R3.0 Advisor Master Programming Guide EN
R3.0 Advisor Master Programming Guide EN
Programming Guide
Programming sequence 1
Basic set up 1
Advanced set up 2
1-Zone database 7
Zone number 7
Zone settings 7
2-Area database 29
Select the area to program 29
Area settings 29
3-RAS database 39
RAS to be polled 39
Select RAS to program 39
RAS settings 39
4-DGP database 48
DGPs to be polled 48
DGP settings 49
5-Alarm groups 50
Alarm group number 50
Alarm group settings 52
6-Timers 62
Timer settings 62
7-System options 70
Configuring system options 70
8-Auto reset 93
Auto reset settings 93
9-Communication options 94
Configuring communication options 94
11-Version 111
Select device 111
13-Timezones 113
Select timezone 114
Timezone settings 114
14-Defaults 116
Select default option 116
18-Vaults 129
30-Printer 148
Printer settings 148
55-Reserved 177
Reporting 182
Troubleshooting 195
ATS control panel - model ATS1000/2000/3000/4000/4500 195
LCD arming stations - models ATS1100, ATS1105 196
4 LED arming station - models ATS1150 and ATS1155 196
Data gathering panels - models ATS1201, ATS1210, ATS1211,
ATS1220 197
Serial printer interface - model ATS1802 198
Output devices - models ATS1810, ATS1811, ATS1820 198
Glossary 207
Index 211
Basic set up
The basic set up involves all settings to put an ATS control panel with the most
common programming in operation.
1. Draw the floor plan and label all zones, equipment, areas etc. Use
programming sheets to fill out all information.
2. Default the control panel (see Installation guide and Quick programming
guide). See also “14-Defaults” on page 116.
3. Change the Master Engineer Code using user menu 14, Program Users.
4. Set the correct time and date using user menu 15, Time and Date.
5. Program specific words that are not in the library using menu 10-Program
text.
6. If any automatic procedure (like auto arm/disarm) is required or users only
should have access during certain periods, program timezones using menu
13-Timezones.
7. Program the area options like Area Names and entry/exit times using menu 2-
Area database.
8. Set up the required alarm groups using menu 5-Alarm groups.
9. Program the RAS connected. First activate polling. Then program the
necessary detail for any specific RAS using menu 3-RAS database.
10. When DGP are connected, activate polling and set the DGP type using menu
4-DGP database.
11. Program the necessary zone details like zone type, zone name and reporting
options using menu 1-Zone database.
12. Program the dialler details using menu 9-Communication options.
13. Set the required reporting options using menu 42-Reporting class database.
14. Program the test call details using menu 43-Test calls.
15. Program users in user menu 14, Program Users.
16. Map any event to outputs as required using menu 16-Event to output.
2. Press Menu and enter 01278 (Master Engineer code), and then press Enter.
The following display appears:
Note: There is a prompt to apply EN 50131 default settings during the first
startup. See “First startup” on page 6 for more details.
3. Press 19 and Enter.
The following display appears:
Simple/Advanced Menu
*-Advanced
4. Press Enter to access the Simple Menu (or press * to access the Advanced
Menu).
The following display appears:
Installer Programming
0-Exit, Menu:
You can now select the menu option you want to program. See “Programming
map” on page 220 for the programming map that lists all the menu options
available in the Programming menu.
Enter or # These keys have the same function. [#] is used on LED keypads
or 40 character LCD keypad (ATS115x or ATS112x).
Menu or * These keys have the same meaning. [*] is used on LED keypads
or 40 character LCD keypads (ATS115x or ATS112x).
How to program
The method of programming depends on the options to be programmed. Some
options require a value, others require a Yes/No setting.
First startup
During the first startup of the panel, after the installer enters the programming
menu, he is prompted to apply EN 50131 default settings.
Siren calibration
For EN 50131 regulation compliance the system must provide monitoring for
sirens and strobes. This monitoring is only possible after siren calibration.
The installer must perform siren calibration manually from keypad using
programming menu “56-Siren calibration” (see Adviros Master Programming
Guide for more details).
In this programming section all parameters are programmed regarding the zones.
Each zone is a physical input on the control panel, a DGP or a plug-in expander.
Zone number
Select the appropriate zone number to program. Every zone has a number
between 1 and 256, depending on the location in the system.
Note: A list of zone numbers can be found with the Advisor Master Installation
Guide.
Zone settings
Zone type
The zone type determines exactly how the zone will function in given
circumstances. Each zone type will behave differently. Most zone types require
an area, but zone types that affect the status of areas (zone types 6, 31, 34, 35)
need alarm groups.
Caution: The zone type is important and influences much of the remaining
programming and functions of the system. Consequently, you must take
considerable care when programming zone types.
Armed or disarmed
Armed or disarmed apply to the status of an area. If an area is armed, certain
zone types will go into alarm when the zone is activated. Other zone types only
go into alarm when the area is disarmed.
Tamper alarms
When the dual zone option (see “7-System options”, page 70) is set to Yes, a
short or open circuit on most zone types will generate a tamper alarm. If set to
No, an open or short circuit is the same as an activated zone.
Zone types that are not used to generate alarms do not generate tamper alarms,
e.g. technical or camera zone types.
Entry/exit times
Where entry/exit times are referred to, the time used is the longest entry/exit time
programmed for any of the areas assigned to the zone.
Zone name
Once the correct zone number is selected, the zone needs to be given a name.
The name identifies the zone to the end-user in case an alarm has occurred or
on arming the zone is still activated. Without a proper name, the end-user would
not be able to check for any problems that might arise in a particular zone.
A zone name can consist of 4 words from the library (called text words), each
separated by a 3 digit number between 1 and 255 (called a text variable). If a
number is not necessary, program the number as 0. This way the number will not
be used and the text words are combined using a space. Text variables can only
be used in combination with a text word. The complete name can have a
maximum length of 36 characters.
Zone names are taken from the library. The library contains a maximum of 900
words. Each word is identified as a number. This number has to be entered on
programming the zone name (see Table 9 on page 105). If a word does not exist,
it can be added in the programmable library, using menu 10-Program text (see
page 103). The programmable library can contain 100 words that have to be
programmed before they can be used.
Examples:
• Office 4 Door 1 Contact
• Office 4 Door 2 Contact
• Building 6 Area 4 Room 1 Door 6
• Building 6 Area 4 Door Right
Reporting of zone
Select the alarm to be reported if the zone generates an alarm. The event is
selected from the class database and the subclasses. The actual message that is
transmitted depends on the chosen protocol and the selected class and sub-
class. The class holds the basic reporting range (medical, fire, panic). The sub-
class is used to provide differentiation in the event being reported. E.g. The panic
class holds Contact ID codes 120 to 122 or SIA events PA and HA. See Table 14
on page 182.
See “9-Communication options” (page 94), “42-Reporting class database”
(page 164), and “Reporting” on page 182.
Report alarm to CS 1
YES-Report To CS1
*-Change 0-Skip
Report alarm to CS 2
See “Report alarm to CS 1”.
Report alarm to CS 3
See “Report alarm to CS 1”.
Report alarm to CS 4
See “Report alarm to CS 1”.
When Yes is selected, this zone allows for audio listen in on alarm.
Yes: Audio Listen in enabled for this zone.
No: No Audio Listen in.
Select Yes to enable engineer reset for alarm in this zone. The user can not arm
the area the zone belongs to, until an engineer reset has been performed.
Yes: Engineer reset enabled for alarms in this zone.
No: No engineer reset.
Select Yes to enable engineer reset for alarm in this zone. The user can not arm
the area the zone belongs to, until an engineer reset has been performed.
Yes: Engineer reset enabled for tamper alarms in this zone.
No: No engineer reset.
Disable inhibit
NO – Disable Inhibit
*-Change 0-Skip
This new option enables the input into soak test mode. The soak period is started
when a zone input is set to ‘soak test’. The period of the soak test is set via menu
Soak test days on page 83 from 0 to 255 days. If the Soak Test days value is set
to 0 then the soak test period is infinite and must be disabled by the user. If an
input is in soak test mode, it does not:
• report to central station
• activate siren
• activate strobe
• activate any outputs
But the change of state is logged in the history file with the new events “soak
alarm” and “soak alarm restore”. If the zone input does not alarm during the soak
test period, the Enable Soak Test option in that zone input’s database will be
reset when the soak test period has elapsed. The soak period is extended by the
Soak Test days period again if the zone input alarms during the soak test period.
The default is set to No.
Area
The zone needs an area to be able to send alarm information to an area and a
central station and to be able to reset when an alarm occurs. Assign the area to
the zone that has to alarm when the zone is activated and the area status (armed
or disarmed) meets the requirement for the zone type.
The function of the zone depends on the zone type selected during
programming.
Common area
Common areas have zones that should only go into alarm when all areas are
armed. E.g. the frontdoor in a building provides an entry to 2 areas, thus the
frontdoor needs to be a common area.
There are two ways to create zones in a common area. The first way is to assign
more then one area to a zone. That way the zone can only go into alarm if all
areas meet the ondition (armed or disarmed). The zone is disarmed if one area is
disarmed. In this option, the longest entry and exit time is used.
The other way to create a common area is to use area linking (see “19-Area
linking”, page 130). Here the common area is an additional area that
automatically arms as soon as the linked areas are armed. The common area
can be disarmed separately and has its own entry and exit times.
Alarm group
Alarm groups are assigned to zones that perform alarm control. It is only
available for zone types 6, 31, 34, and 35.
The function of the alarm group depends on the zone type selected during
programming. These zone types are used for key switches etc. to arm/disarm
areas (i.e. causes the zone to act like a user entering an alarm control code).
Note: Before Alarm Groups can be assigned, they have to be programmed in “5-
Alarm groups” (page 50).
Test option
Use this record to select the automatic testing procedures of each zone. The
zone testing is done via the Disarm test and the Arm test. However, you can still
manually test zones.
There are five test procedure options, each identified by a reference number.
This reference number is used to program a testing procedure. See Table 4
below for a description of each test type.
Notes
• This record is invalid unless the test mode is correctly programmed in the “7-
System options” (see page 70).
• During the arm test, the testing event flag (event flag 16) will be activated
during half the “Testing event flag” time (see “6-Timers”, page 62). Use this
event flag to activate devices to generate alarms, for example when using
vault sensors. The other half is used for the device to switch back to normal
state.
You can program event flags that are activated by a zone. Up to 15 event flags
can be assigned to an individual zone.
An event flag is activated when the zone is in alarm (except for the zone event
flag). The circumstances that cause a zone to generate an alarm depend on the
zone type. The event flags activated by an alarm depend on:
• Which event flags have been assigned to the zone.
• Whether the active time of the event flags corresponds with the alarm time.
Event flags can be active:
- 24 hours
- When disarmed only (when one or more of the areas assigned to the zone is
disarmed)
- When armed only (when all the areas assigned to the zone are armed)
• Whether the option “Make all events 24 hour” on page 24 has been set to
Yes. If so, the active period is 24 hours for all event flags.
Select if the internal siren event flag should be activated. The Internal siren event
flag is assigned in the Area database.
Yes: The Internal siren event flag specified in the area database is activated
when the zone generates an alarm, and all the areas assigned to the zone are
armed.
No: The Internal siren event flag will not be triggered by an alarm in this zone.
Note: For the Internal siren event flag to operate, you must also program the
Internal siren event flag number in the area database for each of the areas that
activate internal sirens and that are assigned to the zone. Refer to “2-Area
database” on page 29. See also “Zone event flag” on page 22.
Select if the external siren event flag should be activated. The External siren
event flag is assigned in the Area database.
Yes: The External siren event flag specified in the area database is activated
when the zone generates an alarm, and all the areas assigned to the zone are
armed.
No: The External siren event flag will not be triggered by an alarm in this zone.
Note: For the External siren event flag to operate, you must also program the
External siren event flag number in the area database for each of the areas that
activate internal sirens and that are assigned to the zone. Refer to “2-Area
database” on page 29.
NO – Keypad Buzzer
*-Change 0-Skip
Yes: Event flag 2 is triggered when the zone generates an alarm and the area is
armed.
No: Event flag 2 will not be triggered.
See also “Zone event flag” (page 22).
Yes: Event flag 6 is triggered if the zone generates an alarm and any area
assigned to the zone is disarmed.
No: Event flag 6 is not triggered.
See also “Zone event flag” (page 22).
Trigger EF 8, 24 hr alarm
Yes: Event flag 8 is triggered if the zone generates an alarm, regardless of the
status of the area(s) assigned to the zone.
No: Event flag will not be triggered.
See also “Zone event flag” (page 22).
Yes: The zone event flag is triggered when the zone is active, regardless of the
status of the area(s) assigned to the zone.
No: The zone event flag is only triggered when the zone generates an alarm.
See also “Zone event flag” (page 22).
Yes: The chime/camera event flag programmed in the area database is activated
whenever the zone generates an alarm and the area is disarmed.
No: Chime/camera event flag will not be triggered.
Note: If the chime/camera event flag is to operate, you must also program the
chime/camera event flag number in the area database for each of the areas that
have cameras and that are assigned to the zone. Refer to “Chime/camera event
flag” on page 32.
To activate the camera event flag when the area is armed, set “Make all events
24 hour” on page 24 to Yes.
If enabled in System Options > “Enable chime” on page 87, the event flag will
become and react as a Zone Chime event flag. During the areas disarmed period
the chime event flag is set each time a zone, enabled for chime, changes from
normal (4K7) to active (9K4). The flag will remain set for the time (1 to 255
seconds) programmed in Timers > “Chime time is set to” on page 68.
The chime function works with the following zone types:
Type Description
2 Armed Alarm
13 Entry Exit no arm check
14 Access no arm check
28 Armed alarm with auto-reset
60 Exit terminator
66 Final door set
68 Anti-mask detector
Notes
• To activate the camera event flag when the area is armed, set Make all
events 24 hour to YES.
