Modicon Quantum Processors - Unity Operating Systems Compatibility Rules 0
Modicon Quantum Processors - Unity Operating Systems Compatibility Rules 0
Modicon Quantum Processors - Unity Operating Systems Compatibility Rules 0
Definitions
Copro = Coprocessor: embedded Ethernet port.
PV = Product Version: the PV increases by one digit when a functional change is made in an Operating System, in a Copro or in a
Hardware part.
SV = Software Version: the version of the Operating System (OS) delivered with the Processor module.
Attention
Do not download an OS version V2.31 or lower in the Minimum version required to update Quantum from Concept to
processors listed below. Otherwise, it will no longer be Unity:
possible to change the OS version: Quantum PV
Quantum PV
140CPU43412A >=04
140CPU65150 >= 15
140CPU53414A >=04
140CPU65150C >= 15
140CPU65160 >= 15 CPUs with PV < 04 include RAM Memory chip whose characteristics
140CPU65160C >= 15 are not totally adapted to the Unity program execution.
According to the used memory size, these CPUs can work in Unity
140CPU67160 >= 13 range but can also present defects in case of Online changes,
140CPU67160C >= 13 configuration changes or programs size increase.
140CPU67160C >= 13 The consequences that can have are:
- No start of the CPU
- Some modules are not working in the configuration.
1/6
EIO000000005603
Quantum HotStandby
A Unity Quantum Hot Standby system must have strictly identical configurations for both PLCs:
• Same Copro version
• Same Operating System (also called EXEC) version.
Notes:
• It is possible to upgrade the CPU (OS and Copro) of a Quantum HSBY configuration with a higher version without stopping the system.
• The new Ethernet I/O offer is totally compatible with HSBy features
Please refer to the “Modicon Quantum Hot Standby System User Manual” for complete information and recommendations.
Also, please refer to the online documentation in Unity Pro to check the executable compatibility (and the exceptions) of an application program
with the Operating System version.
• For the Operating System, it is not recommended to upgrade an OS Version V2.xx to version V2.40 or V2.41.
• For the Coprocessor, it is not recommended to upgrade a Copro version V0.80 to version V2.50.
• It is strongly recommended to use the latest versions of OS V3.0 and the Copro V3.0.
CCOTF features on S908 Remote IO system requires 140CRP93x00 and 140CRA93x00 firmware version V2.0, available under “RIO_modules”
folder in this eCD. To upgrade CRA / CRP modules please refer to the Quantum_Upgrade_Procedure document available on this eCD.
2/6
EIO000000005603
140 NOE 771 11 Upgrade
Due to hardware changes (ROHS compliance), two different firmware files are delivered for the 140 NOE 771 11 module, depending on
the PV version.
Use the appropriate file to upgrade the 140 NOE 771 11 module:
3/6
EIO000000005603
Quantum - Launch History of 140CPU31110, 140CPU43412 and 140CPU53414
OS OS OS OS
PV01 SV2.0 SV2.0 SV1.0 SV2.0
PV02 SV2.01 SV2.01 SV2.0 SV2.01
PV03 SV2.02 SV2.02 SV2.01 SV2.02
PV04 SV2.10 SV2.10 SV2.02 SV2.10
PV05 SV2.10 SV2.10 SV2.10 SV2.10
PV06 SV2.11 SV2.11 SV2.10 SV2.11
PV07 SV2.30 SV2.30 SV2.11 SV2.30
PV08 SV2.31 SV2.31 SV2.30 SV2.31
PV09 SV2.40 SV2.40 SV2.31 SV2.40
PV010 SV2.50 SV2.50 SV2.40 SV2.50
PV011 SV2.60 SV2.60 SV2.50 SV2.60
PV012 SV2.70 SV2.70 SV2.60 SV2.70
PV013 SV2.80 SV2.70 SV2.70 SV2.70
PV014 SV3.0 SV2.80 SV2.70 SV2.80
PV015 - SV3.0 SV2.80 SV3.0
PV016 - - SV3.0 -
Note: To get the version of OS, Copro or Ethernet modules please refer to the Quantum_Upgrade_Procedure document available on this eCD.
