen illustrations in this manual are from the
Windows 3.1 environment. Functionality of the transfer utility is the
same for Windows 3.x and Windows 95.
Publication 2711E-UM003B–EN–P
2–30 Working with the PanelView e Transfer Utility 32
If you have problems running the File Transfer Utility and you
have had previous versions of the File Transfer Utility on your
computer, we recommend you select “Uninstall Transfer Utility”
in the PanelBuilder 1400e folder. The “Uninstall Transfer Utility”
program deletes any of the shared files and windows system file
conflicts that may exist from earlier installations. You will then
have to reinstall the File Transfer Utility software again. If
problems still exist, contact Allen-Bradley Technical Support. For
Technical Support information, see the Preface in this manual.
Starting the PanelView The procedure to start the PanelView 1200 Transfer Utility is the
1200 Transfer Utility same for Windows 95 and Windows 3.x. This utility, available in
FTU Version 3 and earlier, is used to transfer an application created
in PanelBuilder Development Software for DOS, or PanelBuilder
1200 Configuration Software for Windows. Refer to the PanelView
1200 Transfer Utility User Manual (Publication Number
2711-UM010B–EN–P) for more information.
1. Start the PanelView 1200/1400e Transfer Utility using the
method previously described for your operating system.
2. Choose PanelView 1200 Transfer from the Transfer menu. The
following screen is displayed.
Publication 2711E-UM003B–EN–P
Working with the PanelView e Transfer Utility 32 2–31
Exiting the PanelView 1200 When you have finished transferring applications, exit the PanelView
Transfer Utility 1200 Transfer Utility.
Transfer Exit
Yes, exit
Cancel Exit
20016
2. Choose Yes, exit and press ENTER. You will return to the
PanelView 1200/1400e Transfer Utility screen.
If you don’t want to quit, choose Cancel Exit. The PanelView
1200 Transfer Utility remains active.
3. Quit the PanelView 1200/1400e Transfer Utility by choosing Exit
from the Transfer menu, pressing ALT+F4, or clicking on the Close
button.
Exiting the PanelView When you have finished transferring applications, exit the PanelView
1200/1400e Transfer Utility 1200/1400e Transfer Utility.
Publication 2711E-UM003B–EN–P
Chapter 3
Uploading 1000e/1200e/1400e
Application Files and Alarm
History Files
Uploading PanelView You can upload application files using either a serial connection, a
1000e/1200e/1400e network connection, or a Remote I/O connection. For serial transfers,
Application Files you must connect the PanelView terminal to a computer with the
Upload/Download cable (Allen-Bradley Catalog Numbers
2706-NC13, 2711-NC13, 2711-NC14 for PanelView 1000e
terminals; 2711-NC1 for PanelView 1200e/1400e terminals). For
network transfers, you must connect the PanelView terminal to the
computer over a DH+ or ControlNet network. For Remote I/O
transfers, you must connect the PanelView terminal to the PLC over
a Remote I/O network, and connect the PLC to the computer over a
DH+, ControlNet, or Ethernet network.
For Remote I/O applications, you can change the baud rate. The
following shows the Terminal Network Setup screen for a
Remote I/O application.
3 7 Low
2. In the Path box, type the name of the directory to which the
uploaded application file will be saved, or choose Browse to find
a directory.
3. In the Data to Upload box, select Application file.
4. Determine the destination file name for the application file you
are uploading, by pressing the Upload Options button or clicking
from the toolbar. The File Transfer Options dialog box is
displayed.
Uploading 1000e/1200e/1400e Application Files and Alarm History Files 3–7
If you want the file to upload with the same name as the selected
upload file, then clear the Prompt Upload Destination box.
If you want to enter a new name for the uploaded file, select
Prompt Upload Destination. Windows NT or Windows 95 file
naming restrictions apply. The file name can exceed 8 characters,
but the PanelView firmware truncates file names that exceed 8
characters.
5. Click OK to save your settings and exit from the File Transfer
Options dialog box.
6. Configure communications settings for the transfer following
instructions in Chapter 5, Configuring Communications Settings
for 1000e/1200e/1400e Application Transfers.
7. To save your settings, choose System Options from the Options
menu, or from the toolbar.
A progress dialog box appears that shows the status of the upload.
Uploading the PanelView The PanelView e Transfer Utility 32 allows you to upload an
1000e/1200e/1400e Alarm application’s historical alarm data from PanelView
History File 1000e/1200e/1400e terminals. The Alarm History file can be
uploaded using any of the upload methods: Serial, Network, or
Remote I/O Pass-Through.
" Note: The Upload Alarm History function works only for
PanelView 1000e/1200e/1400e terminals with Version 02.00.00 or
later firmware.
The header is followed by a line, that lists the boxes for the alarm
record information. For example:
The third and subsequent lines include the alarm records, each on a
separate line, starting with the most recent alarm. See the following
table for the format of each box in the alarm record.
