Operator Manual 306681a
Operator Manual 306681a
Operator Manual
Release 7.3
306681/A
May 2007
Document history
Document number: 306681
Rev. A May 2007 First version.
The reader
This operator manual is intended as a reference manual for the system operator. The manual is a maximum
manual and may contain information not relevant for your vessel.
Note
The information contained in this document remains the sole property of Kongsberg Maritime AS. No
part of this document may be copied or reproduced in any form or by any means, and the information
contained within it is not to be communicated to a third party, without the prior written consent of
Kongsberg Maritime AS.
Kongsberg Maritime AS endeavours to ensure that all information in this document is correct and fairly
stated, but does not accept liability for any errors or omissions.
Warning
The equipment to which this manual applies must only be used for the purpose for which it was
designed. Improper use or maintenance may cause damage to the equipment and/or injury to personnel.
The user must be familiar with the contents of the appropriate manuals before attempting to operate
or work on the equipment.
Kongsberg Maritime disclaims any responsibility for damage or injury caused by improper installation,
use or maintenance of the equipment.
Comments
To assist us in making improvements to the product and to this manual, we welcome comments and
constructive criticism.
e-mail: [email protected]
Kongsberg Maritime AS
P.O.Box 483 Telephone: +47 32 28 50 00
N-3601 Kongsberg, Telefax: +47 32 28 50 10
Norway Service: +47 815 35 355
www.kongsberg.com
Operator Manual
Table of contents
Glossary....................................................................................................................8
1 SYSTEM DESCRIPTION.................................................... 11
1.1 Where to find K-Chief 700 user documentation .................................................... 11
1.2 K-Chief 700 system outline....................................................................................12
1.3 Decentralised system architecture ..........................................................................13
1.4 Main system components ......................................................................................13
1.4.1 Operator Stations ....................................................................................... 14
1.4.2 Field Stations ............................................................................................. 14
1.4.3 Communication Network ........................................................................... 15
1.4.4 History Station ........................................................................................... 15
1.4.5 Extended Alarm Systems............................................................................. 15
2 USER INTERFACE ........................................................... 17
2.1 Overview ................................................................................................................17
2.1.1 AIM User Guide ......................................................................................... 17
2.1.2 System version information ......................................................................... 19
2.2 Operator Station images .........................................................................................19
2.2.1 Image types ................................................................................................ 20
2.2.2 Image layout............................................................................................... 21
2.2.3 Process images ........................................................................................... 22
2.2.4 Flow Sheet images ...................................................................................... 23
2.2.5 List images................................................................................................. 25
2.2.6 Trend images.............................................................................................. 26
2.2.7 Event List images ....................................................................................... 27
2.2.8 System Status images.................................................................................. 28
2.2.9 PDF images................................................................................................ 29
2.2.10 Multiple images.......................................................................................... 30
2.3 Operator Station panels ..........................................................................................30
2.3.1 Input Panel (INP)........................................................................................ 30
2.3.2 Alarm & Control Panel (ALC)..................................................................... 32
2.3.3 Automation Panel (BU-AUT) ...................................................................... 34
3 BASIC MONITORING AND CONTROL .............................. 36
3.1 Image construction ................................................................................................36
3.1.1 Function module symbols ........................................................................... 36
3.1.2 Pipes ......................................................................................................... 44
3.1.3 Process changes ......................................................................................... 44
3.1.4 Static symbols ........................................................................................... 45
