CPC 100 AppNote CVT Testing With CP TD1 2019 ENU
CPC 100 AppNote CVT Testing With CP TD1 2019 ENU
CPC 100 AppNote CVT Testing With CP TD1 2019 ENU
Author
Lukas Klingenschmid | [email protected]
Thomas Bischof | [email protected]
Date
July 1st, 2019
Application Area
Instrument Transformer Testing
Keywords
CVT, CCVT, Dissipation Factor, Capacitive Voltage Divider, Power Factor, Voltage Transformer
Version
V1.0
Document ID
ANP_17004_ENU
General Information
OMICRON electronics GmbH, including all international branch offices, is henceforth referred to as
OMICRON.
The product information, specifications, and technical data embodied in this Application Note represent the
technical status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this Application Note is useful, accurate and
entirely reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be
present.
OMICRON translates this Application Note from the source language English into a number of other
languages. Any translation of this document is undertaken for local requirements, and in the event of a
dispute between the English and a non-English version, the English version of this note shall govern.
All rights, including translation, reserved. Reproduction of any kind, for example, photocopying, microfilming,
optical character recognition, and/or storage in electronic data processing systems, requires the explicit
consent of OMICRON. Reprinting, wholly or partly, is not permitted.
© OMICRON 2019. All rights reserved. This Application Note is a publication of OMICRON.
DANGER
Death or severe injury caused by high-voltage or current if the respective
protective measures are not complied with.
Only experienced and competent professionals who are trained for working in high-voltage or high current
environments may perform the applications in this document. In addition, the following qualifications are
required:
• Authorized to work in environments of energy generation, transmission or distribution and familiar
with the approved operating practices in such environments.
• Good knowledge of the CPC 100, CPC 80 or TESTRANO 600 and the CP TD1
Reading the ANP_17004 Application Note alone does not release you from the duty of complying with all
national and international safety regulations relevant to working with the CPC 100, CPC 80 or
TESTRANO 600 and the CP TD1.
The regulation EN 50191 "The Erection and Operation of Electrical Test Equipment", as well as all the
applicable regulations for accident prevention in the country and at the site of operation, have to be fulfilled.
Working on HV devices is extremely dangerous. Measurements must only be carried out by qualified, skilled
and authorized personnel. Before starting any work, clearly establish the responsibilities. Personnel
receiving training, instructions, directions or education on the measurement setup must be under the
constant supervision of an experienced operator while working with the equipment.
The operator is responsible for the safety requirements during the whole test. Before performing tests using
high-voltage, read the following:
• Do not perform any test without having carefully read the corresponding User and Reference
Manuals.
Please refer to section 2.3 - Related Documents in regard to the appropriate product literature.
The measurement must comply with the relevant national and international safety standards listed below:
• EN 50191 (VDE 0104) "Erection and Operation of Electrical Equipment".
• IEEE 510 "Recommended Practices for Safety in High-Voltage and High-Power Testing".
Furthermore, additional relevant laws and internal safety standards must be followed.
Before starting a measurement, read the safety rules in the CPC 100 User and Reference Manual, CPC 80
User Manual or TESTRANO 600 User Manual as well the CP TD1 User Manual. In addition, observe the
application specific safety instructions in this Application Note when performing measurements to protect
yourself from high-voltage hazards.
The following documents complete the information covered in this Application Note:
Title Description
Provides basic information on the CPC 100 test system and relevant
CPC 100 User Manual safety instructions.
Contains information on how to use the CPC 100 test system and
CPC 100 Reference Manual relevant safety instructions.
Provides basic information on the CPC 100 test system used with the
CPC 100 PTM User Manual Primary Test Manager software.
Contains information on how to use the TESTRANO 600 test system and
TESTRANO 600 User Manual relevant safety instructions.
Provides basic information on the TESTRANO 600 test system used with
TESTRANO 600 PTM User Manual the Primary Test Manager software.
Contains information on how to use the CP TD1 test system and relevant
CP TD1 Reference Manual safety instructions.
Application Guide: Capacitance and Contains general information about dissipation factor (power factor)
Dissipation Factor Measurement with measurement on different assets.
CPC 100 + CP TD1
Application Guide: CVT-Build-up-2017 Contains general information about the asset CVT.
AN CP0711: Test Templates General information about working with templates for the CPC 100.