Uploading 1000e/1200e/1400e Application Files and Alarm History Files 3–9
Box Data
Alarm Trigger Signed long integer value
Alarm Message The alarm message associated with the trigger value
Message delimited by a pair of double quotes
Double quote character () in the message text is
translated to 2 double quotes ().
For Version 02.00.00 and later applications, the
character sequence \n (backslash-n) in the message text
is translated to \\n
For Version 02.00.00 and later applications, the newline
character in the message text is translated to a
backslash character followed by the letter n (\n).
Trigger Date Each field is separated by a forward slash.
4-digit year (1980 to 2043)
2-digit month (1 to 12)
2-digit day (1 to 31)
Trigger Time Each field is separated by a colon.
2-digit hour (0 to 23)
2-digit minute (0 to 59)
2-digit second (0 to 59)
Acknowledge Date Each field is separated by a forward slash. If the alarm is
not acknowledged, no text follows the alarm event data.
4-digit year (1980 to 2043)
2-digit month (1 to 12)
2-digit day (1 to 31)
Acknowledge Time Each field is separated by a colon. If the alarm is not
acknowledged, no text follows the alarm event data.
2-digit hour (0 to 23)
2-digit minute (0 to 59)
2-digit second (0 to 59)
For Remote I/O application files, you can change the baud rate.
The following shows the Terminal Network Setup screen for a
Remote I/O application file.
3 7 Low
2. In the Path box, type the name of the directory to which the
uploaded application file will be saved, or choose Browse to find
a directory.
3. In the Data to Upload box, select Alarm History.
4. Determine the destination file name for the alarm history file you
are uploading, by pressing the Upload Options button or clicking
from the toolbar. The File Transfer Options dialog box is
displayed.
Uploading 1000e/1200e/1400e Application Files and Alarm History Files 3–15
If you want the file to upload with the same name as the selected
upload file, then clear the Prompt Upload Destination box.
If you want to enter a new name for the uploaded file, select
Prompt Upload Destination. Windows NT or Windows 95 file
naming restrictions apply. The file name can exceed 8 characters,
but the PanelView firmware truncates file names that exceed 8
characters.
5. Select or clear the following upload options:
6. Click OK to save your settings and exit from the File Transfer
Options dialog box.
7. Configure communications settings for the transfer following
instructions in Chapter 5, Configuring Communications Settings
for 1000e/1200e/1400e Application Transfers.
3–16 Uploading 1000e/1200e/1400e Application Files and Alarm History Files
A progress dialog box appears that shows the status of the upload.
Downloading PanelView You can download files using either a serial connection, a network
1000e/1200e/1400e connection, or a Remote I/O connection. For serial transfers, you
Application Files must connect the PanelView terminal to a computer with the
Upload/Download cable (Allen-Bradley Catalog Numbers
2706-NC13, 2711-NC13, 2711-NC14 for PanelView 1000e
terminals; 2711-NC1 for PanelView 1200e/1400e terminals). For
network transfers, you must connect the PanelView terminal to the
computer over a DH+ or ControlNet network. For Remote I/O
transfers, you must connect the PanelView terminal to the PLC over
a Remote I/O network, and connect the PLC to the computer over a
DH+, ControlNet, or Ethernet network.
To download application files, you must complete these steps in
order:
• prepare the PanelView terminal for the download. This section
explains how to prepare a PanelView terminal for a serial,
network, or Remote I/O Pass-Through download.
• configure the PanelView e Transfer Utility 32 for the download
• initiate the application file download
4–2 Downloading 1000e/1200e/1400e Application Files
2. In the Source File box, type the full path and file name of the
download file, or choose Browse to locate a file on the disk. The
file must be a .pvd file created by PanelBuilder 1400e.
A .pvd file may already be displayed in the Source File box. If
you started the Transfer Utility from PanelBuilder 1400e, the
source file defaults to the current application in PanelBuilder. If
you started the Transfer Utility separately, the source file defaults
to the last source file you had saved using Auto-Save All
Settings.
3. In the Terminal Storage box, choose the memory area where the
downloaded application will be stored. The default is Memory
Partition 2.
Memory Partition 1 is the terminal’s first memory partition. It is
typically used for firmware storage and is not available for
application file storage, unless the firmware is located on a
PCMCIA card.
Memory Partition 2 is the terminal’s second memory partition.
It can only be used for application file storage.
Card Partition 1 is the first partition on a card with two
application partitions or the partition on the card with a single
partition. If the firmware is located on a PCMCIA card, then this
storage area is not available for applications.
Card Partition 2 is the second partition on a card with two
application partitions.
4–8 Downloading 1000e/1200e/1400e Application Files
4. Determine the destination file name for the application file you
are downloading, by pressing the Download Options button or
clicking from the toolbar. The File Transfer Options dialog
box is displayed.