3.1.5 Alarm indicators ........................................................................................ 45
3.2 Operation menu buttons ........................................................................................46
3.3 Analogue measurement modules ...........................................................................47
306681/A 3
Kongsberg K-Chief 700
4 306681/A
Operator Manual
306681/A 5
Kongsberg K-Chief 700
6 306681/A
Operator Manual
306681/A 7
Kongsberg K-Chief 700
Glossary
AIM Advanced Integrated Multifunction system
ALC Alarm & Control Panel
BIST Built-In Self Test
BU-AUT Business Unit Automation Panel
CAN Controller Area Network
CPU Central Processing Unit
DG Diesel Generator
DO Diesel Oil
DP Dynamic Positioning
ECR Engine Control Room
EMC Electromagnetic Compatibility
EMD European Union Maritime Directive
FO Fuel Oil
FS Field Station
GMS Graphic Modelling System
HFO Heavy Fuel Oil
HS History Station
IMO International Maritime Organization
INP Input Panel
IO, I/O Input/Output
IP Ingress Protection
K-Bridge Kongsberg Bridge System
K-Chief Kongsberg Vessel Control System
K-Gauge Kongsberg Gauging System
K-Pos Kongsberg Dynamic Positioning System
K-Pos PM Kongsberg Position Mooring System
K-Pro Kongsberg Process System
K-Safe Kongsberg Safety System
K-Thrust Kongsberg Thruster Control System
LAN Local Area Network
LCD Liquid Crystal Display
LED Light Emitting Diode
MTBF Mean Time Between Failure
NDU Network Distribution Unit
OS Operator Station
8 306681/A
Operator Manual
PC Personal Computer
PDU Power Distribution Unit
PID Proportional Integral Derivative
PMS Power Management System
RCU Remote Controller Unit
RIO Remote Input Output
RPM Revolutions Per Minute
UPS Uninterruptible Power Supply
WBU Watch Bridge Unit
WCU Watch Cabin Unit
306681/A 9
Kongsberg K-Chief 700
10 306681/A
System Description
1 SYSTEM DESCRIPTION
Table 1 Information division between K-Chief 700 Operator Manual and AIM User
Guide
306681/A 11
Kongsberg K-Chief 700
12 306681/A
System Description
306681/A 13
Kongsberg K-Chief 700
14 306681/A
System Description
Distributed processing
The system is a distributed processing system due to the fact that
the process control functions are defined locally in the FSs, not
centrally in the OSs. Because the OSs are process independent,
they can be located anywhere on a vessel. This also means that
each OS is capable of controlling any process, provided that it
has control of the appropriate Command Group and the user is
logged on with sufficient access rights.
Each OS has a hard disk containing the software files for the
actual vessel installation. Process variable and parameter
values to be displayed by the OSs are generated in the FSs and
transferred to each OS on request. This means, what you see on
an OS screen is assembled directly from all the FSs.
306681/A 15
Kongsberg K-Chief 700
16 306681/A
User Interface
2 USER INTERFACE
2.1 Overview
TheK-Chief 700 user interface is a colour monitor screen, an
Operator panel and an alphanumeric keyboard. The screen
displays the K-Chief 700 images and the Operator panel is used
to interact with those images. The alphanumeric keyboard is
used for set-up and configuration purposes.
This topic covers all the elements of the interface. It describes the
use of the Operator panel, how to access and select alphanumeric
keyboard operation, and gives an overview of the different
images available.
See also AIM User Guide on page 17 and the Operator Station
topic in the online AIM User Guide.
306681/A 17
Kongsberg K-Chief 700
18 306681/A
User Interface
306681/A 19
Kongsberg K-Chief 700
20 306681/A
User Interface
306681/A 21
Kongsberg K-Chief 700
22 306681/A
User Interface
306681/A 23
Kongsberg K-Chief 700
24 306681/A
User Interface
306681/A 25
Kongsberg K-Chief 700
26 306681/A
User Interface
306681/A 27
Kongsberg K-Chief 700
28 306681/A
User Interface
306681/A 29
Kongsberg K-Chief 700
30 306681/A
User Interface
306681/A 31
Kongsberg K-Chief 700
• Rollerball
This is used for navigation on the screen.
• Mouse buttons
Same function as an ordinary PC-mouse.
• Arrow buttons
These buttons work like arrow buttons on an ordinary
alphanumeric keyboard.
2.3.1.4 Backlight
The backlight is integrated in the panel film and has yellow
colour. The backlight intensity can be adjusted from the computer
via USB, and the function is implemented in the module using
PWM.
32 306681/A
User Interface
306681/A 33
Kongsberg K-Chief 700
• STATUS
The button, when activated, provides a signal to the computer.
2.3.2.5 Backlight
The backlight is integrated in the panel film and has yellow
colour. The backlight intensity can be adjusted from the computer
via USB and is implemented locally using PWM.
2.3.2.6 Buzzer
There are three buzzers. All are controlled by the local controller.
On of them is, in addition, controlled directly by power. If power
is lost, an alarm sounds for at least 60 seconds. The sound
intensity is controlled by the number of buzzers activated, and the
intensity setting can be configured. The sounder can be silenced
both when power is lost and by the local controller.
34 306681/A
User Interface
2.3.3.3 Backlight
The backlight is integrated in the panel film and has yellow
colour. The backlight intensity can be adjusted from the computer
via USB and the function is implemented in the module using
PWM.
306681/A 35
Kongsberg K-Chief 700
36 306681/A
Basic Monitoring and Control
The Tag name of the item of equipment that the function module
controls is displayed in the title bar of the module operation
menu.
Note
The operation menu may differ depending on the software version
of the function module in question.
