C60
IEC
They remotely trip or indicate circuit breakers or Compliance with electrical auxiliaries standards
supplementary protectors. b For UL 489 circuit breaker File #217688.
b For CSA C22.2 No. 5.2 circuit breakers File #179014.
b For UL 1077 Supplementary Protectors File #E90509.
b For CSA C22.2 No. 235-M04 Supplementary Protectors File #179014.
b For IEC 60947-2 and IEC 60947-5-1 circuit-breakers.
b CE Marked.
PB100994-35
PB100993-35
PB100992-35
PB100977A_SE
+ + + +
SD alarm switch
1 26928
MX + OF shunt trip
24 12 to 24 2 27118
48 48 2 27110
110 to 277 110 to 130 2 27109
MN undervoltage release
Instantaneous 24 24 2 27108
48 48 2 27106
120 - 2 27107
220 to 240 - 2 27105
Remote tripping
Remote tripping is possible by means of a shunt trip (MX+OF) or undervoltage
release (MN). A tripped device is indicated by a red indicator flag on the front panel.
MX + OF shunt trip
b When energized, trips the associated device:
DB100993-35
v equipped with an O + F switch that indicates the “open” or “closed” position of the
device
v realize a self-interrupting allowing the control circuit to remain on.
Wiring diagrams
08603083
DB112939
u>
14 12 C2 C1
MN Undervoltage Release
DB100992-35
b When the voltage drops to 70–35% of the supply voltage, the associated device
trips and is prevented from reclosing until the supply voltage is restored:
v uses emergency stop via push button
v uses safety feature on circuit supplying several machines preventing uncontrolled
restarting of the motors.
Wiring diagrams
08603084
08603146a
u<
u<
D1 D2
D1 D2
L or +
N or -
Remote Indication
Operation test button on the front panel of the auxiliary (OF) and alarm switches (SD)
allows simulation of the OF and SD functions without operating the device.
OF auxiliary switch
b Indicates the “open” or “closed” position of the device.
Wiring diagrams
PB100994-35
08603086
DB112940
14 12 11
SD Alarm Switch
b Indicates the “tripped-on-fault” position of the device with a red indicator flag on
the front panel.
Wiring diagrams
PB100995-35
08603085
DB112941
92 94 91
Releases MX+OF
27109 27110 27118
Nominal line voltage (V) (+10, -20%) 120 240 277 110 125 48 48 12 24 24
Alternating current (a) b b b - - b - - b -
Direct current (c) - - - b b - b b - b
Operating frequency 50/60 Hz b b b - - b - - b -
Min. cut-out voltage (V) 60.5 60.5 60.5 60.5 60.5 26.4 26.4 6.6 6.6 6.6
Inrush current (A) 0.4 0.8 1 0.3 0.3 1 0.7 2.5 7.7 5.6
Inrush power (VA) 44 184 277 38 45 48 33.6 30 185 135
Min. control impulse duration (ms) 8 8 8
Power circuit breaking time (ms) 18 18 18
OF contact rated operational current Ie (A) See the auxiliary contact table
Dimensions
DB110258