05.02-05 - Installation Guide For HVDC 380V

This document provides installation instructions for a 380V HVDC power system from Eltek. It describes the key components, including: 1. The Central Office unit which transforms -48VDC to 380VDC and is mounted in the rectifier cabinet or a 19" rack. 2. The Remote Unit which is installed outdoors near radio units and transforms 380VDC back to -48VDC. Up to 6 radio units can connect to each Remote Unit. 3. Details on connecting the Central Office to the -48V rectifiers and distributing the 380VDC output. Instructions are also provided for installing and connecting the Remote Unit. The guide is intended to ensure proper installation of the HVDC

Uploaded by

Alexe Victor
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
245 views13 pages

05.02-05 - Installation Guide For HVDC 380V

This document provides installation instructions for a 380V HVDC power system from Eltek. It describes the key components, including: 1. The Central Office unit which transforms -48VDC to 380VDC and is mounted in the rectifier cabinet or a 19" rack. 2. The Remote Unit which is installed outdoors near radio units and transforms 380VDC back to -48VDC. Up to 6 radio units can connect to each Remote Unit. 3. Details on connecting the Central Office to the -48V rectifiers and distributing the 380VDC output. Instructions are also provided for installing and connecting the Remote Unit. The guide is intended to ensure proper installation of the HVDC

Uploaded by

Alexe Victor
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

Security Page No

INSTALLATION GUIDE FOR HVDC 380V Internal 1 (13)

Created Responsible for document


Martin Gyllenhammar Solveig Aanby Aas
Date Ver Belonging object
2020-03-30 1.0 Telia - Technical Spec
No.

05.02-05

Installation guide for HVDC 380V

Contents
INTRODUCTION ....................................................................................................................................... 2
SCOPE...................................................................................................................................................... 2
PURPOSE .................................................................................................................................................. 2
RELATED DOCUMENTATION .......................................................................................................................... 2
SYSTEM DESCRIPTION ............................................................................................................................. 2
CENTRAL OFFICE (CO) DC -48V/-380V ...................................................................................................... 3
REMOTE UNIT (RU) DC -380V/-48V .......................................................................................................... 5
TECHNICAL DATA AND DESIGN ................................................................................................................ 6
INSTALLATION OF CENTRAL OFFICE (CO) DC -48V / -380V ....................................................................... 7
INSTALLATION OF REMOTE UNIT (RU) DC -380V / -48V ........................................................................... 8
COMMISSIONING THE SYSTEM .............................................................................................................. 11
LABELING............................................................................................................................................... 11
ALARMS................................................................................................................................................. 11
CIRCUIT DIAGRAM 380HVDC ................................................................................................................. 13

Revision history
Rev. Appr. Appr.
Rev: Purpose revision: Rev. date:
sign: Sign. Date.
1.0 New document KK 2020-03-30
Security Page No
INSTALLATION GUIDE FOR HVDC 380V Internal 2 (13)

Created Responsible for document


Martin Gyllenhammar Solveig Aanby Aas
Date Ver Belonging object
2020-03-30 1.0 Telia - Technical Spec
No.

05.02-05
Introduction
Scope
The scope of this document is to make sure that the installation for 380V HVDC is in accordance
with Telia Norways (Telia) Thecnical Spec

Purpose
This document presents a guide on how to install the 380V HVDC system.
These instructions are intended for technicians and installers working for Telia. This guide is
written chronologically and is intended to be followed in its entirety.

Note: You should always follow Eltek's instructions, but this guide will give some extra Telia
specific specifications.