• When set to YES, the Siren Event flag will be ignored to have silent alarms
(Panic or Hold-up alarm).
See also “Zone event flag” (page 22).
Double Knock
NO – Double Knock
*-Change 0-Skip
Yes: This zone will be configured for double knock activation in a certain time
interval
No: Zone will not be configured for double knock functionality
If set to Yes and a zone becomes active, at the point where the alarm condition
will normally be activated, two zone timers shall be triggered. An interval timer is
preset with the value contained in “Double knock interval (min)” on page 67, and
begins counting downwards. A second timer (duration) is preset with the value
contained in “Double knock duration (sec)” on page 67, and also counts
downwards.
Notes
• Only the following zone types are applicable:
- 1: disarmed alarm
- 2: armed alarm
- 4: access alarm
- 14: access alarm (no arm check)
• Default is No.
When this option is set to Yes, the lower alarm window, nominally 2,35 kΩ, is
monitored for a detector masked condition.
Area settings
Area name
Exit time
Every area has its own exit timers. Exit timers allow users that arm an area, to
leave the premises without generating an alarm (using access or entry/exit
zones). Only after the exit timers have expired, an alarm can occur.
Each area can be programmed with one exit time. The exit times apply to zone
types 3, 4, 13, 14, 41, and 42 (all entry/exit or access). The entry time however
can only be started with zone types 3, 13, 41, and 42 (entry/exit).
Behind the area number, a number and an ‘I’ or ‘O’ can show up, in case an
entry (I) or exit (O) time is running. The number indicates the seconds left to
leave the area.
The exit timers can be programmed from 0 to 255 seconds.
Entry time
Every area has its own entry timers. When entering the premises via a entry/exit
zone, the entry time starts. A user can disarm the area while the entry time is
running without generating an alarm.
Each area can be programmed with one entry time. The entry times apply to
zone types 3, 4, 13, 14, 41, and 42 (all entry/exit or access). The entry time
however can only be started with zone types 3, 13, 41, and 42 (entry/exit).
Behind the area number, a number and an ‘I’ or ‘O’ can show up, in case an
entry (I) or exit (O) time is running. The number indicates the seconds left to
leave the area.
The entry timers can be programmed from 0 to 255 seconds.
Note: If zones are assigned to more then one area, the longest entry and exit
time is used. See “1-Zone database” on page 7.
Areas are capable of triggering event flags. Different from event flags in the zone
database, these event flags are triggered by an area event, not from a particular
zone event.
The External siren event flag is triggered if any zone with the External Siren
Event flag set to Yes generates an alarm. Each area can have its own external
siren, using different event flags for each area. See “Event Flags” on page 179.
The Internal siren event flag is triggered if any zone with the Internal Siren Event
flag set to Yes generates an alarm. Each area can have its own internal siren,
using different event flags for each area. See “Event Flags” on page 179.
Note: The default value for this option is 13.
Used to indicate if any zone in the area is active, excluding zones that can be
used to change the status of an area, that are used for camera’s or that are of
zone type Unused.
See also “External siren event flag” on page 30.
Activates on local alarms from firedoor and 24 hr local fail zone types in the area.
See also “External siren event flag” on page 30.
Activates on zone types 15, 16, 18, 21, 30, 41, 42, 44 and 56. See “1-Zone
database”, Table 3 (page 8) for more information.
Activates when a zone with the chime/camera event flag set to Yes generates an
alarm and the area is disarmed. Used to control chime or cameras. The camera
event flag can be reset by pressing Enter, Enter, 0, Enter.
Note: To activate the chime/camera event flag when the area is disarmed, see
“Make all events 24 hour” (page 24) and Trigger chime/camera (page 26).
See also “External siren event flag” on page 30.
For more information on the chime functionality, see “Enable chime” in System
Options on page 87.
Indicates that a delayed disarmed alarm zone is active and the delay time is
running. Used to provide visual indication of a possible alarm.
See also “External siren event flag” on page 30.
This event flag forces the user to test the detectors before the area can be
armed. If an attempt to arm an area that has the anti-mask event flag set to a
non-zero value and any inputs associated with this area are active, the event flag
is set for 30 minutes. The anti-mask reset event flag is active for the duration of
the timer and is reset when either the timer time elapses or the area is
successfully armed.
It is used with PIR detectors with an anti-mask feature. An output is assigned to
the anti-mask reset event flag which is wired to the detectors. When this output is
activated, the detectors must be triggered by a walk test in order for them to
become normal after the output is de-activated (after 30 minutes).
Note: There are no anti-mask reset event flags set in the area default settings.
This event flag is triggered when two valid disarm codes are entered for an area
within 5 minutes and the area is disarmed. The event flag is set for five seconds.
For a further 4 seconds, the zone input type 67 (Latched Detector) associated
with that area are disabled (The zones are disabled for a total of 9 seconds). The
zone input type 67 is a 24 hour alarm, conditional inhibit, conditional on the
abovementioned 9 second (total) timer. It is used to reset latching fire detectors.
Used to generate an event linkable to a relay output to primarily support the Red
Care communications unit in the UK. This event flag follows the ‘A’ event
generated by the AB alarms as sent to the central station event out queue.
Used to generate an event linkable to a relay output to primarily support the Red
Care communications unit in the UK. This event flag follows the ‘A’ event
generated by the AB alarms as sent to the central station event out queue.
Used to generate a report if the area is disarmed while the area should be
armed. The message is reported depending on the type of transmission protocol.
When using alarm group restrictions, one of the options available is to disarm an
area for a disarmed period. If the Area Disarmed time is not ‘0’, then this time will
be used. See 15-Alarm group restrictions on page 118.
Note: If the Disarmed time for the Alarm group Restriction is set to 0, to specify
that the area will not re-arm, the "Area Disarmed Time" does apply for that area
(see 6-Timers on page 62 for more information).
When audio listen in has to be enabled for this area on opening, closing or if
accessed after hours, use this option.
Yes: Audio Listen in enabled for this area.
No: Adio Listen in disabled.
Exit faults occur when an access zone or exit zone is still open at the moment the
exit time expires. On an exit fault a local alarm is generated and a special Exit
Fault is reported to the central station.
Yes: Enable exit fault reporting.
No: No exit fault reporting.
When arming an area should not be possible if all zones within the area are
inhibited, set this menu to Yes.
Yes: No arming available if all zones in the area are inhibited.
No: Arming is available when all zones in the area are inhibited.
Extends the exit time. Immediately after the exit timer expires, the KeyBox timer
starts for a duration of N minutes. Close the zone before this additional KeyBox
timer expires. If it is not closed, a full alarm will be triggered again even if the
previous trigger was also an alarm. During exit timer + KeyBox timer, openings
and closings will not be registered and will not cause an alarm.
This event flag becomes active whenever a tamper alarm is detected on an input
associated with the specific area, and is independent of arming state.
When an event occurs requiring text to be displayed on the user interface during
the disarmed state, the alert indicator activates.
An event flag corresponding to the state of the PA Area Alarm Timer running
state (one per area).
If set to Yes, Part Set arming uses the programmed exit time. If an exit terminator
(zone type 60) is programmed for the area and the Full Set exit time is zero, the
exit time is 20 seconds.
Yes: Buzzer will sound for the Part Set arming exit time.
No: Buzzer will not sound for the Part Set arming exit time.
Note: If the set to NO, although there is no exit buzzer, the exit time is still
retained.
If set to Yes, the operation of any access zone in the Part Set area is change to
operate as an entry exit zone. The purpose of this is to allow access to the
disarming keypad when it is in the view of an access detection zone (PIR).
Example: A residential property with an external entry exit door leading to a hall
in which the arming/disarming keypad is fitted, and is in the view of an access
PIR detector. For Full Set disarming the normal entry will be; to activate the entry
(exit) zone first starting the entry time and inhibiting the access zone; so when
accessing the hall area to disarm, the access zone does not activate the alarm.
Note: This menu is only applicable if Part Set reporting is set to Yes.
Yes: Alarm confirmation (BV) reporting is disabled when Part Set armed. First
alarm report type (BA) is reported for all intruder alarms The B confirmed alarm
event flag and the ‘Engineer reset on B alarm’ are also disabled.
No: Normal Alarm confirmed reporting for Part Set.
Chime on RAS
Chime on RAS: 0
0=NO RAS
Select a RAS address number to sound its buzzer when an area’s chime event
occurs.
• 0: no RAS selected, RAS buzzers will not be activated.
• 1 to 16: RAS 1 to 16. The selected RAS address will activate its buzzer for
the duration of the chime event.
Only one RAS address may be selected in this menu. If all RAS buzzers are to
activate, allocate the Chime event flag number to System Flags Keypad buzzers.
For more information see System Options > “Enable chime” on page 87.
RAS to be polled
1, 2, 3: 4
Poll RAS:
Each arming station has to be polled, in order to be used. Add RAS’s for polling
by entering the dipswitch address it has been given. RAS’s that do not have to be
polled can be deleted by entering the dipswitch address again.
Display shows the RAS’s currently recorded. A RAS number followed by a “,” is
online and followed by a “:” is offline (can not be addressed by the system).
Note: A RAS or DGP being online means it will generate RAS/DGP system
alarms and tamper alarms. When offline, system alarms and tampers will not
occur.
Once the RAS’s have been selected for polling and Enter has been pressed, the
RAS’s can be programmed.
RAS settings
Area alarm group
You need to define an alarm group to state which areas can be controlled from
this RAS.
Note: Only options which are both in the RAS’s alarm group and the users alarm
group can be performed on any RAS.
See menu 5-Alarm groups on page 50 for further information on how alarm
groups operate.
The menu alarm group determines which actions are allowed on a RAS. If no
alarm control is allowed, this can be achieved in the menu alarm group. The
menu alarm group can also have more areas than the area alarm group. The
user can have no alarm control over those areas, but can for example see the
status of zones in these areas.
If the menu alarm group is programmed for alarm group1 - No Access, then the
arming station will use the area alarm group as menu alarm group.
If a door has to be unlocked using the RAS, enter the event flag here. The event
flag can be assigned to an output and will be activated when a valid code is
entered at the arming station.
What is recognised as a valid code for unlocking the door depends on the setting
in “Enter key opens door only” on page 42, and “Alarm code prefix” on page 72.
When the event flag in the above option is active, the effective RAS chime is
activated for duration specified in “Chime time is set to” (programmable from
timer database on page 68). The event flag can be activated by a zone, area,
macro, etc.
Note: The chime must be enabled. See “Enable chime” on page 47.
Keypads with card reader interfaces have an output OUT. To be able to control
the output, an output control group has to be assigned to the RAS. The first
output on the output controller is also the OUT output from the RAS. Whenever
the first output is activated, the OUT output is also activated.
The output control group entered here does not need to be physically available.
Note: If two RAS’s have the same output control group and the user has both
doors in his doorgroup, both relays will be switched simultaneously.
Yes: This arming station is a LCD arming station. This has to be set in order to
be able to operate LCD arming stations.
No: This is not a LCD arming station.
See Table 5 on page 41 for further information on options available to arming
stations.
Legend:
Y Must be set to Yes
N Must be set to No
O Optional
[1] The "Toggles area status" option is NOT recommended
[2] CAUTION! If a LCD arming station is used as master; and "Arm Using One Key" is set to
Yes; the system must be programmed so that areas 9 to 16 can never be armed
Toggle area status provides users with an option to have arm control on keypads
combined with readers.
Yes: The On and Off keys have lost their function. For arm control one needs to
enter the user code followed by On, Off or Enter. If a list of areas appears,
pressing the area number and Enter toggles the status of the area. If no list is
available, the status of the area(s) is toggled immediately.
No: Normal alarm control.
Yes: When using LCD arming stations, using the On and Off key for alarm
control results in a clearer user interface. It also provides an option to use the
Enter key for opening a door with a keypad.
No: The Enter key unlocks the door, but also provides alarm control and resets
alarms.
See Table 5 on page 41 for further information on options available to arming
stations.
Note: Set this option to Yes for the best user interface on LCD arming stations.
Yes: If user codes with alarm control and door groups perform alarm control, the
door will unlock.
No: User codes with alarm control will not unlock doors.
See Table 5 on page 41 for further information on options available to arming
stations.
Note: The user needs to have alarm control and a door group.
Yes: When a zone is shunted, the text ‘Zone shunted,’ will appear on the display.
No: Nothing is shown when a zone is shunted.
See Table 5 on page 41 for further information on options available to arming
stations.
Yes: Provides an option to arm or disarm areas by pressing the number of the
area without Enter, after having entered the user code.
No: Normal alarm control.
Note: This option is only available for areas 1-8.
See Table 5 on page 41 for further information on options available to arming
stations.
Yes: Allows cards to disarm areas without using the Off key.
No: Only the door is unlocked, except if “Card always arms/disarms” below is set
to Yes or the On/Off key is used.
See Table 5 on page 41 for further information on options available to arming
stations.
Yes: Allows cards to arm/disarm areas without using the On/Off keys. Also
“Toggle Area status” on page 41 has to be set to Yes.
No: Normal alarm control.
See Table 5 on page 41 for further information on options available to arming
stations.
Note: The card user's alarm group and the arming station's (reader's) alarm
group must both allow arm and/or disarm functions before a card can be used to
arm/disarm.
Yes: Allows users to reset alarms by pressing Enter, Enter (show alarms)
followed by 0, Enter. The areas in alarm have to be assigned to the arming
stations alarm group.
No: Reset only with user code.
See Table 5 on page 41 for further information on options available to arming
stations.
Yes: Users with alarm group restrictions can only disarm or delay automatic
arming. It cannot be used for alarm group restrictions with arm and reset.
