Manual OP25 Manual
Manual OP25 Manual
Introduction
Operator Panel
OP25, OP35, OP45 Commissioning and Operation
Appendices
Glossary, Index
6AV3991–1AD02–0AB0
Release 04/96
Safety Guidelines This manual contains notices which you should observe to ensure your own personal safety, as
well as to protect the product and connected equipment. These notices are highlighted in the
manual by a warning triangle and are marked as follows according to the level of danger:
Danger
! indicates that death, severe personal injury or substantial property damage can result if proper
precautions are not taken.
Caution
! indicates that minor personal injury or property damage can result if proper precautions are not taken.
Note
draws your attention to particularly important information on the product, handling the product, or
to a particular part of the documentation.
Qualified Personnel Equipment may be commissioned and operated only by qualified personnel. Qualified personnel
within the meaning of the safety notices in this manual are persons who are authorized to commis-
sion, ground and identify equipment, systems and circuits in accordance with safety engineering
standards.
Warning
! The equipment may be used only for the applications stipulated in the catalog and in the techni-
cal description and only in conjunction with other equipment and components recommended or
approved by Siemens.
Faultless and safe operation of the product presupposes proper transportation, proper storage,
erection and installation as well as careful operation and maintenance.
Startup must not take place until it is established that the machine, which is to accommodate this
component, is in conformity with the guideline 89/392/EEC.
Trademarks SIMATIC and SINEC are registered trademarks of SIEMENS AG. Some of the other desig-
nations used in these documents are also registered trademarks; the owner’s rights may be violated
if they are used be third parties for their own purposes.
Purpose This equipment manual contains precise information about the functionality
and technical design of operator panels OP25, OP35, and OP45.
Audience The present equipment manual is written for operators, fitters, configurers, and
system support engineers.
The operator of an operator panel will find all the information he requires for
handling the device in Part II.
For the fitter, Part IV contains all the information he requires to install and
commission the operator panel.
Applicability The different versions of the equipment manual refer to the following OP firm-
ware and ProTool versions:
Further support Should you have any queries regarding technical matters, please get into touch
with your point of contact at the Siemens agency or branch responsible. You
will find the addresses in Appendix F of this manual, in catalogs, and in Com-
puserve (go autforum) ..., for instance. In addition, you can call our hotline by
dialing +49(911) 895-7000 (fax 7001).
Related The illustration shown below provides an overview of how the complete range
documents of documents covering manuals and online help is organized. The present
manual is shaded.
PC
!
Configuration
" "
OP
Installation
Operation
"!
"!
"!
" " "
PLC
"#
Connection !
"
!
Part I: Introduction
1 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1 The Operator Panel at a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.2 Process Visualization and Manipulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
2 Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Part V: Appendices
A Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
B Interface Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
B.1 Interface Assignment for OP25 and OP35 . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
B.2 Interface Assignment for OP45 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
C Test Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
C.1 Hardware Test for OP25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-2
C.1.1 General Operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
C.1.2 Individual Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
C.1.3 Test Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-7
D System Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
E ESD Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-1
F Siemens Worldwide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1
Application of Operator panels OP25/35/45 allow a realistic graphical display of the ma-
operating panels chine or system under supervision and are designed for easy machine control.
With operator panels OP25/35/45 you can
Control and supervise the process by means of menus – for example, you
can control setpoints or signal control elements by means of inputs, soft
keys, and function and system keys.
Visualize processes, machines and systems as pixel or character graphics
images.
Display event and alarm messages as well as process variables as an out-
put field, a bar graph, trends or a status display, for instance.
Intervene in the process flow using the integrated keyboard.
Installation Operator panels OP25, OP35 and OP45 are panel mounting devices for use
options locally on the machine.
Due to the high degree of protection (IP65 at the front panel), the OP is also
suitable for hostile industrial environments.
Possible installation locations for the OPs are:
Cabinets or panels
19” cabinets or racks (OP35 and OP45 only)
Controller
OP25, OP35, OP45
Printer
OP45
OP35
OP25
Screens Process values and process sequences are shown by screens which can con-
tain graphics, texts and values. Process values in a system are often related
in some way. Screens show this relationship and thus represent an image of
the process.
Full graphic plant The OP permits you to represent machines and plants as full graphic
screens screens. This improves operator orientation.
Bars, curves You can show current process values (e.g., filling level and speed) as numeric
values, or symbolically as text or bars.
Curves are a particularly good way to show changeable process values (e.g.,
changes in temperature) over a period of time.
Symbolic graphics Symbolic graphics are another way to indicate process values. Symbolic
graphics are graphic elements (i.e., bit maps) which are indicated alternately
to show different process states (e.g., valve open or closed).
Process manipula- The operator can use the OP’s integrated keyboard to intervene in the process
tion sequence.
For example, you can control actuators (e.g., valves) by specifying process
values (i.e., setpoints).
Features important to operator control include ease of handling, short training
periods, and a high degree of reliability.
You can configure the structure of the OP operating environment as desired
(i.e., you can tailor operator control to your particular application).
A few features:
Free configurable function keys
Softkeys
Pop-up windows for symbolic entries
Messages Process or machine states (e.g., the current operating mode) are displayed by
the OP as plain-text event messages.
Alarm messages provide information on critical machine states.
Current measured values (e.g., temperatures, speeds, etc.) can also be in-
cluded in the text of event or alarm messages.
Event and alarm messages are stored with date and time in a message buffer.
At the same time, all event and alarm occurrences can be printed (if message
logging is switched on and a printer is connected).
Information texts Information texts can be configured. You can use them to give the operator
additional information which will help him/her to correct a malfunction.
Recipes Complete blocks of machine data can be stored as recipes on the OP.
The structure of a recipe is specified during the configuring phase. It makes
no difference whether the recipes are “real recipes” or only piece number
specifications, traversing paths or temperature progressions.
You can change or redefine recipe data directly on the OP.
Password protec- The OP offers password protection. Each operator can be assigned a differ-
tion ent password. A password level can then be used to enable or disable each
operator’s access to special operating functions. This prevents incorrect en-
tries and improves system security.
Multiple languages All messages and texts for screens can be stored in the OP in up to three dif-
ferent languages.
This permits international use even when operating personnel speak different
languages.
2) The immunity to interference cannot be guaranteed on account of the hardware characteristics of the OP45
3) Driver available as an option
Screen section One screen takes up the entire display. An example of a possible layout is
shown below.
Fixed window
Fixed window The fixed window provides the operator with a continuous stream of important
process variables regardless of which screen is open at the moment.
Main screen area The main screen area contains the actual contents of the currently opened
screen.
Additional windows (e.g., message windows, help windows and pop-up win-
dows) are faded in over the main screen area and the fixed window.
3.1 Keyboard
Function keys/ A function key always triggers the same action in the OP or controller (i.e.,
softkeys global significance for the OP) regardless of which screen is currently open.
A few possible actions are listed below.
Open a screen
Indicate the current alarm messages
Start a hardcopy of a screen
Indicate the time window
The term softkey means that function keys can have a meaning related to the
currently open screen (i.e., local).
The function of a softkey can vary from screen to screen. When a screen is
open, a softkey’s function is shown by an icon in the margin of the monitor
screen.
