Flatpack2 48V HE Rectifiers: The Original HE Rectifier
Flatpack2 48V HE Rectifiers: The Original HE Rectifier
Flatpack2 48V HE Rectifiers: The Original HE Rectifier
FIBER OPTICS
MICROWAVE
CABLE
BROADBAND
BROADCAST
DATACENTERS
POWER UTILITIES
SCADA
Flatpack2 Power core in T3 Outdoor cabinet 108kW System
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2018 – www.eltek.com
Flatpack2 48V HE Rectifiers
Doc 24111x.105.DS3 – v4
INPUT DATA
Voltage (nominal) 185 - 275 V AC / 185 - 275 VDC 176 - 277 VAC
Voltage (range) 85 - 300 VAC / 85 - 275 VDC 85 - 305 VAC
1)
Frequency 45 - 66 Hz, 15-18.5 Hz / 0 Hz 45 - 66 Hz
Current (maximum) @ nominal input, full load 11.6 ARMS 19.2 ARMS
Fuse in both lines Fuse in both lines
Protection Varistor for transient protection Varistor for transient protection
Disconnect above 300 V AC/DC Disconnect above 305 V AC
OUTPUT DATA
Voltage (default) 53.5 VDC
Voltage (adjustable range) 43.5 - 57.6 VDC
Power (maximum) 2000 W 3000 W
Power @ 85 V AC 850 W 1380 W
Current (maximum) @ nominal input, full load 41.7 A 62.5 A
Ripple, 30MHz bandwidth < 100 mVpp < 150 mVpp
Psophometric noise < 2 mVRMS < 2 mVRMS
Static Voltage regulation ±0.5% for 10 - 100% load
Dynamic Voltage regulation ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Protection Fuse, Short circuit proof, High temperature protection, Hot plug-in inrush current limiting
OTHER SPECIFICATIONS
Efficiency @ nominal input 96 %
Isolation 3.0 kV AC - input to output, 1.5 kVAC - input to earth, 500 VDC - output to earth
Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown
Alarms: Red LED 'on'
on output, Fan failure, Low voltage alarm, CAN bus failure
Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range,
Warnings: Yellow LED 'on'
flashing at overvoltage
Normal (module running): Green LED 'on'
Acoustic noise, full load @ Tambient = 25°C < 20 dBA < 40 dBA
full load @ Tambient = 40°C < 56 dBA < 58 dBA
MTBF (Telcordia SR-332 Issue I method III (a)) >350 000 (@ Tambient : 25 °C) >300 000 (@ Tambient : 25 °C)
Operating temperature -40 to +75°C (-40 to +167°F), humidity 5 - 95% RH non-condensing
Temperature de-rating above 45°C (110°F) 2000W to 1200W @ 75°C (167°F) 3000W to 2100W @ 75°C (167°F)
Storage temperature -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight 109 x 41.5 x 327mm (4.25 x 1.69 x 13”) / 1.95 kg (4.3 lbs)
DESIGN STANDARDS
EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, UL 60950-1:2014,
Electrical safety
CSA C22.2 No.60950-1-07:2014
EN 61000-6-1:2007, -6-2:2005, - 6-3:2007 + A1:2011, - 6-4:2007 + A1:2011, EN 61000-3-2
EMC
ETSI EN 300 386 V.2.1.1, Telcordia NEBS GR1089 CORE
Marine DNVGL-CG-03392) -
ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3)
2011/65/EU (RoHS) & 2012/19/EU (WEEE)
Environment
Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as
per IEC 62040-5-3:2016 clause 4.3, must be advised
1) power de-rating, maximum 1000W @ 230Vac 16 2/3 Hz
2) only valid for part number 241115.105M
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2018 – www.eltek.com