Before starting a measurement, read the safety rules in the CPC 100 User and Reference Manuals,
CPC 80 User Manual or TESTRANO 600 User Manual as well the CP TD1 User Manual carefully and
observe the application-specific safety instructions in this Application Note when performing measurements
to protect yourself from high-voltage hazards.
General
Always observe the five safety rules:
► Disconnect completely.
► Secure against re-connection.
► Verify that the installation is dead.
► Carry out grounding and short-circuiting.
► Provide protection against adjacent live parts.
CAUTION
Minor or moderate injury may occur if the appropriate safety instructions are
not observed.
DANGER
Death or severe injury will occur if the appropriate safety instructions are not
observed.
WARNING
Death or severe injury can occur if the appropriate safety instructions are not
observed.
CAUTION
Minor or moderate injury may occur if the appropriate safety instructions are
not observed.
NOTICE
Cn
Design Capacitance
20000 pF
C1 Capacitance
24184 pF
C2 Capacitance
120647 pF
Each capacitor unit is sometimes equipped with its own nameplate where the capacitance value is stated.
The dissipation factor reading from the dielectric measurement shall correspond to the stated dissipation
factor on the nameplate of each capacitor unit.
The dissipation factor reading depends on:
• Good solid test connections.
• Clean and dry insulators.
NOTICE
The capacitance values obtained during field tests may differ from the nameplate values.
Obtained data from the field tests shall be used as a reference for future comparison (trending).
A capacitor element failure will result in an increase of the total capacitance.
o The capacitance increase is in proportion with the remaining number of capacitor
elements in operation and the original number of capacitor elements.
o An increase of around 1 % in capacitance, obtained from the reference measurement in
the field, can be considered as significant.
There are no limits for the dissipation factor. Limits may be agreed between the manufacturer
and the purchaser.
o Often the limits are defined by the manufacturer.
o It is not uncommon for the dissipation factor values obtained @ 10 kV to exceed the
factory values which are measured at operating voltage.
© OMICRON 2019 Page 11 of 65
Accessibility of C1 and C2 Dependent on the CVT Design
Depending on the accessibility of the CVT circuit, C1 and C1-1 respectively (on multi-unit capacitor stacks)
and C2 can be tested individually.
NOTICE
If the CVT has a potential grounding switch or the intermediate voltage terminal can be
disconnected and isolated from the magnetic circuit, all related dielectric measurements can be
performed.
If the intermediate voltage terminal is not accessible, only the CR values can be measured.
o If there is more than one unit, each unit capacitance can still be measured
independently.
Table 1 – Possible measurement configuration dependent on the CVT design
C1 or C2 No influence.
Measurement is not
possible as the complete
Not possible
test current is not going
through C1 or C2.
Depending on the CVT design, previous measurement data and reference data from factory acceptance test
(FAT) reports, one measurement mode may be chosen over another.
NOTICE
Using the same measurement mode, the same measurement setup compared to previous
measurements on the CVT is recommended.
The respective naming of the UST and GST measurement modes may differ, depending on the
manufacturer.
In general, the UST measurement modes are more accurate, as influences from the ground are not
measured.
For further information about UST and GST measurement modes, please refer to chapter 7.5 .
C1_2 UST-A 1 2 -
NOTICE
Orange marked fields are optional for the measurement setup.
o If a CP TD1 input is connected to an orange marked connection point, currents will be
guarded at these points if an appropriate test mode is used.
Recommended test voltage is 10 kV for the measurement configuration stated in Table 2.
C1_2 UST-A 1 2 -
C1_3 UST-A 2 3 -
NOTICE
Orange marked fields are optional for the measurement setup.
o If a CP TD1 input is connected at an orange marked connection point, currents will be
guarded at these points if an appropriate test mode is used.
Recommended test voltage is 10 kV for the measurement configuration stated in Table 3.
The IEC 61869-5 standard (clause 7.2.501) gives some recommendations regarding the capacitance and
dissipation factor measurement at power frequency. These specifications are recapitulated in this chapter.
Pre-check Measurement
The IEC 61869-5 standard recommends performing a preliminary capacitance measurement with a test
voltage of less than 15 % of the rated voltage to ensure that no puncture of an element will occur.
Miscellaneous
Depending on the number of capacitive elements in series on the tested unit, it may be difficult to ascertain
whether a puncture has occurred because of the following uncertainties:
► Reproducibility of the measurement.
