Calculations For Touch Voltage and Step Voltage (Spreadsheet)
Calculations For Touch Voltage and Step Voltage (Spreadsheet)
Calculations For Touch Voltage and Step Voltage (Spreadsheet)
Sheet 1 of 9
BLOCK1 : 110KV Switchyard
Reference Documents
a) Electrical resistivity test report at plant site for 110KV Switchyard at Punalur Paper Mills Ltd.
b) IEEE80-2000
c) Plant General Layout
D) CBIP Manual on substation publication number : 223
1.0 DESIGN BASIS
1) Resistivity data has been taken from the available soil report .
67
37.5M
(Fig-1)
Power Plant
Sheet 2 of 9
Subject : EARTHING DESIGN CALCULATION FOR 1X10MW BIOMASS BASED POWER PLANT
1) IEEE 80-2000
2) Soil resistivity Report.
3) CBIP Manual on substation publication number : 223
Input data :-
(i) Conductor material = MS
Conductor Size :-
t c ar r r x 104
TCAP
A = If Ko + Tm
ln
K o + Ta
Sheet 3 of 9
2. CALCULATIONS FOR TOLERABLE TOUCH VOLTAGE (Etouch )& STEP VOLTAGE( Estep)
Sheet 4 of 9
Sheet 5 of 9
2.2) Calculation of Tolerable Etouch & Estep Voltage :
a) Tolerable Etouch50 :
From IEEE Std 80-2000
Tolerable Etouch50= [(1000 + 1.5CS rS) 0.116/ ÖtS ] ( From eq.32of IEEE Std 80-2000 )
Where,
Cs = Reduction factor for derating the nominal value of surface layer
resistivity.
Cs = 0.7832
tS = Duration of shock current in seconds = 0.5
( from clause 16.2.2 of IEEE Std 80-2000 )
Substituting the above values,
Tolerable Etouch50 = 934.97 Volts
b) Tolerable Estep50 = [(1000 + 6CS rS) 0.116/ ÖtS ] (from eq.29 of IEEE Std 80-2000)
r2 2 Lc k 1 Lc
R1 = ln + - k2 From eq.54 of IEEE Std 80-2000
p Lc a' A
Where,
r = Soil Resistivity in Ω-m 240 ohm-m
Lc = Total length of all connected grid conductors in m 2018 m
a
'
= a.2h for conductors buried at depth h in m 0.1300 m
2a = Diameter of conductor in m 0.0320 m
A = Area covered by conductors in m2 2800 m2
k1 = Coefficient from fig 25(a) of IEEE Std 80-2000 1.043
k2 = Coefficient from fig 25(b) of IEEE Std 80-2000 4.313
Coefficient K1 and k2 of schwarz's fromula IEEE Std 80-2000 )
R1 = 1.7334 Ω
Sheet 6 of 9
Ground resistance of the rod bed, R2
From eq.55 of IEEE Std 80-2000
r 4 LR 2 k1 . Lr
R2 = ln -1 + ( nR - 1 )2
2p nRLR b A
Where,
Lr = length of each rod in m 10 m
2b = diameter of rod in m 0.032 m
nR = number of rods placed in area A 177
LR = Total length of ground rods 1770
k1 = Coefficient from fig 25(a) of IEEE Std 80-2000 1.043
R2 = 0.017 Ω
Mutual ground resistance between the grid and the rod bed, Rm
From eq.56 of IEEE Std 80-2000
r 2 Lc k 1 Lc
Rm = ln + - k2 + 1
p Lc Lr A
Rm = 1.6068 Ω
Subtituting the above values,
Rg = 1.7443 Ω
IG = 18.9 KA
Substituting the values,
Since, GPR > Estep50 (as per Figure 33 of IEEE Std 80-2000),calculate Attainable Emesh and Attainable
Estep voltages
From Eq.80 of IEEE Std 80-2000, for Grid rods in the periphery,
Emesh = [ r Km Ki I G / LM ]
Lr
LM = Lc + 1.55+1.22 LR From eq.91 of IEEE Std 80-2000
Lx+Ly
2 2
Where,
Lr = Length of each ground rod = 10 m
Lx = Maximum length of grid conductor in x-direction = 70 m
Ly = Maximum length of grid conductor in y-direction = 40 m
Sheet 7 of 9
IG = grid current = 18.9
Ki = corrective Factor, = 3.85
LM = 5351.34 m
As per Eq.81 of IEEE Std 80-2000, the Spacing Factor for Mesh Voltage,
1 D2 (D + 2h)2 h Kii 8
Km = ln + - + ln
2p 16hd 8Dd 4d Kh p(2n-1)
Kh = 1.26
Where,
Lp = Peripheral length of the grid = 220 m
Dm = Maximum distance between any two points
on the grid = 80.6 m
Substituting the above values,
na = 21.27 nb = 1.020
nc = 1 nd = 1.00
= 3.85
Substituting the values,
Km = 0.1433
Sheet 8 of 9
2.6) Calculation of Attainable Estep voltage :
As per Eq.94 of IEEE Std 80-2000, the Spacing Factor for Step Voltage,
1 1 1 1
Ks = + + (1 - 0.5n-2) From eq.94of IEEE Std 80-2000
P 2h D+h D
Ks = 0.4955
Ls = 3259.5 m
3. CONCLUSION :
Tolerable
Etouch = 934.97 Volts
Attainable
Emesh = 473.07 Volts
Tolerable
Estep = 3247.72 Volts
Attainable
Estep = 2685.14 Volts
1) From the above results,it can be seen that the Attainable Emesh and Attainable Estep voltages are less
than the Tolerable Etouch and Tolerable Estep voltages.
2) The grid resistance is less than 1 ohm.
3) Hence the design value of conductor size and length of conductor are adiquate and safe.
4) Buried earth mat conductor size - 32MM Dia Ms rod