SRB 301Lc / Lci / Lci/7 Operating Instructions Safety-Monitoring Module
SRB 301Lc / Lci / Lci/7 Operating Instructions Safety-Monitoring Module
SRB 301Lc / Lci / Lci/7 Operating Instructions Safety-Monitoring Module
9 EU Declaration of conformity
EN Operating instructions������������������������pages 1 to 6
Original
1.1 Function
This operating instructions manual provides all the information you
need for the mounting, set-up and commissioning to ensure the safe
operation and disassembly of the safety-monitoring module. The
operating instructions must be available in a legible condition and a
complete version in the vicinity of the device.
Please make sure that you have read and understood these operating
instructions and that you know all applicable legislations regarding
occupational safety and accident prevention prior to installation and
putting the component into operation.
5 Operating principle and settings Further technical information can be found in the Schmersal
5.1 LED functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 catalogues or in the online catalogue on the Internet:
5.2 Description of the terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 www.schmersal.net.
5.3 Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
The information contained in this operating instructions manual is
6 Set-up and maintenance provided without liability and is subject to technical modifications.
6.1 Functional testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
6.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 There are no residual risks, provided that the safety instructions as well
as the instructions regarding mounting, commissioning, operation and
7 Disassembly and disposal maintenance are observed.
7.1 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
7.2 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
EN 1
Operating instructions
Safety-monitoring module SRB 301LC / LCI / LCI/7
1.6 Warning about misuse 2.4 Technical data
General data
In case of inadequate or improper use or manipulations of Standards: EN 60204-1, IEC 60947-5-1;
the safety-monitoring module, personal hazards or damage ISO 13849-1, IEC 61508
to machinery or plant components cannot be excluded. Climate resistance: EN 60068-2-78
The relevant requirements of the standards ISO 14119 and Mounting: snaps onto standard DIN rail to EN 60715
ISO 13850 must be observed. Terminal designations: IEC 60947-1
Material of the housings: Plastic, glass-fibre reinforced
thermoplastic, ventilated
1.7 Exclusion of liability Material of the contacts: AgSnO, self-cleaning, positive drive
We shall accept no liability for damages and malfunctions resulting from Weight: 230 g
defective mounting or failure to comply with this operating instructions Start conditions: Automatic or start button
manual. The manufacturer shall accept no liability for damages Feedback circuit (Y/N):yes
resulting from the use of unauthorised spare parts or accessories. Pull-in delay: approx. 30 ms
Drop-out delay in case of emergency stop: ca. 50 ms
For safety reasons, invasive work on the device as well as arbitrary Mechanical data
repairs, conversions and modifications to the device are strictly Connection type: refer to 2.1 Ordering code
forbidden; the manufacturer shall accept no liability for damages Cable section: refer to 2.1 Ordering code
resulting from such invasive work, arbitrary repairs, conversions and/or Connecting cable: rigid or flexible
modifications to the device. Tightening torque for the terminals: 0.6 Nm
With removable terminals (Y/N): SRB 301LC: No
The safety-monitoring module must only be used when the enclosure is SRB 301LCI: Yes
closed, i.e. with the front cover fitted. SRB 301LCI/7: Yes
Mechanical life: 10 million operations
Electrical life: Derating curve available on request
2. Product description Resistance to shock: 10 g / 11 ms
Resistance to vibrations
2.1 Ordering code to EN 60068-2-6: 10 ... 55 Hz,
This operating instructions manual applies to the following types: amplitude 0.35 mm
