HONEYWELL

DC 1010 / 1020
1030 / 1040

DIGITAL CONTROLLER
PRODUCT MANUAL

51-52-25-113
06/02
Before using this manual, please check to ensure the Model number, input type
Range and output match your requirements.

1. Front Panel Overview


1.1 Display
PV :Process Value, 4-digit display (Color Red)
SP :Set Point, 4-digit display (Color Green)
1.2 LED Indicators
OUT1 :Output 1, color green
OUT2 :Output 2, color green
AT :Auto-Tuning, color yellow
PRO :Program, color yellow
AL1 :Alarm 1, color red
AL2 :Alarm 2, color red
MAN :Manual, color yellow
1.3 Keys
SET :MODE & SET key
:SHIFT key
:DOWN key
:UP key
A/M :Auto/Manual key

2. Auto Tuning
2.1 When AT is set to ‘YES’, auto tuning can be initiated.
2.2 After completion of auto tuning, the PID parameter are automatically
Entered into memory.
2.3 ATVL = auto tuning offset, the off set value when entered will be calculated
and subtracted from the SP.
(It prevents over-shooting during auto tuning)
SP-ATVL = Auto-tuning value, ATVL = Auto tuning offset
Ex.) SP = 200°C, ATVL = 5, Auto tuning point is at 195°C
* ATVL means auto-tuning point (195°C) in the above example.
2.4 Auto tuning failure
2.4.1 ATVL is too large.
à If unsure, set ATVL = 0)
2.4.2 Process lag is to long for Auto Tune to function correctly.
à Set PID parameter manually.

2
DC1010/1020/1030/1040 PRODUCT MANUAL
3. Error Information

Open circuit sensor input 1


* A/D converter failed
* Cold junction compensation failed
Open circuit of sensor input 2
PV exceeds USPL
PV under LSPL
Input 2 signal has exceeded the upper limit
Input 2 signal has exceeded the lower limit
* RAM failed
Interface failed
Auto tuning failed
Note) Error * code indicates critical failure unit must be replaced.

3
DC1010/1020/1030/1040 PRODUCT MANUAL
4. Operating Flow
4.1 Level 1

Display PV PV
Display SP SP
SET

Output

Percentage Press SET key


for 5 sec
SET

Auto Tuning

Status

SET

Alarm 1 Set

SET

Alarm 2 Set

SET

Alarm 3 Set

4.1.1 Press the SHIFT key ( ) to change the parameters, when the SHIFT key
is pressed, the first digit will start to blink. Press UP key ( ) or DOWN
key ( ) to increase or decrease the value of the digit, then press SHIFT
key again to go to the next digit, repeat the above procedure until the
required has been selected. Press the SET key to enter the desired value.
4.1.2 The SET key also has the function of changing MODEs. If SET key is
pressed, the display shows the next MODE.
4.1.3 Press SET key for 5 sec. The display goes to level 2, press the SET key
again to return to level 1.
4.1.4 If any key is not pressed for 1 minute the display will return to level 1.
4.1.5 If the A/M key is pressed the controller will switch to level 1.
4.1.6 If the output percentage is “0”, the controller output is off.

4
DC1010/1020/1030/1040 PRODUCT MANUAL
4.2 Level 2

Main Control Range: 0~200%


Proportional Band ON/OFF at P=0
SET
Main Control Range: 0~3600 sec
Integral Time Integral off at I=0
SET
Main Control Range: 0~900 sec
Derivative Time Derivative off at D=0
SET
Main Control Dead Time Compensation
Dead-band Time Range: 0~1000 sec
SET
Main Control Range: 0~USPL
Auto Tuning off-set
SET
Main Control Output (SSR à 1, 4~20mAà0, relayàover 10)
Proportional Cycle Range: 0~150 sec * Refer to 8.10 Cycle Time
SET
Main Control For ON/OFF control only
Hysterisis Range: 0~1000
SET
Sub Control Same as P1
Proportional band
SET
Sub Control Same as I1
Integral Time
SET
Sub Control Same as D1
Derivative Time
SET
Sub Control Same as CYT1
Proportional Cycle
SET
Sub Control Same as HYS1
Hysterisis
SET
Main Control For output 2 use only, set the value turning
Gap (Output 1) “OFF” early to SP
SET
Sub Control For output 2 use only, set the value turning
Gap (Output 2) “ON” early to SP
SET
Function Lock

SET LCK=0100, To enter Level 1 & 2 and to change their parameters allowed.