306681/A 37
Kongsberg K-Chief 700
38 306681/A
Basic Monitoring and Control
306681/A 39
Kongsberg K-Chief 700
40 306681/A
Basic Monitoring and Control
306681/A 41
Kongsberg K-Chief 700
The menu will always contain the same commands, but those
available will depend on the function module symbol selected
and the user group to which your user name is assigned.
If you are logged on as a member of the Users user group, the
Alarm Limits and Module Status commands will be
unavailable.
42 306681/A
Basic Monitoring and Control
Note
1: see Station Status topic in the online AIM User Guide.
2: see Module Editor topic in the online AIM User Guide.
Note
Process status colours are configurable.
306681/A 43
Kongsberg K-Chief 700
3.1.2 Pipes
Lines in images, representing pipes carrying fluids, can be
coloured to indicate content.
The standard colours used to indicate pipe content are listed in
the following table:
Note
Pipe colours are configurable.
44 306681/A
Basic Monitoring and Control
306681/A 45
Kongsberg K-Chief 700
46 306681/A
Basic Monitoring and Control
3.3.1 Symbols
A selection of how analogue measurement modules may be
represented by symbols is shown in the following figure:
306681/A 47
Kongsberg K-Chief 700
48 306681/A
Basic Monitoring and Control
306681/A 49
Kongsberg K-Chief 700
3.3.4.3 IO failure
Analogue measurement modules have an IO failure function
that controls the value shown in the numeric value field when a
failure is detected by the IO self-test system. If an IO failure is
detected, the displayed value will be one of the following:
• Frozen at the last legal input value (default).
• Set to a configurable fixed value.
• Based on the measured input signal value and the IO failure
status ignored.
See IO system topic and Alarms and messages topic in the online
AIM User Guide.
3.4.1 Symbols
A set of measured analogue values is used to indicate the exhaust
gas temperatures of each cylinder of the engine as shown in a
typical symbol in the following figure:
50 306681/A
Basic Monitoring and Control
3.5.1 Symbols
An example of how Digital measurement modules may be
represented by symbols is shown in the following figure:
306681/A 51
Kongsberg K-Chief 700
52 306681/A
Basic Monitoring and Control
• Text string
• Module inhibit.
The status of these functions can be viewed and changed using
the commands on the module shortcut menu (see Shortcut menu
on page 40) that gives you access to the module set-up facilities.
3.5.4.1 Alarm delay
Digital measurement modules have a configurable alarm delay
function that prevents short-duration signal changes from
generating alarms.
3.5.4.2 Alarm suppression
Digital measurement modules have an alarm suppression
function that is enabled/disabled externally from other modules.
It has two types of suppression, one that sets the output signals
to "logical 0" and one that sets the output signals to "logical 1".
The resetting of this function can be delayed by a configurable
time (see Event system topic and Alarms and messages topic in
the online AIM User Guide).
3.5.4.3 Text string
Digital measurement modules have a text string function that
displays one of two configurable text strings. The displayed text
string is controlled by the logical state of the module’s output
signal.
3.5.4.4 Module inhibit
The module inhibit function, which is manually controlled via
the INHIBIT ON/INHIBIT OFF command on the module
operation menu, can also be enabled/disabled externally by other
function modules.
3.6.1 Symbols
An example of how a Pulse measurement module may be
represented by symbols is shown in the following figure:
306681/A 53
Kongsberg K-Chief 700
54 306681/A
Basic Monitoring and Control
306681/A 55
Kongsberg K-Chief 700
3.7.1 Symbols
A Motor/Pump control function module is represented
graphically by a symbol accompanied by a tag mark character
that indicates the current operational mode of the motor/pump.
56 306681/A
Basic Monitoring and Control
306681/A 57
Kongsberg K-Chief 700
58 306681/A
Basic Monitoring and Control
306681/A 59
Kongsberg K-Chief 700
Note
The operation menu may differ depending on the software version
of the function module in question.
60 306681/A
Basic Monitoring and Control
306681/A 61
Kongsberg K-Chief 700
3.7.7.6 Shut-down
All Motor/Pump control modules have a shutdown function that
overrides all other control inputs to the function module and
provides an emergency stop facility.
62 306681/A
Basic Monitoring and Control
306681/A 63
Kongsberg K-Chief 700
3.8.1 Symbols
A Valve control module is represented graphically by a symbol
accompanied by a tag mark character that indicates the current
operational mode of the valve. The symbol may also be
accompanied by a numeric value if the valve has a controllable
movement. This value indicates either the actual position of the
valve or the setpoint of the valve in percent.
64 306681/A
Basic Monitoring and Control
306681/A 65
Kongsberg K-Chief 700
66 306681/A
Basic Monitoring and Control
306681/A 67
Kongsberg K-Chief 700
68 306681/A
Basic Monitoring and Control
3.8.7.3 Shut-down
All Valve control modules have a shutdown function that
overrides all other control inputs to the function module. This
function may be used as an emergency close facility.
