Technical data
Type Drawing Max. operating Range of diameter over prepared cable insu- Equivaltent cable cross-section (Cu/Al)1 Max. cable dia-
voltage Um lation, min. - max. meter
kV mm mm² mm
1 Values for reference only. The exact application depend on the diameter over the prepared cable insulation.
Note: for installations > 45° oil expansion tanks type ET-2 are required. For 420 kV and 550 kV ET-2 tanks are necessary.
20170718-1
www.bruggcables.com
(x) Dimensionen gemäss IEC 62271-209 für
Flüssigkeit gefüllte Endverschlüsse /
Dimensions according to IEC 62271-209 for fluid filled
terminations
Dichtung / Sealing
Isolator / Insulator
Typprüfung nach IEC 60840 / Type Test Data according to IEC 60840
Teilentladungsprüfung / Partial discharge test <5pC 131 kV
Lastwechselspannung / Heating cycle voltage test 174 kV
Blitzstossspannungsprüfung / Lightning impulse voltage test (BIL) 750 kV
Produktion Stückprüfung am Silikonsteuerteil / Factory Routine Test on silicone stress cone
Wechselspannungsprüfung 30 min. / Power frequency voltage test 30 min. 218 kV
Teilentladungsprüfung bei Umgebungstemperatur / Partial discharge test at ambient temperature( <5pC) 131 kV
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.1.3 Terminations
Conventional/Plug-in/Fluid Filled/Dry
Type Fluid Filled.
4.2.1 Ratings
a. Insulation or Voltage Class,
(69,110, 115, 132, 230 or 380 kV) 132 132
For 69 kV 44
For 110 kV 71
For 115 kV 73
For 132 kV 84 84
For 230 kV 146
For 380 kV 241
REFERENCE
SECTION
DESCRIPTION 'A' 'B' 'C'
NO.
For 69 kV *
For 110 kV *
For 115 kV *
For 132 kV * 750
For 230 kV *
For 380 kV *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
n. Termination Class 1 1
Leakage Distance in mm
for 40/50mm/kV
Outdoor
For 69 kV 2760/3450 N/A
For 110 kV 4400/5500
For 115 kV 4600/5750
For 132 kV 5280/6600
For 230 kV 9200/11500
For 380 kV 15200/19000
REFERENCE
SECTION
DESCRIPTION 'A' 'B' 'C'
NO.
Indoor
For 69kV 1725 N/A
"
# $
" "
%! % % $
" %! % %
$