► Capacitance change caused by the mechanical forces on the elements during the dielectric tests.
► Capacitance change caused by temperature difference of the capacitor before and after the test.
The IEC 61869-5 standard also states the measurement uncertainty should be reduced by performing a
capacitance measurement on each unit.
The change of capacitance C of a unit is defined in Equation 1:
Equation 1 - Limit of the allowed capacitance change
∆𝐶 1 𝐶
≤ =
𝐶 𝑛 𝐶0
NOTICE
There are no general limits for the dissipation factor.
Limits may be agreed between the manufacturer and the purchaser.
The dissipation factor is dependent on the insulation design, the test voltage and frequency as
well as the insulation temperature.
IEC 61869-5 defines the temperature coefficient of capacitances as the fractional change of the capacitance
for a given change in temperature.
NOTICE
This applies only to the capacitor divider (C1, C2 and dissipation/power factor).
Equation 2 – Temperature coefficient Invalid source specified.
∆𝐶 1
𝑇𝐶 = [ ]
∆𝑇 ∗ 𝐶20° 𝐾
T C: Temperature coefficient of capacitance
∆T: Temperature interval (difference) in reference to 20°C
∆C: Observed change in capacitance over the temperature interval ∆T
C20°: Capacitance value measured at 20 °C
NOTICE
The term ∆C/∆T per this definition is only usable if the capacitance is an approximate linear
function of the temperature in the range under consideration.
Otherwise, the capacitance temperature dependency shall be shown in a table or in a graph.
The CVT’s FAT report may contain curves for the temperature coefficient (T C) otherwise curves
for the temperature coefficient can be requested from the manufacturer.
The effect of the shorted capacitive layer is explained in the paper Invalid source specified.:
“Shorted elements in C2 has a larger impact than shorted C1 elements and drifts towards negative values
whereas C1 causes a drift towards positive values. The influence of shorted capacitive elements is linear.
The capacitive ratio rc decreases slightly with shorted C1 elements and increases more significantly for C2.
As C1+C2 increases, the impedance XC decreases and thus the reactive part of the short circuit impedance
increases towards inductive values.”
XSC,Healthy = 14 mΩ
XSC,1C1 = 32 mΩ (1 x C1 element shorted)
XSC,5C1 = 71 mΩ (5 x C1 element shorted)
XSC,1C2 = 56 mΩ (1 x C2 element shorted)
XSC,5C2 = 190 mΩ (5 x C2 element shorted)
Figure 9 - Phase displacement depending on different failure modes on a 66 kV CVT (lab experiment)
𝑛
𝐶𝑛𝑒𝑤 = 𝐶𝑜𝑙𝑑 ∗
𝑛−𝑚
n: number of capacitive elements in the capacitor unit
m: number of shorted capacitive elements
4.1 Safety Instructions for Connecting the CP TD1 to the Test Setup
DANGER
Death or severe injury will occur if the appropriate safety instructions are not
observed.
Do not enter the work area while working with the CPC 100,
CPC 80, TESTRANO 600 or CP TD1
Make sure to position the CVT in the work area.
Use a ground point as close as possible to the CVT.
Do not enter the work area if the red warning light of the CPC 100, CPC 80
or TESTRANO 600 is on since outputs may carry dangerous voltages or
current.
Never touch any terminal without visible ground connection.
Always obey the five safety rules and follow the detailed safety instructions
in the respective user manuals.
Always establish a proper ground connection for the CPC 100, CPC 80 or
TESTRANO 600 and the device under test (CVT/CCVT) with at least
6 mm².
Beware of nearby parallel systems which are not disconnected. They can
induce hazardous loads in floating segments of a substation.
Always touch the leads and terminals with a grounding hook first.
Only use the cables included in the CP TD1, CPC 100, CPC 80 or
TESTRANO 600 delivery.
Prior to connecting a test object to the CP TD1, the following steps need to be
carried out by an authorized employee of the utility:
Turn off and disconnect the high voltage from the test object.
Protect yourself and your working environment against an accidental re-
connection of high voltage by other persons and circumstances.
Verify a safe isolation of the test object.
Ground and short-circuit the test object’s terminals using a suitable
grounding set
Protect yourself and your working environment with suitable protection
against other (possibly live) circuits.
Protect others from accessing the dangerous area and accidentally
touching live parts by setting up a suitable barrier and, if applicable,
warning lights.