If you want the file to download with the same name as the
selected download file, then clear the Prompt Download
Destination box.
If you want to enter a new name for the download file, select
Prompt Download Destination. All DOS file-naming restrictions
apply.
Downloading 1000e/1200e/1400e Application Files 4–9
6. Click OK to save the settings and exit from the File Transfer
Options dialog box.
7. Configure communications settings for the transfer following
instructions in Chapter 5, Configuring Communications Settings
for 1000e/1200e/1400e Application Transfers.
8. To save the settings in the Download main dialog box, choose
System Options from the Options menu, or from the toolbar.
Selecting Communication The following information and table will help you determine which
Hardware and Driver driver packages and drivers you need for your particular system
Packages configuration, and what the appropriate transfer link will be for your
communication hardware setup. You need to know:
• what hardware you have
• what transfer link you’re using
• which driver package you’re using
• which driver options must be configured
Table 5.A provides a matrix to help determine your hardware and
driver requirements.
For DH+, use RSLinx; if you do not have RSLinx, use the Serial 1 or
Serial 2 driver to communicate over the KF2 module.
For ControlNet, use RSLinx; if you do not have RSLinx, use the
Serial 1 or Serial 2 driver to communicate over the KFC module.
For Remote I/O Pass-Through, use whichever driver you would use
for DH+, ControlNet, or Ethernet.
FTU32 Version 5 Table 5.A Table of PC Host Hardware and Applicable Drivers
PC COM Port RS-232 Serial DF1 Direct / Modbus Internal Drivers Serial 1 or 2
1770-KF2 / KE Network DH+ Internal Drivers Serial 1 or 2
RSLinx AB_DF1
Remote I/O DH+ Internal Drivers Serial 1 or 2
Pass-Through RSLinx AB_DF1
1784-KT / 1784-KTX / Network DH+ RSLinx AB_KT
PCMK Remote I/O DH+ RSLinx AB_KT
Pass-Through
1770-KFC Network ControlNet Internal Drivers Serial 1 or 2
RSLinx AB_DF1
Remote I/O ControlNet Internal Drivers Serial 1 or 2
Pass-Through RSLinx AB_DF1
1784-KTC / Network ControlNet RSLinx AB_KTC
1784-KTCX Remote I/O ControlNet RSLinx AB_KTC
Pass-Through
Ethernet Network Card Remote I/O Ethernet RSLinx AB_ETH
Pass-Through
FTU Version 3 Table 5.B Table of PC Host Hardware and Applicable Drivers
If you have this Decide which Select Network Choose one of these Select the corresponding driver
communication transfer link to use Type and driver packages
hardware Address
PC COM Port RS-232 Serial DF1 Direct Internal File Transfer Serial 1 or 2
Utility
WIN LINX 1770-KF2/KE to DH/DH+ & PLC-5 CH0
INTERCHANGE INTERCHANGE Port 1 – 8
1770-KF2 / KE Network Direct DH+ Internal File Transfer Serial 1 or 2
Utility
WIN LINX 1770-KF2/KE to DH/DH+ & PLC-5 CH0
WIN LINX using INTERCHANGE to DH+
INTERCHANGE Interchange Port 1 – 8
Remote I/O DH+ Internal File Transfer Serial 1 or 2
Pass-Through Utility
WIN LINX 1770-KF2/KE to DH/DH+ & PLC-5 CH0
WIN LINX using INTERCHANGE to DH+
INTERCHANGE Interchange Port 1 – 8
Configuring Communications Settings for 1000e/1200e/1400e Application Transfers 5–3
If you have this Decide which Select Network Choose one of these Select the corresponding driver
communication transfer link to use Type and driver packages
hardware Address
1784-KT / KT2 / PCMK Network Direct DH+ WIN LINX 1784-KT/KT2/PCMK to DH+
WIN LINX using INTERCHANGE to DH+
INTERCHANGE Interchange Port 1 – 8
Remote I/O DH+ WIN LINX 1784-KT/KT2/PCMK to DH+
Pass-Through WIN LINX using INTERCHANGE to DH+
INTERCHANGE Interchange Port 1 – 8
1784-KTX Network Direct DH+ WIN LINX 1784-KTX to DH+
WIN LINX using INTERCHANGE to DH+
INTERCHANGE Interchange Port 1 – 8
Remote I/O DH+ WIN LINX 1784-KTX to DH+
Pass-Through WIN LINX using INTERCHANGE to DH+
INTERCHANGE Interchange Port 1 – 8
SS Technologies Network Direct DH+ WIN LINX SS Technologies 5136–SD to DH+
5136-SD Remote I/O DH+ WIN LINX SS Technologies 5136–SD to DH+
Pass-Through
SS Technologies Network Direct DH+ WIN LINX SS Technologies 5136–SD2 to DH/DH+
5136-SD2 Remote I/O DH+ WIN LINX SS Technologies 5136–SD2 to DH/DH+
Pass-Through
1770-KFC Network Direct ControlNet Internal File Transfer Serial 1 or 2
Utility
WIN LINX 1770-KFC to ControlNet (DH+ Mode)
WIN LINX using INTERCHANGE to
ControlNet
INTERCHANGE Interchange Port 1 – 8
Remote I/O ControlNet Internal File Transfer Serial 1 or 2
Pass-Through Utility
WIN LINX 1770-KFC to ControlNet (DH+ Mode)