3.9.1 Symbols
PID controllers may be shown in many ways, from a simple box
to a bar chart with multiple values.
The standard symbols for a PID controller are shown in the
following figure:
306681/A 69
Kongsberg K-Chief 700
70 306681/A
Basic Monitoring and Control
• set a manual output value for the PID controller. The output
is set via the Numeric input dialog box. The command is only
available in the Manual mode.
• turn the module inhibit function onor off. When the
module operation menu is opened, the button text indicates
the state that can be selected. When the module inhibit
function is active (turned on), no action is sent out to other
modules and the output signals are set to "logical 0". Alarms
are indicated if the module is in an alarm state. When
the module inhibit function is disabled (turned off), the
INHIBIT ON/INHIBIT OFF command is also disabled.
The parameter inhibit types are as follows:
0 - Operation menu button "INHIBIT ON" has no function
1 - INHIBIT ON inhibits Freeze terminal
2 - INHIBIT ON inhibits Ok terminal
3 - INHIBIT ON inhibits both Freeze and Ok terminal.
306681/A 71
Kongsberg K-Chief 700
72 306681/A
Basic Monitoring and Control
3.11.1 Symbol
The layout of the symbol for the Sequence Step module will
depend upon the number of conditions that must be fulfilled by
the step.
An example of a typical Sequence Step module symbol is shown
in the following figure:
306681/A 73
Kongsberg K-Chief 700
Step description A text field that describes the action of the step.
Status indicator A rectangular border that uses colour to indicate
the status of the step.
Colour Status
Red failed
Green active
Yellow hold
White completed
Background not active
Condition status A red, current condition, status text field together
with a list of conditions. Each condition is
preceded by a status check box and followed by a
collective logical operation indicator.
A status check box with a tick indicates that the
condition has been fulfilled.
The collective logical operation indicator shows
the type of logical operation to be performed by
the listed conditions.
& (AND) — all conditions to be fulfilled
> (OR) — one condition to be fulfilled.
74 306681/A
Basic Monitoring and Control
3.12.1 Symbol
The symbol for a typical Sequence Administrator module is
shown in the following figure:
306681/A 75
Kongsberg K-Chief 700
76 306681/A
Basic Monitoring and Control
306681/A 77
Kongsberg K-Chief 700
78 306681/A
Basic Monitoring and Control
3.13.1 Symbol
The symbol for the Sequence Recipe module, which is only
Figure displayed in Flow Sheet views, is shown in the following figure:
51 Sequence
Recipe module
symbol
306681/A 79
Kongsberg K-Chief 700
3.13.3.2 Interlock
All Sequence Recipe modules have an Interlock function that,
when set, blocks the update to the Sequence Administrator
module.
3.13.3.3 Freeze
All Sequence Recipe modules have a Freeze function. When the
"Freeze recipe data" parameter is set to "0", recipe data can be
changed. If the parameter is set 999, the recipe data is frozen.
Once the recipe data has been frozen, it can never be changed
from the function module.
80 306681/A
Basic Monitoring and Control
306681/A 81
Kongsberg K-Chief 700
4 POWER MANAGEMENT
The Power Management application provides monitoring, control
and safety functions for the power generating systems.
The Power Management Process image visualises the entire
power plant, generators and consumers. From this image you
can monitor the power network and operate the generators,
switchboards and circuit breakers. Major power consumers
are also shown in the graphic representation of the power
network. They are, however, operated from other applications
and therefore not described here.
A typical Power Management Process image is shown in the
following figure:
82 306681/A
Power Management
306681/A 83
Kongsberg K-Chief 700
84 306681/A
Power Management
4.3.1 Symbols
The graphic representation of a generator (MDG, Shaft or HG)
comprises a measurement graph that displays the load on the
generator and a generator symbol with four lines of status text
above it showing the current operational state of the generator.
An example of the symbols used to represent a generator is
shown in the following figure:
306681/A 85
Kongsberg K-Chief 700
86 306681/A
Power Management
306681/A 87
Kongsberg K-Chief 700
88 306681/A
Power Management
• select the Fix mode, which is only available for generators that
are connected to the switchboards of the power distribution
network. It is one of three automatic modes for controlling
distribution of the load to a single generator. The other two
modes are Symmetric and Asymmetric. You cannot stop
a generator when it is operating in the Fixed Load mode:
Manual, Symmetric or Asymmetric must be selected. To
leave this mode, Manual, Symmetric or Asymmetric must be
selected.