No: There is no restriction.
See Table 5 on page 41 for further information on options available to arming
stations.
Entry/exit buzzers
NO – Timed Lockout
*-Change 0-Skip
When a wrong code has been entered 10 times, the RAS access is blocked for
90 seconds.
After a correct code with the proper authorisation in the alarm group (Alarm
system control) has been entered, the code tamper event flag will reset.
Yes: On a code tamper, the RAS locks out for time defined in “RAS lockout time”
on page 68.
No: Only event is reported. The RAS is available.
This is an added option to arm an assigned area. When set to Yes, 3 badges of a
valid card will arm the assigned area(s).
Notes
• The 3 badges must occur within 10 seconds. If not, they will not be
recognised for arming.
• The default is set to No.
This option disables the optical indicators on the BUS device card readers. The
option to enable or disable the status LED's will have to be set by the user
because not all non-LCD BUS devices are card readers therefore this option will
have to be set based on the hardware connected.
If this option is set to Yes, the panel, when polling / commanding the card reader
RAS, it will not set any of the LED bits in the packet. This will result in the LED's
not being active.
Note: Limitation: Certain card reader settings override the status of command
packet LED bits - i.e. LED's remain illuminated even though LED bits are
disabled. In order to use this feature, it may be necessary to alter card reader
configurations.
Altering card reader configurations:
• For the ATS1170 Smart Door Controller:
- Menu 5 - Led 1 Options: Led 1: Door Unlocked Only
• For the ATS1190 Smart Card Reader:
- Menu 1-Leds On-Line: 1-Blue Led: Door Open Only
- Menu 3-Valid Card Flash: Flash Disabled
- Menu 4-Night Light: Night Light Disabled
3 LED RAS
NO – 3 LED RAS
*-Change 0-Skip
Yes: Both card and PIN are required to disarm the system.
No: The system will disarm with card or PIN
The panel is not currently able to discriminate if an ATS1190/92 or ATS1151/56
type RAS is in use by polling the device.
Notes
• The default is set to No.
• See also “RAS card & PIN timeout” on page 67.
When a wrong code has been entered 10 times the RAS access will be blocked
for 90 seconds. At the same moment the event flag “Code tamper” will be
triggered.
See also “Timed lockout by wrong codes” on page 44.
Enable chime
YES-Enable Chime
*-Change 0-Skip
The RAS chime is triggered by any of the following input: Event flag, Zone
activation, Zone shunting, Keys sequence. The chime is only activated on the
RAS that has chime option enabled.
For more information, see System Options > “Enable chime” on page 87.
If the Timed Lockout by Wrong Badges option is set to Yes, 10 wrong badges will
cause a RAS lockout as well as wrong codes.
See also “Timed lockout by wrong codes” on page 44.
DGPs to be polled
1, 2, 3: 4
Poll DGP:
Each DGP has to be polled, in order to be able to exchange data with the ATS
control panel. Add DGP’s for polling by entering the dipswitch address it has
been given. DGP’s that do not have to be polled can be deleted by entering the
dipswitch address again.
The display shows the DGP’s currently recorded. A DGP number followed by a
“,” is online (available) and followed by a “:” is offline (can not be addressed by
the system).
Note: A RAS or DGP being online means it will generate RAS/DGP system
alarms and tamper alarms. When offline, system alarms and tampers will not
occur.
Once the DGP’s to be polled have been programmed and Enter has been
pressed, the DGP to be programmed has to be entered before going further.
Note: The four-door/four-lift DGP’s (ATS1250/ATS1260) must not be addressed
higher than Address 12.
Removing a DGP from the polling list clears all alarms for zones and system
points for that DGP address. If the next DGP address number is not polled,
alarms on any of the 32 zones that belong to the DGP are cleared.
For further information on addresses and numbering, refer to “Zones and Outputs
allocated to DGP’s” (see Advisor Master Installation Guide).
Standard
Type:
The type of DGP being polled has to be programmed. The available DGP types
are:
Caution: You must be extremely careful when changing alarm groups. Both the
functions performed by users in that alarm group, and the functions available at
remote arming stations and door readers with that alarm group, are affected.
Every alarm group must be numbered. They are numbered from 1 to 138.
Alarm groups 14 to 29 are for individual areas. The areas assigned to the alarm
groups are as follows:
Every alarm group can be programmed with a name to identify the alarm group.
The words are selected from a list already held by the ATS system. They can be
either from the list of standard words available (see Table 9 on page 105), or
from a list of words that you have programmed yourself (see “10-Program text”
on page 103).
The display shows the current alarm group name, preceded by its reference
number).
Areas assigned
1,2,3,5,7,8,9,
Area:
Assign the areas to be controlled by the alarm group. An alarm group can only
control the functions of areas that are assigned to it.
Define if the alarm group can be assigned to users, or only to zones and RAS’s.
Yes: This alarm group can be assigned to users. The group is displayed in the
list of alarm groups when creating a user in user menu 14-Users. This option is
not set for alternate user alarm groups.
No: This alarm group is for a zone, door or RAS.
Press 0 to go to the user menu items available.
Note: An alarm group is only displayed in User Codes when the user who is
creating a new user has at least the same options (includes check of alternate
alarm group). A user cannot create a code for another user who has higher
security clearance.
This record lets you assign alarm system control functions to a user, door or
RAS. Only when alarm system control is enabled can users arm or disarm areas
in the alarm group.
List of areas
Select whether the areas assigned to a user are displayed during the arm/disarm
procedures.
Yes: After the user has entered a PIN and pressed On or Off, the areas assigned
to the user are displayed. The user can then select from the arm/disarm options
(e.g., specific areas, all areas, etc.).
This feature is useful when a user can control several areas but usually only
arms/disarms specific areas.
No: The areas assigned to the user are not displayed. Areas are immediately
armed/disarmed once the user has entered a PIN and pressed On or Off.
Press 0 to go to the user menu items available.
Keypad duress
This record allows the alarm group to reset latching system alarms. System
alarms are conditions, such as DGP tamper, siren fail, low battery, report fail, etc.
Yes: A user with this alarm group can reset the latching system alarms.
No: A user cannot reset latching system alarms.
Press 0 to go to the user menu items available.
Disable auto-uninhibit
NO – Disable Auto-Uninhibit
*-Change 0-Skip:
Determines that inhibited zones are uninhibited on disarming the area the zone
belongs to.
Yes: Disarming the area will not automatically uninhibit zones in the area. Used
for cleaners, etc.
No: Disarming the area will automatically uninhibit zones.
Press 0 to go to the user menu items available.
Note: “Auto uninhibit on disarm” on page 73 in “7-System options” has to be set
to Yes.
Disarm only
Prevents disarming when there are active zones. It is used when there are
Disarmed Alarm zone types such as type 1 and type 11 in the system.
Yes: Area(s) cannot be disarmed if there are active zones of type I or II
No: Area(s) can be disarmed even if there are active zones of type I or II
Press 0 to go to the user menu items available.
Prevents the alarm group restriction timer to arm the areas if a user without
restriction has disarmed the areas.
Yes: If an area has been disarmed and there is no alarm group restriction timer
running, an alarm group restriction timer cannot be started.
When an alarm group restriction timer expires, it arms the area. By setting this
option you prevent an area from being armed if a user without alarm group
restriction originally has disarmed it.
No: Normal alarm group restrictions apply.
Press 0 to go to timezone.
Allows the user (if he has access to Menu 14- program users) to change his own
PIN. All other menus of Delete, Display and Create will be absent. The user
cannot see nor display even his own Alarm Group, Door Group, Floor Group or
User name.
Yes: The user can change his own PIN.
No: The user can change the PINs of other users and can access the Menu 14
menus of Delete, Display and Create.
If the “Change own PIN only” option is set to Yes and if the system option
“Disable code from displaying” on page 76 is set to No, then the display will show
the following, if 1111 is the actual PIN.
Followed by entering:
The user can change the code again, or press Enter to exit.
If the “Change own PIN only” option is set to Yes and if the System Option
“Disable code from displaying” is set to Yes, then the display will show the
following:
The user can then enter his new PIN and will be asked to confirm.
The user can change the code again, or press Enter to exit.
YES-1-Panel Status
*-Change 0-Skip:
Determines if the user menu item is available in this alarm group to users or
RAS’s.
Each user menu is displayed and must be set to Yes for it to be available to the
alarm group. The user menus available for selection are:
See the Advisor Master Manager’s Manual for further information on each option.
Press 0 to go to timezone.
Timezone
Alm-Grp 14 Timezone 4
Timezone:
Determines the timezone that applies to this alarm group. The alarm group is
only available if the timezone is valid.
You can program each alarm group to have an alternate alarm group. The
alternate alarm group is used whenever the original alarm group is disabled due
to an invalid timezone. The alternate alarm group can have other areas or menus
as the original alarm group.
Example: During normal working hours, users can arm and disarm from a list.
After hours, only arm/alarm reset is allowed without presenting a list of areas.
Notes
• The alternate alarm group can also be programmed with an alternate alarm
group and so on - up to three alarm groups (the original plus two alternates).
If a function is denied by the timezone of one alarm group, the next will be
checked, etc.
• When alternate alarm groups are active and these have alarm group
restrictions, the alternate alarm group restrictions apply. See also 15-Alarm
group restrictions on page 118.
User level
A read-only option User level allows you to discriminate between the user access
levels. The following values are available:
• Disabled (standard ATS panel user - has no overriding capability)
• Level 2 user
• Level 3 user
Items that prevent setting but may be overridden by the Grade 2 level 2 user:
• Detector masked
• Detector fault
• AC mains fail (this includes any DGP)
• Battery low or missing (this includes any DGP)
• All signalling paths in fault
• All warning devices and all signalling paths in fault
Items that prevent setting but may be overridden by the Grade 2 level 3 user:
• Detector masked
• Detector fault
• AC mains fail (this includes any DGP)
• Battery low or missing (this includes any DGP)
• All signalling paths in fault
When programmed to YES, the user associated with this alarm group (regardless
of user level or the panel security grade) is able to override the Line Fault
condition where all communication paths have failed. If the condition is
overridden, the action will be logged to the history database.
Timer settings
AG restriction 1 disarmed time
You need to program the individual times (from 0 to 255 minutes) for each alarm
group restriction 1 to 7 for the time it is disarmed. The alarm group restriction has
to be programmed for timed disarm and be assigned to an alarm group.
Notes
• If set to 0, the area(s) will not re-arm automatically. See “15-Alarm group
restrictions” on page 118 for more information.
• The alarm group restriction time will be over-ridden by the “Area disarmed
time” on page 34 (if programmed) in the Area database.
After the disarmed time has expired, not only the area(s) are armed, but also an
emergency alarm will be sent to the central station.
See “AG restriction 1 disarmed time” on page 62 and “15-Alarm group
restrictions” on page 118.
The disarmed time for alarm group restriction 8 does not have any significance,
because the system ignores any values entered here. Alarm group restriction 8,
when used counts every user disarming and arming again. The timer is internally
set to 0.
See “15-Alarm group restrictions” on page 118.
Determines the test time available to perform the disarm test (0 to 255 minutes).
See “7-System options” on page 70, and “1-Zone database” on page 7 for more
information on testing zones.
Determines the test time available to perform the arm test (0 to 255 minutes).
Warning time
When alarm group restrictions are used and areas are programmed for timed
disarm, a warning will sound (if a warning time is programmed) indicating the
areas are about to arm. The duration this warning will sound is programmed in
this menu (0 to 255 minutes)
When a warning time is set, an audible alert is provided for the warning period
preceding the expiry. It MUST always be shorter than the shortest alarm group
restriction time.
Determines the delay time (0 to 255 seconds) before an alarm from a delayed
disarmed alarm is reported to the central station. The delay time is ignored if
another delayed zone type has already been activated.
Note: The delay is available for zone types 8, 11, 22 and 40. See “1-Zone
database” on page 7 for more information.
Suspicion time
The suspicion time is the length of time that a camera continues to operate after
a suspicion zone type has switched to normal state. The zone types that use this
record are 7, 40, and 47.
The suspicion time is available for zone types 7, 40 and 47. See “1-Zone
database” on page 7 for more information.
User menu 17 can be used to give access to service technicians. The alarm
group for the technician needs timezone 25 to be assigned. When a user enables
the service technician, timezone 25 will be valid during the service time (0 to
255 min).
Note: See “5-Alarm groups” on page 50, “13-Timezones” on page 113, and
Advisor Master Manager Manual.
The time that can elapse between acknowledging a local alarm and a re-alarm
occurring, including the audible alert (if the cause of the local alarm is not fixed).
Note: See “2-Area database” on page 29, and Advisor Master Manager Manual,
“Local alarms”, for further information
The time doors will unlock (using the door event flag) in order to allow doors to
be opened. This time value is common for all door event flags from RAS’s
connected to the ATS system, i.e. doors 1 to 16. Doors 17 to 64 are connected to
ATS1250/1260 4-DoorDGP’s that are individually programmed in the DGP.
Note: See also “3-RAS database” on page 39.
Specify the time the testing event flag is triggered to activate devices in order to
perform an arm test. The event flag will only be triggered for half the programmed
time. The remaining time is used to allow the device to switch back to normal
state.
The event flag used is preset to 16.
More on event flags in “Event Flags” on page 179.
This option specifies the amount of time (0 to 255 minutes) that the on-board
external siren drivers activate. The maximum time is 255 minutes.
See “1-Zone database” on page 7 and “2-Area database” on page 29 for more
information.
This option specifies the amount of time (0 to 255 minutes) that the on-board
internal siren drivers activate. The maximum time is 255 minutes.
This option allows you to set the delay time (0 to 255 minutes) before the sirens
actually activate after an alarm has occurred. This can be used for recording any
sounds before the siren activates.