The following keys can have softkey functionality:
For OP25: F1 to F14
For OP35/OP45: F1 to F20
Repeat function The repeat function activates when a key is repeatedly pressed.
(for OP45 only)
Note
Do not press several keys on the OP45 at the same time. This can cause incor-
rect entries.
System keys The system keys are used to make entries on the OP.
Figure 3-2 shows the system keyboard for the OP25 and OP35/OP45.
OP25 OP35/OP45
A B C D E F
7 8 9
A B C D E F G H
/ 7 8 9
G H I J K L
4 5 6
I J K L M N O P
* 4 5 6
M N O P Q R
1 2 3
Q R S T U V W X
– 1 2 3
S T U V W X
. 0 +/–
Y Z : \ = , ( )
+ . 0 +/–
Y Z INS
ALT
A–Z A–Z
ACK
A–Z
ACK
A–Z
CTRL
A–Z
SHIFT
HELP ENTER
HELP ENTER
Note
The TAB, ALT, CTRL and SHIFT keys of the OP35 have no function.
Key functions The control keys of the OP have the following functions:
Key Description
Shift key This key is used to shift the input keys from numeric to
A–Z
alphanumeric.
The key is equipped with two LEDs which indicate the
current status.
No LED is on.
Numeric assignment of the input keys is active.
Alphanumeric assignment of the input keys becomes
active when this key is pressed once.
One of the two LEDs (i.e., left or right) is on.
Left or right alphanumeric assignment of the input
keys is active.
Input key assignment alternates between the left and
right alphanumeric assignment each time this key is
pressed.
A–Z
A–Z Switches the active window (OP25/OP35 only)
Switch from alphanumeric assignment of the input
keys back to numeric assignment
INS Activates edit mode (OP25/OP35 only)
DEL
Deletes/inserts single characters
Cancel key This key cancels already started actions. Some examples
ESC are listed below.
Delete an already entered character for a value input
Delete a queued system message
Acknow- This key acknowledges the currently indicated alarm
ACK ledgement message or all messages of an acknowledgement group.
key The LED remains on as long as an unacknowledged
alarm message is queued.
Info key This key is used to open a window containing a help text
HELP for the selected object (e.g., message, input field).
The LED goes on when a help text is available for the
selected object.
The help window is closed by pressing any key.
Procedure The basic procedure for entering values on the OP is described below.
1. Using the cursor keys, position the cursor on the desired input field.
2. Enter the value. The method of entry varies depending on the type of field.
See the following subsections for information on handling the individual
fields.
3. Confirm the entry with with ENTER key.
Correcting/cancel- The following methods of correction are available before the entry is applied.
ing entries
Using the INS/DEL key, insert/delete single characters where the cursor is
positioned. Then use the ENTER key to confirm the correct value.
Cancel the entry with the ESC key.
The original value is then automatically rewritten in the field. Enter the
correct value, and confirm with the ENTER key.
Edit mode An edit function is available on the OP25/35. This edit function can be used to
(OP25/35 only) edit entries which have already been applied.
1. Position the cursor on the desired input field.
2. Activate edit mode by pressing the INS/DEL key.
In contrast to input mode, the indicated value is retained.
3. Move the cursor to the appropriate position of the input field.
4. Using the INS/DEL key, insert/delete characters where the cursor is posi-
tioned.
5. Confirm the entry with the ENTRY key.
The entry can be canceled with the ESC key. The old value is indicated
again.
The shape of the cursor changes in input mode. Input starts at the right-hand
edge of the input field. Digits are shifted to the left similar to a pocket calcula-
tor.
Enter S B T
A E F The characters A to F must be entered in
hexadecimal to alpha mode.
value 0 9
to
Enter digital S0 1
,
value
2 Apply entry The entered value becomes valid.
The entry becomes invalid if the en-
ENTER
Correction If you have made a mistake and have not yet applied the entry, proceed as fol-
lows:
Both numeric characters (i.e., digits) and alphanumeric characters (i.e., letters
of the alphabet) can be entered in a string field. Strings may also contain
blanks.
The cursor changes shape in input mode. The entry starts at the left edge of the
input field. The cursor jumps one position to the right each time a character is
entered.
S BT
A Y Z
to
2 Apply entry The entered string becomes valid.
ENTER
Switch back from alpha mode4
Or
Cancel entry The input cursor is deleted.
Switch back from alpha mode1
ESC
Correction If you have made a mistake and have not yet accepted the entry, proceed as
follows:
Key Display
A–Z
U V
A–Z
, V
E F
A–Z VA
,
M N
A–Z VAL
,
S T
VALV
I J
A–Z VALVE
,
K L
A–Z
, VALVE
A–Z
, VALVE
0 VALVE 0
5 VALVE 05
Entries in symbolic fields are made with a pop-up window indicating the en-
tries available for this field.
2 Select entry
–
Off
On
–
Off
On
Selecting a win- Use the middle cursor key to select the window in which you want to work or
dow make entries.
Key Description
A–Z
A–Z
Each time you press this key the cursor jumps from one
window to the next.
The window in which the cursor is located is the active window (i.e., you can
make entries or perform other operations in this window).
Restrictions/ You cannot switch to windows which do not contain input fields.
special features
Exceptions: Message line, message window and message page
For these exceptions, the cursor is positioned on the first message. You can
then select the information text pertaining to the message.
Static and dynamic The position of the displayed window is static on the OP25.
windows
When an alarm message window or a pop-up window is displayed, for exam-
ple, an entry field hidden by the window cannot be used.
Generally, entries on the OP25 cannot be made unless all windows are closed.
The OP35 can be configured with dynamic window positioning.
When a window is to be displayed, it jumps automatically to a position which
does not cover up the input field or the cursor.
This means that entries can always be made regardless of the contents of the
display.
The OP is to control and monitor a plant which mixes and bottles various fruit
juices. Plant functions are divided roughly into the mixing and bottling sta-
tions.
Mixing station The ingredients for the juices are stored in three tanks. The ingredients are
mixed in certain proportions depending on which fruit juice is to be produced.
Bottling station After the juice is mixed, a valve is opened, and the finished fruit juice flows
into a filling tank and is then bottled. The bottles are transported on a con-
veyor belt. Before being filled, they are checked for glass breakage. After
being filled, the bottles are sealed, labelled and palletized.
MIXER
Bottling station
Labelling
From
the mixer
Palletization
Mixing Station
Ingredients (in l)
1 Tank 1 Tank 2 Tank 3
2
3
4
Amount in 5
the mixer Valve 4
(in l)
6
4 4 7
Via function key You can open a certain screen by pressing a function key (or a softkey).
Via input field A screen is opened after an entry has been executed in an input field config-
ured for the selection of this screen.
Via job from the When the state of the process/plant requires, the controller causes a screen to
controller be selected on the OP.
Main screen The standard screens are called from a main screen via softkey.
Main screen
Softkeys for
selecting
the stan-
dard
1
screens
2 3 4 5 6
1 Password processing
2 Printer settings
3 Status Variable
4 System settings
5 Message processing
6 Mixing station (our example)
For detailed information on function and use of the standard screens, see the
applicable sections in this manual.