Note
You cannot select the Fixed Load mode for a "standby"
generator.
306681/A 89
Kongsberg K-Chief 700
90 306681/A
Power Management
306681/A 91
Kongsberg K-Chief 700
4.4.1 Symbol
The switchboard module symbol comprises a box with text
and measurement values that shows the identification of the
switchboard, the status of Load and Consumer Control, the
current power loading on the switchboard and the available
unused power (spare capacity).
An example of a switchboard symbol is shown in the following
figure:
This module allows you to switch Load Start, Load Stop and
Consumer Control on and off by means of a module operation
menu. This menu is opened by clicking the ON/OFF text in the
Load and Consumer Control status field of the symbol using
the left trackball button.
92 306681/A
Power Management
306681/A 93
Kongsberg K-Chief 700
94 306681/A
Power Management
4.5.1 Symbol
A circuit breaker is represented by the following symbols.
306681/A 95
Kongsberg K-Chief 700
Note
The operation menu may differ depending on the software version
of the function module in question.
4.6 Consumers
Consumers appear in the Power Management application Process
images for clarity. They are usually controlled directly from
Process images within other applications. For example, the
thrusters are controlled from the Thruster/Propulsion application
Process images.
The colours used to indicate the operational status of consumers
are as follows:
Green: the consumer is running
White: the consumer is stopped
Yellow: the consumer is in a transient state (starting,
stopping or changing speed).
96 306681/A
Power Management
Note
The operation menu may differ depending on the software version
of the function module in question.
306681/A 97
Kongsberg K-Chief 700
98 306681/A
Power Management
306681/A 99
Kongsberg K-Chief 700
100 306681/A
Power Management
306681/A 101
Kongsberg K-Chief 700
102 306681/A
Power Management
306681/A 103
Kongsberg K-Chief 700
5 PROPULSION CONTROL
The Propulsion Control application provides monitoring, control
and safety functions for the vessel’s thruster and main propulsion
system.
The main control locations for the vessel’s thruster and main
propulsion systems are the K-Thrust and/or K-Pos Operator
Stations (see K-Thrust Operator Manual and/or K-Pos Operator
Manual).
The K-Chief 700 Operator Stations are therefore normally
used to provide details on thruster status and alarm monitoring.
However, the K-Chief 700 Operator Stations are provided with
a downgraded control mode (called the Maintenance mode).
This mode, which allows individual manual control of each
component within the propulsion system, is mainly for use during
maintenance when performing fault-finding.
The Propulsion Process image, which is basically a "Bridge
Information" image, visualises the thrusters and main propulsion
system. From this image you can see the command control
location (K-Thrust, K-Pos or K-Chief 700), and monitor the
status of the thrusters and main propulsion units. The main
electrical generators and information concerning vessel loading
and draught are normally also shown in the image.
The following figure shows a typical Propulsion Process image:
104 306681/A
Propulsion Control
306681/A 105
Kongsberg K-Chief 700
106 306681/A
Propulsion Control
The thruster control mode plus facilities for manual and sequence
control together with pitch and/or rpm measurements may be
shown.
A number of status indicators may appear on the image to indicate
operational and fault conditions. If there is not enough space,
these will be placed on a separate Thruster Safety Process image.
306681/A 107
Kongsberg K-Chief 700
108 306681/A
Propulsion Control
306681/A 109
Kongsberg K-Chief 700
110 306681/A
Propulsion Control
306681/A 111
Kongsberg K-Chief 700
112 306681/A
Propulsion Control
306681/A 113
Kongsberg K-Chief 700
5.5.7 Safety
Emergency Stop buttons that are connected directly to the starter
control circuits by hard wiring may be provided for each thruster.
If installed, these will normally be located on a panel near the
K-Thrust Operator Station.
Control and feedback signals for pitch and azimuth are
monitored, and any failure in these signals will normally stop the
thruster. The control actions taken depend on the application and
the type of thruster system. Deviations outside a specified limit
between setpoint and feedback values over a certain time will
cause an alarm to be generated. For sine/cosine measurements,
an alarm will be generated if the two signals do not match.
114 306681/A
Propulsion Control
Note
The operation menus may differ depending on the software
version of the function module in question.
306681/A 115
Kongsberg K-Chief 700
116 306681/A
Propulsion Control
306681/A 117
Kongsberg K-Chief 700
118 306681/A
Propulsion Control
306681/A 119
Kongsberg K-Chief 700
120 306681/A
Redundancy and Criticality Assessment System
306681/A 121
Kongsberg K-Chief 700
122 306681/A
Redundancy and Criticality Assessment System
306681/A 123
Kongsberg K-Chief 700
Indicator
Colour Warning State
Magenta PU or one or more SSs tripped, or conditions exist that will quickly
implement a trip.