If there is a long distance between the location of the CP TD1 and the area
of danger (that is, the test object), a second person with an additional
"Emergency Stop" button is required.
Make sure that both sides of the capacitive voltage transformer are completely
disconnected.
2. Verify that the test has ended by checking the status lights of the Control device:
The green status light must be on and at the same time the red status light must be fully extinguished.
DANGER
Death or severe injury caused by high voltage or current possible
The green status light indicates that the outputs of the Control device are not activated
Even if you switched off the Control device, wait until the red status light is fully
extinguished. As long as this status light is lit, there is still voltage potential on the
output.
4. Note: For more details, refer to the corresponding User Manual of the Control device.
5. Ground and short-circuit the test object’s terminals using a suitable grounding set.
9. Disconnect the HV and LV cables from the CP TD1 and the test object.
10. Disconnect the measurement ground from the test object and the CP TD12/15.
Figure 10 - Connecting the CP TD1 to the CPC 100, CPC 80 or TESTRANO 600
DANGER
Death or severe injury caused by high voltage or current possible
2. Without trolley:
► Properly connect the Control Device and the CP TD1 grounding terminals to the substation ground.
►Properly connect the CPC 100 or TESTRANO 600 and CP TD1 grounding terminals to the trolley’s
ground bar.
3. Make sure that all cable connectors are clean and dry before being tightly connected.
4. Connect the CP TD1’s "BOOSTER IN" to the Control Device’s "EXT. BOOSTER" with the booster
cable.
5. Connect the CP TD1’s "SERIAL" to the Control Device’s "SERIAL" with the data cable. This cable also
provides the power supply for the CP TD1.
6. Pull out the measuring cables from the cable drum and connect the test object to the CP TD1’s
measuring inputs IN A and IN B.
7. Connect the high-voltage cable from the test object to the CP TD1’s high-voltage output.
► At the CP TD1, press the high-voltage cable’s plug into the connector tightly and turn the screw cap
manually, without using any tools, until you feel a mechanical stop. If you notice a rough-running of the
screw-cap, clean the screw thread and use a lubricant (Vaseline recommended).
►Insert the yellow banana plug (the high-voltage cable’s grounding) into the respective plug socket.
►At the test object, insert the high-voltage cable’s plug carefully until you feel a "click". They are now
locked. Confirm this by trying to pull them out. This should not be possible.
The images below show how to unlock the cable connection again. This is also shown on a label fixed to the
high-voltage cable.
► After the HV cable connection is established, use the strain relieve delivered with the HV cable to fasten it
to the test object.
The high-voltage cable is double-shielded and therefore safe. However, the last
50 cm (20 inch) of this cable has no shield.
During a test, consider this cable a life wire and, due to the high-voltage, life-
hazardous.
8. Connect the Control Device to the mains power supply using the provided cable.
WARNING
Death or severe injury caused by high voltage or current possible
10. The green warning light comes on, showing that the Control Device’s output does not carry a
dangerous voltage or current yet (on the TESTRANO 600 the blue ring of the Start/Stop button is
additionally lit).
WARNING
Death or severe injury caused by high voltage or current possible
If none or both warning lights are on, the unit is defective and must not be used.
11. An error message appears if either the PE connection is defective or if the power supply has no
galvanic connection to ground. The latter is the case on very special power supplies such as generators
or when insulation transformers are used.
WARNING
Death or severe injury caused by high voltage or current possible
This is a safety-relevant message. If the reason for this message is that neither the PE nor
the grounding terminal is connected, it can cause injury or possibly death of the operating
staff. The operator is fully responsible for any hazard that might occur due to improper
grounding.
For safe operation always make sure that both the PE and the grounding terminal
are connected.
Figure 11 – Basic measurement setup for testing the overall DF and CAP of a CVT
5.1 Procedure
1. Check the stated primary and secondary voltage levels on the CVT nameplate.
Example: The CVT nameplate information at Figure 12 states a voltage ratio of 1200.
Equation 4 – Ratio calculation for the CVT
3. Observe the stated safety instructions in section 4.1 before connecting the CPC 100 to the CVT.
NOTICE
Make sure that the CVT is disconnected from mains.
Make sure that the CVT is de-energized on ALL terminals and disconnected from any HV
voltage.
The HV terminal of the CVT shall be connected to ground potential.