WIN LINX using INTERCHANGE to
ControlNet
INTERCHANGE Interchange Port 1 – 8
1784-KTC Network Direct ControlNet WIN LINX 1784-KTC to ControlNet (DH+ Mode)
WIN LINX using INTERCHANGE to
ControlNet
INTERCHANGE Interchange Port 1 – 8
Remote I/O ControlNet WIN LINX 1784-KTC to ControlNet (DH+ Mode)
Pass-Through WIN LINX using INTERCHANGE to
ControlNet
INTERCHANGE Interchange Port 1 – 8
5–4 Configuring Communications Settings for 1000e/1200e/1400e Application Transfers
If you have this Decide which Select Network Choose one of these Select the corresponding driver
communication transfer link to use Type and driver packages
hardware Address
1784-KTCX Network Direct ControlNet WIN LINX 1784-KTC to ControlNet (DH+ Mode)
WIN LINX using INTERCHANGE to
ControlNet
INTERCHANGE Interchange Port 1 – 8
Remote I/O ControlNet WIN LINX 1784-KTC to ControlNet (DH+ Mode)
Pass-Through WIN LINX using INTERCHANGE to
ControlNet
INTERCHANGE Interchange Port 1 – 8
Configuring The procedure and dialog boxes are the same for application
Communications downloads, application uploads, and alarm history uploads.
Configuring the Transfer You can configure the transfer parameters using either of the
Parameters following methods:
• obtain transfer parameter values from an application file
• manually select the transfer parameter values
2. Enter the name of the *.pvd file from which you want to get the
values for the communication parameters, or choose Browse to
find the *.pvd file.
3. Click Preview Contents to view the communication parameters of
the *.pvd file you have selected.
Configuring Communications Settings for 1000e/1200e/1400e Application Transfers 5–7
4. Click Apply. The transfer path, network type, and driver values
from the *.pvd file are placed in the appropriate boxes in the
Configure Transfer Method dialog box. If you are performing a
Remote I/O Pass-Through transfer, the Pass-Through (device
type, rack, word, and byte) values from the *.pvd file are placed
in the appropriate boxes in the Configure Transfer Method dialog
box. The transfer method is entered in the main download/upload
dialog box.
If you selected Application as your transfer method, do not exit
using OK or Apply. Instead, click Close. Clicking OK or Apply
removes Application as your transfer method.
Before the RSLinx driver appears on the driver list, you must first
configure the RSLinx driver, and then refresh the list of available
drivers. To configure an RSLinx driver, you must start RSLinx by
clicking the Invoke RSLinx button. To refresh the list of available
drivers, choose the Refresh List button.
" Note: Serial 1 and Serial 2 drivers enable you to configure two
different serial setups (for example, baud rates). Also, they can
accommodate the two communication ports on many computers.
Refer to the physical communication ports on your computer to
determine the correct port for your application.
Parity
Specify None or Even for the type of error-checking to be used.
This must match the parity configured for the 1770-KF2/KE or
1770-KFC. The default setting is None.
Error
Specify the error-detection protocol used by the device. BCC is
Block Check Character and CRC is Cyclic Redundancy Check.
This must match the error-checking protocol configured for the
1770-KF2/KE or 1770-KFC. The default setting is BCC.
To set the transfer path:
Set the transfer path using one of the following methods:
• enter the transfer path manually
• use Station Browse to start RSWho
• use the transfer path value from a runtime PV file
To set the transfer path manually:
" If you know the transfer path, enter it in the Transfer Path box.
See Appendix A for transfer path formats.
You cannot enter a transfer path manually for file transfers over
ControlLogix Gateway bridging.
To set the transfer path using Station Browse:
1. Click Station Browse to start RSWho.
2. Highlight the device name.
3. Click OK. The transfer path you selected in RSWho is displayed
in the Transfer Path box in the Configure Transfer Method dialog
box.
To set the transfer path using Runtime PV File:
" See “Obtain Transfer Parameters from an Application File” in
this chapter for details.
Configuring Communications Settings for 1000e/1200e/1400e Application Transfers 5–13
" Note: Serial 1 and Serial 2 drivers enable you to configure two
different serial setups (for example, baud rates). Also, they can
accommodate the two communication ports on many computers.
