SPECIFICATION FOR
TABLE OF CONTENTS
1.0 SCOPE
4.1 General
4.2 Design Criteria
4.3 Materials
4.4 Fabrication
4.5 Marking
5.0 TESTS
The latest revisions of the following Codes and Standards shall be applicable
for the equipment/material covered in this SMSS. In case of conflict, the
vendor/manufacturer may propose equipment/material conforming to one
group of Industry Codes and Standards quoted hereunder without jeopardizing
the requirements of this SMSS.
4.1 General
4.2.2 The power cable, rated 115kV or 230kV shall be designed for
ambient temperature conditions specified in 01-SMSS-01.
4.3 Materials
4.3.1 Conductor
For 115 kV power cable, conductor sizes shall be 400, 630, 800,
1000 and 1200 mm².
Table-1
Conductor Size (mm²) Conductor Construction
400, 630, 800, 1000 Segmental or non-segmental
1000, 1200, 1500, 2000, 2500 Segmental
4.3.3 Insulation
4.4 Fabrication
4.4.2 The cross-linking process shall be by the dry cure dry cooling
method.
4.5 Marking
4.5.1 The jacket for all the cables shall be marked by embossing in
English at intervals not exceeding one meter with the following
minimum information:
5.0 TESTS
All tests results shall be provided for review and acceptance by SCECO-East.
5.1.1 For 115 kV power cable, routine and type tests per AEIC CS7
or IEC 60840 are acceptable. For 230 kV power cable, routine
and type tests shall be as per WG 21.03.
5.1.3 The completed reeled cable partial discharge test data shall be
submitted on a printout shut of an X-Y recorder showing the
partial discharge curve of each cable.
6.1 The cable ends shall be sealed with a waterproof, heat shrinkable
plastic or elastomeric end cap with adhesive type sealing compound.
Cable ends shall be properly secured to the reel.
6.2 The cable shall be delivered without splices, on standard sized non-
returnable steel drums of sturdy construction properly packed and
lagged externally to prevent the cable from possible damage to the
cable during transportation. Wood lagging shall be used and have a
minimum thickness of 50mm. The wood lagging shall also be secured
with steel straps to provide physical protection for the cables during
transit and during customary storage and handling operations.
6.3 The arbor hole for wooden reel shall be reinforced with galvanized steel
plates.
The minimum diameter of the drum of the shipping reel shall not be
less than the minimum bending diameter of the power cable.
REFERENCE
SECTION No DESCRIPTION 'A' 'B' 'C'
d. Maximum conductor
short circuit current
temperature, °C 250
e. Maximum permissible
continuous conductor
temperature, °C 90
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
f. Emergency Loading
• Maximum emergency
conductor loading temp.,°C 105
4.3.1 Conductor :
Material COPPER
No. of strands *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Diameter, mm *
Conductor AC resistance
at 20°C *
Conductor DC resistance
at 20°C *
Resistivity at 20°C *
Material SEMICON
Average thickness, mm
400mm² 0.64
800 to 1200mm² 0.76
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Minimum thickness, mm
400mm² 0.512
800 to 1200mm² 0.608
Conductor Moisture
Impervious layer
Material Semi-Conducting
Tape
Thickness *
4.3.3 Insulation:
SUPER CLEAN
Material XLPE
Average thickness, mm 20.32
Minimum thickness, mm 18.288
Diameter over insulation, mm *
Thermal resistivity, K.m/W *
Relative permittivity or
dielectric constant (ε) *
Loss factor (δ ) *
Specific Resistance, MΩ-km
(Actual Test Value) *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Material SEMICON
Average thickness, mm 1.75
Minimum thickness, mm 1.40
Diameter over insulation
shield, mm *
Thermal resistivity, K.m/W *
Maximum thickness, mm 2.29
Material
Total effective cross-
sectional area mm² *
Diameter over metallic shield, mm *
Temp. coefficient at 20°C,/°C *
DC resistance at 20°C, Ω/km *
AC resistance at 20°C, Ω/km *
Self inductance, mH/km *
AC resistance at 90°C *
DC resistance at 90°C *
Resistivity at 20°C *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.3.6
4.3.7 Jacket:
Material
(LLDPE or LMDPE?)
Average thickness, mm 3.95
Minimum thickness, mm 3.55
Overall cable diameter, mm *
Material *
Thickness, mm *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
6.0 PACKING
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
b. 3-phase inductance in
trefoil formation, mH/km *
c. 3 phase capacitance in
trefoil formation µF/km *
d. Maximum permissible
overload in % of 3 cables
in underground cable duct
trefoil formation, at 40°C
soil temperature, for
1/2/3 hours starting with
a prior loading of
50% *
75% *
100% *
Official Seal/Stamp
of the Company
REFERENCE
SECTION No DESCRIPTION 'A' 'B' 'C'
d. Maximum conductor
short circuit current
temperature, °C 250
e. Maximum permissible
continuous conductor
temperature, °C 90
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
f. Emergency Loading
• Maximum emergency
conductor loading temp.,°C 105
4.3.1 Conductor :
Material COPPER
No. of strands *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Diameter, mm *
Conductor DC resistance
at 20°C *
Conductor AC resistance
at 20°C *
Resistivity at 20°C *
Material SEMICON
Average thickness, mm 1.0
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Conductor Moisture
Impervious layer
Material Semi-Conducting
Tape
Thickness *
4.3.3 Insulation:
SUPER CLEAN
Material XLPE
Average thickness, mm 24.0
Minimum thickness, mm 21.6
Diameter over insulation, mm *
Thermal resistivity, K.m/W *
Relative permittivity or
dielectric constant (ε) *
Loss factor (δ ) *
Specific Resistance, MΩ-km
(Actual Test Value) *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Material SEMICON
Average thickness, mm 2.0
Minimum thickness, mm 1.6
Diameter over insulation
shield, mm *
Thermal resistivity, K.m/W *
Material
Total effective cross-
sectional area mm² *
AC resistance at 90°C *
DC resistance at 90°C *
Resistivity at 20°C *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.3.6
4.3.7 Jacket:
Material
(LLDPE or LMDPE?)
Average thickness, mm 3.95
Minimum thickness, mm 3.55
Overall cable diameter, mm *
Material *
Thickness, mm *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
6.0 PACKING
b. 3-phase inductance in
trefoil formation, mH/km *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
c. 3 phase capacitance in
trefoil formation µF/km *
d. Maximum permissible
overload in % of 3 cables
in underground cable duct
trefoil formation, at 40°C
soil temperature, for
1/2/3 hours starting with
a prior loading of
50% * / / / / / /
75% * / / / / / /
100% * / / / / / /
Official Seal/Stamp
of the Company