Related documentation
• 01.01-01 - Working environment and HSE
• 05.01-01 - Requirements – Electrical
• 05.01-01 - Requirements – Earthing
• 05.03 - Eltek Central Office – 341093
• 05.04 - Eltek Remote Unit - Indoor – 340231
• 05.05 - Eltek Remote Unit Outdoor - 340230

System Description
The HVDC system in from Eltek delivers 380VDC from the site room to the RRUs when there are
long distances between the site room and the RRUs.
-48VDC is supplied by the site's rectifiers to the Central office. The central office transforms the -
48VDC to 380VDC. You can reuse existing cables or add new ones. Outside where the RRUs sits you
need to install a Remote Unit (RU) that transforms from 380VDC back to -48VDC. Up to 6 RRUs can
be installed per RU (Max load of RU is 3000W).
The distance between the rectifiers and RRU can be much longer with this system.
There are great advantages in being able to supply power to all radio equipment via a rectifier with a
battery bank and not split this up with several rectifiers and battery banks. This will simplify
calculations and installation of battery capacity on sites that have requirements for 2h and 4h backup
time.
Projects that choose this solution can use Telia's price calculator which compares the standard
solution with the HVDC solution
Security Page No
INSTALLATION GUIDE FOR HVDC 380V Internal 3 (13)

Created Responsible for document


Martin Gyllenhammar Solveig Aanby Aas
Date Ver Belonging object
2020-03-30 1.0 Telia - Technical Spec
No.

05.02-05

Central Office (CO) DC -48V/-380V


Central Office is a 19 "power core that is mounted either below -48V power core in rectifier cabinet
or in a standard 19" Rack. If its installed in a rack you need to use a shelf or sliding rails because of
weight.
It is connected to load fuse in -48V rectifiers. This must be secured with a 125A.
In the front there are 2 fuses, as well as 2 pieces SPD (Surge protection device) and here you insert the
modules.
Security Page No
INSTALLATION GUIDE FOR HVDC 380V Internal 4 (13)

Created Responsible for document


Martin Gyllenhammar Solveig Aanby Aas
Date Ver Belonging object
2020-03-30 1.0 Telia - Technical Spec
No.

05.02-05
There is space for 8 FP2 1350W DC / DC -48V / 280V modules which are fitted as shown in the table
3 in chapter 5.

On the back sits the connection for the -48VDC, grounding rail, terminal blocks that go to 380VDC
distribution which has a maximum cross-section of 10mm2. Here are also the terminal blocks for the
alarm outputs that go to the SPD alarm and module failure alarm.
Security Page No
INSTALLATION GUIDE FOR HVDC 380V Internal 5 (13)

Created Responsible for document


Martin Gyllenhammar Solveig Aanby Aas
Date Ver Belonging object
2020-03-30 1.0 Telia - Technical Spec
No.

05.02-05
Remote unit (RU) DC -380V/-48V

• Remote Unit comes with outdoor and indoor cabinet. They are exactly the same inside, but
the IP degree of the two is different.
• The outdoor enclosure is mounted near RRUs and can be mounted on a wall, pipe or gravity
mount.
• Indoors are used in technical rooms, equipment rooms or in dusty environments.
• Both cabinets have a thermostatically controlled cooling fan
• RU has a 2-part modem shelf where each section is secured with a 6A circuit breaker on the
380VDC side.
• Each section has 2 FPS DCDC 380V / 48V 750W modules and distribution for 6 pluggable
fuses. A maximum of 3 RRUs are connected to each section.
• Vacant positions 2 + 3 are should not be used for RRUs.
• SPD is mounted on the 380VDC side.
Security Page No
INSTALLATION GUIDE FOR HVDC 380V Internal 6 (13)

Created Responsible for document


Martin Gyllenhammar Solveig Aanby Aas
Date Ver Belonging object
2020-03-30 1.0 Telia - Technical Spec
No.