Ambient conditions
SRB 301➀ Ambient temperature: – 25 °C … +45 °C
No. Option Description Storage and transport temperature: –40 °C … +85 °C
Protection class: Enclosure: IP40
➀ LC Screw terminals 0.25…2.5 mm², glass fuse Terminals:
LCI Plug-in screw terminals 0.25…2.5 mm², electronic fuse IP20
LCI/7 Plug-in cage clamps 0.25…1.5 mm², electronic fuse Clearance: IP54
Air clearances and creepage distances
Only if the information described in this operating instructions to IEC 60664-1: 4 kV/2 (basic insulation)
manual are realised correctly, the safety function and EMC rating: to EMC Directive
therefore the compliance with the Machinery Directive is Electrical data
maintained. Contact resistance in new state: max. 100 mΩ
Power consumption: max. 1.7 W / 1.9 VA
2.2 Special versions Rated operating voltage Ue: 24 VDC –15% / +20%,
For special versions, which are not listed in the order code below 2.1, residual ripple max. 10%
these specifications apply accordingly, provided that they correspond to 24 VAC –15% / +10%
the standard version. Frequency range: 50 / 60 Hz
Fuse rating for the operating voltage:
2.3 Destination and use - SRB 301LC: glass fuse;
The safety-monitoring modules for integration in safety circuits are internal T 0.5 A (5 x 20 mm);
designed for fitting in control cabinets. They are used for the safe - SRB 301LCI + SRB 301LCI/7: electronic trip;
evaluation of the signals of positive break position switches for safety tripping current > 0.25 A
functions on sliding, hinged and removable safety guards as well as Monitored inputs
emergency stop control devices. Cross-wire detection (Y/N): Yes
Wire breakage detection (Y/N): Yes
The safety function is defined as the opening of the enabling circuits Earth leakage detection (Y/N): Yes
13-14, 23-24 and 33-34 when the inputs S11-S12 and/or S21-S22 are Number of NO contacts:0
opened. The safety-relevant current paths with the outputs contacts Number of NC contacts:2
13-14, 23-24 and 33-34 meet the following requirements under Cable length: 1-channel without cross-wire short detection:
observation of a PFH value assessment (also refer to chapter 2.5 – 1,500 m = 1.5 mm²
"Safety classification"): – 2,500 m = 2.5 mm²
- Control category 4 - PL e to ISO 13849-1-1 2-channel without cross-wire short detection
- SIL 3 to IEC 61508-2 Conduction resistance: max. 40 Ω
- SILCL 3 to IEC 62061 Outputs
Number of safety contacts:3
To determine the Performance Level (PL) to ISO 13849-1 of the entire Number of auxiliary contacts:1
safety function (e.g. sensor, logic, actuator), an assessment of all Number of signalling outputs:0
relevant components is required. Switching capacity of the safety contacts: 13-14; 23-24; 33-34:
max. 250 V, 6 A ohmic
The entire concept of the control system, in which the safety (inductive in case of appropriate protective wiring);
component is integrated, must be validated to the relevant min. 10 V / 10 mA
standards. Switching capacity of the auxiliary contacts: 41-42: 24 VDC / 2 A
2 EN
Operating instructions
Safety-monitoring module SRB 301LC / LCI / LCI/7
Fuse rating of the safety contacts: external (Ik = 1000 A) 4. Electrical connection
to IEC 60947-5-1
Safety fuse 8 A quick blow, 6 A slow blow 4.1 General information for electrical connection
Fuse rating for the auxiliary contacts: external (Ik = 1000 A)
to IEC 60947-5-1 As far as the electrical safety is concerned, the protection
Safety fuse 2.5 A quick blow, 2 A slow blow against unintentional contact of the connected and therefore
Utilisation category to IEC 60947-5-1: AC-15 / DC-13 electrically interconnected apparatus and the insulation of the
Dimensions H x W x D: SRB 301LC: 100 × 22.5 × 121 mm feed cables must be designed for the highest voltage, which
SRB 301LCI: 120 × 22.5 × 121 mm can occur in the device.
SRB 301 LCI/7: 130 × 22.5 × 121 mm
The data specified in this manual are applicable when the component is
operated with rated operating voltage Ue ±0%. The electrical connection may only be carried out by authorised
personnel in a de-energised condition.