LCK=0110, To enter Level 1 & 2 and to change the parameters on Level 1 allowed.

LCK=0001, To enter Level 1 only and to change SP allowed.


Return to
LCK=0101, Nothing allowed except to change LCK.
‘P1’

5
DC1010/1020/1030/1040 PRODUCT MANUAL
4.3 Level 3
When LCK=0000, press the SET key and SHIFT key for 5 seconds to enter level 3.

Main Control Select the input range.


Input Selection Refer to 5.1 Input selection on P.13~P.14
SET
Main Control Used as input code which are AN1 to AN5
Analog Zero set Range: LSPL~USPL
SET
Main Control Same as ANL1
Analog Span set
SET
Decimal point To set the position of decimal point

SET
Lower Set-point limit To set the lowest point within INP1

SET
Upper Set-point limit To set the highest point within INP1

SET
Sub Control Used as input code which are AN1 to AN5
Analog Zero set Range: LSPL~USPL
SET
Sub Control Same as ANL2
Analog Span set
SET
Alarm mode of AL1 Range: 00~19
Refer to ‘6.1 Alarm Function Selection’ on P.15
SET
Time set of Alarm 1 Used in program function (Range: 0~99.59 min.)
0=switching, 99.59=continuous, others = on delay time
SET
Alarm mode of AL2 Range: 00~19

SET
Time set of Alarm 2 Same as ALT 1

SET
Alarm mode of AL3 Range: 00~19

SET
Time set of Alarm 3 Same as ALT 1

SET
Hysterisis of Alarm Range: 0~1000

SET

6
DC1010/1020/1030/1040 PRODUCT MANUAL
Main Control To calibrate the low value of output
Calibration Range: LSPL~USPL (Current output only)
SET
Main Control To calibrate the high value of output
Calibration high Range: 0~9999 (Current output only)
SET
Sub control Same as CL01
Calibration low
SET
Sub Control Same as CH01
Calibration high
SET
Transmitter control Same as CL01
Calibration low
SET
Transmitter control Same as CH01
Calibration high
SET
Timer for Full run time of proportional motor (without potentiometer)
Motor valve control Range: 5~200 sec
SET
To use in program for 0=No wait
waiting continued operation Others = Wait time
SET
Relay Contact & 0= “a” contact, 1= “b” contact
Program RUN & End ALM SET A.4=0 RUN alarm, SET A.4=1 END alarm
SET
ID number Communication ID number
(please skip this step)
SET
Baud rate UART band rate selection
(please skip this step) Range: 110~9600 BIT/sec
SET
Compensate SP Range: -1000~1000

SET
Compensate PV Range: LSPL~USPL

SET
Unit of PV & SP Range: C, F, A (analog)

SET
Soft filter Adjust the response time of PV (the bigger, the faster)
(please skip this step) Range: 0.05~1.00
SET

7
DC1010/1020/1030/1040 PRODUCT MANUAL
Please skip this step

SET
Action mode Alternative: heat, cool

SET
Control action Alternative: PID, Fuzzy

SET
Frequency Alternative: 50, 60Hz
* Check if the frequency is right. If not, change it, please.