Refer to the physical communication ports on your computer to
determine the correct port for your application.
Port
Specify COM1, COM2, COM3, or COM4 as the serial port used
to connect the serial cable to the 1770-KF2/KE or 1770-KFC.
The default setting is COM1.
Parity
Specify None or Even for the type of error-checking to be used.
This must match the parity configured for the 1770-KF2/KE or
1770-KFC. The default setting is None.
Error
Specify the error-detection protocol used by the device. BCC is
Block Check Character and CRC is Cyclic Redundancy Check.
This must match the error-checking protocol configured for the
1770-KF2/KE or 1770-KFC. The default setting is BCC.
To set the device type:
" Select a device type from the list.
You cannot enter a transfer path manually for file transfers over
ControlLogix Gateway bridging.
To set the transfer path using Station Browse:
1. Click Station Browse to start RSWho.
2. Highlight the device name.
3. Click OK. The transfer path you selected in RSWho is displayed
in the Transfer Path box in the Configure Transfer Method dialog
box.
5–16 Configuring Communications Settings for 1000e/1200e/1400e Application Transfers
Rack
Select the rack number that contains the Pass-Through control
byte. Your selection should match the rack number configured in
your application file or in the PanelView terminal. The default
rack is 3.
Word
Select the word in the rack that will contain the Pass-Through
control byte. Your selection should match the word configured in
your application file or in the PanelView terminal. The default
word is 0.
Byte
Specify the High or Low byte of the word that will be used as the
Pass-Through control byte. Your selection should match the byte
configured in your application file or in the PanelView terminal.
The default byte is Low.
For details about PanelView terminal transfer configuration
settings, see “Transferring Application Files” in Chapter 5,
“Configuring PanelView Terminals” in your PanelView 1000e,
1200e, and 1400e Operator Terminals User Manual (Publication
Number 2711E-6.17).
Saving the To save the communication settings for the current session, choose
Communication Settings Apply in the Configure Transfer Method dialog box. To save the
communications settings for the current session and exit from the
Configure Transfer Method dialog box, choose OK. To exit without
saving the settings, choose Cancel.
Icon Description
Indicates a problem you may encounter while uploading or downloading
PanelView application files, or uploading alarm history files. For problems,
the file transfer is immediately halted.
Indicates a warning you may receive during a file transfer, advising you to
take or avoid a specific action. For warnings, you have the option of
ignoring them and continuing with the file transfer.
General Upload/Download Use the following table to identify problems you may encounter
Problems while trying to upload or download PanelView application files, or
upload alarm history.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Problem Cause What to do
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Application file won’t download or upload. You are using the wrong serial cable. Check the serial cable.
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
The application file is too large. Ensure the memory size of the application
file does not exceed the User Memory Limit.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
For information on application file size, see
Chapter 1, Introducing PanelView
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Terminals, in the PanelView
1000e/1200e/1400e Operator Terminals
User Manual.
6–2 Troubleshooting for the PanelView e Transfer Utility 32
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Problem Cause What to do
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Application file won’t download or upload. The computer is not connected to the Connect the computer to the PanelView
(con’t) PanelView terminal. terminal.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
The terminal’s serial communication port is
not configured for upload/download.
Configure the serial communication port for
upload/download.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ The PanelView terminal is turned off. Turn on the PanelView terminal.
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
The PanelView terminal is in the wrong
mode when a serial upload/download is
attempted.
To transfer an application file serially,
ensure the PanelView terminal is in
Configure mode; then press the Transfer
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Application button on the Terminal
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Configuration screen.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
The PanelView terminal is not in Run mode Put PanelView in Run mode.
when you attempt a network file transfer.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
The computer’s serial port does not work. Ensure the serial port is working by testing it
with another device such as a printer.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Possible corrupt application file. Try backup file or demo file download and
upload.
Some other device may be using the serial Check your hardware connections and
port. reconfigure the serial port.
Pass-through configuration is not properly For more information about configuring
set up. pass-through application file transfers, see
Chapter 5, Configuring Communications
Settings for 1000e/1200e/1400e Application
Transfers, in this manual.
You have not selected Transfer Application Choose Transfer Application from the
from the PanelView terminal’s Configuration Configuration menu.
menu.
Faulty network connection. Check the network connection in
PanelBuilder and/or to the PanelView
terminal.
Check the communication drivers setup.
Unable to communicate with terminal. During a serial upload/download, the Check that you are in configure mode. On
PanelView terminal is not in the Transfer the PanelView terminal, check that you are
Application screen. in the Transfer Application screen and you
have selected the Serial tab.
Wrong baud rate. Check that the baud rate, parity, and error
settings on the Transfer Setup screen
correspond with the host computer settings.