2.5 Safety classification
Standards: ISO 13849-1, IEC 61508 Wiring examples: see appendix
PL: up to e
Control category: up to 4
DC: 99% (high) 5. Operating principle and settings
CCF: > 65 points
PFH: ≤ 2.00 × 10-8/h 5.1 LED functions
SIL: up to 3 • K1: Status channel 1
Service life: 20 years • K2: Status channel 2
• UB: S tatus operating voltage (LED is on, when the operating voltage
The PFH value of 2.00 × 10-8/h applies to the combinations of contact on the terminals A1-A2 is ON)
load (current through enabling contacts) and number of switching • Ui: Status internal operating voltage (LED is on, when the operating
cycles (nop/y) mentioned in the table below. At 365 operating days per voltage on the terminals A1-A2 is ON and the fuse has not been
year and a 24-hours operation, this results in the below-mentioned triggered).
switching cycle times (tcycle) for the relay contacts.
Diverging applications upon request. 5.2 Description of the terminals
3.2 Dimensions
All measurements in mm.
Fig. 1
Device dimensions (H/W/D):
SRB 301LC: 100 × 22.5 × 121 mm 5.3 Notes
SRB 301LCI: 120 × 22.5 × 121 mm
SRB 301 LCI/7: 130 × 22.5 × 121 mm SRB 301LCI and SRB 301LCI/7: due to the operating
principle of the electronic fuse, the customer must check
that no hazard is caused by an unexpected restart in circuits
without reset button (automatic start).
EN 3
Operating instructions
Safety-monitoring module SRB 301LC / LCI / LCI/7
6. Set-up and maintenance 8. Appendix
X1 X1
J
KB KB
S S
KA KA
X2 X2
Fig. 3 Fig. 4
4 EN
Operating instructions
Safety-monitoring module SRB 301LC / LCI / LCI/7
8.3 Sensor configuration 8.4 Actuator configuration
Single-channel emergency stop circuit with command devices to Single-channel control with feedback circuit (Fig. 11)
ISO 13850 and IEC 60947-5-5 (Fig. 5) • Suitable for increase in capacity or number of contacts by means of
• Wire breakage and earth leakage in the control circuits are detected. contactors or relays with positive-guided contacts.
• Category 1 – PL c to ISO 13849-1 possible. •S = feedback circuit:
If the feedback circuit is not required, establish a bridge.
Dual-channel emergency stop circuit with command devices to
ISO 13850 and IEC 60947-5-5 (Fig. 6) Dual-channel control with feedback circuit (Fig. 12)
• Wire breakage and earth leakage in the control circuits are detected. • Suitable for increase in capacity or number of contacts by means of
• Cross-wire shorts between the control circuits are not detected. contactors or relays with positive-guided contacts.
• Control category 4 – PL e to ISO 13849-1 possible •S = feedback circuit:
(with protective wiring) If the feedback circuit is not required, establish a bridge.
N N
Fig. 11 Fig. 12
S12 S22 S12 S22 S12 S22
Fig. 5 Fig. 6 Fig. 7
EN 5
Operating instructions
Safety-monitoring module SRB 301LC / LCI / LCI/7
9. EU Declaration of conformity
EU Declaration of conformity
Original K.A. Schmersal GmbH & Co. KG
Möddinghofe 30
42279 Wuppertal
Germany
Internet: www.schmersal.com
We hereby certify that the hereafter described components both in their basic design and construction conform
to the applicable European Directives.
Description of the component: Safety-monitoring module for emergency stop circuits and guard
door monitoring
Notified body for the prototype test: TÜV Rheinland Industrie Service GmbH
Alboinstr. 56, 12103 Berlin
ID n°: 0035
Authorised signature
Philip Schmersal
Managing Director
Phone: +49 - (0)2 02 - 64 74 - 0
Telefax: +49 - (0)2 02 - 64 74 - 1 00
E-Mail: [email protected]
Internet: http://www.schmersal.com
6 EN