4/6
EIO000000005603
Quantum - Launch History of 140CPU65150, 140CPU65160 and 140CPU65260
140CPU65150 (C)
140CPU65260 140CPU65260C
140CPU65160 (C)
OS Copro OS Copro OS Copro
PV01 - - - - SV2.41 V2.20 (IE69)
PV02 - - SV2.40 V2.20 (IE69) SV2.41 V2.20 (IE69)
PV03 - - SV2.41 V2.20 (IE69) SV2.50 V2.50 (IE77)
PV04 - - SV2.41 V2.20 (IE69) SV2.60 V2.60 (IE 78)
PV05 SV1.0 V1.0 (IE46) SV2.41 V2.20 (IE69) SV2.61 V2.60 (IE 78)
PV06 SV2.0 V2.0 (IE56) SV2.50 V2.50 (IE77) SV2.70 V2.70 (IE82)
PV07 SV2.01 V2.0 (IE56) SV2.60 V2.60 (IE78) SV2.70 V2.70 (IE82)
PV08 SV2.02 V2.0 (IE56) SV2.61 V2.60 (IE78) SV2.80 V2.80 (IE83)
PV09 SV2.10 V2.10 (IE62) SV2.70 V2.70 (IE82) SV3.0 V3.50 (IE88)
PV010 SV2.11 V2.10 (IE62) SV2.70 V2.70 (IE82) - -
PV011 SV2.11 V2.10 (IE62) SV2.80 V2.80 (IE83) - -
PV012 SV2.23 V2.10 (IE62) SV3.0 V3.50 (IE88) - -
PV013 SV2.30 V2.20 (IE69) - - - -
PV014 SV2.31 V2.20 (IE69) - - - -
PV015 SV2.32 V2.20 (IE69) - - - -
PV016 SV2.40 V2.40 (IE72) - - - -
PV017 SV2.41 V2.40 (IE72) - - - -
PV018 SV2.50 V2.50 (IE77) - - - -
PV019 SV2.50 V2.50 (IE77) - - - -
PV020 SV2.60 V2.60 (IE78) - - - -
PV021 SV2.61 V2.60 (IE78) - - - -
PV022 SV2.70 V2.70 (IE82) - - - -
PV023 SV2.70 V2.70 (IE82) - - - -
PV024 SV2.80 V2.80 (IE83)
PV025 SV3.0 V3.50 (IE88)
Note: To get the version of OS, Copro or Ethernet modules please refer to the Quantum_Upgrade_Procedure document available on this eCD. 5/6
EIO000000005603
Quantum - Launch History of 140CPU67160 and 140CPU 67261
140CPU67261 140CPU67160
140CPU67261C 140CPU67160C
OS Copro HSBY OS Copro HSBY
PV01 SV2.80 V2.80 (IE22) - -
PV02 SV2.80 V2.81 (IE23) - -
PV03 SV3.0 V3.0 (IE27) SV2.0 V2.0 (IE78)
PV04 SV2.01 V2.0 (IE78)
PV05 SV2.02 V2.0 (IE78)
PV06 SV2.10 V2.0 (IE78)
PV07 SV2.11 V0.79
PV08 SV2.11 V0.80
PV09 SV2.11 V0.80
PV010 SV2.23 V0.80
PV011 SV2.30 V0.80
PV012 SV2.31 V0.80
PV013 SV2.32 V0.80
PV014 SV2.40 V0.80
PV015 SV2.41 V0.80
PV016 SV2.50 V2.50 (IE04)
PV017 SV2.50 V2.50 (IE04)
PV018 SV2.50 V2.51 (IE06)
PV019 SV2.60 V2.60 (IE08)
PV020 SV2.61 V2.60 (IE08)
PV021 SV2.70 V2.70 (IE10)
PV022 SV2.70 V2.70 (IE10)
PV023 SV2.80 V2.80 (IE22)
PV024 SV2.80 V2.81 (IE23)
PV025 SV2.80 V2.81 (IE23)
PV026 SV3.0 V3.0 (IE27)
6/6
EIO000000005603