The siren delay is set to 0.
The delay time (0 to 255 minutes) before a Mains Fail is reported to the central
station. Enter a value of “0” for no delay.
See also “34-Program system event flags” on page 154 and “9-Communication
options” on page 94.
The delay time (0 to 255 seconds) before a burglar alarm (BA) or BA Class
Tamper Alarm (TA) is reported to the central station. Can be used to prevent
alarm reporting for users that have problems disarming their area in time. After a
burglar alarm or input tamper activation, there will be a delay of 20 seconds
before the burglar alarm (BA) or BA Class Tamper Alarm (TA) will be reported to
the Central Station. All other (non-BA & non-TA) Alarms are reported
immediately, without delay.
The delay time (0 to 255 seconds) that the system waits for a second alarm. If
the second alarm happens within the delay time, it will be reported as a verified
alarm.
Note: See also “A&B alarm reporting (ACPO)” on page 35 in “2-Area database”.
The screen saver timeout value will be in the range of 5 to 180 seconds with an
accuracy of 1 second. The screen saver timer will be reset with the programmed
period every time a RAS key is pressed when the screen saver is not active. The
system user can also activate the screen saver manually by pressing the CLEAR
key at the Enter Code prompt.
Allows you to set the delay time (0 to 255 seconds) between badging the card
and entering the PIN (default is 8 seconds).
If enabled for a particular zone, Double Knock Interval specifies the maximum
permitted time a zone may remain active. If the time for which a zone remains
active exceeds the permitted time, an alarm condition is registered. If this value is
set to zero (‘0’), an alarm is not generated by prolonged activation, but is
determined by Double Knock Interval.
If enabled for a particular zone, Double Knock Duration specifies the maximum
permitted time a zone may remain active. If the time for which a zone remains
active exceeds the permitted time, an alarm condition is registered. If this value is
set to zero (‘0’), an alarm is not generated by prolonged activation, but is
determined by Double Knock Interval.
Reserved
When the setting procedure has been satisfactorily completed there is a time
limited completion of setting indication to show the system or part thereof has
changed to a set state. A common (global) timer setting is used to initialise each
area timer at the beginning of the confirmation period.
When the unsetting procedure has been satisfactorily completed there is a time
limited completion of unsetting indication to show the system or part thereof has
changed to an unset state. A common (global) timer setting is used to initialise
each area timer at the beginning of the confirmation period.
Allows you to set the time, for which the RAS becomes locked after a code
tamper. The allowed range is 1 to 255 seconds.
See also “Timed lockout by wrong codes” on page 44.
The active time for the chime event flag. If applicable, this time is also applied to
the RAS chime buzzer duration. For more information see System Options >
“Enable chime” on page 87.
Reserved
This field has an effect only when “Authorize computer connection” option on
page 147 is set. The option specifies how long the special authorization for
computer connection is valid. The default value is 60 min meaning that after the
installer authorizes the computer connection, the authorization is valid for
60 minutes.
Enter the time in minutes, for which the provided response code is valid and the
new code is not required. See “PIN of the day option” on page 89 for more
information.
16
Disarm Areas:
Note: When using this option, make sure the areas programmed for total disarm
can only be disarmed under correct conditions.
The film level number programmed is the film frame count. When this frame
count is reached, a film low is reported to the central station. Used for still video
or photo-cameras.
Note: Relates to zone types 23-26 and 36-39 (camera count). See “1-Zone
database” on page 7.
The film level number programmed is the film frame count. When this frame
count is reached, an out of film is reported to the central station. This option is
related to the camera count zone types 23 to 26 and 36 to 39.
Note: Relates to zone types 23 to 6 and 36 to 39 (camera count). See “1-Zone
database” on page 7.
Test mode
The test mode determines if or when an arm or disarm tests has to be performed
(formerly called walktest).
There are four options available. An option is programmed using its reference
number.
Option Function
0. No Test No automatic tests. A disarm test can be performed using User
menu 13, Start auto disarm test.
1. Enable Auto Test The disarm or arm test starts automatically when the system is
disarmed or armed.
2. Manual Disarm Test/Auto The arm test starts automatically when the system is armed. The
Arm Test disarm test can only be done using User menu 13, Start auto
disarm test.
3. Auto Disarm Test Only The disarm test starts automatically when the system is
disarmed. No arm test is available.
Notes
• For the "Auto disarm test" to operate, the area(s) containing the zones to test
have to be programmed as vaults. See “18-Vaults” on page 129.
• This record does not affect manual testing of any individual zone (User
menu 12). See Advisor Master Manager Manual.
Enter the number of output controllers that are fitted to the main control panel
(J14, see Advisor Master Installation Guide). An output controller has 8 outputs
available.
Valid values:
• 0: No output controller or a 4-way relay (ATS1810).
When zone types 57 and 58 are active, this zone event text will be displayed on
LCD keypads. The text is taken from the text word library and is programmed as
a reference number. A free programmable text can be programmed using “10-
Program text” on page 103.
The zone event text only appears when the zones are active, for example
“Freezer open”.
See also “1-Zone database” on page 7 and “10-Program text” on page 103.
The alarm code prefix enables user codes to be used for both access control and
alarm control. The prefix indicated the number of digits that have to be entered to
have alarm control. If those digits are not entered, only access control can be
performed.
For example: If the alarm code prefix is two digits and a users PIN is 123456,
then you would enter 123456 for alarm control or 3456 for access control. A
value between one to four digits can be entered.
Note: The minimum PIN length entered has to be 4 digits. The total length of a
users PIN is 4 + alarm code prefix.
The time before text on the LCD display starts rotating can be altered. The
default value 0, which is equal to 8.
Any value from 9 to 15 increases the time before text rotation starts.
Any value from 1 to 7 decreases the time before text rotation starts.
Note: This option can only be programmed for LCD arming stations, like
ATS1100.
Rotate Speed Is 0
Time:
Not only the time before text rotation starts can be altered, but also the speed
with which the text rotates. The faster the speed, the harder to read. But when
the speed is too slow, long texts might take too long to show. The default value 0,
which is equal to 8.
Any value from 9 to 15 decreases the text rotation speed.
Any value from 1 to 7 increases the text rotation speed.
Note: This option can only be programmed for LCD arming stations, like the
ATS1100.
Dual zone
NO – Dual zone
*-Change 0-Skip
Determines if dual zone is used. For dual zone to operate, every zone needs two
resistors of 4,7 kΩ. This enables the panel to detect whether a zone is in normal
state, is active or is tampered.
Yes: Dual zone used: Normal = 4k7; Tamper = Open or Short; Active = 2k35 or
9k4.
No: No dual zone; Normal = 4k7; Alarm = Open or Short or 2k35 or 9k4.
Press 0 to skip further options and leave system options.
Note: End of line resistors have to be connected to the zone. See the installation
guide.
This record controls the way zone names and numbers are displayed on the LCD
during user functions.
Yes: One zone at a time is displayed even though there may be more than one in
the list of zones to be displayed. The user must scroll through the zones. eg.
Active 2. Building 1 Workshop PIR.
No: Zones are displayed as a list of numbers and it is necessary to select the
zone number to display the individual zone name. eg. Active 1, 2, 3.
Press 0 to skip further options and leave system options.
Username file
Determines if users have names with their PINs programmed. Only users 1 to
200 can have a name with their PIN (if memory extension available).
Yes: The appropriate prompts for programming a username, are displayed when
programming user codes.
No: The appropriate prompts for programming a username, are not displayed
when programming user codes.
Press 0 to skip further options and leave system options.
See also Advisor Master Manager Manual regarding programming users.
System alarms are RAS/DGP Offline, cabinet tamper, siren tamper, mains fail,
fuse fail, low battery, etc.
Siren testing
NO – Test Siren
*-Change 0-Skip
Defines the procedure to stop cameras from operating. See the Manager Manual
for more information.
Yes: 0, Enter can not be used to stop cameras operating. The cameras continue
to operate until someone who is authorised to control cameras, resets them.
No: 0, Enter stops the cameras operating (after pressing Enter, Enter for the
"Quick alarm log".
Press 0 to skip further options and leave system options.
See also Advisor Master Manager Manual regarding alarms, camera’s and alarm
logs.
Disables the option to treat areas as vaults. By disabling this option, the non-
vault areas will not be automatically armed.
Yes: Disables the special procedure for automatically timing on non-vault areas
when arming vaults.
Reserved
Indicate if area LED’s should flash when there is an alarm and/or tamper alarm in
the area.
Yes: The area LED will not flash on alarm.
No: The area LED will flash on alarm.
Press 0 to skip further options and leave system options.
Determines that two users are required to enter their PIN to enable programming
of users (user menu 14). When entering this option, a request for a second PIN is
shown before access is granted.
User 50 (Master code) is not required to have a second code to authorise the
option.
Yes: Two users are required to enter their PIN before access is granted to
program users.
No: No validation is needed when entering user menu 14, Program users.
Press 0 to skip further options and leave system options.
When set to Yes, Siren event flags are only activated on alarms if the ATS
control panel has failed to report to the central station. Fail To Report (FTC) is
registered at the end of the fourth dial attempt. The siren activates for the normal
siren cut-off time programmed.
Yes: Sirens will only activate on alarms when a FTC has occurred.
No: Sirens will operate on alarms.
Press 0 to skip further options and leave system options.
Financial options
NO – Financial Options
*-Change 0-Skip
Enable the special user flags to be displayed when programming users. The
special user flags are Two Card function, Guard, Visitor, Trace User, Card only,
Privileged and Extended Access.
Yes: The special user flags are displayed in sequence after the "Floor group"
display when programming users.
No: The special user flags are not displayed.
Press 0 to skip further options and leave system options.
See also Advisor Master Manager Manual for more information on users and
user flags.
Indicate if zone expanders (ATS1202) are fitted on the control panel (not for
ATS1201 DGP).
Yes: Zone expanders are fitted on the control panel.
No: No zone expanders fitted.
Press 0 to skip further options and leave system options.
See Advisor Master Installation Guide for information on fitting zone expanders
on the control panel.
The system is able to report multiple alarms that occurred in a zone (depending
on the reporting format).
Yes: Report multiple alarms as a separate alarm for each alarm that occurs.
No: Only report the first alarm. Every next alarm that occurs will not be reported.
Press 0 to skip further options and leave system options.
The system is able to generate a restore for each alarm being reported, even for
multiple alarms in a zone.
Yes: Report a restore for every alarm that occurred.
No: Report only one restore for every zone that generated an alarm.
Press 0 to skip further options and leave system options.
If an engineer reset is required on system alarms, set this option to Yes. A user
can not arm any area until an engineer reset has been performed.
Yes: After a system alarm, an engineer reset is required.
No: No engineer reset required.
Press 0 to skip further options and leave system options.
Engineer Reset?
*-Reset 0-Skip
If an engineer reset is required on system tamper alarms, set this option to Yes.
A user can not arm any area until an engineer reset has been performed.
Yes: Engineer reset required on system tampers.
No: No engineer reset required.
Press 0 to skip further options and leave system options.
Set this option to Yes if an engineer reset is required. An engineer reset can then
be done by the user entering the ‘ATS System Code’ computed from the number
displayed on the RAS.
Note: This option by default does not allow users to perform an engineering
reset, except the Installer via Key-switch – Input type 65, Titan or Installer Menu
19/51.
This option protects against unauthorised entry by an installer. If set to Yes, you
can only enter menu (19) (Installer programming) by opening the box tamper
If set to Yes, when armed, an area will defer the reporting of arming to the central
station until the exit time has ended.
User offset
The offset is used to report user ID’s to management software. The offset is 0 to
65535. When a user ID is sent to the management package, this offset is added
or subtracted. The control panel itself uses the user ID without offset.
The End of line resistor code is used to set the correct value for the end of line
resistor used. By default this is set to 4,7 kΩ.
Duress mode
Duress Mode 0
Mode:
If siren type “0” has been selected, then when the 16th relay is activated, a saw
tooth signal is generated at the signal output. If siren type “1” has been selected,
then when the 16th relay is activated, a constant DC voltage is set at the siren
output. If siren type “2” has been selected, then the 12th, 13th, 14th, 15th and
16th relays are mapped to the siren output. These relays have priority 1 to 5
respectively. Hence relay 12 will have a higher priority over relay 16 when both
are active, thus generating a DC voltage at the siren output. The following
happens when the following relays are activated:
• 12th relay active = generates constant DC voltage at the siren output
• 13th relay active = generates a warble tone at the siren output
• 14th relay active = generates a sawtooth tone at the siren output
• 15th relay active = generates 2 tones at the siren output
• 16th relay active = generates an inverted sawtooth tone at the siren output
If set to Yes, a zone input tamper/restore will not report to the central station if
the assigned area(s) are disarmed. Similarly, system tampers/restores will not
report to the central station if all areas are disarmed. If a tamper occurs when the
area(s) are armed, this will report and send the restores when the areas are
disarmed.
If set to Yes, zone input tampers will only activate the internal siren if the areas
are disarmed. System tampers operate similarly except that all areas are
disarmed.
If the system code is 00000, the old algorithm is used to calculate the
engineering reset code. If not, the system code value and the engineering code
value are used in a special calculation to generate the reset code.
The default is set to 00000.
This option sets the numbers of days for the soak test period. It can be set from 0
days to 255 days. Refer to “Enable soak test” on page 20 for more information.
The default is set to 7 days.
ACPO
NO – ACPO
*-Change 0-Skip
When this option is set, all alarms triggered within the entry time, provided an
entry/exit zone is triggered first, will be dealt with as an “A” Alarm. They will not
be reported to the CS before the entry time has elapsed. The first zone triggered
after the entry time has elapsed will be reported as an “A” Alarm. Any zone
triggered after that will be reported as a “B” Alarm.