Troubleshooting for the PanelView e Transfer Utility 32 6–3
FTU32 Ver 5 Use the following table to identify communication problems you
Communication Errors may encounter.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Problem Cause What to do
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Cannot start any transfer command. Channel is
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
busy.
The PanelView terminal may currently be
busy.
Wait for the PanelView terminal to complete
its current process, and try again.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Error 2103)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
File was not found. The specified download application file Ensure the specified download application
(Error 2112) cannot be read. file exists and is not corrupted.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Could not create specified upload file.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Error 2113)
The specified upload application file cannot
be written.
Ensure the directory exists, and there is
enough disk space.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
No current application file exists. There is no current application selected in Ensure a current application is selected in
(Error 2114) the PanelView terminal. the terminal.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Could not read data from download file.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Error 2115)
The specified download application file
cannot be read.
Ensure the specified download application
file exists and is not corrupted.
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
(Warning 2117) ÁÁÁÁÁÁÁÁÁÁÁ
It is now too late to abort the file transfer.
ÁÁÁÁÁÁÁÁÁÁÁ
All packets are sent; you cannot cancel the
file transfer at this point.
If you want to delete the transferred
application, start the file transfer again with
the same application. Immediately cancel
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Bad communication, PV missed a download There may be an unrecoverable error.
the file transfer. The second file transfer
overwrites the first file transfer.
Exit and run the program again.
packet.
(Error 2118)
Could not write data to the upload file. The specified upload application file cannot Choose another drive that has available
(Error 2119) be written. disk space, or free up some space on the
disk drive that is full.
The destination drive has insufficient free space The destination drive has insufficient free Choose another drive that has available
to perform the requested operation. Free up disk space. disk space, or free up some space on the
some disk space on the target drive and try disk drive that is full.
again.
(Error 2120)
PLC Inhibit bit is set. The application that is currently running in Check the PLC inhibit bit. Reset the bit if
(Error 3101) the PanelView terminal may be inhibiting file you want to continue with the transfer.
transfers.
The selected terminal storage is out of space for The selected terminal storage area has Choose Yes to select another terminal
the download application. insufficient storage space in the PanelView storage area. Choose No to cancel the
Do you want to select another terminal storage? terminal. download.
(Warning 3103)
PCMCIA card ejected. The card is ejected from the PanelView Insert the PCMCIA card into the PanelView
(Error 3108) terminal. terminal, or select another terminal storage
area. Then try the transfer again.
The download file already exists on the An application with the same name may Choose Yes to overwrite the download file
PanelView terminal. Do you want to overwrite it already exist in the PanelView terminal. on the PanelView terminal. Choose No to
on the PanelView terminal? cancel the file transfer.
(Warning 3111)
PCMCIA card is write protected. The card is write protected. Disable write protection. Or, select another
(Error 3114) storage area.
Alarm History is empty, therefore, no file was You cannot upload an empty alarm history Wait for alarm entries in the alarm history
uploaded. file. file.
(Warning 3120)
The download file already exists on the Either an application with an identical name Choose Yes to overwrite the application file
PanelView terminal. already exists in the PanelView terminal, or on the PanelView terminal and make the
Do you want to overwrite it on the PanelView there is not enough space, or you did not application current. Choose No to cancel
terminal and make the application current? choose to make the application current. the file transfer.
(Warning 3121)
6–4 Troubleshooting for the PanelView e Transfer Utility 32
*.pvd File Errors Use the following table to identify Transfer Utility problems you
may encounter due to *.pvd files. In the following error or warning
messages, %s is the name of the file.
Compatibility Errors Use the following table to identify Transfer Utility problems you
may encounter due to incompatibility between the *.pvd file and the
PanelView terminal.
Driver Errors Use the following table to identify Transfer Utility problems you
may encounter due to driver selection.
PanelView 1400e Transfer Consult the following table to identify and respond to some common
Utility Error Messages FTU error messages that can appear on the screen when you upload or
Version 3 download data, or upload Alarm History files.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Message Cause What to do
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data received too fast from PanelView terminal. Upload speed too high. Reduce baud rate.
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
Invalid baud.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
Might not be accessing COM port. Check other program or devices that use
the COM port.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
If there is one, check to see that the internal
modem is turned off.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
No response from PanelView terminal. Baud rate too high. Reduce baud rate.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Other possible causes are the same as the See solutions for items marked in the
items marked in the previous table. previous table.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Message Cause What to do
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Might not be accessing COM port. Check other program or devices that use
the COM port, and ensure that they do not
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parity error detected. Serial cable becomes disconnected during
conflict with the interrupt request (IRQ) or
the COM settings.
Ensure the serial cable is properly
a serial download. connected, and try the download again.
Cannot obtain com port. The wrong COM port has been chosen with Select the correct COM port.
the native serial driver (either Serial 1 or
Serial 2).