Event messages The fruit juice plant has finished a mixing procedure. An event message in-
forms the operator of this. The event message might look something like this:
Alarm messages The operator would now like to start the bottling procedure but has forgotten to
open the filling valve. The controller automatically stops the bottling proce-
dure and outputs an alarm message. The alarm message might look something
like this:
Available methods The OP offers the following ways to indicate event and alarm messages.
of indication
Message line, You can indicate a current event or alarm message in a message line or in a
message window message window.
You can configure one of the following combinations:
Event message The operator can look at all still queued event messages or alarm messages on
page, alarm the appropriate message page.
message page
Message buffer The OP stores all messages in a battery-buffered memory. The operator can
look at these stored messages.
Indication priori- Each message is given a priority during configuration. This priority deter-
ties mines the importance of the message.
When several messages are queued, the message with the highest priority is
indicated first.
When several, unacknowledged alarm messages are queued, either the first
(i.e., the oldest) or the last (i.e., the latest) message is indicated.
The operator can change the configured type of indication (first/last).
When several event messages with the same priority are queued, the latest
is indicated.
Message indicator At least one alarm message is still queued when this symbol appears on the
OP’s display.
Acknowledging Alarm messages must be acknowledged by either the operator or the controller.
alarm messages
Key Description
Acknowledge indicated alarm message
ACK
Message line The message line is always present regardless of which screen is selected.
Depending on your configuration, event messages and/or alarm messages are
displayed in the message line.
Example of an event message:
Flashing alarm Alarm messages flash to distinguish them from event messages.
messages
Priorities of indica-
Alarm messages Alarm messages always take precedence
tion over event messages.
Message window In addition to the message text, messages in a message window contain other
information (e.g., message number and date/time of the arrival of a message).
Example of an alarm message window:
Event message The event message window is not automatically faded in. It must be selected
window by the operator or the controller and then deselected again later.
A standby message is displayed when no current event message is queued.
Alarm message The message pages give the operator an overview of the still queued (i.e., not
page, yet departed) alarm or event messages.
event message
The event message page or the alarm message page can be selected on the OP
page
or via the controller.
The individual message occurrences are sorted by indication priority and, if
alarm messages, listed by first/last setting.
Example of an alarm message page:
If all messages do not fit on the display at the same time, you can scroll the
contents of the message page up/down with the , cursor keys.
The message page contains the following information for each message occur-
rence.
Message number
Message status with date and time
The OP updates the message status display (e.g., K for arriving, Q for
acknowledged).
Acknowledgement group to which an alarm message belongs
Message text, with process values if applicable
When a message contains process values, the OP indicates these values as
they were when the state occurred or stopped occurring (i.e., time of arrival
or time of departure).
The OP does not acquire current process values after the message has been
acknowledged.
To message buffer You can switch back and forth between indication of the message page and the
and back message buffer by repeatedly pressing the function key which you used to call
the alarm message page/event message page.
Message logging All message occurrences are logged directly on a printer (if message logging is
switched on and a printer is connected).
Alarm message The stored message occurrences are indicated in the alarm message buffer or
buffer, event the event message buffer depending on what type of message they are.
message buffer
A buffer page can be selected on the OP or via the controller.
All messages are indicated in the order of when they occurred. The latest
message is shown at the top of the display.
Example of indicating the alarm message buffer:
If a message text contains process values, the OP indicates these values as they
were when the message occurrence arrived and departed.
Otherwise, the information is identical to that of the event message page or
alarm message page.
Deleting the buffer The event message buffer/alarm message buffer can be deleted by operator
input on the OP or via the controller.
Exceptions:
Queued messages
Not yet acknowledged alarm messages
Buffer overflow The OP stores message occurrences in a common memory area for event and
alarm messages (i.e., the so-called message buffer).
If there is only a certain amount of memory space left in the message buffer
(i.e., remaining buffer space), the OP can fade in a system message to that ef-
fect.
If there is no space left in the message buffer and new messages arrive, the OP
continues deleting message occurrences from the message buffer until a certain
remaining buffer space is available again.
The oldest message occurrences are deleted in the following order.
1. Event messages which have already departed
2. Alarm messages which have departed and have been acknowledged
3. Event messages which are queued
4. Alarm messages which are queued
A forced printout of the deleted messages is made (if overflow was configured
as on, and a printer is connected).
Layout Event and alarm messages can be processed with the standard screen Message
Processing.
Message Processing
ESC Softkeys
1 2 3 Return to main
screen
System messages inform you of certain internal operating states of the OP.
The messages include everything from informational notes to serious and fatal
error messages.
System messages can be caused by the following:
Operator errors
(e.g., illegal entries)
System errors
(e.g., disturbed communication between OP and controller)
System message As soon as a certain operating state/error occurs, the OP automatically fades in
window a window containing a system message.
Example of a system message window:
Message number
i
210 Buffer overflow warning
A system message consists of a message number and a message text. The mes-
sage text can also contain internal system variables which help to localize the
cause of the error message.
Some system messages expect a confirmation from or a decision by the opera-
tor. For example:
“Format data medium? 0 Yes/ 1 No”
The entry of 0 (yes) or 1 (no) then determines what happens next.
Deselecting The system message window can be closed by pressing the cancel key or by
selecting another screen.
Error causes, The appendix of this manual contains a list of system messages including addi-
remedies tional information on the cause of the message and any system variables indi-
cated. In some cases, possible remedies are also shown.
Tank 1
Tank 2
Mixing time
Bottle size
Label
Bottles per case
Data records The data records for a recipe are put together on the OP. An example of how
they could appear is shown below.
Tank 1 90 70 0
Tank 2 10 30 100
Mixing time 5 10 0
Bottle size 1 0.7 1
Label 4 2 1
Bottles per case 6 12 6
Analogy of a file A file cabinet is a good way to illustrate how recipes function.
cabinet
The file cabinet is the plant or the process to be controlled. Each of the indi-
vidual drawers represents the fixed structure of one recipe. Index cards in the
drawer contain the data records for that recipe.
LEMON
.......
Juice
Nectar
Drink
ORANGE
The operator uses the operator panel to “handle the index cards”.
We will now show you how to do this in the following subsections.
The standard screen Data Record Processing is available for processing data
records. A second standard screen called Data Record Transmission provides
you with special transmission functions.
Softkeys
ESC
Softkey Description
A-Z SAVE Copy the current values from the PLC to the OP and store
them as a data record on the required storage medium
( Chap. 13):
OP25/35: internal flash memory or Jeida / PCMCIA-
module
OP35/45: floppy disk
OP45: hard disk
A-Z LOAD Load the selected data record from the selected storage
medium in the OP and transfer to the controller
A-Z DELETE Delete the selected data record from the selected storage
medium
Note:
If you want to delete all data records, it is easier to just
reformat the FLASH memory or floppy disk.
A-Z EDIT Edit (change) the selected data record on the selected
storage medium
Data record trans- You can transfer the current values back and forth between the OP and the con-
mission screen troller without storing the values on a data medium. This makes process start-
ups easier, for example.
Transmission between OP and data medium is also possible.
The Data Record Transmission screen is available for these transmissions.
ESC Softkeys
Softkey Description
Transfer the current values from the controller to
SPS OP the OP (update values in the OP)
General use The following table shows you how to use the standard screens “Data Record
Processing” and “Data Record Transmission”.