When this option is set, all alarms triggered within the entry time, provided an
entry/exit zone is triggered first, will be dealt with as an “A” alarm. They will not
be reported to the CS before the entry time has elapsed. Any zone triggered after
the entry time has elapsed will be reported as an “A” alarm only.
Notes
• AB alarm option must be set to Yes in the area database.
When this option is set, you do not need an engineer reset when only an “A”
alarm has been triggered
Note: “A&B alarm reporting (ACPO)” on page 35 must be set to Yes.
Engineer reset for alarm must be set to Yes in zone database and system option.
NFA2P
YES – NFA2P
*-Change 0-Skip
The second user must have Alarm System Control and not have access to
menu 19. If the second user does not meet these conditions, then the display will
show:
When Enter is pressed, the display will return to the user menu.
Note: The function does not work and user code is not requested:
• When the system is in the Service In mode. See Manager Manual for more
details.
• If PIN of the day option is set to Yes. See “PIN of the day option” on page 89.
Informs the Central Station in the event of opening or closing faults. In case of a
burglar alarm or tamper activation and when the “delay reporting alarms” timer
has expired, the user will be informed after disarming by the text “Call Central
Station” on the LCD if the reporting to the Central Station was successful. This
displayed message “Call Central Station” shall only be displayed for 30 seconds,
and is only displayed on RAS’s linked to the AREA or AREAs that went into
Alarm. The user can decide to call the Central Station to inform the status i.e. on
opening or closing faults.
Exceptions
This text will not appear after reporting PANIC, HOLD-UP Alarms (HA) reports or
disarming by a Duress PIN. Also when a LINE FAULT is concurrently active, this
text will not appear.
Scandinavian indicators
Limits the number of repeating intrusion events from the same source within the
same arm/disarm cycle. A limit of three (3) times has been set.
Input types excluded from log limitations are as follows: 6, 7, 9, 12, 16, 18, 19,
20, 23 to 27, 31, 32, 34 to 39, 57, 58, and 65.
These types are generally associated with access control, or have a special
function, and are not associated with the normal alarm functionality.
Alerts the system user at the RAS with an optical and audible indication that
zones are inhibited in an area that is being armed. The inhibited zones need to
be listed and the user prompted with the option whether to arm the system or not.
Confirm area
1,2,4,5,7,8,
Confirm Area:
Security grade
The Security grade option allows the panel behaviour to change based on the
grade level of the installation. The following grade levels are implemented:
• Disabled: Existing ATS panel behaviour
• Other: Low to medium risk installation
• Grade 3: Medium to high risk installation
There are conditions in the current panel implementation that already prevent
arming, and cannot be overridden (e.g. unsealed zone, zone/system alarm,
zone/system tamper, engineering reset). These conditions must be either
restored, or the zone/device inhibited, before arming can proceed.
In addition to the current conditions that prevent arming, there are additional
conditions that must prevent arming when the selected security grade is option 3.
When the security grade is not Disabled, these new conditions can prevent a
security system from arming, however, may be overridden by authorised users.
When an event is overridden, the event is logged to the alarm history database
including time and date, and the number of the user who performed the override.
To discriminate between the levels, use option “User level” (described on page
60) in the Alarm Group menu.
Note: Security grade 3 also sets minimum PIN length to 5 digits.
When set to Yes, all conditions latch. Once latched, a user PIN is required to
reset the event. When this option is set to No, each event automatically clears
once the condition has been restored
When set to Yes, and a Line Fault, or Fail-To-Communicate, condition exists, the
operation of a silent panic alarm changes to that of an audible panic alarm. When
the Line Fault, or FTC, restores, the silent panic alarm reverts to silent operation.
When set to Yes, and at least one area of the control panel is armed, the
jamming alarm condition will latch, and a user code is required to reset the
condition. To reset the jamming alarm, the user alarm group must permit the
reset of system alarms.
When this option is set to Yes, and the area with the AWDGP zone assigned is
armed, the long supervision / smoke supervision alarm on that zone will latch,
and a user code is required to reset the condition. To reset the long supervision /
smoke supervision alarm, the user alarm group must permit alarm reset.
When this option is set to No, the jamming alarm and supervision/smoke alarm
conditions are self-resetting when the condition restores. Regardless of this
setting, when the area is disarmed, only a device tamper condition will latch. All
other AWDGP fault and alarm conditions are non-latching, and automatically
restore when the condition clears.
Enable chime
When set to Yes, chime/camera events are treated as chime events in Zones
and Areas databases. Otherwise these events are treated as camera events.
Synchronization allows restoring user record in DGP user database, if the card
number is missing.
If the DGP does not recognize a badge card, it queries this card in the ATS
panel. If the user exists in the ATS panel user database, the panel resends this
record to all DGPs.
This functionality allows connecting four-door DGP to the ATS panel without
downloading user database. Four -door DGP automatically learns user PINs,
alarm groups, etc. when a user presents his card first time.
If the Engineer reset on RAS lockout option is set to Yes, an engineer reset is
required to unlock a RAS lockout. Otherwise, the RAS is unlocked normally.
See also “Timed lockout by wrong codes” on page 44.
For more information on engineer reset, refer to “Engineer reset for system
alarms” on page 79 and “User can do engineering reset” on page 80.
Setting to Yes prevents arming on faults and events listed in the list below:
• Detector in active condition
• Tamper condition
• Detector range reduction
• Interconnection fault
• Auxiliary power source fault
Note: “Ignore battery fault when arming” on page 80 must be set to No.
• Primary power source fault
Note: “Ignore AC mains fault when arming” on page 87 must be set to No.
• Communication module fault
• Watchdog fault
• Exit fault
• Other alarm system component fault
The default is Yes.
Caution: Once this option is switched to Yes, it cannot be switched back to No.
If PIN of the day option is set to yes, the installer can only enter the system with a
response code, which can be obtained from the appropriate security manager.
The code is calculated basing on the PIN of the day that is generated for the
particular session.
How to log in the system when the PIN of the day option is set to Yes:
1. Log in as an installer.
The following screen appears:
2. Contact the security manager and give him the PIN of the day. Using
dedicated code calculating software, he generates the response code from
the Challenge code.
Press Enter.
If set to Yes, the user can manually override AC mains fault when arming.
The default value is Yes.
If set to Yes, the user can manually override battery fault when arming.
The default value is Yes.
If set to Yes, the user can manually override reporting fault when arming.
The default value is Yes.
If set to Yes, the user can manually override siren fault when arming.
The default value is Yes.
If set to Yes, the user can manually override detector trouble when arming.
The default value is Yes.
If set to Yes, the user can manually override tampers when arming.
The default value is Yes.
If set to Yes, the user can manually override interconnection fault when arming.
The default value is Yes.
If set to Yes, the user can manually override RAS fault when arming.
Note this does not apply for RAS offline scenario. (Offline RAS must be isolated
by installer to proceed arming).
The default value is Yes.
If set to Yes, the user can manually override DGP fault when arming.
Note that the overriding does not work if DGP is offline. Offline DGP must be
isolated by installer to proceed arming.
The default value is Yes.
If set to Yes, the keypad provides a 5-second audible alert when user action is
necessary on a keypad in a disarmed state, usually when unacknowledged
alarms or faults are present. The alert reactivates after each period of time
programmed in “Local alarm reminder time” on page 64.
The audible alert only works on a keypad if:
• All areas assigned to the RAS are disarmed, and
• There are unacknowledged alarms or faults at least in one of areas assigned
to this RAS.
Enter the number of attempts that can be made to enter a responce code before
the keypad becomes locked and the code tamper occurs.
0 means that attemts are unlimited.
See “PIN of the day option” on page 89 for more information.
The display shows the existing reset time. This is the amount of time that elapses
between the alarm occurring and reset.
The control panel has to know which areas to auto reset. Using an alarm group
does this.
See also “5-Alarm groups” on page 50.
*-Pause, Ph No:
PABX:
A PABX number hold a number that precedes any other number being dialled.
Used only if the dialler is connected via a PABX to the telephone network.
MSN number
*-Pause, Ph No:
MSN No:
For ISDN dialler, a MSN number can be programmed. This number is sent to the
ISDN network on dialling to a computer or central station.
See “PABX number” above.
MSN may not contain characters P and T, but only digits between 0 and 9.
Select tone or pulse dialling. For ISDN diallers, this option has no meaning.
Yes: Use tone dialling.
No: Use pulse dialling.
A line monitor will detect if the line voltage on the telephone network is within
limits. If not, a telephone line failure will occur.
Yes: Enable the line monitor.
No: Line monitor is disabled.
Press 0 to skip further options and move to central stations.
Select if SIA reporting uses 2 or 3 digit zone, point or user numbers. When 2
digits are used, numbers above 99 will be converted to 99.
Yes: SIA reporting uses 3 digit numbers.
No: SIA reporting uses 2 digit numbers.
Press 0 to skip further options and move to central stations.
This option allows you to select the point to point mode of operation for the plug-
in ISDN dialler.
If set to Yes, the line monitor will detect if the line condition on the telephone
network is within limits. If it is not, a telephone line fault condition will be
activated.
If set to No, disarm events are reported as type “A” and arm events are reported
as type “R” (Default)
If set to Yes, disarm events are reported as type “R” and arm events are reported
as type “A”
The X25 TEI value for the ISDN-D channel connection. The range is from 1
to 63.
The total time in seconds that the panel will transmit audio to the monitoring
station. Note that the actual time of the audio transmission can be manually
stopped or extended by the receiver. Range is 10 to 255 s.
The time in seconds for each audio frame. During transmission the audio is
broken into frames or blocks. Range is 10 to “Audio listen in time” above.
Disabled
Format No:
Every central station can report using a different format. There are following
reporting formats available:
Format Name
1 Tecom Dialler V1 (only used in Australia)
2 DTMF Contact ID – Small
3 DTMF Contact ID – Large
4 SIA – Small
5 SIA – Large
6 X-SIA - Small
7 X-SIA - Large
8 200 Baud FSK - 1
9 200 Baud FSK - 2
10 200 Baud FSK - 3
11 200 Baud FSK - 4
12 X25 ENAI
13 Voice Reporting - Acknowledge
14 Voice Reporting – No Acknowledge
Note: X-SIA – Small and X-SIA – Large are protocol options. The difference
between “Small” and “Large” is the amount of system events it will report. The
large formats will report most system events.
See also “42-Reporting class database” (page 164) and “Reporting” (page 182)
*-Pause, Ph No:
Ph1:
Every central station can report to 2 telephone numbers: 1 main and 1 back-up
number. Enter the main number here.
See also “PABX number” (page 94).
*-Pause, Ph No:
Ph2:
Every central station can report to 2 telephone numbers: 1 main and 1 back-up
number. Enter the back-up number here.
See also “PABX number” (page 94).
Program the account code for area 1. Account codes can be 4 to 6 digits long. If
no reporting should be made for this area, program 0000 as account code.
Program the account codes for areas 2 to 16. See “Enter the area 1 account
number” on page 98.
Dual reporting
If an acknowledge should be received from both phone numbers, set this option
to Yes.
Yes: Use dual reporting.
No: Use normal reporting.
Press 0 to skip further options and move to central stations.
NO – Listen In
*-Change 0-Skip
Reserved
Specifies the maximum number of characters for XSIA. This option tells the panel
to send either MAX the first 16 or MAX the first 30 characters to the CS.
Connection type
Suppresses Report Fail (FTC) messages and Fault LED on the RAS for when
the panel fails to complete voice message delivery only. The “'Voice I/F fail”
message, caused by hardware failure when the panel is unable to communicate
with the ATS7200 board, is not suppressed by this option. The FTC will still be
LOG.
Retry Count: 14
Count:
Enter the maximum number of retries allowed on each Central Station. The
default is 14 retries. The exception is Italy where the default is 2 retries (on
Central Stations set on Voice Reporting).
Allows the user to send multiple areas O/C using the same account code (as in
CID).
It allows identifying more than one area using only one account code. System
events are reported using the configured system account number (current
behaviour) and an area code 0 (see example below). All area events use area 1
account number.
Examples are:
• Nri02/BA12: New event, Area 2, BA on zone 12.
• Nri11/ZR123: New event, Area 11, ZR on input 123.
• Nri00/RR316: New event, power-up
X25 D-Bit
Specifies the X25 D-Bit option ON or OFF for an ISDN-D network configuration.
Yes: D-Bit option for an ISDN-D network is ON.
No: D-Bit option for an ISDN-D network is OFF.
Notes
• Default setting for The Netherlands is ON.
• Default setting for Belgium if OFF.
The panel detects a Mains Fail event when the AC mains supply is absent for
longer than the programmed “Mains fail delay time” on page 66 (in “6-Timers”).
The mains failure event is reported to a programmed central station if “Report
mains fault” on page 96 is set to Yes (“9-Communication options”).
When this option is set to Yes, the alternative SIA reporting code will be
transmitted to the Central Station.
When programming text, first select the reference number to use (900 to 999). If
words are already programmed, press Menu to go through the list. Select the
number to program.
When the number is selected, the word already programmed is shown and can
be changed. Press Enter to move to the next character.
To change a character, select it by pressing the correct number button (see
Figure 1 on page 104). To accept the character, press Enter. The maximum
length of text is 16 characters.
Once the text is correct, press Menu to accept the text. It will be shown to
confirm. Press Menu again to accept the text.
To delete a character, select a whitespace character (under [9], see Figure 1 on
page 104).
Select device
Version 1 - ATS CP 2 - RAS 3 - DGP
0-Exit, Menu:
Notes
• ATS Panel Type — it can identify a 2000, 3000, 4000 or 4500 series panel
type.
• Markets Supported — up to 30 characters can be displayed here.