The COM port is assigned to an enabled Choose the INTERCHANGE port. Or
INTERCHANGE port and is trying to be disable INTERCHANGE, reboot, and
used with the native serial driver (Serial 1 or choose the native serial driver.
Serial 2).
Unable to communicate with terminal. During a serial upload/download, the Check that you are in configure mode. On
PanelView terminal is not in the Transfer the PanelView terminal, check that you are
Application screen. in the Transfer Application screen and you
have selected the Serial tab.
Wrong baud rate. Check that the baud rate, parity, and error
settings on the Transfer Setup screen
correspond with the host computer settings.
You cannot perform a serial download. Check that the COM port you are using is
enabled by your Windows operating
system. This can be done by checking the
Ports settings under Control Panel. For
more information, refer to your Windows
3.1, Windows 95, or Windows NT user
documentation.
Check if you are using the same COM port
that your mouse is using. Typically, the
mouse is plugged into COM 1; however, it
may be plugged into COM 2. Check the
labelling on the rear of your computer to
determine which port the mouse is hooked
up to and which port your upload/download
cable is hooked up to.
Check if the COM port you are using is
using the same IRQ number as another
device in your system. Possible causes of
conflict are PCMCIA device cards, Ethernet
cards, sound cards, or other PC add-on
cards. To determine the IRQ settings for
your serial port, refer to your computer’s
user documentation.
Check the settings for the port in the Control
Panel, and check that the settings match.
Then check the IRQ settings for the other
devices listed above to ensure there is not a
conflict.
If you have been using another software
package to access the serial port (such as a
communications package, A-B 6200
software, or even INTERCHANGE), you
may need to restart the computer. To do
this, close the application using the serial
port, disconnect the cable, attach the
PanelView upload/download cable, restart
your computer, and retry the download.
Troubleshooting for the PanelView e Transfer Utility 32 6–11
General Download and Consult the following table to identify and respond to some common
Upload Error Messages error messages that can appear on the screen when you upload or
download data, or upload alarm history.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Messages/General Types of Messages Cause What to do
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
File/path name error messages for either source Either no file name was entered, or an Be sure you’ve entered a valid source or
file or destination file. incorrect file name was entered. destination file name in the File and Path
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
fields. Must have a valid 8-character DOS
file name, a valid DOS path, and a valid
extension (none, *.pvd to upload/download
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
applications, or *.csv to upload alarm
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
history). The “download as file name” must
also satisfy the above conditions.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Selected source file cannot be accessed.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Check that the source file path name is
correct or that it exists.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Destination file already exists. Do you want to Informational or prompt message. Select Yes to overwrite the destination file.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
overwrite it? Select No to abort the upload/download.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Destination file cannot be created. Probably a problem with the PCMCIA card Reformat the card, or try another card. If
or flash memory. there is still a problem, contact your A-B
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Sales Representative.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Incompatibility messages. Firmware version incompatibility. Check firmware version compatibility.
Obtain the PanelView terminal version from
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
the Terminal Configuration screen. Refer to
Appendix E, “Version Control”, in the
PanelBuilder 1400e Configuration Software
DH+ Networks Bridged by The format of the transfer path on remote DH+ networks is:
a 1785-KA
Transfer Path Format Valid Entries
ll.rrr.ss
ll local KA address 0 – 77 (octal)
rrr remote KA address 0 – 376 (octal)
ss PanelView address on remote DH+ 0 – 77 (octal)
or
You can shorten the offlink address by combining the remote KA address and remote
transfer path into one three-digit number. The system reads only the first digit of the remote
KA address, and adds the two-digit remote PanelView address to produce a shorter
address.
ll.rss
ll local bridge address 0 – 77 (octal)
rss combined remote KA address and remote PanelView 0 – 376 (octal)
address
The valid transfer paths for the various PanelView terminals in the
figure are:
Remote DH+
10 21
1785-KA
PLC-3 1785-KA
Local DH+ 7
10
Development Computer
A–4 Constructing the Transfer Path
Multiple DH+ Networks The format of the transfer path on a remote DH+ network is:
Connected by a Pyramid
Integrator (PI) Transfer Path Format Valid Entries
ll:rrrrr.ss
ll local PI address 0 – 77 (octal)
rrrrr PI Link number 0 – 65535 (decimal)
ss PanelView address on remote DH+ 0 – 77 (octal)
The Pyramid Integrator (PI) Link number for each DH+ network
must be unique. Use your PI Programming Software to configure
link numbers.