4. Make sure that the carrier grounding switch and the potential grounding switch are closed.
The red CPC 100 high voltage lead is connected to the high voltage terminal of the CVT.
The black CPC 100 high voltage lead is connected to the grounded NHF/HF point.
NOTICE
If a Carrier Accessory Box is installed, the NHF is grounded over the closed carrier
grounding switch.
If no Carrier Accessory Box is installed, then the NHF point needs to be grounded either
via an appropriate grounding switch or an external grounding (minimum diameter is 6
mm²).
8. Apply a test voltage (for example 1 kV) to the CVT HV terminal and measure the secondary voltage.
NOTICE
The VTRatio test card can be used for performing a CVT ratio measurement.
13. Repeat the steps 5-9 for measuring all windings and tappings of the CVT.
The following overview provides information on how to proceed if any abnormal test results are observed.
The list provides possible failure modes.
Table 5 – Troubleshooting guidelines for a CVT ratio measurement
• Open-Circuit on VT.
o Measure C1 and C2 capacitance.
▪ Check the values for plausibility!
o Measure the secondary winding resistance.
▪ Should be “low-resistive” → Check with Factory
Acceptance Values.
• Short-Circuit on secondary windings.
No secondary voltage o Remove external wiring and measure the output voltage.
▪ If there is still no voltage, an insulation resistance
test may be performed.
▪ Obtained values should be high-resistive → MΩ
range or higher.
• Potential grounding switch is closed.
Open the grounding switch.
• Failure in a C2 element.
o Increase of the C2 capacitance.
o Ratio error turns positive.
Secondary voltage is low
o Measure the capacitance of C2 and compare with
nameplate or FAT values.
• Poor secondary connection.
• Failure in a C1 element.
o Increase of the C1 capacitance.
Secondary voltage is high o Ratio error turns negative.
• Measure the capacitance of C1 and compare with nameplate or
FAT values.
NOTICE
Option 1 can be used if the NHF/HF point is accessible.
o NHF/HF point shall be grounded.
Option 2 can be used if the NHF/HF point is not accessible.
o NHF/HF should be internally connected to ground potential.
o If available, verify if the carrier grounding switch is closed.
If available, the Potential Grounding Switch needs to be open.
This chapter gives some recommendations on how to perform the dissipation/power factor and capacitance
measurement on various types of CVTs. Before starting, please be aware of the following points.
NOTICE
The internal CVT build-up can vary.
o C1 or C2 cannot always be tested!
o When testing a CVT, the internal connection scheme is crucial information to check
which CVT parts (C1, C2 or CR) can be tested.
o Testing only the (I)VT part is not possible as it cannot be separated either from the
compensating reactor or from the capacitive divider stack.
CR can be tested with one side grounded, LV windings or with floating LV windings.
o Check the Factory Acceptance Test Report regarding the used measurement setup to be
able to compare the determined dissipation/power factor and the capacitance values.
o Usually 1n, 2n etc. are grounded and 1a, 2a etc. are open.
o Never ground both points (for example, 1a and 1n) of the LV winding(s).
o Manufacturers often test with floating LV winding(s) and respective floating tank.
o Measurement results may be different when comparing one-side grounded and floating
LV winding(s) and respective floating tank.
When performing the dielectric measurement, please be aware that additional internal parts may
have an influence on the obtained measurement results.
o When testing C1 and C2, the compensating reactor in particular may influence the
obtained measurement results.
o For testing CR, the compensating reactor in particular and (I)VT part may influence the
obtained measurement results.
o The values can be compared with reference data, as previous reference measurements
(for example, from the FAT report) were also performed with an assembled CVT.
The Carrier Accessory Box (CAB) must either be disconnected, or the internal Carrier Grounding
Switch must be in the closed position.
o It would be recommended to disconnect the CAB and have a floating (N)HF point, when
testing C1 or C2.
It is recommended to limit the maximum test voltage to 10 kV and not 12 kV to compare the
obtained dissipation/power factor and the capacitance values with reference or future
measurement data.
o Do not exceed a test voltage of 3 kV when injecting against the NHF point!
Naming schemes are dependent on the manufacturer’s country and standard used
(IEC or IEEE).
Orange marked fields are optional for the measurement setup.
o If a CP TD1 input is connected at an orange marked connection point, currents will be
guarded at these points if an appropriate test mode is used.