E.g. ABC_XY_AA_F_AN_AQ_E_D.
• When calling the technical support, this information might be asked to be able
to provide answers to questions.
This function is used to test all LEDs in the system. This includes LEDs on
arming stations, card readers, etc.
You can turn all the LEDs on by entering a valid code, exit the Programming
menu, check the LEDs on all Arming Stations, then return to the menu to turn the
LEDs off by entering a valid code again.
How to program
Press one of these keypad buttons to:
• Code, Enter: Enter a valid user code and press Enter to turn on/off all the
LEDs in the system.
• Enter: Return to the Programming menu.
Note: Do not forget to turn off the LEDs again.
Timezone settings
Program start time, hours
First program the hour for starting time for the timezone, sub-timezone 1.
Enter the minutes for the starting time for the timezone, sub-timezone 1.
Program the hours for this sub-timezone to end the valid period.
Finally, program the minutes for this timezone to end the valid period.
Once you have entered the valid time period for the sub-timezone, the next
display that appears lets you enter the days of the week and holidays on which
the timezone is valid.
For the days of the week, enter their numerical value, where Sunday is “1” and
holiday is “8”.
Note: The next displays contain sub-timezones 1.2 to 1.4. These are
programmed in the same way as sub-timezone 1.
99-All Resets all the system records to the factory default. All
programming is erased.
98-STD (standard) Resets some of the programming menus. The following menus
are defaulted:
• Area database
• Alarm groups (11-29)
• Timers
• System options
• Auto reset
• Timezones
• Alarm group restrictions
• Auto Arm/disarm
• Areas assigned to vaults
• Area linking
• Timezone to follow output
97-Outputs and groups Resets the event to output records, the door and floor groups.
95-Software IUM This new option upgraded the panel to Software IUM. By using
this option the different memories will be converted as listed in
Table 10 below.
93-Grade 3 Set default values for EN 50131 Grade 3 compliance.
See “Options required by EN 50131 compliance” on page 200 for
more information.
Note: There is a prompt to apply these settings after the first
installer login. See “First startup” on page 6 for more details.
Alarm group restrictions 1 to 6: The areas arm again when the timer has expired unless other
timers are still running.
When disarming the programmed
areas and a timer starts running. Users can arm the area by re-entering their code, provided
the display does not show Ending. If other timers are running
and the code is re-entered, the individual alarm group
restriction is cleared but the area is not armed.
Users can extend the timer by re-entering their code when the
display shows Ending for their alarm group restriction.
A buzzer sounds as a warning when the timer is running out
and the area is about to arm.
2. Arm/reset of areas
Only arm/reset functions apply to areas assigned to an alarm group and
programmed as “Areas to arm/reset” on page 120 in Alarm group restriction
menu. When a user enters a code, it arms the programmed areas, regardless of
any timers running (but cannot disarm), or it resets alarms in the programmed
areas.
Restriction number
Alarm Group Restrictions
Restr. No:
Select the name of an alarm group restriction from the list of words already held
by the ATS system. These words can be from the standard word library (see
Table 9 on page 105) or from a list of words that you have programmed yourself
(programming menu option “10-Program text” on page 103).
Program the alarm group restriction name, using the reference number of the
word. The name should be easily recognisable.
1,2,3,6,7,
1, Timed Area:
When a user enters a code, the programmed areas are disarmed and a timer
starts running. In order for the function to be enabled, the areas listed in this
option must also be listed in the alarm group to which the alarm group restriction
is assigned and alarm system control has to be enabled.
See also “5-Alarm groups” on page 50.
Areas to arm/reset
1,2,3,4,5,
1, A/R Area:
When a user enters a code, the programmed areas are armed or alarms are
reset. In order for the function to be enabled, the areas listed in this option must
also be listed in the alarm group to which the alarm group restriction is assigned
and alarm system control has to be enabled.
See also “5-Alarm groups” on page 50.
9,10,
2, Timed Area:
For example
Three alarm groups have been set up:
User 2
Alarm group 32
Areas: 1, 2
AG restriction: 4
Timezone: 1 Alarm group restriction 4
Alternate AG: 33
Use standard
restriction
1, Timed Area:
Timezone 2 invalid 1, A/R Area: 2
Alarm group 33
Areas: 1, 2 Use 1st alternate 2, Timed Area: 2
AG restriction: 4 restriction 2, A/R Area:
Timezone: 0 (always)
Alternate AG: 1 (none)
3, Timed Area: 1
3, A/R Area:
9,10,
2, A/R Area:
See “Areas to arm/reset”, “1st alternate timed disarm area” and “5-Alarm groups”
(on page 50).
12,
3, Timed Area:
12,
3, A/R Area:
Timezone
Output number
Event To Ouput
Output No:
This is the physical number of the output. Each output has a specific number that
will identify the output to the control panel. The output number is determined by
the address of the device the relay card is connected to.
See Advisor Master Installation Guide for more information on output numbers on
devices.
An event flag or a timezone activates an output. Enter the event flag number
here.
The output follows the event flags during a valid timezone. If event number 0 is
programmed, the output does not follow any event flag.
Output 3 Timezone 12
Timezone No:
The timezone entered controls the times that an output is active or inactive. If a
timezone is programmed, it sets the output when the time is valid. The status of
the event flag is irrelevant when the timezone is valid. If the timezone is invalid,
the output follows the event flag. If no timezone is programmed the output follows
only the event flag.
See also “13-Timezones” on page 113.
Invert output
Output 3 is NON-Inverted
*-Change
Inverted: If the output is inverted, the logic controlling the output is reversed. E.g.
if the previous logic determines that the output is to be ON, this setting would
change it to OFF.
Non-inverted: The output follows the event flag. If the event flag is active, the
output is ON.
Pgm: 1 TimeZone 2
Timezone No:
The alarm group is used to determine which areas are automatically armed or
disarmed, and if the specified areas are to be automatically armed, disarmed or
both.
If an alarm group restriction is linked to the alarm group, the automatic arming
can be postponed by a preset time (alarm group restriction disarmed time, see
“6-Timers” on page 62).
Notes
• The settings in the alarm group determine the exact operation of this function.
The function follows all the guidelines of the alarm group regarding alarm
control. For example, if the alarm group setting for Arm and Reset only is set
to Yes, then the areas assigned will only automatically arm.
2, 3, 4,
Area:
Linking areas
Linking areas is done by first selecting the common area.
Area Linking
Common area:
Next select the areas to be linked to the common area. Remove linked areas by
entering these again.
Area 1: 2, 3, 4
Area to Link:
Enter the first system code here. The system code is provided by the supplier
and is unique to the reader device and card range
The system code normally has 6 digits. If less then 6 digits are provided, add
leading zeroes.
Card offset 1
Card Offset 1: + 0
*-Chg, No:
Specify the number to be added or subtracted from the actual card ID number,
for cards in System Code A. The ATS control panel will calculate the user
number from:
User Number = CARD ID + (or −) card offset
The calculated user number is used for programming the user and when
reporting events to the central station or the computer.
For example: The card offset is programmed as −5000. The actual physical card
ID number is 5001. The card will be programmed as User 1, and will report as
User 1.
How to program
Press one of these keypad buttons to:
• Menu: Change the offset to + (add) or − (subtract).
• ?, Enter: Enter the card offset required.
• Enter: Save the displayed setting and move to the next display.
Specify the second system code, if required. See “System code 1” on page 131
for further information.
Card offset 2
Card Offset 2: + 0
*-Chg, No:
Specify the card offset for cards in system code B. See “Card offset 1” on page
131 for further information.
Shunt options
Zone number to shunt
Determine the zone that is to be shunted. The zone can only be assigned to one
shunt timer.
The display shows the current zone number that relates to this shunt timer.
Select the output to start the shunt timer. The display shows the assigned output.
The output condition controls whether or not the zone remains shunted. If the
output is active, the zone is always shunted. When the output de-activates, the
shunt timer continues to run for the programmed shunt time.
Note: The total shunt time is the time the output activates + the shunt time.
Program the amount of time that the zone will be shunted. If the time expires and
the zone remains active, an alarm condition occurs, depending on the zone type
and the status of the area.
If the value entered is less than 128, the time is in seconds. I.e. 1 to
127 seconds.
To set the time in minutes the value entered is 128 plus the time required in
minutes.
E.g. for 30 minutes enter 158. (128 + 30 = 158).
The value 128 is invalid and cannot be used. For accurate timing of 1 or 2 minute
periods, set the time in seconds. i.e. 60 or 120 seconds.
Note: Do not use a time of 0 seconds, unless for doors when “Cancel door event
flag” on page 135 is set to Yes. The zone could otherwise be shunted indefinitely.
Shunt Warning Is 0
Warn Time:
Program the time the shunt warning event flag will be activated before the shunt
timer expires. If the shunt time is programmed in seconds, the warning time is
also in seconds. If the shunt time is in minutes, then the warning time is also in
minutes.
The event flag assigned is activated when the shunt timer is running.
The event flag assigned is activated when the shunt warning time is active.
Specify if the zone will be shunted when one or more of the areas assigned to
the shunted zone are disarmed.
Press 0 to end programming this shunt timer and to select a new shunt timer.
Note: Set either “Shunt zone when disarmed” or “Shunt zone when armed” to
Yes. Otherwise the shunt procedure will not operate.
It records whether the door shunt procedure operates when all the areas
assigned to the shunted zone are secure.
Press 0 to end programming this shunt timer and to select a new shunt timer.
Note: Set either “Shunt zone when disarmed” or “Shunt zone when armed” to
Yes. Otherwise the shunt procedure will not operate.
Delay cancelling of the door event flag. It is used for doors with magnetic locks
and drop bolts.
Yes: In order to allow time for a door to be properly closed, there is a 2-second
delay after the zone switches to normal and before it cancels the door event and
shunt timer.
No: There is no delay.
Press 0 to end programming this shunt timer and to select a new shunt timer.
Entry/exit shunting
NO – Entry/Exit Shunting
*-Change 0-Skip
Allow for the zone to be logged on printer as door open/close when it switches
between normal and active.
Yes: Every time the zone changes status, it is logged to the printer.
No: No reporting to the printer.
Press 0 to end programming this shunt timer and to select a new shunt timer.
Note: If “Print zone when active” on page 26 is set to Yes for the zone assigned
to the shunt timer, a door open message is sent twice.
Select timezone
Output To Timezone
Tz (26-41)
Tz 27 To Follow Output 3
Output No:
Select the type of devices to view the number of poll errors on. Optionally the
error counters can be reset. The available options are:
• 1 - RAS: View poll errors for remote arming stations
• 2 - DGP: View poll errors for DGP’s or the dialler
• 3 - Reset: Reset all poll error counters.
After selecting the device type, a list of all devices is shown. Select a particular
device by entering its device number. The device numbers are as follows:
• RAS 1 to 16: Arming stations 1 to 16
• DGP 0: Panel communications to central station
• DGP 1 to 15: Data gathering panels 1 to 15
Two menus are available. The first menu displays the download status. The
second menu is used to select the item to download.
Download all
1. Abort Aborts any download in progress. Erases the current database being
downloaded to the four-door/four-lift DGP.
2. Users All users
3. Grps All door groups and floor groups
4. Tz Timezones 0 to 24
5. Hol Holidays
In this example the display shows the system code as “SC=0023” and the cars ID
as “User=987654”.
How to program
• Enter: Return to the Programming menu.
Note: The card must have a valid format that the system is programmed to
recognise.
If the correct system code is not entered in option 20, only the system number is
displayed and not the card ID.
If the correct system code is programmed in option 20, the system code and card
ID are displayed.
26-Reserved menu
Reserved. Do not use.
27-Reserved menu
Reserved. Do not use.
To establish a connection to the remote device, select the device type first. The
type is either a RAS (e.g. ATS1270, 1-Door RAS) or a DGP (e.g. ATS1250/1260,
four-door/four-lift DGP).
Specifies if arming areas, controlling outputs and door control is allowed from a
remote computer via dialler.
Yes: Remote arming of areas, controlling outputs and door control is allowed,
when disarmed.
No: Remote arming of areas, controlling outputs and door control is not allowed,
when disarmed.
Press 0 to go directly to menu 29.8
Note: This option will only disable remote control function and not status
requests, and will only operate if 29.1 is set to Yes, and also depends on option
29.2 and the status of the areas.
If Menu 29.5 is set to Yes, enter the modem initialization string (you can enter up
to 32 characters.) This modem initialization string is sent to a compatible modem
on the ATS1801 (serial printer/computer interface board). The 32 character entry
allows for the following characters: @&/=%+-,;
Press OFF or “*” twice to move onto Menu 29.6.
*-Pause, Ph No:
Cmp:
*-Pause, Ph No:
Cbk:
*-Pause, Ph No:
Srv:
Computer address
Security password
The ATS control panel requires a security password before granting access to
the panel using the upload/download PC software (e.g. ATS8100). A connection
can be made using a telephone line (dial-up) or using RS232, if the interface is
available (ATS1801).
Security passwords are always 10 digits. The default password is 0000000000.
The ATS8100 up/download software can always connect to an ATS control panel
with the default password. However, it updates the password to the password
programmed in the up/download software for the ATS control panel currently
opened.
Number Of Rings: 0
Rings:
Enter the number of rings before answering an incoming call. If set to 0, incoming
calls will not be answered at all.
Enter the number of calls before answering an incoming call. If set to 0, incoming
calls will not be answered at all. Each incoming call will have to exceed the
number of rings, set in “Number of rings before answering”.
If the number of rings programmed and the number of calls is met, the next
incoming call will be answered immediately.
See also “Number of rings before answering” and “Number of calls before
answering”
Reserved
NO – BELL Modem
*-Change 0-Skip
Enables BELL 103 modem tones for the PSTN or ISDN analogue line connection
for Computer reporting.