ORANGE Recipe
Drinks 05.10 11:34 Commentary
Nectar 05.12 20:17 Commentary
Juice 05.13 08:56 Commentary
Only the recipe structure is specified during configuration of the OP. No data
records exist yet. These are generated/set up on the OP.
Setting up/editing The standard screen called Data Record Processing contains an edit function.
data records You can use this function to accomplish the following.
Set up new data records on a selected data medium
Change the contents of data records stored on a data medium
To set up/edit data records, proceed as follows.
1. Select recipe.
2. Enter data record names.
If you are setting up a new data record, enter a data record name which
does not exist yet.
3. Select data medium on which the data record is to be stored.
Note
The data medium must be formatted before data are stored on it for the first
time.
The screen called Data Record Processing contains a format function which
you can use to format flash disks and diskettes.
Note
Comments entered in the data record trans-
mission screen are not included in the edit
window.
Accepting values If you want your data records to contain the current values from the controller,
from the controller perform the following steps in the Data Record Processing screen.
1. Select recipe to which a data record is to be assigned.
2. Enter data record name and commentary (commentary is optional).
3. Select data medium on which you want the data record stored.
4. Store the data record.
The current values from the controller will now be transferred to the OP
and stored as a data record on the data medium you have selected. The
time at which the storage took place is also included.
Note
If the recipe does not yet contain a data record with the same name, the record
is stored immediately.
Otherwise, you will be asked if you really want to store the record before it is
overwritten.
5. To set up additional data records, repeat steps 1 to 4 for each data record.
Copying data Copying means that you use the current values in the OP as your basis, and
records transfer these values to the data medium under different data record names.
You can then edit/adjust these data records later.
Proceed as described below in the Data Record Transmission screen.
1. Select recipe.
2. Enter data record name and commentary (commentary is optional).
3. Transfer data record from the OP to the data medium.
4. Repeat steps 1 to 3 for each new data record.
Definition The parameter record is a combination of one data record each from various
recipes with a common name.
The data records of a parameter record contain all values required to set a ma-
chine or plant. For example, you can use a parameter record to load the basic
settings for machines which are identically equipped but produce different
products.
Example We will now expand our example of a fruit juice plant to include three identi-
cally equipped production lines. The recipes ORANGE, GRAPEFRUIT and
LEMON are run parallel on these production lines. Each of the recipes con-
tains a “drink” data record. These three data records make up the parameter
record called “drink”.
At the beginning of a shift, for example, each of the three production lines
must be set to produce a special drink. You can do this with just one load op-
eration.
Processing A parameter record is processed in the Data Record Processing screen in the
same manner as a data record.
The following can be performed on a parameter record.
Select
Store (set up)
Load
Delete
Selection Parameter record must be selected as the recipe name in the Recipe: symbolic
field.
Note
When parameter record” is selected as the recipe, all data records of all
recipes are indicated after the SELECT softkey is pressed in the data record
selection window.
Parameter records (data records which exist more than once with the same
name) are identified with an asterisk (*) preceding the name.
Saving (setting up) There are two ways to set up (i.e., to save on data medium) a parameter record
in the Data Record Processing screen.
a) Save a data record for each recipe.
1. Select Parameter Record as recipe.
2. Specify data record name and data medium.
3. Save parameter record the same as a data record.
b) Store a data record individually for recipe selected.
1. Select recipe name.
2. Specify data record name and data medium.
3. Save data record.
4. Repeat steps 1 and 3 for each data record.
Load All data records with the selected name on the data medium are loaded to the
OP, and then to the controller.
Use the procedure described in section 6.1.1.
Note
Depending on the scope of the recipes, it may require a relatively long period
of time to transfer a parameter record to the controller. For this reason, a pa-
rameter record should only contain those recipes which are absolutely neces-
sary.
7.1 Hardcopy
Trigger The hardcopy is triggered by pressing a function key. The screen indicated on
the display is then printed as characters (ASCII) or as pixel graphics. Win-
dows currently opened in the screen (e.g., message windows) are not included
in the hardcopy.
Cancel You can cancel an already started hardcopy by pressing the HARDCOPY key
again. A system message is issued each time a hardcopy is cancelled.
Switch message You can switch message logging on and off on the OP.
logging on/off
All message occurrences for which logging is configured are printed out if
message logging is active.
Buffering print During message logging, you can print out messages at the same time. Mes-
jobs sages arriving while the copies are being printed are stored in the buffer and
printed somewhat later.
Configure forced If forced logging has been configured, the messages deleted from the OP are
logging automatically output on a printer when the message buffer overflows.
Function For logging purposes, you can configure a list containing up to 20 screens,
which are printed automatically one after the other, one screen per page, after a
print job has been initiated.
If a screen contains output fields for process values, the current values from the
controller are printed for these fields.
Trigger Printing is initiated by the PLC by pressing a function key or job 85. If printing
is initiated by the PLC job, a maximum of 3 screens can be printed.
Printing several You can define and print several different screen lists by embedding this func-
screen lists tion several times – for example, by assigning it to several function keys – or
by passing on PLC job 85 several times.
Restrictions Printing is performed in ASCII mode (i.e., graphic elements in the screens such
as full-graphic screens, curves and bars are not printed). Hardcopy is disabled
during the printing procedure.
Password, A protected function cannot be used without first entering a password with a
password level certain password level. This password level determines the access rights of the
operator.
The required password level is specified during configuration and can be a
number from 0 (lowest level) to 9 (highest level).
Super user This super user has a level-9 password which is especially specified for this
purpose during configuration. It permits all operator actions.
The default system superuser password is ”100” on the standard screen on
leaving the factory. The super user password can be changed on the OP.
Password screen A standard screen called Password Processing is available for entering pass-
words and assigning passwords/levels.
Password Processing
Login:
Edit:
ESC
Password list
Figure 8-1 Standard screen: Password Processing
Login via A login window appears automatically if you want to make an entry or use a
login window function which requires a higher password level than the current one.
After you have entered a valid password, a jump is made back to the place at
which you attempted to make an entry or use a function.
You can now repeat your entry.
Automatic logout The operator is automatically logged out if no operator actions are performed
on the OP within a period of time specified during configuration.
Access rights You only have access rights to passwords whose level is equal to or less than
the level under which you are logged in.
View password list The password list is called from the Password Processing standard screen with
a softkey.
The passwords and their assigned level are displayed in a pop–up window.
Note
Only those passwords are displayed whose password level is less than or equal
to the level in which you are currently logged in.
If there are so many passwords that they cannot all be displayed at the same
time, you can scroll through the display with the cursor keys.
Status Variable You can use Status Variable to display the status of operands of a SIMATIC S5
or S7.
Force Variable You can control operands of a SIMATIC S5 or S7 with Force Variable by mo-
difying the variable values and transferring them back to the PLC.
Status Variable The Status Variable standard screen is selected in the main screen with a soft-
standard screen key.
Status Variable
MPI Operand Format Value
12 DB, DBB 100 10 BIN = 00000000 00000000
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
123
Status: ESC
Update running
With the OP35/45, every line contains data for an operand; with the OP25, the
display is spread over two lines owing to the limited display area.