Table 6 – Recommended measurement settings for testing the TRENCH TCVT 170 (only valid for this example)
C1 - - - - No measurement possible.
C2 - - - - No measurement possible.
Table 7 – Recommended measurement settings for testing the Haefely TCT 245 - ME83K (only valid for this example)
C1 - - - - No measurement possible.
C2 - - - - No measurement possible.
• HF is grounded.
• P2 is grounded.
LV
CR GSTg-A+B A - Optionally the LV winding can be guarded over
windings
Input A.
→ Do not short the LV windings
Table 8 – Recommended measurement settings for testing the CPA/CPB 72-550 kV (only valid for this example)
Table 9 – Recommended measurement settings for testing the Arteche DFK-420kV (only valid for this example)
The following example measurement was performed on a TRENCH CVT (Type CVT 145) in a high voltage
laboratory.
NOTICE
When a connection from the test set to the CVT is established or changed, it is strongly
suggested the emergency stop button is always pressed and the safety key is in the locked
position.
An appropriate grounding rod is connected to the HV terminal of the CVT to ensure that the capacitance is
discharged before setting up the measurement.
NOTICE
This CVT does not have an installed grounding switch.
The NHF point was connected to the ground potential via a 4 mm banana connector.
CVT Ground
potential
NHF
Afterwards, the 2 kV AC output of the CPC 100 is connected to the HV terminal of the CVT and to the NHF
point (refer to Figure 15 and Figure 24). The grounding rod is still connected during the wiring.
Figure 24 - Connection to the grounded NHF point (left) and to the HV terminal of the CVT (right)
In the next step, the corresponding LV windings (1a and 1n, and, 2a and 2n respectively) are connected to
the CPC 100 V1 AC input (refer to Figure 26)
Figure 26 - Setup for testing the CVT Ratio for LV windings 1a and 1n (on TRENCH CVT 145)
© OMICRON 2019 Page 42 of 65
The results in Figure 27 show a slight increased ratio and phase deviation for the 0.5 class CVT. The
positive ratio deviation may indicate a punctured element in the C2 stack. For further information please
refer to chapter 5.2.1
NOTICE
The “low” test voltage in comparison to the nominal voltage of the CVT may also have an
influence.
NOTICE
Don’t forget to ground the CVT HV terminal and press the Emergency stop button before
entering the working area.
Dielectric measurement
The CVE 145 type from TRENCH has a similar internal build-up to the Haefely TCT 245 from Figure 17.
Only the dissipation factor and capacitance for the complete CVT and the C R capacitance can be measured.
The individual C1 and C2 capacitances cannot be measured for this type of CVT.
Five different measurement configurations were used to demonstrate the influence of correct and incorrect
measurement techniques.
NOTICE
Measurements 1 and 2 used an incorrect measurement setup!
Measurements 3, 4 and 5 used a correct measurement setup!
Figure 29 –Dielectric measurement setup: NHF not grounded and LV windings grounded on both sides
© OMICRON 2019 Page 44 of 65
6.2.2.2 Measurement setup 2 - NHF grounded and LV windings grounded on both sides
This measurement setup is not correct and leads to inaccurate measurement results.
Although the NHF point is now properly grounded which leads to reasonable determined capacitance
values, the measured dissipation factor is highly increased, by 12%, which is reasonable due to the shorted
LV winding.
Figure 30 - Dielectric measurement setup: NHF grounded and LV windings grounded on both sides
Figure 31 - Dielectric measurement setup: NHF grounded and LV windings grounded on one side
Figure 32 - Dielectric measurement setup: NHF grounded, LV windings grounded on one side and surface currents are guarded via a
hot collar band
NOTICE
If the CVT has more than one winding, then the windings are connected with each other in series and at one
point are connected to the Input A (UST-A mode) or Input B (UST-B mode).
Measurements with a floating CVT tank may have the advantage that influence from the grounding system
can be reduced as the connection between the CVT and the test set is more low-resistive due to the shorter
distance.
NOTICE
Additionally, a hot collar band could also be connected to Input A or B to guard the surface
currents as shown in Measurement Setup 4.
o The measurement mode does not change (UST-A or UST-B) if the other input is used as
a guard input.
7 Appendix
CR Rated capacitance of a unit (If only one unit → CR = Cn = (C1 + C2) / (C1
+ C2).