Red Major fault in the PU or one or more SSs. For example, a High
High (HH) or Low Low (LL) alarm condition, as defined in the
appropriate RCA-PU or RCA-SS State Diagram (see State diagrams
on page 129) is active.
Yellow Minor fault in the PU or one or more SSs. For example, a High (H)
or Low (L) alarm condition, as defined in the appropriate RCA-PU or
RCA-SS State Diagram (see State diagrams on page 129) is active.
SS requirements warning (see on page and on page ).
Cyan The required SS standby equipment is "not ready".
124 306681/A
Redundancy and Criticality Assessment System
306681/A 125
Kongsberg K-Chief 700
Note
The background colour of the status field is always the same as
the colour of the PU symbol.
Indicator
Colour Warning State
Magenta PU tripped or conditions exist that will quickly implement a trip.
Red Major fault in the PU. For example, a High High (HH) or Low Low
(LL) alarm condition, as defined in the appropriate RCA-PU State
Diagram (seeState diagrams on page 129) is active.
Yellow Minor fault in the PU. For example, a High (H) or Low (L) alarm
condition, as defined in the appropriate RCA-PU State Diagram (see
State diagrams on page 129) is active.
SS requirements warning (see on page and on page ).
126 306681/A
Redundancy and Criticality Assessment System
— Minor warnings.
Note
Field C is only used when Field B indicates "Not required".
306681/A 127
Kongsberg K-Chief 700
The Sequence Process image for each Vessel Control mode can
be displayed by means of a Sequence hot spot, located next to
the corresponding control mode selection button.
An example of a typical Sequence Process image for a Vessel
Control mode transfer is shown in the following figure:
128 306681/A
Redundancy and Criticality Assessment System
306681/A 129
Kongsberg K-Chief 700
130 306681/A
Redundancy and Criticality Assessment System
306681/A 131
Kongsberg K-Chief 700
132 306681/A
Redundancy and Criticality Assessment System
306681/A 133
Kongsberg K-Chief 700
Note
The events have been filtered to show only RCA events. This is
achieved by creating an alarm filter (e.g. Group: Mode_RCA)
that allows only events from the RCA Command group to be
displayed (see Event system topic in the online AIM User Guide).
The above example shows the RCA events that are generated
when the DP Vessel Control mode is selected and running, and
then suddenly the generator cooling water pump (PUMP43.01)
stops.
134 306681/A
Redundancy and Criticality Assessment System
306681/A 135
Kongsberg K-Chief 700
136 306681/A
Cargo and Ballast Control
From the Cargo Pump Process image you will be able to monitor
and control the cargo and stripping pumps together with the
valves for routing of fluids to and from the cargo tanks. This
image may also allow you to monitor and control some of the
auxiliary equipment associated with the cargo pumps.
A typical Cargo Pump Process image is shown in the following
figure:
306681/A 137
Kongsberg K-Chief 700
138 306681/A
Cargo and Ballast Control
306681/A 139
Kongsberg K-Chief 700
The starting and stopping of pumps and the opening and closing
of the valves is normally a part of the automatic cargo and ballast
tank filling and emptying sequences initiated from the Operator
Station.
In the Manual operation mode, the pumps and valves can be
controlled from the module operation menu for each individual
item of equipment (see Basic Monitoring and Control on
page 36).
In addition to tank, valve and pump symbols, the images may
contain a Global Control module which makes it possible
to control the operation of several tanks, pumps and valves
simultaneously.
The Cargo and Ballast second (lower) level Process images are
displayed using one of the following methods:
• A hot spot on the Ballast Process image or, where applicable,
one of the other second (lower) level Process images.
• The Navigator (see the Toolbars section in the Operator
Station topic in the AIM User Guide).
• The NAVIGATOR (VIEW MAP) button on the Operator panel
(see Automation Panel (BU-AUT) layout on page 35).
7.4.1 Symbol
The Global Control module symbol comprises a box with
text components that show the current operational state of the
function module.
An example of a Global Control module symbol is shown in the
following figure:
140 306681/A
Cargo and Ballast Control
The text box at the left of the symbol shows the selected
control mode for the function module, i.e. BALLAST MODE
or STRIPPING MODE.
The MODE: field shows the selected operating mode, i.e.
MANUAL or AUTO.
The UNIT: field shows the units that are being used for the
Measured and Requested Level Values in the tank symbols (see
Symbols on page 143).