Status Variable
12 DB, DBB 100 10
BIN = 00000000 00000000
1 ?????? 0
????????? 0
1 ?????? 0
????????? 0
1 ?????? 0
????????? 0
1 ?????? 0
????????? 0
Operands for Figure 9-3 shows an example of the layout of a line for the SIMATIC S5.
SIMATIC S5
DB, DW 28 34 KF 20
Operands for Figure 9-4 shows an example of the layout of a line for the SIMATIC S7.
SIMATIC S7
Note
A system message appears if you make a wrong entry (e.g., data
format does not agree with data type entered). The first entry
from the pop-up window is then accepted by default in the field.
2 START When this softkey is pressed, status processing is switched to Update running.
123
update The values of the operands are then shown in the last column. The values are
updated cyclically.
3 STOP When this softkey is pressed again, status processing returns to Status stop.
123
update
Function In addition to the functions of Status Variable, values of operands can be modi-
fied ( = controlled) with Force Variable.
Force Variable You have to configure the Force Variable standard screen in ProTool; you se-
standard screen lect it by means of a function key.
Force Variable
MPI Operand Format Wert
12 DB, DBB 100 10 BIN = 0000000000100000
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
1 ?????? 0 ????????? 0
Force Input/Start
Return to the main screen
Start/Stop update
Figure 9-5 Force Variable screen of OP35 and SIMATIC S7
With the OP35/45, every line contains data for an operand; with the OP25, the
display is spread over two lines owing to the limited display area.
4 START 123 The following occurs when the softkey is pressed again.
force All operand values marked with an modification identifier are transferred to
the controller.
The modification identifiers are reset.
A return to status processing is made automatically (status Update running).
Or
Cancel ESC
The modified values are not transferred to the controller when the FORCE
entry VARIABLE screen is exited or
OP25/OP35 OP45
Software
installation
Start screen
Caution
! With the SIMATIC S5, compression of the internal program memory on the
PLC (PU ”Compress” function, integrated COMPR FB) is not allowed if an
OP is connected. During compression, the absolute addresses of the blocks are
modified in the program memory. Since an OP reads the addresses only during
start-up, it does not detect the change of address and accesses wrong memory
areas.
If compression cannot be avoided during routine operation, switch off your
OP before compression.
Proceed as follows:
1. Using a suitable standard cable, connect the IF2 (V.24/TTY) interface of
the OP with the configuration computer (PC/PG).
2. Switch on the power supply of the OP.
Since no configuration is loaded, the OP automatically goes into transfer
mode and waits for data to be transferred.
3. Download your configuration from PC/PG to the OP.
The firmware of the OP is automatically transferred too.
Note
See the ProTool description for a detailed description of how to proceed.
After successful completion of the data transmission, the OP boots (the mes-
sage AG-Anlauf disappears when the ESC key is pressed) and displays the
start screen.
Caution
! Make a backup copy of the original floppy disk, and only use the backup copy.
Transferring the Transferring the configuration is described in detail in the ProTool User’s
configuration Guide.
10.3 Recommissioning
Serial Transfer When the serial transfer is used, the configuration is transferred via a
V.24/TTY link between the PC/PG and the OP.
Proceed as follows.
1. Using a suitable standard cable, connect the IF2 interface of the OP25/35
respectively the COM2 interface of the OP45 with the configuration com-
puter (PC/PG).
2. Turn on the power supply of the OP.
3. During startup5, press the key combination
+
ESC
5) OP35: Press these keys when the RAM test (“Testing Memory...”) has been concluded in the self
test, and keep these keys pressed until the test results have been deleted.
Note
Disconnection/reconnection of the cables is not necessary for the transfer
if the OP and the configuration computer are already linked on the MPI
bus.
If you are using the PPI bus, we recommend disconnecting the OP from
this bus since you can perform the transfer at a much higher speed than the
9600 baud rate of the PPI bus.
MPI TRANSFER
Indication of the cur-
rent (configured) baud
rate/entry of another
MPI Baudrate = 187.5 baud rate
V.24/
TTY ESC
The baud rate can be set from 9.6 Kbaud to 1.5 Mbaud.
5. Transfer configuration from configuration computer (PC/PG) to the OP.
See ProTool User’s Guide for details on how to proceed.
During the self-test, the OP checks the functionality of the most important
components and indicates the test results.
OP startup
The test results are deleted.
If the OP does not contain a configuration, it goes automatically into transfer
No configuration mode.
exists or
ESC
+ pressed?
No Yes
Transfer
mode
Establish link to During this phase of the startup, the OP attempts to establish a link to the con-
controller troller.
If communication is not possible (e.g., because the cable to the controller is
not connected), the OP displays a system message.
START
SCREEN
The start screen is then displayed after conclusion of the OP startup.
The operating data of the OP (variables and message buffer) are retained when
a power failure occurs.
The OP25/OP35 and OP45 use the following measures to achieve this.
OP25, OP35 The operating data of the OP25 and OP35 are stored in a buffered SRAM.
The operating data are retained when the power is turned off or a power failure
occurs.
OP45 The operating data of the OP45 are saved cyclically on hard disk once per min-
ute.
Caution
! A system conclusion must be performed before the OP45 is switched off (see
System Settings standard screen).
If no system conclusion is performed, the OP45 operating data can be lost.
The following settings can be made in the System Settings standard screen.
Operating modes:
– Normal operation (online/offline),
– loop-through operation,
– transfer mode,
– MPI transfer,
– system conclusion for OP45, and
– DOS operation of OP45
Message indication: First (oldest) or last (latest) alarm message
Switch message logging on/off
Set current date and time
Switch buffer overflow warning on/off
Choice of up to 3 languages
Blanking of the display (OP25/35 only)
Select backup/restore standard screen (OP25/35 only)
Layout of the standard screen:
System Settings
Operating mode:
Message indication:
Message logging:
Date:
Time:
I USA
D
E ESC
F GBR
The type of printer and the transmission parameters can be specified on the
OP with the standard screen entitled Printer Settings.
The printer and the OP must have the same transmission parameters.
The standard settings are listed below.
Baud rate: 9600
Data bits: 8
Stop bits: 1
Parity: None
Printer screen This standard screen can be used to set the following parameters.
(OP25)
Printer Settings
General: Hardcopy:
IF number: Printout:
Baud rate: 00 Color:
Data bits: Bold:
Stop bits: Density:
Timeout (sec): Matrix printer:
Parity:
Type:
Printer type:
ESC
Printer screen This standard screen can be used for the following purposes.
(OP35/OP45)
Setting the printer parameters
Fading out single monitor screen colors for the printout
Printer Settings
General: Hardcopy:
IF number: Printout:
Baud rate: 00 Color:
Data bits: Bold:
Stop bits: Density:
Timeout (sec): Matrix printer:
Parity:
Type:
Type of printer:
Color Assignment
OP <-> Printer OP <-> Printer
(0) Black: (4) Red:
(1) Blue: (5) Magenta:
(2) Green: (6) Yellow:
(3) Cyan: (7) White: –1
ESC
(Value –1 = “no color”)
Lifespan of CCFL The background illumination of the display uses a CCFL tube (Cold Cathode
tubes Fluorescence Lamp).