Option Description
0 PSTN
1 ISDN
2 Not Used
3 GSM
4 Universal Interface
Printer settings
Enable real-time printer
Enables the printer to only operate outside the timezone, and not during it.
Yes: The printer is only active if the timezone specified is invalid.
No: The printer is only active if the timezone specified is valid.
Press 0 to leave Printer menu.
Notes
• Any event that takes place when no data is dumped to the printer will be lost
for the printer. Use “Print history” in the user menu to print these events.
• “Enable real-time printer” on page 148 has to be set to Yes to be able to print
events.
The printer is only active during the timezone specified unless print data outside
timezone (above) is set to Yes. The default timezone is TZ 0 (always valid).
Printer options
You can program the printer interface for an Epson (compatible) dot matrix or
HPII (compatible) laser printer with optional communication settings.
Select 1 to program the battery test options or 2 to perform a manual battery test.
Program the time of day, in hours and minutes, when the battery test will start.
Program the period, in minutes (with a minimum of 2), that the automatic battery
test will run. If a battery test on any device fails, that device immediately restores
AC power.
This allows the ATS panel and DGP batteries to be tested manually. This test
does not affect the automatic battery testing. If a DGP is tested, the DGP number
will be displayed.
How to program
Enter: Move to the next manual battery test display.
How to program
Enter: Move to the next manual battery test display.
Use the text option on the keypad to enter a text of up to 32 characters. Keys 1
to 9 have alphabetical characters printed above them. To enter a letter, press the
key the number of times relative to the position of the letter. Both upper and
lower case letters are available as well as numerical values and spaces. See
Figure 1 on page 104.
Note: When the Menu key is used, only letters preceding the cursor are saved. If
you want to save an existing word, you must enter it again or, using the Enter
key, move the cursor to the end of the word.
Time and Date can be displayed in the RAS LCD display if there are no alarms
active. By entering a point (.) as the first character in custom message, the time
and date will be displayed in the following format: (HH:MM DAY/MONTH/YEAR)
For example: 8:45 02/10/2001.
Maintenance date
Service Required at 0/0/0
Enter Day:
Enter the next date on which the user will get a text displayed to signal that
service is due.
Maintenance message
Routine Service Due, (*) - End
Routine Service Due
Program a text (32 characters maximum) that will be displayed on the LCD
arming stations on the date specified as the service date.
How to program
See “32-Custom LCD message” on page 152.
This event flag is activated when a Mains Failure is detected on the ATS control
panel or a DGP.
Note: Do not use a preset event flag number (1 to 16). Program 0 to disable an
event flag.
This event flag is activated when a low battery is detected on the ATS control
panel or a DGP.
See also “Mains fail event flag” above.
This event flag is activated when a fuse fail is detected on the ATS control panel
or a DGP.
See also “Mains fail event flag” above.
This event flag is activated when a Panel Tamper is detected on the ATS control
panel or a DGP (includes RAS tampers).
See also “Mains fail event flag” above.
This event flag is activated when a Siren Fail condition is detected on the ATS
panel or a DGP.
See also “Mains fail event flag” on page 154.
This event flag is activated when a DGP has been isolated via User menu 16,
Isolate/deisolate RAS/DGP.
See also “Mains fail event flag” on page 154.
This event flag is activated when a DGP that is programmed to be polled, does
not reply to polling.
See also “Mains fail event flag” on page 154.
This event flag is activated when a Remote Arming Station, which has been
programmed to be polled, does not reply to polling.
See also “Mains fail event flag” on page 154.
This event flag is activated when the film count for a camera exceeds the
programmed film out level described in “Film out level” on page 71.
This event flag is activated when the ATS control panel fails to report to the
central station (also referred to as FTC).
See also “Mains fail event flag” on page 154.
This event flag is activated when the ATS panel is in test mode.
See also “Mains fail event flag” on page 154.
This event flag is activated when all areas to report opening/closing are armed,
there are no alarm conditions, and no entry/exit timers are running.
See also “Mains fail event flag” on page 154.
When this event flag is activated, the keypad buzzers are activated. The event
flag also has to be assigned to the events that you want the keypad buzzer to
sound on.
See also “Mains fail event flag” on page 154.
Not in use
Not in use
This flag is active whenever a dialler connection between the panel and CS is
active.
The flag is active whenever a computer connection between the panel and
management software (Titan) is active. The flag is not to be activated until after
the connection has been established.
Line fault
Battery test active event flag is activated when a battery test is being performed
on the Advisor Master Panel or a DGP.
This event flag is active for 5 seconds after each walk test (failed, or completed).
Event flag associates an event flag with a system A event. A system A event flag
is set whenever any ACPO area A flag is set.
System B (ACPO)
Event flag associates an event flag with a system B event. A system B event flag
is set whenever any ACPO area B flag is set.
Panic alarm
The PA Global Alarm Event Flag goes active on a trigger of any PA Area Alarm
Event Flag.
The PA Global Alarm Event Flag goes inactive on a state change from active to
non-active of any PA Area Alarm Event Flags.
RAS isolated
A RAS connected to the panel LAN may be isolated via the keypad, via the Titan
Control Panel menu RAS (Isolate/De-isolate), or automatically isolated as a
result of timed persistent failure (e.g. ACPO, NFA2P).
When any RAS is isolated, regardless of how it was done, the flag will be set.
De-isolating the RAS will reset the flag.
The Panel CPU Restart even flag becomes active after the panel CPU is
restarted. It remains active until the CPU restart event is acknowledged.
Caution: It is very important to plan the Macro Logic carefully on paper, noting all
details, and the origin of every zone and/or event flags, before attempting to
program.
See also “Event Flags” (page 179) and “16-Event to output” (page 124).
Program number
Macro Logic Number
Macro No:
Enter the number of the macro logic program. There are 24 programs available.
M 1 Disabled
*-Change, 0-Exit
The result of a macro, the macro output, will trigger an event flag or a zone. The
macro output can have some timing functions.
Option Function
Disabled This macro logic program is disabled.
Non Timed Follows the result of the logic equation only. If an event flag or output for this
macro changes, the logic equation will be calculated again.
On Pulse Activates for the programmed time or the active period of the logic result,
whichever is the shortest.
On Timed Activates for the programmed time regardless of the macro output changing.
On Delay Activates after the programmed time period unless the result of the logic equation
is no longer valid.
Off Delay Follows the result of the logic equation, but remains active for the time
programmed after the result of the logic equation is no longer active
Latched Activates on any of the first three macro inputs in the logic equation and is only
reset by the fourth macro input. Any programmed AND / OR function is not used)
How to program
Press one of these keypad buttons to:
• Menu: Display a new output function.
• 0: Leave the 35-Program macro logic menu.
• Enter: Save the displayed function and move to the next display.
Time
The time period (2 to 255 seconds) that is used when any of the timed macro
output functions is selected (pulse, on timed, on delay or off delay). Use any
value of 2 or higher.
Specify if the macro output should trigger an event flag or a zone and which
event flag or zone.
How to program
Press one of these keypad buttons to:
• ?, Enter: Enter and display new event flag or zone number. Enter the same
number twice to invert the macro output. It will now trigger the event flag or
output if the result of the equation is not true. An inverted macro output is
recognised by the exclamation mark (!) preceding the number.
• Menu: Select “Event Flag” or “Zone”.
• Enter: Save the displayed details and move to the next display.
Macro inputs
M 1 = E0 Or E0 Or E0 Or E0
*-Chg, Input 1:
Program up to four macro inputs (event flag or output numbers) and whether
each of those inputs performs an AND or an OR function in the logic equation.
When all conditions of the logic equation are met, the macro output is active and
the event flag or zone programmed in the previous step is activated (depending
on any timing function programmed on the macro output).
How to program
Press one of these keypad buttons to:
• ?, Enter: Enter and display new event flag or output number. Enter the same
number twice to invert the macro input. Before calculating the result of the
macro logic equation, the input is inverted. An inverted input is recognised by
the exclamation mark (!) preceding the “E” or “R”.
• Menu: Select “Event Flag” (E) or “Output” (R).
• Enter: Save the displayed details and return to the original macro logic
display.
M 1 = E0 Or E0 Or E0 Or E0
*-Chg, Logic 1:
Specify the logical operators that create the macro logic equation. Two operators
are available: AND and OR.
Operator Description
OR Result is true if one of the inputs was active.
AND Result is true only if both inputs are active.
36 to 41-Reserved menus
Reserved. Do not use.
Each class has multiple types of alarms it can report. e.g The class Panic Alarms
contain SIA reporting for both PA (panic alarm) and HA (hold-up alarm).
For more information on classes or reporting, see “9-Communication options” on
page 94 and “Reporting” on page 182.
Class settings
Select the class condition
Condition Reports
1 Alarms
2 Alarm Restore
3 Tamper
4 Tamper Restore
5 Inhibit
6 Inhibit Restore (=uninhibit)
Use this option to select whether this condition should be reported to Central
Station 1.
Enter the time in hours and minutes, when a test call should be made. The time
programmed is based on the real time clock.
Only send a test call if no reporting during the test call interval.
Yes: Only if no event at all has been reported during the test call interval, a test
call will be made.
No: Test calls will be made after each test call interval.
44 to 49-Reserved menus
Reserved. Do not use.
Inputs
Each sub menu is broken down into group menus. For example:
Areas
Each sub menu is broken down into group menus. For example,
Area group 1 to 8
Enter channel number 00 to 99 for each area. A separate channel can be
programmed for auto arm/disarm events. The defaults are:
• Areas 1 to 16 > channels 74 to 89
System
Each sub menu is broken down into group menus. For example,
System group 1 to 10
The user can program a channel number, 00 to 99, for each of the available
system events. System events will be displayed as System Event 1 to System
Event 40. A user cross reference table will then be used to determine which
event is System Event 1 etc.
The defaults are:
Engineer Reset?
This option allows the engineer to perform a reset without having to calculate the
“ATS System Code”. When the installer presses the “*” button, the RAS displays
“Done”.
As well as the above, the user can also program alarm messages to the following
event codes, allowing for greater flexibility as required. Macros can then be used
to trigger these event codes from various sources.
E.g. an input can be programmed to report to event code 131 BA Perimeter. The
input can then be triggered using macros etc.
Note that event code 130 BA Burglary in the user table and code 1 – Burglar
Alarm BAA in table 1 are the same event codes (130). If 130, BA in the user table
is programmed with an alarm message, then this will have priority over event
code 1 - BA Burglar alarm in table 1.
This menu controls the setting to trigger an alarm input from the DVMRe by
programming an output of the ATS panel. In total 16 DVMRe alarm inputs can be
linked to an ATS output. All 255 ATS outputs can be programmed.
Setting or un-setting an ATS output triggers a DVMRe alarm input. ATS outputs
are used rather than event flags because outputs can be activated via time zones
as well.
The DVMRe can be programmed to execute a macro linked to a DVMRe input.
Enables the High Level Integration between the ATS panel and the DVMRe.
Yes: The ATS panel and DVMRe connection can be established and the next
following control flags will be considered.
This feature will ensure that the time and date of the DVMR are synchronised
approximately every 60 seconds with the ATS panel. When performing video
history searches the time and date will be based upon the occurrence of ATS
panel events.
Yes: The ATS panel time and date will be synchronised to the DVMRe.
No: No time and date synchronisation will take place.
This option automatically inserts event text from the ATS panel (printer output)
into camera 1 text box of the DVMRe. This text will be associated with the
footage recorded to all cameras with that time stamp.
Yes: The ATS panel will insert the event text to the DVMRe text box.
No: No event text insertion will take place.
The DVMR has the facility to issue user programmable strings on the occurrence
of user definable alarm conditions and motion detection. The strings will be sent
out via the HLI and received by the ATS panel. Based upon the content of the
received strings after processing, the ATS panel can manipulate zone inputs
allowing alarm reporting and control of various types to be performed.
Yes: The DVMRe will send out the user programmable strings on the occurrence
of pre-defined alarm condition.
No: No alarm condition strings will be send out.
The ATS panel will have a new menu set added which will be used to emulate a
subset of the DVMR front panel controls. This feature will allow an ATS panel
RAS permission
No RAS Assigned
RAS Permitted:
2,
RAS Permitted:
The RAS permission menu enables the Installer to select, which RASs are
connected to the panel, have permission to issue Search and Play. It also
controls commands to the DVMRe while in the Quick or User Histories.
Up to 16 RASs can be selected in this menu option to have Search and Play and
command control of the DVMRe.
Introduction
The engineer walk test allows testing of all zones that are configured for an
engineering walk test in selected areas. These areas are tested by a
technician/engineer. This test is independent to the zone configured test type and
is only run manually from a new installer menu item.
Zones are configured to be included in the engineer walk test (See 19.1.33,
Engineer walk test). The default is Yes (include in engineer walk test).
A technician/engineer starts the engineer walk test from menu 54. The areas do
not need to be armed/disarmed before a new test is started. The test can be
initiated whenever needed.
Procedure
When starting the engineer walk test the user will be prompted to select area/s to
test by the display shown below. Initially no areas are selected and the top line of
the display would be blank.
The user selects an area by entering the area number followed by the Enter key.
Areas selected are displayed as shown on the display below. Areas will be
masked so that only areas that are available for the test are those that both the
user and RAS have access to. If a user enters an area that is not available the
RAS buzzer will sound a warning (several short beeps) and the area will not be
displayed in the selected list.
1, 2
0 – All, Area
The user may select all available areas by pressing the “0” key followed by the
Enter key. Pressing Clear will cause the test to be aborted and the user will
return to the installer menu. If aborted at this stage, no event (test started, failed,
etc) will be logged and no test event flag will be set.
Press Enter (without an area number) to start the test.