IT Instrument Transformer
VT Voltage Transformer
The electrical performance of capacitive voltage transformers (CVT), and thus the accuracy of the device, is
not only dependent on the transformation ratio of the intermediate voltage transformer but also on the
capacitive divider, the compensating reactor and the damping components.
All components of the CVT are prone to aging when they are in operation over a long lifetime, especially
under harsh environmental conditions.
The accuracy requirements, as well as the equipment condition, can be affected during the overall lifetime
but generally no diagnostic measurements are performed on CVTs.
As a result, the failures or errors remain hidden. Failures and errors of CVTs may not only result in economic
damage if the voltage is not measured correctly. It can also cause malfunctions of the protection system or
outages and technical damages to the CVT and the surroundings when the asset explodes.
Figure 34 shows an example equivalent circuit and its phasor diagram of a CVT.
Instrument Voltage Transformers (VT), either inductive (IVT) or capacitive (CVT, CCVT), are used in
electrical grids to transform the line voltage at line frequency to a lower voltage level (for example, 100 V/3
or 110 V/3) for further data processing.
Compared to inductive VTs, a capacitive voltage divider is also used to reduce the transmission line voltage
and an inductive component (compensating reactor) to compensate the phase displacement. This phase
displacement is caused by the capacitive voltage divider. Therefore, the inductive element compensates the
phase displacement at line frequency.
As the capacitive divider of a CVT steps down the transmission line voltage, for example, a voltage of
132 kV to 20 kV for the intermediate voltage transformer part, a smaller design such as an inductive VT (IVT)
Sof the same voltage level (here: 132 kV) can be offered.
Especially for high voltage applications (>132 kV), the IVT design may, compared to the CVT design, be
very uneconomical and bulky due to increased requirements for the insulation and active part. The
intermediate voltage transformer of a CVT is basically an IVT. The insulation of the intermediate VT from a
CVT doesn’t need to withstand such high voltages as a conventional IVT for the same voltage level.
Therefore, smaller designs are possible.
The intermediate inductive transformer of a CVT is located in the tank and is typically oil-filled.
The following Figure 35 shows an example CVT from the manufacturer TRENCH including the nameplate
and circuit diagram.
Capacitor Divider
The capacitor divider is used as a voltage divider to step down the line voltage to a lower level, typically
20 kV.
The divider is made up of many in-series connected capacitor elements which are connected between line
and ground (refer to Figure 36). By rule of thumb, the number of single elements corresponds to Equation 5
and reflects a typical voltage drop of Velement ≈ 0.85 kV over each element at rated voltage VR with standard
rated capacitance (CR) values. Higher or lower values of Velement are possible and depend on the CR or
design criteria of the manufacturers. Invalid source specified.
Equation 5 - Number of single capacitance elements (rule of thumb)
𝑉𝑅
𝑛𝑡𝑜𝑡𝑎𝑙 = ∑𝑛𝑖=1 𝑛𝑖 ≈ ∗ 0.7 Invalid source specified.
1000
Figure 36 – Capacitor elements connected in series for the CVT Capacitor Divider
A tap connection within the capacitive divider is brought out at an appropriate voltage level carefully
coordinated with the intermediate voltage transformer to provide the required output voltages.
Equation 6 – Relationship between primary C1 und secondary capacitance C2 / Relationship of number of single C-elements (n1/n2)
𝐶2 𝑛1
𝑟𝑐 = 1 + =1+
𝐶1 𝑛2
𝑁1
𝑟𝑉𝑇 =
𝑁2
Typically the capacitor elements between the tap and the high voltage side are named C1 and the capacitor
elements between the tap and the low voltage side are named C2. There are more C1 capacitor layers than
C2 layers to achieve an appropriate voltage for the intermediate voltage transformer. The layers are
integrated in hollow porcelain or composite insulators filled with an impregnating fluid like oil.
1
𝐿𝑐𝑜𝑚𝑝 =
(𝐶1 + 𝐶2 ) ∗ (2 ∗ π ∗ 𝑓𝑟 )²
𝑟𝑉𝑇 = 𝑁1𝑁2
The adjustment of the total CVT accuracy (winding correction) can be realized by additional winding turns at
the compensation reactor for the phase displacement ∆φ and at the primary winding of the intermediate
voltage transformer for the voltage error εU.
There are various designs on the market using R, L and/or C components in different configurations. The
design of the damping circuit depends on the manufacturer.