For technical reasons, the brightness of these CCFL tubes decreases with use.
The average lifespan is given as 10,000 hrs by the manufacturer of the dis-
play.
An automatic blanking circuit can be used to increase the useful life of CCFL
tubes.
Blanking circuit for This blanking circuit can be configured via ProTool.
OP25/OP35
If no key is pressed within a configured period of time, the display back-
ground illumination is switched off automatically.
Note
Blanking cannot be configured for the OP45.
Cancelling the The background illumination goes on again automatically when any key is
blanking circuit pressed.
A–Z +
Display contrast Higher
Lower
A–Z +
A–Z +
Brightness of the Higher
display back-
ground illumina- A–Z
+
Lower
tion
Key assignment On delivery, your OP45 has the key assignment described in this manual.
on delivery
You will never need to change the key assignment unless you install different
system software (e.g., COROS LS-B) on your OP45 later.
Configuration disk The ProTool software includes a floppy disk containing the TASTDRV.EXE
keyboard driver. You can use this driver to set the code table you want to use
for your system software.
Changing the Setting is performed under DOS with the following command.
key assignment
TASTDRV [–s1|2|3|a|b|c|x]
–s1 DOS table is set.
–s2 LS-B/WIN code table is set.
–s3 LS-B/FlexOS code table is set.
–sa standard code table for LS-A is set.
–sb standard code table for LS-B is set.
–sc standard code table for LS-C is set.
–sx standard code table is set.
–? or –h displays the syntax.
Overview Depending on the requirements on the machine or system, you can also set a
different key assignment. The procedure for doing this is described on the
next few pages.
Scope of supply The scope of supply includes a program package with which you can pro-
gram the two keyboards of the OP45.
The program package comprises the following files:
KEYVERS.EXE for retrieving the version of the keyboard controller
DEFPAD.EXE for compiling the configuration file
TASTDRV.EXE for downloading the compiled configuration file to the
keyboard controller
TSCAN.EXE for retrieving the key codes
OP45_FUN.DEF File with example configuration for the function keyboard
OP45_FUN.PAD compiled example file for the function keyboard
OP45_SYS.DEF file with example configuration for the system keyboard
OP45_SYS.PAD compiled example file for the system keyboard
Creating the confi- Under MS-DOS, you create a configuration file containing the key defini-
guration file tions for every keyboard that you wish to program (system and/or function
keyboard(s)).
The key definition includes the key code and the key characteristic – for ex-
ample, auto-repeat. The key code is discontinued on pressing or releasing the
key.
Note
Make sure that an LED is assigned to keys 1 to 16 on the system keyboard.
TOGGLE ALPHA key changes its status every time the key
is pressed.
GLOBAL ALPHA key affects both OP keyboards.
LOCKOUT ALPHA key automatically turns off the other
ALPHA key.
The ALPHA level (1 + 2) can be used only with the TOGGLE ALPHA
flag. The ALPHA levels disable each other with the LOCKOUT ALPHA
flag. Thus only two ALPHA levels are available.
make codes key code that is discontinued when the key is pressed
(hexadecimal – for example, 6C)
break codes key code that is discontinued when the key is released
(hexadecimal – for example, F0 6C)
key flags characteristics of key
You can assign any file name. The extension, however, must always be
”.DEF”.
Example: PADSYS.DEF for the system keyboard
PADFUNC.DEF for the function keyboard
Compiling the Every configuration file has to be compiled using the DEFPAD program.
configuration file When this is done, the consistency of the key definitions is checked, and a
file having the extension ”.PAD” is created.
Downloading the The compiled file is downloaded to the keyboard controller using the
compiled file TASTDRV driver.
Checking the key Using TSCAN, you can check which code is discontinued when a key is pres-
codes sed. The check can be made for any of the keyboards that can be connected.
To perform a check, call the program called TSCAN. If you then press a key,
the corresponding key code is shown on the display. You can terminate and
quit the program by pressing ESC.
Validity of Programmed and downloaded key assignments are valid until the operating
programming panel is turned off. A RESET does not clear key assignments. The default
assignment of the keyboard controller takes effect when the operating panel
is turned on again.
If you wish the key assignments you have configured to take effect every
time you switch on your OP45, make the following entry in your
AUTOEXEC.BAT file:
C:\KEYDEF\TASTDRV
C:\[pfad]\FILE1.PAD
C:\[pfad]\FILE2.PAD
Normal operation, This is the standard operating mode for unrestricted manipulation and visual-
online ization of the processes.
The OP is connected to the controller and exchanges data with it.
Normal operation, Communication with the controller does not take place in this operating mode.
offline
Process manipulation and visualization are not possible. Entries can still be
made on the OP.
Note
Loop-through operation requires the AS 511 protocol be used to link the OP
with the controller.
Transfer mode Configuration data can be downloaded from the PC/PG to the OP in transfer
mode.
Entries cannot be made on the OP in this operating mode.
MPI transfer If MPI transfer is configured, configuration data for the SIMATIC S7 can be
(OP25/35 only) transferred to the OP via an MPI link.
Overview You can set/change the operating mode of the OP either on the OP or via a job
from the controller.
The current operating mode is stored by the OP and cannot be lost during a
power failure. After the power is switched on, the OP returns to the operating
mode which was set last.
During operation Setting/changing the operating mode can be performed in the System Settings
standard screen, for example.
During startup You can use key combinations during OP startup6 to set the operating modes
shown below.
6) For OP35: Press this key combination when the RAM text (“Testing Memory...”) is concluded
during the self test, and hold the keys down until the test results are deleted
Operating states of The OP45 can be operated with two different operating systems. For this, the
OP45 hard disk is divided into two partitions:
RMOS partition: the OP45 operates during normal operation as an operator
panel.
DOS partition: the OP45 operates as a PC/AT-compatible computer on
which DOS/Windows applications can be run.
OP45 as configura- The primary advantage of DOS operation is the fact that configuration via Pro-
tion computer Tool can be performed on the OP45. This makes the OP both the configuration
computer and destination computer to which the configuration is transferred
(self-configuration).
ESC
+
Exiting During installation of the OP45 software, the program BOOT.EXE is stored in
DOS operation the catalog OP45TOOL.
This program is used to change from DOS operation to normal operation of the
OP45.
Proceed as follows:
1. Exit all DOS/Windows application programs.
2. Change to the OP45TOOL catalog.
3. Enter:
BOOT /OP45
The OP45 performs a new start and goes into normal operation operating
mode.
Purpose Depending on the volume and type of the data, the data are loaded onto the
storage medium to
Back up the data.
Restore saved data.
Load or store recipe data records.
Load the data from the place where they were configured onto a different
target OP.
Storage principle Data can be meaningfully stored only in the following combinations:
Firmware and configuration and recipe data records.
Firmware and configuration7.
Recipe data.
Internal flash me- The default storage medium in the OP25/35 is the internal flash memory ha-
mory ving a storage capacity of 1 Mbyte on the OP25 and 2 Mbytes on the OP35.
You can store all kinds of data on the flash memory – configuration, firmware
and recipe data.