SET
Return to ‘INP1’

4.4 Level 4 (LOCK FUNCTION)


4.4.1 Functions of LCK
LCK=0100, To enter Level 1 & 2 and to change their parameters allowed.
LCK=0110, To enter Level 1 & 2 and to change the parameters on Level 1 allowed.
LCK=0001, To enter Level 1 only and to change SP allowed.
LCK=0000, To enter Level 3 allowed then press SET + SHIFT key ( )
LCK=1111, To enter Level 4 allowed then press SET + SHIFT key ( )
LCK=0101, Nothing allowed except to change LCK.

4.4.2 Let the display go to “LCK” in level 2, and set “1111” in LCK, then press
SET key and SHIFT key ( ) for 5 seconds to enter “SET” status. There
are SET0.1 to SET9.4 for use.

PV SET No. (SET 0 . ∗)

SP

Status of SET ∗.1


Status definition
Status of SET ∗.2
0= lock (skip)
Status of SET ∗.3
1= open (display)
Status of SET ∗.4

8
DC1010/1020/1030/1040 PRODUCT MANUAL
4.4.3 Functions of SETs

SET Function SET Function


1.1 OUTL 5.1 CL02, CH02
1.2 AT 5.2 CL03, CH03
1.3 AL1 5.3 Rucy, WAIT, HYSM
1.4 AL2 5.4 IDNO, BAUD
2.1 AL3 6.1 SVOS
2.2 ANL1, ANH1, DP 6.2 PVOS
2.3 LSPL, USPL 6.3 UNIT
2.4 ANL2, ANH2 6.4 SOFT
3.1 ALD1 7.1 CASC
3.2 ALT1 7.2 OUD
3.3 ALD2 7.3 OPAD
3.4 ALT2 7.4 Hz
4.1 ALD3
4.2 ALT3
4.3 HYSA
4.4 CL01, CH01

SET Function Remarks


0= No Repeat
8.1
1= Program Repeat
0= No Power Failure
8.2 Program Use
1= With Power Failure
0= Start from 0
8.3
1= Start from PV
9.3 TRS SP
Auxiliary Output Use
9.4 TRS PV
0= No Remote SP
0.3
1= Remote SP

* Caution: Please don’t operate SET8.4, otherwise the process of the controller will
be in confusion.

9
DC1010/1020/1030/1040 PRODUCT MANUAL
4.5 Program Level

Level 1

SET

Set program pattern Set point for Seg.5


Range: 0~2
SET SET
Program segment display Set time for Seg.5
Range: (1-0)~(2-8)

SET SET
Program timer display Set output for Seg.5
Range: 99hour 59min
SET SET
Set point for Seg.1 Set point for Seg.6
Range: LSPL~USPL
SET SET
Set time for Seg.1 Set time for Seg.6
Range: 0~99H59M
SET SET
Set output for Seg.1 Set output for Seg.6

Range: 0~100% (if out=0, no program)


SET SET
Set point for Seg.2 Set point for Seg.7

SET SET
Set time for Seg.2 Set time for Seg.7

SET SET
Set output for Seg.7
Set output for Seg.2

SET SET
Set point for Seg.8
Set point for Seg.3

SET SET
Set time for Seg.8
Set time for Seg.3

SET SET
Set output for Seg.8
Set output for Seg.3

SET SET

Set point for Seg.4 Return to Normal(PV,SP)