Depending on the selection made, via the Global Control module
operation menu, the text displayed in the UNIT: field will be one
of the following:
VOL% Percentage of the tank’s capacity, occupied by the fluid in
the tank.
LEVEL Height of the fluid in the tank (in m)
VOLUME Content of the fluid in the tank (in m3)
WEIGHT Weight of the fluid in the tank (in tonnes)
ULLAGE Height of the free space above the fluid in the tank (in
metres)
DENSITY Density of the fluid in the tank (in tonnes/m3)
306681/A 141
Kongsberg K-Chief 700
142 306681/A
Cargo and Ballast Control
7.5.1 Symbols
The graphic representation of both tank modules comprises text
components and a symbol with a graphic level indicator. The
piping and manifolds between tanks are not part of the tank
module symbol. However, they are related to the symbols in
order to show emptying and filling routes.
306681/A 143
Kongsberg K-Chief 700
144 306681/A
Cargo and Ballast Control
306681/A 145
Kongsberg K-Chief 700
146 306681/A
Cargo and Ballast Control
306681/A 147
Kongsberg K-Chief 700
7.5.3 Routes
The graphic representation of the connections between tank
symbols and their inlets and outlets varies according to the route
indication requests from a specific tank module. Normally, flow
is indicated as opposed to line (pipe) pressure.
The interconnections, including valve and pump symbols which
are not part of the requested route, are Grey. There is no flow
in Grey pipes.
When a request to show the route for a specific tank is made, the
colour of the relevant pipes, valves and pumps changes to White.
There is, however, still no flow.
As the emptying or filling operation proceeds, the pipes and
manifolds change colour to Green to indicate that there is
pressure or flow. Note that valves and pumps have their specific
colour conventions to indicate the closed/stopped, transient and
open/running states.
148 306681/A
Cargo and Ballast Control
5 Move the cursor over the module symbol for the valve in the
route which is closest to the tank and press the left trackball
button.
The Valve module operation menu is displayed.
6 Click OPEN.
The valve operates and changes colour. The part of the route
which is filled with ballast fluid changes colour to Green.
7 Repeat steps 5 and 6 until all valves included in the route
are opened.
It is important to open the valves in the correct order.
8 Move the cursor over the module symbol for the pump and
press the left trackball button.
9 Click START.
When the pump is running, the entire route changes colour to
Green to indicate that the fluid is flowing towards the tank.
Dependent on the type of pump, it may be required to
execute steps 13 and 14 prior to step 10.
10 When the tank is filled up to the required level, move the
cursor over the module symbol for the valve and press the
left trackball button.
11 Click CLOSE.
12 Repeat steps 10 and 11 until all valves in the route are closed.
13 Move the cursor over the module symbol for the pump and
press the left trackball button.
14 Click STOP.
The entire route is now white.
15 Move the cursor over the module symbol for the tank and
press the left trackball button.
16 Click HIDE FILL.
306681/A 149
Kongsberg K-Chief 700
1 Move the cursor over the module symbol for the Global
Control module and press the left trackball button.
The Global Control module operation menu is displayed.
2 Click AUTO.
The operational mode indicator changes from MANUAL
to AUTO, and the valve and pump symbols which are
controlled from the Global Control module, change from
outline to solid.
3 Move the cursor over the Tank module symbol and press
the left trackball button.
The Tank module operation menu is displayed.
4 Click VOL% and then enter 50 in the displayed Numeric
input dialog box, using the numeric buttons on the Operator
panel. Confirm by clicking the OK button on the dialog box.
The displayed Requested Level Value for Tank A changes to
the value which represents 50% of the total tank capacity.
5 Click EMPTY.
The emptying route is highlighted. Even if the entire system
is under pressure, only the route for the selected tank(s)
turns Green to give a clear presentation of the flow.
Valve and pump symbols in this route change colour
according to their operational status. The route becomes
Green when there is flow in the pipes. As the requested
volume is reached, the valves and pumps operate and the
route indication changes colour from Green to Grey (not
highlighted). Note that the Measured Level Value now
equals the Requested Level Value.
150 306681/A
Cargo and Ballast Control
1 Click EMPTY.
The Requested Level Value changes to 0.0, the route is
highlighted and, as the ballast fluid flows through the pipes,
the colour of the route changes to Green.
The Measured Level Value decreases gradually.
2 Click HALT.
The valve and pump symbols in the emptying route operate,
the flow stops and the colour of the route changes from
Green to White.
The route remains highlighted and the Requested Level
Value remains unchanged.
3 Click CONTINUE.
The valve and pump symbols in the emptying route operate,
flow is indicated in the pipes, and the colour of the route
changes from White to Green.
The emptying process is re-established as if step 2 had not
occurred.