Untested On 1, 2, 4
0-Cancel, Zone
Each zone that transitions from sealed to unsealed and then back to sealed will
be marked as tested. While the test is running, the displayed list of untested
zones updates automatically without user action so that zones disappear from
the displayed list as they are tested.
While the test is running, the user may enter the number of an untested zone
followed by the Enter key to display that zone’s name as shown below. Here the
user may press Next (down arrow) to scroll through the names untested zones,
or press Enter to return to the numeric list of untested zones shown above.
The test is cancelled if either the “0” or Clear or key is pressed. There is also a
maximum time limit on the test, “Disarm test time” on page 63. The test fails if
this timer expires. In either case, the “Test not completed” display shown below
will be displayed. A message is sent to the central station to indicate test failed,
see events logged table below.
Note: The warning timer functions as normal during this test. That is, a warning
will sound (if warning time programmed) in the normal fashion.
Otherwise, once all zones have been tested successfully a message “Test
Complete” is displayed, and a message is sent to the central station (see events
logged table below).
Test completed
Press ENTER
If the Clear key is pressed while the test is running, “Please wait” display shown
below is displayed while the aux output is pulsed (described further below).
When the aux output pulsing is completed, the walk test will be exited
automatically to the install menu.
At the end of the walk test, the walk test event flag will be deactivated.
Note: If Titan is connected to the panel (computer connection active event flag
set), the “WALK_TEST_ZONE_TESTED”,
“WALK_TEST_ZONE_NOT_TESTED”, “ACCESS_TEST_FAILED” or
“ACCESS_TEST_COMPLETED” will be logged in the panel and send to Titan
history.
If Titan is NOT connected to the panel (computer connection active event flag
NOT set), the “WALK_TEST_ZONE_TESTED” and
“WALK_TEST_ZONE_NOT_TESTED” will be Ignored and not logged.Only the
“ACCESS_TEST_FAILED” or “ACCESS_TEST_COMPLETED” will be logged in
the panel.
This is to prevent the panel memory from being filled with events when Titan is
not connected.
After each walk test (failed, or completed) an “Engineer Walk Test Reset” system
event flag will be activated for 5 seconds. Users may use this event flag to switch
the aux output (output 251) to reset any latched detectors in alarm.
If the user presses the Enter key to exit the test menu while the aux output is
deactivated, a closing message will be displayed as shown below. The test will
then automatically exit from the engineer walk test when the aux output is
restored.
Test closing
Please wait
55-Reserved
If the siren impedance is acceptable, the panel calculates the allowed treshold.
The panel calculates two allowed impedance ranges, one for mains supply, and
another one, wider, for battery supply.
Notes
• This data is stored in the panel non-volatile memory. It can be changed during
another siren calibration, or by setting the panel to the factory defaults. See
“14-Defaults” on page 116 for more details.
• If the siren has not been calibrated, the panel detects siren faults using the
defalut values. In this case the siren fault detection does not comply with the
EN 50131 regulations.
• The calculated values can be requested and displayed via the management
software.
The list of system events depends on the selection of the protocol type being
large or small. The small protocols only report summarised events. The large
format reports as much as possible (see Table 15 and Table 16).
Table 15 and Table 16 show a list of events to be reported split up to Contact ID
and SIA. Contact ID reports most events separately. Contact ID not only reports
the event and the point or user, but also the area. SIA reporting does not. SIA
also uses an offset to events reported from DGPs (+300) or RASs (+400).
The following zone types are additional and are not certified — do not use in
EN 50131 certified systems.
6. Pulsed Keyswitch 33. 24Hr Alarm & Inhibit
8. Dis. delay/Arm Gen. Alm 34. Area Dis/AlmGrp Restr. Arm
9. Reset Delayed Zones 35. Area AlmGrp Restr Arm Only
11. Dis. Delay Alarm 40. Dis. Susp. Delay/Arm Alm
12. Restart Exit Timer 59. 24 Hour Alarm If No TZ 41
16. 24Hr Local Mains Fail 65. Engineering reset switch
22. Dis. Delay Reset/Arm Alm 72. GVE zone
28. Armed Alarm with Reset 73, 74. Request to arm / disarm
29. 24-Hour Alarm with Reset 76. VdS tamper zone
31. Latching Keyswitch
ATS21xxE 8 to 64 zone integrated security panel with 3 A PSU, small enclosure, EN 50131
Grade 3
ATS34xxE 8 to 128 zone integrated security panel with 3 A PSU, medium enclosure,
EN 50131 Grade 3
ATS46xxE 16 to 256 zone integrated security panel with 3 A PSU, large enclosure, EN 50131
Grade 3
ATS1201E 8 to 32 zone DGP expander with 3 A PSU, small enclosure, EN 50131 Grade 3
ATS1203E 8 to 32 zone DGP expander with 3 A PSU, medium enclosure, EN 50131 Grade 3
ATS1204E 8 to 32 zone DGP expander with 3 A PSU, large enclosure, EN 50131 Grade 3
ATS1210E 8 to 16 zone DGP expander, no PSU, small plastic enclosure, EN 50131 Grade 3
ATS1210LE 8 to 16 zone DGP expander, no PSU, medium plastic enclosure, EN 50131
Grade 3
ATS1211E 8 to 16 zone DGP expander, no PSU, small steel enclosure, EN 50131 Grade 3
Isolators / repeaters
ATS LAN bus can make use of 3 isolator/repeaters in series (maximum cable
length can be extended from 1.5 to 6 km).
Reporting devices
Panel can support 1 GSM device connected onto MI bus.
When any option, any additional function or any additional zone type in this
section does not comply with the EN 50131 requirements, the EN 50131 Grade 3
label must be removed from the system. Refer to “EN 50131 compliance
precautions” in Advisor Master Installation Guide.
Access control The control of entry to, or exit from, a security area.
Active See Normal/Active/Tamper/Inhibited
Alarm The state of a security system when a device connected to a zone is
activated and the condition of the area is such that activation should be
signalled. E.g. a door lock is broken, causing a siren to sound.
Alarm group Alarm groups define the options available to users, arming stations or
door reader to allow alarm control. Alarm groups are defined by a set of
areas, alarm control functions and menu options.
Zone types for area control (keyswitches) also make use of alarm
groups.
Alarm group restriction An alarm group restriction can be assigned to an alarm group to enable
different types of user to:
• Use timed disarm option for certain area(s)
• Restrict alarm control to “Arm/reset only” on certain area(s) or
• Utilise the “User Count” or “Emergency” function.
Alarm reporting A procedure to transmit alarm events or other events to a central station
by means of a dialler and a set of rules called a protocol.
Alarm control The control over alarm functions.
Area A section of a premise which has specific security requirements. The
ATS system allows any premise to be divided into 16 areas of different
security requirements. Each area has its own zones. Each area is
identified by a number and a name. E.g. Area 1 Office, Area 2
Workshop, Area 3 Boardroom, etc.
Armed The condition of an area where a change in the status of any zone (from
normal to active) causes an alarm. An area or premise is only armed
when it is unoccupied. Some zones (like vaults) can remain armed
continually.
Armed The condition of an area or premise when it is armed (security turned
on) and unoccupied.
Arming stations (RAS) A device that is the user’s control panel for security functions for an
area(s) or for access points (doors). The arming station can be an ATS
console (LCD keypad, reader) or any other device that can be used to
perform security function, such as arm/disarm, open doors, etc.
Burglar alarm An alarm triggered by a security device like a PIR or door contact,
indicating someone has entered without authorised access.
Central station A company that monitors whether an alarm has occurred in a security
system. A central station is located away from the premise/area it
monitors.
Control panel An electronic device that is used to gather all data from zones on the
premises. Depending on programming and status of areas, it will
generate alarm signals. If required, alarms and other events can be
reported to a central station.
Cursor A flashing underline character on the liquid crystal display (LCD) that
indicates where the next character entered on the keypad will appear.
2-Area database
Select the area to program
Area name Report to Central Station 2
Exit time Report to Central Station 3
Entry time Report to Central Station 4
External siren event flag Enable audio listen in
Internal siren event flag Enable exit fault reporting
Area disarmed event flag A&B alarm reporting (ACPO)
Area active event flag Disable arming if all inhibited
Inhibited event flag KeyBox time (min)
Armed Alarm event flag Area tamper alarm event flag
Disarmed alarm event flag Arm complete event flag
Local alarm event flag Disarm complete event flag
Exit timer event flag Alert indicator event flag
Entry timer event flag Panic alarm event flag
Warning timer event flag Anti-mask/fault event flag
Chime/camera event flag Part set exit time
Pre-alarm timer event flag Part set entry time
Anti-mask reset event flag Part set exit buzzer
Latched reset event flag Part set external siren
Alarm-A event flag Part set access to E/E
Alarm-B event flag Enable part set reporting
Out-of-hours timezone Disable part set B-alarms
Area disarmed time Chime on RAS
Report to Central Station 1
4-DGP database
DGPs to be polled
DGP type
DGP Tamper (ACPO) Area
DGP battery test event flag
5-Alarm groups
Alarm group number
Alarm group name Modem access
Areas assigned Alarm group restriction 1
User alarm group Alarm group restriction 2
Alarm system control Alarm group restriction 3
List of areas Alarm group restriction 4
Keypad duress Alarm group restriction 5
Reset system alarm Alarm group restriction 6
Disable auto-uninhibit AlmGrp restriction 7, Emergency
Restricted To Arm & Reset AlmGrp restriction 8, Counter
Disarm only No arming if restriction not timing
Alarm reset only Change own PIN only
Auto inhibit active zones Allow Stop Voice reporting
Forced arming when active Timezone
Prevent forced disarming Alternate alarm group
7-System options
Areas selected for total disarm Inhibit alarm report on exit fault
Film low level Disable tamper report in disarm
Film out level Inhibit ext.sir&strobe for disarm tamper
Test mode ATS system code
No. of output controllers Soak test days
Zone event text ACPO
Alarm code prefix EE confirm disable (ACPO)
LCD rotation delay Engineer reset on ACPO zone B alarm
LCD rotation speed NFA2P
Dual zone Installer dual code
Auto uninhibit on disarm Enable buzzer on mains/line fault
Display one zone at a time Enable "Call Central Station" display
Username file Scandinavian indicators
System alarms set siren and strobe Enable log limitations
Latching system alarms Indicate inhibited zones
Siren testing Confirm area
Disable "0, ENTER" for camera reset Eng Rst on ACPO zone B tamper
Disable insert of AG restriction Eng Rst on ACPO system B tamper
Reserved Security grade
Disable code from displaying Ignore AC mains fault when arming
Disable flashing area LEDs Latch mains/battery/line faults
Two users before programming code Enable PA siren on FTC
Display alarms instantly on LCD Latch AWDGP jam and supervision
Sirens only after FTC Enable chime
Financial options Synchronize DGP users records
Display user flags Engineer reset on RAS lockout
Delayed disarmed alarm lockout Prevent arming on faults
Zone expansion fitted PIN of the day option
Inhibit zone tamper Override AC mains fail
Report multiple alarms Override battery fault
Report multiple restores Override signalling fault
Engineer reset for system alarms Override siren fail
Engineer reset for system tampers Override detector trouble
Ignore battery fault when arming Override tamper
User can do engineering reset Override interconnection fault
8-Auto reset
Auto reset time
Reset alarm group
9-Communication options
PABX number Select the reporting format
MSN number Enter the 1st phone number
Dial tone detection Enter the 2nd phone number
Select tone dialling System account number
Enable PSTN line fault monitor Area account numbers
Monitor service tones Use BELL modem tones
Use 3 digit SIA extensions Dual reporting
ISDN point to point Allow audio listen in
Enable ISDN line fault monitor Disable reporting of inhibits
200 baud reverse area OP/CL Reserved
X25 TEI value X-SIA max characters
Audio listen in time X25 account code
Audio listen in frame X25 line type
Report mains fault Connection type
Report line fault Suppress FTC for voice
GSM line fault Retry counter
Select the central station
SIA area modifier
X25 D-Bit
Mains fail reporting delay [min]
Enable IP line fault monitor
AWDGP reporting codes for IMQ
12-LED test
13-Timezones
Select timezone
Program start time, hours Program end time, minutes
Program start time, minutes Days
Program end time, hours
17-Auto arm/disarm
Auto arm/disarm program
Timezone to arm/disarm Alarm group to auto arm/disarm
18-Vaults
20-System codes
System code 1 System code 2
Card offset 1 Card offset 2
21-Zone shunts
Shunt timer number
Zone number to shunt Shunt zone when disarmed
Output number to start shunt Shunt zone when armed
Shunt time Cancel door event flag
Shunt warning time Zone holds event flag for 2 seconds
Shunt event flag Entry/exit shunting
Shunt warning event flag Log door open/close
Door open command starts shunt
26-Reserved menu
27-Reserved menu
29-Computer connection
Enable remote up/download Computer address
Up/download if any area armed Security password
Enable remote control Connection attempts
Remote control if any area armed Number of rings before answering
Use modem init string Number of calls before answering
Enter modem init string Answering machine defeat
Report alarms to computer Reserved
Report access events Use Bell 103 protocol
Computer telephone number Connection type
Up/Download callback number Authorize computer connection
Service telephone number
31-Battery testing
Select battery test program Select battery test
Battery test frequency Manual battery test
Start battery test Battery test report
Battery test period Select DGP for battery test
36 to 41-Reserved menus
44 to 49-Reserved menus
50-Channel mapping
Inputs Input group 1-16
51-Engineering reset
52-Voice reporting
53-Program DVMRe
DVMRe alarm input map Enable event text insertion
Enable DVMRe interface Enable alarm feedback
Enable time update Enable history Search and Play
54-Test zone
55-Reserved
56-Siren calibration