The FSU is connected to the intermediate VT (more often to the secondary side) and is sometimes buried in
the tank or disconnected in the terminal box.
For modern CVTs, the main types of ferroresonance suppression circuits are the Active Ferroresonance
Suppression Circuits (AFSC) and the Passive Ferroresonance Suppression Circuits (PFSC).
The AFSC is based on a series RLC filter and the PFSC is based on a saturable inductor in series with a
damping resistance.
Compared to the PFSC, the AFSC is more effective in damping the ferroresonance oscillations.
A disadvantage of the AFSC technique is the higher influence of the transient response compared to the
PFSC technique.
NOTICE
It must be noted that the presence of a ferroresonance suppression circuit will affect the
transient performance of a CVT due to the reactive and non-linear components.
It is quite common that the damping unit is applied to the residual winding. Sometimes damping circuits are
not accessible and cannot be disconnected from the VT’s secondary winding.
NHF
CAB
V1: Primary voltage C1: Primary capacitance Xσ1 & X’σ2: Leakage inductance RCO,FE: Resistance of the iron core of
compensating reactor
V2: Secondary voltage C2: Secondary capacitance R1 & R’2: Winding resistance RCO: Winding resistance of
compensating reactor
Ip: Primary current I0: No-load current X’H: Main inductance XCO: Inductance of compensating
reactor
Is: Secondary current ZB: Load RFE: Resistance of the iron core
In an ideal capacitor without any dielectric losses, the current vector is shifted exactly 90° in respect of the
applied voltage vector. For real insulations with dielectric losses, the angle is less than 90°.
For a single frequency, an insulation can be modelled by a loss-free capacitor with a parallel resistor
representing the losses in the insulation system (Figure 41).
In the equivalent circuit, the vacuum capacitance and all polarization are represented in a single, ideal
capacitor. This capacitor represents the actual test object capacity at the selected frequency.
All polarization and conduction losses are represented by the resistor which is connected in parallel to the
ideal capacitor.
The circuit with the resistor and capacitor describes the behavior of the test object at a single frequency.
Usually, for every test frequency used, different values for the resistor and capacitor of the equivalent circuit
are obtained.
Applying a voltage to the parallel components causes a capacitive current IC to flow through the capacitor as
well as a resistive current IR through the resistor (Figure 42). The overall current ITest, which is the sum of
both, therefore has a resistive and a capacitive component. The higher the losses, the higher the resistive
current. The angle δ = 90° - φ between IC and ITest is caused by the resistive part IR of the overall current ITest
and increases with the losses.
The parameter tan(δ), which is the ratio of the resistive current IR to the capacitive current IC, is one
parameter often used to describe the quantity of losses of an insulation system (Figure 41).
Another way to describe the losses is the power factor, which is the cosine of the angle φ, (Equation 11).
𝐼𝑅
𝐷𝑖𝑠𝑠𝑖𝑝𝑎𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟 = = tan(𝛿)
𝐼𝐶
Equation 11 – Power factor (DF)
𝐼𝑅
𝑃𝑜𝑤𝑒𝑟 𝐹𝑎𝑐𝑡𝑜𝑟 = = cos(φ)
𝐼𝑇𝑒𝑠𝑡
The CP TD1 has three external measuring inputs, IN A, IN B and ground. These three inputs can be
individually switched to guard or to the measuring unit. If an input is switched to the measuring path, the
connected capacitance is part of the measurement. If it is switched to guard, the current bypasses the
measurement path and is not included in the measurement. The advantage of using a switch matrix to
configure the measurement is that multiple measurements can be made without changing the measurement
setup or wiring.
In the GST configuration, 4 configurations are possible (see Table 9 below). The naming is slightly different
compared to the UST modes as it indicates the channels which are guarded, not the channels which are
measured. The measurement result is also the sum of all measured channels.
Define voltage or
frequency sweep
Averaging
Define the number of
sequences per test point
NOTICE
Special naming in the frequency column "Hz" and their meanings:
*50 Hz (*60 Hz) = Measurement mode suppressing the mains frequency interferences; doubles
the measurement time.
!30 Hz = The selected test voltage is not available in Automatic measurement (applies to
frequencies below 45 Hz only).
?xx Hz = Results with reduced accuracy, for example, in case of a low testing voltage,
influences of partial discharge etc.
© OMICRON
www.omicronenergy.com
Subject to change without notice.