The valid transfer paths for the various PanelView terminals in the
figure are:
R K E
M A I
PI Chassis
2 2
3 3
Bridge
Address 6 7 8 9 Link 4 DH+
10
Link 3 DH+
23
Link 2 DH+
3
Link 1 DH+
12 11
Development Computer
I–1 Index
Symbols C
*.csv file, 3-8 Communication Driver
Configuration, dialog box, 5-9,
*.pvd file, 1-3
5-11, 5-14
Communications settings, saving,
Numbers 5-16
ControlLogix bridging, 2-4, 2-8
1770ĆKF2, 2-4
ControlNet
1770ĆKFC, 2-8 direct transfers, 2-8
1784ĆKL, 2-4 equipment required for transfer,
2-12
1784ĆKTC, 2-8 selecting driver, 5-1
1784ĆKTCX, 2-8 ControlNet addressing
1784ĆKTK1, 2-4 local station address, A-1
Logix55xx address, A-1
1784ĆKT, 2-4
CRC, errorĆdetection protocol, 5-9,
1784ĆKT2, 2-4 5-12, 5-15, 5-16
1784ĆKTX, 2-4 Cyclic Redundancy Check. See CRC
1784ĆPCMK, 2-4
1785ĆKA, A-2
bridging DH+ networks, A-2 D
1785ĆKE, 2-4 Data Transmission, errors, 3-2,
3-10, 4-2
Devices
A local station addressing, A-1
Logix55xx addressing, A-1
Alarm History
remote station address, A-1
configuring communications, 5-4
record, 3-8 DH+, 2-4
uploading, 3-10 equipment required for transfer,
2-12
Alarm trigger value, 3-9
PassĆThrough transfers, 2-12
AllenĆBradley, PI Programming remote station address
Software, A-4 bridged by 1785ĆKA, A-2
Application bridged by Pyramid Integrator,
downloading, tips, 1-4ć1-7 A-4
uploading, tips, 1-4ć1-7 RIO PassĆThrough, 2-12
selecting driver, 5-1
AUTOEXEC.BAT file, 2-20, 2-22,
2-24, 2-25 DH+ addresing, remote station
address, A-1
DH+ addressing
B local station address, A-1
Logix55xx address, A-1
Baud rate, 5-9, 5-11, 5-14 DH+/RIO PassĆThrough, 2-12
default, 3-2, 3-10, 4-2
Direct transfers, 1-4
BCC, errorĆdetection protocol, 5-9,
5-16 Downloading, 1-3
DH+/RIO PassĆThrough, 1-4
Block Check Character. See BCC
methods, 1-3
Bridged DH+ networks tips, 1-4ć1-7
with 1785ĆKA, A-2
Driver packages, selecting , 5-1
with Pyramid Integrator, A-4
Publication 2711E-6.16
Index I–2
E RM, A-4
P
H PanelBuilder 1400e, support services,
Hardware requirements, minimum, P-4
2-1 PanelBuilder software, 2-2
Help. See Online help for doing file transfers, P-1, 1-2
PanelView 1200/1400e Transfer
Utility
I exiting, 2-31
starting, 2-30
Installation requirements, 2-1 from Windows 3.x, 2-29
Installing FTU, floppy disks from Windows 95, 2-29
on Windows 3.x, 2-21, 2-24 starting FTU, 2-29
on Windows 95, 2-17, 2-21, Accessing, PanelView e Transfer
2-23, 2-24 Utility 32, 1-1
on Windows NT, 2-17, 2-23
Icon, PanelView e Transfer Utility
INTERCHANGE software, 1-6, 32, 1-1
1-7
PanelView e Transfer Utility 32,
and device drivers, 1-6
about, 1-1
Invoke RSLinx, 5-11, 5-14
Starting FTU32, 2-26
Starting FTU32 from PanelBuilder
K 1400e, 2-28
PanelView terminals, catalog
KA, modules, A-4 numbers, 2-2
Parity, 3-2, 3-10, 4-2, 5-9, 5-12,
5-15
L PassĆThrough Byte Definition
Local station address Byte, 5-16
ControlNet, A-1 Rack number, 5-16
DH+, A-1 Word, 5-16
U
S Upload application, selection from
Settings, changing, 3-2, 3-10, 4-2 menu, 3-6, 3-14
Software requirements, minimum, Upload/Download cable, 2-3, 5-9,
2-1 5-11, 5-15
Starting Transfer Utility Uploading, 1-3
from PanelBuilder 1400e, 2-28 Alarm History files, 1-3
from Windows 3.x, 2-26, 2-29 DH+/RIO PassĆThrough, 1-4
from Windows 95, 2-29 tips, 1-4ć1-7
Support services, P-4
System requirements, 2-1 W
WINtelligent LINX
T drivers, 1-7
port selected, 5-11, 5-14
Technical support services, P-4
Publication 2711E-6.16
Publication 2711E-UM003B-EN-P - September 2001 PN 41061-138-01(2)
Supersedes Publication 2711-E-6.16 - November 1999 © 2001 Rockwell International Corporation. Printed in the U.S.A.