4 Click TERMINATE.
The valve and pump symbols in the emptying route operate,
flow in the pipes stops and the colour of the route changes
from Green to Grey.
306681/A 151
Kongsberg K-Chief 700
152 306681/A
Liquefied Natural Gas
306681/A 153
Kongsberg K-Chief 700
154 306681/A
Liquefied Natural Gas
From the Cargo-Control Process image you can monitor the deck
piping instruments (sensors for pressure, temperature and flow)
and valve position indicators. Temperature pressure sensors
in void spaces are interfaced to the K-Chief 700 by means of
barriers installed in the Process Stations. Process control stations
for control of compressors, heaters and vaporizers are installed
in the CER.
306681/A 155
Kongsberg K-Chief 700
From the Gas-Handling Process image you can monitor all the
control of valves, heaters, vaporizers and compressors. All deck
piping instruments (pressure, temperature and flow) and valve
position indicators are interfaced to K-Chief 700 by remote in-
or output. Process control stations for control of compressors,
heaters and vaporizers are installed in the CCR.
The gas-handling plant consists of the following main equipment:
• Low-duty gas compressor control
The main task for the low-duty gas compressors is to compress
the boil-off gas from the cargo tanks to a pressure sufficient
for the burners. The main task of the LD Compressor control
logic is to maintain a stable operating point for the fuel gas
control valve.
• High-duty gas compressor control
The high-duty gas compressors are used for return of vapour
to shore during loading, tank purging and tank warming up.
The HD compressor control must maintain a stable vapour
main pressure during these operations.
• Forcing vaporizer control
The forcing vaporizer is used to produce extra LNG gas, either
to increase the LNG gas rate to the burners or to increase the
cargo tank pressure.
156 306681/A
Liquefied Natural Gas
• LNG vaporizer
During unloading, the volume of unloaded LNG has to be
replaced, either from shore via the vapour crossover header
or, if LNG gas is not supplied from shore, by using the LNG
vaporizer. The LNG vaporizer is also used for vaporising N2
for purging of tanks.
• Boil-off gas heating
The main purpose of the vapour heaters is to heat the boil-off
to be used as fuel gas during voyage.
Interface with boiler controller
There is a set of control signals that runs between the boil-off gas
heating control and the boiler controller.
8.3.1 Control
A typical Boiler-Control Process image is shown as follows:
306681/A 157
Kongsberg K-Chief 700
158 306681/A
Liquefied Natural Gas
306681/A 159
Kongsberg K-Chief 700
8.3.2 Monitoring
In some projects, boiler control is performed by the boiler
manufacturer. In these cases the K-Chief 700 system is interfaced
to the boiler control and performs monitoring and alarm
inititation. A typical Boiler-Monitoring Process image is shown
as follows:
160 306681/A
Extended Alarm Systems
306681/A 161
Kongsberg K-Chief 700
First-time/original alarm
The first-time/original alarm is relayed to:
• The area designated as Watch Responsible
• The On Duty engineers Watch Cabin Units
• The Watch Cabin Units in all public areas
162 306681/A
Extended Alarm Systems
The main difference between the two types is that the LCD type
can display individual alarm messages, whilst the LED type has a
larger number of alarm groups.
• The LCD type will display date and time when no-one is ON
DUTY.
• For the LED type all indicators will be dark when no-one is
ON DUTY.
• The repeat alarm function is activated if an alarm is not
acknowledged within a set period of time.
306681/A 163
Kongsberg K-Chief 700
164 306681/A
Extended Alarm Systems
The main difference between the two types is that the LCD type
can display individual alarm messages, whilst the LED type has a
larger number of alarm groups.
• The LCD type will display date and time when no-one is ON
DUTY.
• For the LED type all indicators will be dark when no-one is
ON DUTY.
• The repeat alarm function is activated if an alarm is not
acknowledged within a set period of time.
306681/A 165
Kongsberg K-Chief 700
166 306681/A
Extended Alarm Systems
306681/A 167
Kongsberg K-Chief 700
168 306681/A
System Startup and Shutdown
306681/A 169
Kongsberg K-Chief 700
170 306681/A
System Startup and Shutdown
306681/A 171
Kongsberg K-Chief 700
172 306681/A
System Startup and Shutdown
306681/A 173
Kongsberg K-Chief 700
174 306681/A
System Startup and Shutdown
306681/A 175
©2007 Kongsberg Maritime
Kongsberg Maritime AS
P.O.Box 483 Telephone: +47 32 28 50 00
N-3601 Kongsberg, Telefax: +47 32 28 50 10
Norway Service: +47 815 35 355
www.kongsberg.com