05.02-05
Technical data and design

Type HxBxD Weight Max number Art nr.


module
Central office 145x445x400 12 kg 8stk. FP2 341093
1350W
241115.615
Remote unit 630x450x350 17 kg 4stk. FPS 750W 340230
outdoor 241122.185DT
Remote unit 600x300x400 16 kg 4stk. FPS 750W 340231
indoor 241122.185DT

Table 1 - Technical data

DC 380V DC48V
Cable cross-section MAX. length DC48V m/OVP*
4mm^2 250 22 (600W-4mm^2)
6mm^2 380 N/A
10mm^2 630 N/A
*The lengths are calculated by Telenor and are based on Eltek's calculation model and are controlled by Telenor's own Electrical
Engineers.
Table 2 - Max cable lengths. (380VDC max 14.5V voltage drop allowed at 3000W load)

Number of DC units Number of modules


Number of Central Office Remote Units FPS 1350W
RRU pr. sector Pr.output
1-2 1 1 2 2
3-4 1 1 3 4
5-6 1 1 4 4
Number of
sectors
1 1 1*
2 1 2*
3 2 3*
4 2 4*
Table 3 - Module setup
Security Page No
INSTALLATION GUIDE FOR HVDC 380V Internal 7 (13)

Created Responsible for document


Martin Gyllenhammar Solveig Aanby Aas
Date Ver Belonging object
2020-03-30 1.0 Telia - Technical Spec
No.

05.02-05
New and existing Remote Units -48VDC output.
* -48VDC cables from RU can be max 22m. 6 pieces of RRUs placed in 2 or 3 sectors can be no more
than 22m from the Remote Unit if it is to be supplied from one remote Unit.
** Each Central Office has two sections for FP2 1350W modules, the top one supply’s output 1. and
the lower 380VDC output 2.
Note! FP2 1350W DCDC 241115.615 modules have a different connection at the rear than FP2 48 /
2000W 241115.105. This will ensure that these cannot be placed wrong. The 48V system and the
380VDC system should not be connected to the CAN-Bus cable. This will short circuit the system and
equipment may be damaged.

Installation of Central Office (CO) DC -48V / -380V

• When mounting the Central Office in Telia Standard 16kW rectifier cabinet, the unit is placed
just below -48VDC powercore. It comes with transition plates from 24 "to 19" which are
mounted from U28 downwards.
• Connect a -48VDC supply cable between the - and + on the back of the unit, to the rectifiers +
rail and -48V load fuse in the distribution. These are connected with cable shoes with 8mm
bolt holes at the Central Office. See the sizing table below. The cables must have sufficient
length to be inserted on the side of the Powercore, and allow the central office unit to be
pulled out while it is connected.
• The Central Office can be placed on a battery shelf or a transition plates that is screwed into
the rack. A battery shelf can be mounted under the central office, so it can be placed on top of
it. If you install 3 pcs of battery string in the cabinet, all shelves must be moved slightly
down, and you need to order a shelf for the central office as well. If there are less than three
battery strings, the last shelf is used for the central office. If a central office no. 2 is to be
mounted, the shelf under the first central office needs to be moved down to make space for
the second one under the first one.
• Central office is pulled forward and the -48VDC (one conductor) cables are inserted on the
side of Powercore with insulated cable ends. These are not connected until all other
connections are made in the Central Office.
• The 380VDC cables, alarm cables and grounding are routed down through the top of rectifiers
and down the side of Powercore.

Fuse 125A Length DC48V cable.


25mm2 < 2m
35mm2 >2m<8m
Table 4

Connection of 380 / 48VDC: Use the enclosed system wiring diagram SD - FP2 1U dist 2x10A MCB dcdc SPD (A - 2232110 -
1 - 4) - 1 to check that the connection is correct. – “05.03-03 - Schematic Drawing – 341093” in spec

+ and - in 380VDC cable is connected to terminal blocks X2.1 and X2.2, the screen in the cable is
connected to the ground rail next to the terminal Block.
Security Page No
INSTALLATION GUIDE FOR HVDC 380V Internal 8 (13)

Created Responsible for document


Martin Gyllenhammar Solveig Aanby Aas
Date Ver Belonging object
2020-03-30 1.0 Telia - Technical Spec
No.