SET

Set time for Seg.4

SET

Set output for Seg.4

SET

10
DC1010/1020/1030/1040 PRODUCT MANUAL
4.5.1 This program has 2 patterns, each pattern contains 8 segments. The
segment can be arranged a period of RAMP status or SOAK status.
4.5.2 Terminologies
Pattern : A program consists of some segments
Step : A RAMP status + a SOAK status
RAMP status : The status with changing SP
SOAK status : The status with fixed SP
4.5.3 Operating
1) Key functions (No changing parameters)
(START) : To start program procedure, PRO in panel flicker
(WAIT) : To suspend program procedure, PRO in panel will
stop flicker but light
+SET (JUMP) : To jump segment
+SET (RESET) : To reset program procedure, PRO in panel will be
“off”
2) Alarm function
If ALD1 to be set 07 (*refer to the selection),
AL1 to be set 2 (AL1=2, it means alarm in segment 2 end),
ALT1 to be set 00.10 (alarm time 10 sec.).
*In this case, when program proceeds to segment 2 end, ALM1 relay
will be on 10 sec.
3) End function
If ALD to be set 17 (* refer to the selection), this program will be end
in segment 8 or 16.
* In this case, PV and END will flicker in display window, and the
alarm relay acts.
This controller does not have END order if program procedure are less
than 8 segments. In this case, please set next segment’s out=0, then
this program will be end in last set segment. Otherwise, it will
proceed 8 or 16 segments.
4) Linking function
PTN=1, Proceed pattern1, which contains 8 segments
PTN=2, Proceed pattern2, which contains 8 segments
PTN=0, linking proceed pattern 1 and 2 ,totally 16 segments
(Set PTN1 and PTN2 first, then set PTN=0)

11
DC1010/1020/1030/1040 PRODUCT MANUAL
5) Other function (*refer to level 4)
SET8.1=1 Program repeat
SET8.2=0 No power failure
SET8.2=1 With power failure function
(If power suspended, the controller will keep the memory)
SET8.3=0 Program start from 0
SET8.3=1 Program start from PV

12
DC1010/1020/1030/1040 PRODUCT MANUAL
5. Input
5.1 Input selection (INP 1)

TYPE CODE RANGE HEX


0.0~200.0°C/0.0~392.0°F 01H
0.0~400.0°C/0.0~752.0°F 02H
0.0~600.0°C/0.0~1112.0°F 03H
K
0.0~800.0°C/0.0~1472.0°F 04H
0.0~1000.0°C/0.0~1832.0°F 05H
0.0~1200.0°C/0.0~2192.0°F 06H
0.0~200.0°C/0.0~392.0°F 07H
0.0~400.0°C/0.0~752.0°F 08H
0.0~600.0°C/0.0~1112.0°F 09H
J
0.0~800.0°C/0.0~1472.0°F 0AH
0.0~1000.0°C/0.0~1832.0°F 0BH
0.0~1200.0°C/0.0~2192.0°F 0CH
0.0~1600.0°C/0.0~2912.0°F 0DH
R
0.0~1769.0°C/0.0~3216.0°F 0EH
0.0~1600.0°C/0.0~2912.0°F 0FH
S
0.0~1769.0°C/0.0~3216.0°F 10H
B 0.0~1820.0°C/0.0~3308.0°F 11H
0.0~800.0°C/0.0~1472.0°F 12H
E
0.0~1000.0°C/0.0~1832.0°F 13H
0.0~1200.0°C/0.0~2192.0°F 14H
N
0.0~1300.0°C/0.0~2372.0°F 15H
-199.9~400.0°C/-199.9~752.0°F 16H
T -199.9~200.0°C/-199.9~392.0°F 17H
0.0~350.0°C/0.0~662.0°F 18H
0.0~2000.0°C/0.0~3632.0°F 19H
W
0.0~2320.0°C/0.0~2372.0°F 1AH
0.0~1300.0°C/0.0~2372.0°F 1BH
PLII
0.0~1390.0°C/0.0~2534.0°F 1CH
-199.9~600.0°C/-199.9~999.9°F 1DH
U -199.9~200.0°C/-199.9~392.0°F 1EH
0.0~400.0°C/0.0~752.0°F 1FH
L 0.0~400.0°C/0.0~752.0°F 20H
0.0~800.0°C/0.0~1472.0°F 21H
* The initial set in factory mode is K2 without any certain requirement.