Memory module With ProTool 2.0 or higher, you can also use memory modules on the
OP25/35. If you intend using a memory module, you must first load version
2.0 of the firmware onto the OP (refer to ProTool Readme file).
Caution
! Jeida/PCMCIA modules containing stored configurations can be used only on
OPs of the corresponding type. A system crash will result if the modules are
inserted in other types of OP.
Jeida/PCMCIA The memory modules use the Jeida/PCMCIA8standard, which defines, among
standard other things, the storage format for the data, data organization and system spe-
cifications.
7) This function is not contained on the standard screen and has to be configured.
8) Personal Computer Memory Card International Association = PCMCIA
Japan Electronic Industry Development Association = JEIDA
Benefits Compared to the internal flash memory, the Jeida/PCMCIA module features
the following benefits:
The Jeida/PCMCIA module is a portable storage medium; for example,
recipe data can be ported from one OP to another.
Configurations can be run directly from the module, since the OP detects
whether a module has been inserted and, in this instance, first accesses the
module and then the internal flash memory.
A storage capacity of up to 16 Mbytes means that there is space for large
configurations or a large number of recipe data records.
Distribution of sto- The configuration and the firmware must always be stored on the same storage
red data medium. You should not store recipe data on different storage media.
The following table shows you a few ways in which you can store data:
3.5” floppy disk The OP35 can be supplied as an option with a 3.5” floppy disk drive. By de-
drive (OP35/45) fault, the OP45 is equipped with a floppy disk drive.
Note
You can store only recipe data records on a floppy disk.
Benefits If you frequently require or have to load new or modified data records on the
system but the configuration remains unchanged, the 3.5” floppy disk drive is a
convenient and advantageous solution, since it is accessible from the front of
the OP35.
Hard disk drive The hard disk of the OP45 is divided into two partitions for the two operating
(OP45 only) systems RMOS and DOS, so that the OP45 can be operated as an OP or a PC.
Benefits In this way you have the option, if you connect an additional external keyboard
and a mouse, of performing the configuration directly on the OP45.
Standard screen The standard screen for backup and restore is called from the System Settings
Backup/Restore standard screen by means of a soft key. The soft keys have the meanings
shown in Figure 13-1:
ESC
Escape
Restore: data records
Backup: data records
Restore: firmware + configuration + data records
Backup: firmware + configuration + data records
Figure 13-1 Soft Keys for Backup and Restore
The backup and restore functions of configuration and firmware are not contai-
ned on the standard screen; they can be configured.
Note
To avail yourself of the backup and restore functions, you must have logged in
as the system administrator.
Deleting the flash/ Before you can store new recipe data or a modified configuration on the sto-
memory module rage medium, it is preferable to create a defined starting condition beforehand.
Initially, you do not insert a memory module.
1. Change to Transfer mode:
+
– During start-up, press the ESC keys.
Or
– On the ”System Settings” standard screen, select ”Serial Transfer”
mode.
2. Before the OP changes to Download mode, press on the OP the
+ +
ESC keys
3. Insert the Jeida/PCMCIA module. The following messages appear on the
OP:
Press ’DEL’ to erase total Flash.
Press ’DEL’ to init Flash.
Press ’DEL’ to erase total Module.
Press ’DEL’ to init Module.
Caution
! If you delete a memory module or flash memory, or if you delete or format a
floppy disk, all your data will be lost.
If you initialize a memory module or a flash memory, any configurations that
are present will be deleted; recipe data records are not affected.
ENTER
4. Select with the function which you wish to execute:
Example:
If you wish to delete the flash memory, select:
Press ’DEL’ to erase total Flash
or
If you wish to delete the Jeida/PCMCIA module, select:
Press ’DEL’ to erase total Module
INS
Reserved storage A storage area is reserved for recipe data on the flash memory and on the
area for recipe Jeida/PCMCIA module. The default settings are
data
S 64 Kbytes on the internal flash memory
S 128 Kbytes on the Jeida/PCMCIA module.
If the default values are not sufficient, you can re-define this storage area. Re-
member, though, that you will have less space for your configuration.
1. In ProTool, use the menu command System Parameters Miscella-
neous to open the ”Miscellaneous” dialog box.
2. In the bottom right rectangle, you can reserve the storage area in blocks of
128 kB for both the flash memory and the memory module.
Note
Remember that, apart from the storage area reserved for the recipe data re-
cords, a further 64 kB are required on the internal flash memory and 128 kB
on the Jeida/PCMCIA module for management purposes.
Backup You can perform a backup from the internal flash memory module during
flash module normal operation of the OP:
1. Insert the memory module in the module shaft on the OP.
2. Delete or initialize the module before creating a backup.
3. Start the backup function with the function key or soft key; a corresponding
message is output on the OP once transfer has been successful.
4. Remove the memory module from the OP.
Restore If a memory module contains nothing but recipe data records, these can be re-
module flash stored during normal operation of the OP:
1. Insert the memory module in the module shaft on the OP.
2. Start the Restore function with the function key or soft key.
The recipe data records in the internal flash memory are now overwritten
with the data records stored on the module.
3. Remove the memory module.
Note
Recipe data records stored with Backup on the Jeida/PCMCIA module have to
be transferred first with Restore to the internal flash memory before they can
be edited.
Recipe data records which have been created directly on the Jeida/PCMCIA
module – for example, by means of a standard screen – cannot be uploaded
with Restore into the internal flash memory.
Restore firmware/ To restore a backup of the firmware or configuration to the OP, proceed as fol-
configuration lows:
1. Insert the memory module containing the firmware or configuration in the
module shaft on the OP.
The OP now starts up with the firmware or configuration contained on the
memory module.
2. Start the Restore function with the function key or soft key.
The memory contents of the internal flash memory are overwritten by the
firmware and configuration contained on the memory module.
Initializing Backup/ If you suspend the Backup and Restore functions at the ”Initialize” entry point,
Restore this function is executed whenever loading is performed from the memory mo-
dule. You are then prompted to decide whether or not the internal flash me-
mory should be overwritten with the data on the memory module.
1. In ProTool, choose System Functions Initialization from the menu:
2. Specify the direction of transfer and the type of data which you want to
transfer. The parameters mean:
Application option Thanks to the Jeida/PCMCIA module, you can load the stored data directly on
the target OP on the machine or system, that is, the configuration or recipe data
records can be updated or modified irrespective of the location of the target OP.
COROS OP25
A B C D E F
7 8 9
G H I J K L
F1 F2 4 5 6
M N O P Q R
F3 F4 1 2 3
S T U V W X
F5 F6 . 0 +/–
Y Z INS
F7 F8 DEL ESC
A–Z
A–Z
ACK
A–Z
K1 F9 F10 F11 F12 F13 F14 K2
Designation Description
Display LC display (monochrome) with background illumination
Resolution of 320 x 240 pixels
System keys 24 system keys with fixed functions
Function keys 24 configurable function keys (18 of these keys are equipped with an LED.)