05.02-05
The twist the screen and use Y/G stocking.
The PE connections on X2.1 and X2.2 must also be connected to the same ground rail.
Make sure that the two 1.5mm2 earth conductors to the right at the rear edge, where the connecting
end is, are pulled out when mounting. Ground rail is connected to system ground, directly from
ground plate or via C-pres from ring ground on cable bridge. 25mm2 G / G ground conductor is used.
All connections must be of sufficient length to allow Central office to be pulled out to make all
connections at the back of the device accessible.
The Central office is pushed in and attached to the transition plate.
-48V DC single conductor cables are then connected with nite at the end in + rail and - in -48VDC
125A load protection
The CO is pushed in and attached to the transition plate.

Installation of Remote Unit (RU) DC -380V / -48V


The Remote unit cabinet has a Unistrut rail which makes the mounting flexible and it can be mounted
on pipes, walls and posts. The Remote unit is mounted as close to the RRU as possible. You can use
several different brackets and clamps.
Ex. Kathrein's pipe mount, Griptel / AgderSveis A3 mount.
Remote Unit must have at least 70 cm from the bottom of the cabinet and down to the floor for
outdoor installation.

This cabinet should have Telia standard 051 key cylinder. Replace the key/sylinder that followes the
cabinet.
Security Page No
INSTALLATION GUIDE FOR HVDC 380V Internal 9 (13)

Created Responsible for document


Martin Gyllenhammar Solveig Aanby Aas
Date Ver Belonging object
2020-03-30 1.0 Telia - Technical Spec
No.

05.02-05

Pictures: Shows mounting of RU outdoor and RU indoor

RU has capacity for 2 + 2 FPS DCDC 750W modules (max. 3000W).


Each module section has a signal selector switch (S1 / S2) that must be set relative to the number of
modules installed in each section. The switch selects between 1M and 2M.

-48VDC connection in each section “feed A” and “feed B”.


Each section has 6 outputs/connections.
When connecting the RRU, courses 2, 3, 4 are used in “Feed A” and 7, 8, 9 on “Feed B”.
Course F1 is for cooling fan. The cooling fan thermostat is at the back of the cabinet and is set to 30
degrees.

Use the enclosed system wiring diagram SD FPS 48V 3kW 400VDC DCDC SPD (A - 2231279 - 1 - 4) - 1 to check that the installation
is correct. “05.05-03 - Schematic Drawing – 340230” in spec
Security Page No
INSTALLATION GUIDE FOR HVDC 380V Internal 10 (13)

Created Responsible for document


Martin Gyllenhammar Solveig Aanby Aas
Date Ver Belonging object
2020-03-30 1.0 Telia - Technical Spec
No.

05.02-05

380VDC connection + and - are connected to the terminal blocks under module position.
The cable shield connects to the ground rail at the bottom right. The PE terminal block at 380VDC +/-
, the connections are also grounded to ground rail with 10mm2 G / G ground conductor.

NB! For only 1 FPS 750W in one or both sections, they must be placed in the position furthest
from the signal selector switch.

Use the enclosed system wiring diagram SD FPS 48V 3kW 400VDC DCDC SPD (A - 2231279 - 1 - 4) - 1 to check that the installation
is correct. “05.05-03 - Schematic Drawing – 340230” in spec
Security Page No
INSTALLATION GUIDE FOR HVDC 380V Internal 11 (13)

Created Responsible for document


Martin Gyllenhammar Solveig Aanby Aas
Date Ver Belonging object
2020-03-30 1.0 Telia - Technical Spec
No.

05.02-05
Commissioning the system
Check that the system is in accordance with guidance and that all units are mounted securely. Once
you have done a physical review of all connections and mounting, you can start commissioning. The
system's accompanying documentation is used to verify that you have connected correctly.