13
DC1010/1020/1030/1040 PRODUCT MANUAL
TYPE CODE RANGE HEX
-199.9~600.0°C/-199.9~999.9°F 22H
-199.9~400.0°C/-199.9~752.0°F 23H
JIS -199.9~200.0°C/-199.9~392.0°F 24H
Pt100 0.0~200.0°C/0.0~392.0°F 25H
0.0~400.0°C/0.0~752.0°F 26H
0.0~600.0°C/0.0~1112.0°F 27H
-199.9~600.0°C/-199.9~999.9°F 28H
-199.9~400.0°C/-199.9~752.0°F 29H
DIN -199.9~200.0°C/-199.9~392.0°F 2AH
Pt100 0.0~200.0°C/0.0~392.0°F 2BH
0.0~400.0°C/0.0~752.0°F 2CH
0.0~600.0°C/0.0~1112.0°F 2DH
-199.9~600.0°C/-199.9~999.9°F 2EH
-199.9~400.0°C/-199.9~752.0°F 2FH
JIS -199.9~200.0°C/-199.9~392.0°F 30H
Pt50 0.0~200.0°C/0.0~392.0°F 31H
0.0~400.0°C/0.0~752.0°F 32H
0.0~600.0°C/0.0~1112.0°F 33H
AN1 -10~10mV/-1999~9999 34H
AN2 0~10mV/-1999~9999 35H
AN3 0~20mV/-1999~9999 36H
AN4 0~50mV/-1999~9999 37H
AN5 10~50mV/-1999~9999 38H

14
DC1010/1020/1030/1040 PRODUCT MANUAL
6. Alarm
6.1 Alarm function selection
CODE DESCRIPTION Hold-On
/ None
Deviation high limit alarm Yes
Deviation high limit alarm No
Deviation low limit alarm Yes
Deviation low limit alarm No
Deviation high/low alarm Yes
Deviation high/low alarm No
/ Deviation high/low range alarm No
Absolute value high limit alarm Yes
Absolute value high limit alarm No
Absolute value low limit alarm No
Absolute value low limit alarm Yes
Segment end alarm (use for program only) -
Program run alarm (use for program only) -
System error alarm-on -
System error alarm-off -
On delay timer alarm -
* Note : “Hold-On” means the alarm does not work at the first time.

15
DC1010/1020/1030/1040 PRODUCT MANUAL
6.2 Alarm action description
6.1.1 CODE 00/10 : None
6.1.2 CODE 01 : Deviation high alarm inhibit

: SP
: Alarm set value

6.2.3 CODE 11 : Deviation high alarm no inhibit

6.2.4 CODE02 : Deviation low alarm inhibit

6.2.5 CODE12 : Deviation low alarm no inhibit

6.2.6 CODE03 : High/low alarm inhibit

6.2.7 CODE13 : High/low alarm no inhibit

6.2.8 CODE04/14 : Band alarm

6.2.9 CODE05 : Absolute high alarm inhibit

16
DC1010/1020/1030/1040 PRODUCT MANUAL
6.2.10 CODE15 : Absolute high alarm no inhibit

6.2.11 CODE06 : Absolute low alarm inhibit

6.2.12 CODE16 : Absolute low alarm no inhibit

6.2.13 CODE07 : Segment end alarm (program only)


i) ALD 1~3, set 07
ii) AL1~3, alarm segment no. set
iii) ALT1~3, if set 0 = flicker alarm
set 99.59 = alarm continued
set others = on delay time

6.2.14 CODE17 : Program run alarm (program only)

Program End

6.2.15 CODE08 : System Error- ON

17
DC1010/1020/1030/1040 PRODUCT MANUAL
6.2.16 CODE18 : System Error-OFF

6.2.17 CODE19 : on delay timer


when PV=alarm SP, it keeps a certain period (set time)
before alarm action (Range: 00H00M~99H59M)

18
DC1010/1020/1030/1040 PRODUCT MANUAL
7. Modification of HEAT/ALARM àHEAT/COOL (on PC board)
7.1 DC1010

7.2 DC1030

7.3 DC1020/1040

19
DC1010/1020/1030/1040 PRODUCT MANUAL
8. Special Function Description

8.1 Level set

SET 1

SET 0

INP2 * Input 2 mode setting as below

OUTY * Output mode setting as below

8.1.1 Second input mode


INP 2 = 0, Non
INP 2 = 1, 1~5V/4~20mA/2~10V
INP 2 = 2, 0~5V/0~20mA/0~10V
8.1.2 Output mode
OUTY = 0, Single output
OUTY = 1, Double output
OUTY = 2, Non
OUTY = 3, Motor Postion Control
OUTY = 4, Single phase SCR (Single phase control)
OUTY = 5, Three phase SCR (Three phase control)

20
DC1010/1020/1030/1040 PRODUCT MANUAL
8.2 Ramp & Soak
8.2.1 RAMP
i) Set “SET2.1= 1”, “SET4.1= 1” at Set level
ii) Set “ALD 3 = 9” at Input level
iii) Then, “AL 3” menu will not be displayed

PV Range = 00.00~99.99 (°C/minute)


If RAMP not used, set ALD 3 = 0
SP

8.2.2 SOAK
i) ALD1/ALD2 = 19
ii) Then, AL1/AL2 will be displayed

PV Range = 00.00~99.59 (hour/minute)

SP

Example)
SP = 100°C, RAMP = 10.00 °C/minute
Time(minute) = 10 minute à AL1 = 00.10
PV = 25°C

°C Time on
If PV SV(100° C)

100°° C

PV=25°° C
t

21
DC1010/1020/1030/1040 PRODUCT MANUAL
8.3 Remote SP
8.3.1 Hardware must be mounted
8.3.2 Set ‘INP2’ to 1or 2 (ANL2, ANH2 used for Cal.)
8.3.3 SET 0.3 = 1 means Remote SP from Input 2 channel
(*SET 0.3 = 0 means Local SP)
8.4 Alarm Timer ALT1/ALT2/ALT3 description
8.4.1 ALT 1 = 0 means Switching if AL 1 is ON
8.4.2 ALT 1 = 99.59 means ‘continuous alarm’ if AL 1 is ON
8.4.3 ALT 1 = 00.01~99.58 means AL 1 is on delay timer

8.5 Function SET A

PV

SP

If SET A.1 = 1 set, AL1 relay reversed


DC1010 is not available
If SET A.2 = 1 set, AL2 relay reversed ‘a’ contact only
If SET A.3 = 1 set, AL3 relay reversed
If SET A.4 = 0 set, program run alarm
Program model only
If SET A.4 = 1 set, program end alarm

8.6 Function SET 8


8.6.1 SET 8.1 = 0 Non
SET 8.1 = 1 Program Repeat
8.6.2 SET 8.2 = 0 Non (program model only)
SET 8.2 = 1 Power failure access
8.6.3 SET 8.3 = 0 Zero start (program model only)
SET 8.3 = 1 PV start
8.6.4 SET 8.4 = 0 Non
SET 8.4 = 1 Display will be transferred to single display.
(Don’t change this digit)
* SET 8 = 0000 can make return to double display

22
DC1010/1020/1030/1040 PRODUCT MANUAL
8.7 Function SET 9
8.7.1 SET 9.1 = 0 Non
SET 9.1 = 1 PV/SP switching
* This is for the single display set (refer to SET 8.4)
8.7.2 SET 9.2 = 0 Non
SET 9.2 = 1 Non Program model : No display RAMP
Program mod el : Timer change from H.M to M.S
8.7.3 SET 9.3 = 0 Non
SET 9.3 = 1 Transmission SP
8.7.4 SET 9.4 = 0 Non
SET 9.4 = 1 Transmission PV

8.8 Function SET 0


8.8.1 SET 0.1 = 0 Non
SET 0.1 = 1 Non (function not available for DC1010/1020/1030/1040)
8.8.2 SET 0.2 = 0 Non
SET 0.2 = 1 Rate for AL3 (ALD 3 = 0)
8.8.3 SET 0.3 = 0 Non
SET 0.3 = 1 Remote SP
8.8.4 SET 0.4 = 0 Motor valve close = “b” out (contact normally close)
SET 0.4 = 1 Motor valve close = “a” out (contact normally open)