1. Make sure that all FP2 1350W modules in the Central Office are fitted correctly to
the outputs and shelves used.
2. Ensure that all FPS 750W modules in the Remote unit are properly inserted and
inserted. (Remember to set section switches if there is 1M or 2M in each section)
3. Insert load switch on the -48V system.
4. Insert the fuses in CO on the connected outputs.
5. Do a control measurement of the voltage at Remote Unit.
6. If item 5 is OK then the course fuses for the RRUs can be entered and Kurd F1 for the
cooling fan. Do this one by one while making sure that the correct course is
connected to the correct RRU and that the light turns on in the RRU.
7. Check the voltage on the connection of the RRUs and make sure that the correct LED
lights on the RRU are lit.
8. Check that cylinder in RU is switched to Telia standard 051.
9. If point 5 is OK, then the course fuses for the RRUs can be entered and course F1 for
cooling fan. Do this one by one while making sure that the correct course is
connected to the correct RRU and that the light on the RRU turns on.

Labeling
Labelling is done according to Telia – Technical spec document “08.01-01 - Requirements –
Labelling”

Alarms
We use alarm input at RRU (Eriksson and Huawei) to RU. There are 2 alarm inputs at RRU and 2
alarm inputs at RU. The Remote Unit (RU) alarms are configured and defined in the database (OSS).
Alarm output is for SPD and module errors.
Alarm relays in RU are normally closed (NC) and give alarm at open (NO).
The alarms must be defined in the OSS as SPD and DC POWER FAULTY B ALARM 2

RU is alarm-free:
• When main fuse -48V for modem shelves F13 and F14 is in the ON (on) position.
• A minimum of 1 piece must be fitted. module in both sections lower position
RU is alarm-free:
Security Page No
INSTALLATION GUIDE FOR HVDC 380V Internal 12 (13)

Created Responsible for document


Martin Gyllenhammar Solveig Aanby Aas
Date Ver Belonging object
2020-03-30 1.0 Telia - Technical Spec
No.

05.02-05
• When main fuse -48V for modem shelves F13 and F14 is in the ON (on) position.
• A minimum of 1 module must be installed in both sections of the lower position.

Number of 1M/2M switch Pos.1M/2M


modules
Module shelve 1 1* S1 1M
Module shelve 1 2 S1 2M
Module shelve 2 1* S2 1M
Module shelve 2 2 S2 2M
* Must be mounted in the lower section, furthest from the signal selector.

RU gives alarm:
• When module lights red.
• When both main fuses 48V F13 and F14 are not in the ON position.
• When you have set the signal selector switch 1 and 2 to 2M when only one module is
installed.
• If you have one module and it is placed in the wrong position closest to the signal selector
switch.

Functional tests of these alarms are possible.


When assembled:
• Disconnect -48V main fuse F13 or F14.
• If only 1 piece is inserted. module then S1 or S2 is set to 2M.
In operating situation:
• If you only have one module in each of the sections, you can put the corresponding S1 or S2
to 2M under test.
• If all modules is inserted in RU, then disconnect one alarm cable from the terminal block
during the test.

The SPD in RU is tested by removing one of the modules.

Central office alarm functions are connected via Krone plinth. The SPD is connected in series with the
existing SPD on the crown terminal (2a and 2b).

Module fault clock is connected to crown block Termination 2 5a and 5b DC POWER FAULTY B
ALARM 2 in the database.

An overview of alarm connections can be found in Chapter 9 Alarms in Technical Spec “09.01-01 -
Drawing - External alarm connections”.

Price list is completed on site. It must be a separate course listing for CO and RU.
Security Page No
INSTALLATION GUIDE FOR HVDC 380V Internal 13 (13)

Created Responsible for document


Martin Gyllenhammar Solveig Aanby Aas
Date Ver Belonging object
2020-03-30 1.0 Telia - Technical Spec
No.

05.02-05
Circuit diagram 380HVDC
The courses to be used must be found in circuit diagram in technical spec “12.06-01 - Circuit diagram,
380V High Voltage DC”