8.9 Input level wait


Wait = 0 means “no wait”. When used as a programmer, i the
Wait = 0 means “wait”

8.10 Cycle Time


Range: 0~150 sec
CYT1= 0 (i) mA
(ii) Phase control(SCR)
CYT1= 1 (i) SSR
(ii) Phase zero control(SCR)
CYT1= over 10 Relay output.

23
DC1010/1020/1030/1040 PRODUCT MANUAL
Application 1. Single Phase Control, Phase angle control
-. Avalable models: DC1030/1040, DC1030P/1040P
-. Data Change: OUTY = 4
CYT = 0
CL01 = 0, CH01 = 5000 if used for resistance load
CL01 = 0, CH01 = 4000 if used for inductor load

S R

FAST
FUSE CONTROLLER

K2
G1
G2
SCR
Module K1

G1
G2
K1

K2

Short

PROT

U V

** Controller source phase must be same as load source phase

24
DC1010/1020/1030/1040 PRODUCT MANUAL
Application 2. Three Phase Control , Phase angle control
-. Available Models: DC1040/DC1040P
-. Data Change : OUTY = 5
CYT = 0
CL01 = 0, CH01 = 5000 only if used for resistance load

R S T
CONTROLLER

FAST G1
FUSE
K2
K1 K2 K3 DIODE/SCR
G1 G2 G3 Module G2

K2

G3

K3

U V W

PROT
Short

3φ LOAD

25
DC1010/1020/1030/1040 PRODUCT MANUAL
Application 3. Single Phase Zero crossover Control
-. Available Models: DC1030/1040
DC1030P/1040P
-. Data Change: OUTY = 0
CYT1 = 1

R S

FAST
FUSE CONTROLLER

G1
G1
SCR
Module

G2
G2

Short

PROT

U V

TIME CHART:

OFF
ON

CYCLE TIME = 200 mSEC.

26
DC1010/1020/1030/1040 PRODUCT MANUAL
Application 4. Three Phase Zero crossover Control
-. Available Models: DC1040/1040P
-. Data Change: OUTY = 0
CYT1 = 1

R S T CONTROLLER

FAST RG 1
FUSE

SCR RG 2
Module
RG 1 TG 1
TG 1
RG 2 TG 2

TG 2

U V W
WE CAN SUPPLY
HEATER SINK

PROT
Short

TIME CHART:

OFF
ON

CYCLE TIME = 200 mSEC.

27
DC1010/1020/1030/1040 PRODUCT MANUAL
Application 5. Motor Valve Control
-. Available Models: DC1020/1030/1040
DC1020P/1030P/1040P
-. Data Change: OUTY = 3
CYT1 = 1~100 sec. (Normally, set 5 sec.)
RUCY = 5~200 sec.
* 1. CYT1 is the cycle time of Open/Close
2. RUCY is the running time of motor valve 0~100%

MOTOR VALVE

COM
R CONTROLLER

CLOSE OUT2
Relay
CLOSE

OPEN

OPEN
COM OUT1
Relay

28
DC1010/1020/1030/1040 PRODUCT MANUAL
Application 6. Single Phase Control ( for TRIAC module)
-. Available Models: DC1030/1040
DC1030P/1040P
-. Data Change: OUTY = 4
CLO1=0 CHO1=5000 if use for resistance load
CLO1=0 CHO1=4000 if use for inductor load

S R

FAST
FUSE CONTROLLER

G1
T2
TRIAC
Module K1

G1
G2
T1

K2

Short

PROT

U V

** Controller source phase must be same as load source phase

U V
1/2W
100£[ 0.1uf/630V

AC

29
DC1010/1020/1030/1040 PRODUCT MANUAL