Designation Description
Serial interfaces Level Use
IF1 A V.24/TTY (active/passive) Controller
IF2 V.24/TTY (active/passive) PC, PG, printer, second TD/OP
RS 422/RS 485 (floating) Controller
IF1 B
TTY (passive) / Not used at present
IF3 RS 422/RS 485
Relay output Relay contact to control a horn or lamp, for example, to call attention to
dangerous situations
Module slot For PCMCIA/JEIDA cards
Digital outputs 8 digital outputs (only available on OP with direct key module)
(optional)
296 59 8
COROS OP25
176
192
280
All dimensions in mm
COROS OP35
A B C D E F G H
/ 7 8 9
I J K L M N O P
F1 F2 * 4 5 6
Q R S T U V W X
F3 F4 – 1 2 3
Y Z : \ = , ( )
F5 F6 + . 0 +/–
INS
F7 F8 TAB DEL
ESC
F9 F10 ALT
A–Z A–Z
ACK
A–Z
F11 F12 CTRL
SHIFT
HELP ENTER
TEMP
DISK F13 F14 F15 F16 F17 F18 F19 F20
HD BUSY
POWER
K1 K2 K3 K4 K5 K6 K7 K8
Designation Description
Display LC display (monochrome or color) with background illumination
Resolution of 640 x 480 pixels
System keys 32 system keys with fixed functions
Function keys 36 configurable function keys (28 with LED)
Label strips for customized labelling
Operating indicators TEMP Interior temperature has exceeded the permissible
limit values.
DISK Read/write access to PCMCIA module
HD BUSY No function
POWER OP is in operation.
Floppy disk drive (option) 31/2” drive for HD floppy disks (1.44 MB)
Keyboard connection Not used at present
Front flap IP65 protection rating (when closed)
LPT1
Designation Description
Serial interfaces Level Use
IF1 A V.24/TTY (active/passive) Controller
IF2 V.24/TTY (active/passive) PC, PG, printer, second TD/OP
(loop-through operation)
IF1 B RS 422/RS 485 (floating) Controller
IF3 TTY (passive) /RS 422/RS 485 Not used at present
Parallel interface LPT1 Not used at present
Relay output Relay contact to control a horn or lamp, for example
Module slot For PCMCIA/JEIDA cards
Digital outputs (optional) 16 digital outputs (only available on OP with direct key module)
482.6
85
(158) 12
465.9
COROS OP35
293
310
235
287
53
8
434
55 368 Dimensions in parentheses ( ) apply to OP35
with floppy disk drive and direct key module
6.8
All dimensions in mm 10.3
COROS OP45
A B C D E F G H
/ 7 8 9
I J K L M N O P
F1 F2 * 4 5 6
Q R S T U V W X
F3 F4 – 1 2 3
Y Z : \ = , ( )
F5 F6 + . 0 +/–
INS
F7 F8 TAB DEL
ESC
F9 F10 ALT
A–Z
ACK
A–Z
F11 F12 CTRL
SHIFT
HELP ENTER
TEMP
DISK F13 F14 F15 F16 F17 F18 F19 F20
HD BUSY
POWER
K1 K2 K3 K4 K5 K6 K7 K8
Key-operated switch Function keys Keyboard Floppy disk drive Front flap
connection
Operating indicators
Designation Description
Display TFT color display with background illumination
Resolution of 640 x 480 pixels
System keys 32 system keys with fixed functions
Function keys 36 configurable function keys (28 with LED)
Label strips for customized labelling
Key-operated switch The key-operated switch has three switch positions. The key can be removed in
every position.
3 2 1
1 OP45 is on; keyboard entries possible.
2
OP45 is on; keyboard entries not possible.
3 OP45 is off.
Operating indicators The operating indicators have the following meaning:
TEMP No function
DISK Read/write access to floppy disk drive
HD BUSY Read/write access to hard disk
POWER OP is in operation.
Floppy disk drive 31/2” drive for HD floppy disks (1.44 MB)
Keyboard connection Connection for external MF2 keyboard (front and rear)
Front flap IP65 protection rating (when closed)
Serial interfaces, Figure 14-8 shows the location of the connections on the right side of the
keyboard and OP45.
monitor connec-
tion
OP45 (right side)
Direct key module (optional)
Monitor
(VGA)
COM2
COM1
MPI
LPT19
Keyboard connection
Designation Description
Serial interfaces Level Use
COM1 V.24/TTY SIMATIC S5 (AS 511 only)
COM2 V.24 Printer, PC, PG,
second TD/OP
(loop-through operation)
MPI RS 485 No function
Parallel interface LPT1 Connection for printer (can only be used under DOS)
Mouse connection (PS/2) Can only be used under DOS
Digital outputs (optional) 16 digital outputs
Keyboard connection Connection for external MF2 keyboard
(An additional connection is located on the front of the OP.)
Monitor VGA connection for external monitor
Power connection Figure 14-9 shows the location of the connections on the left side of the OP45.
and voltage selec-
tion switch
OP45 (left side)
Fan
Fan
+
+
+
Designation Description
Power connection The OP45 can be operated on 230 V AC or 115 V AC power.
Power connection for monitor Connection for external monitor (230/115 V AC)
Voltage selection switch Selector switch for either 230 V or 115 V power. 230 V set at
the factory
Caution
! Switching the voltage also changes the voltage on
the power connection for the monitor.
482.6
180 12
465.9
COROS OP45
310
235
290
160
35 100
437
410
Detail drawing of drill hole:
6.8
10.3
All dimensions in mm
14.4 Options
Direct key modules You can order the OP25 with one optional direct key module and the OP35
with two, optional direct key modules.
These modules are permanently installed. They cannot be added later.
The direct key modules for the OP45 can be ordered separately as a plug-in
card. A detailed description is supplied with the plug-in card.
Purpose of the Each direct key module (DTM) provides eight, digital outputs.
direct key module
These outputs are
set by pressing the corresponding function key or
controlled via configurable ports by the software.
The function can be set via DIP switches.
External voltage Since the digital outputs are galvanically isolated from the operator panel by
supply optocouplers, the direct key module requires its own voltage supply.
Connection and Pin strip and DIP switch of the direct key module are located on the back of
setting elements the OP.
DIP switch
Pin strip
Figure 14-11 OP25: Location of the connection and setting elements of the direct key
module
Pin strip The pin strip has the following pin assignment.
1 2 3 4 5 6 7 8 9 10
The components to be addressed by the digital outputs (e.g., relays, etc.) are
connected via the two 5-pin terminal blocks as described below.
Connect the lines (line cross section: 0.5 to 2.5 mm2).
Insert terminal blocks on the pin strip of the direct key module.
DIP switch The digital outputs are set in accordance with the setting on the DIP switch
by pressing a key (F1 to F8) or
by the software.
Setting of the DIP Switch:
S1 S2 S3 S4
OFF
ON
Switches S1 and S2 are always set to ON. Switches S3 and S4 each manipu-
late a group of outputs.
S3 manipulates DQ 1, DQ 3, DQ 5, and DQ 7.
S4 manipulates DQ 2, DQ 4, DQ 6, and DQ 8.
OFF ON
S3 F1/F3/F5/F7 DQ 1/DQ 3/DQ 5/DQ 7
TM A
When switch S3 or S4 is set to OFF, the digital outputs are permanently as-
signed to keys F1 to F8.
Key F1 sets output DQ 1.
Key F8 sets output DQ 8.
Connection and Each of the two direct key modules is equipped with the following:
setting elements
A 10-way, pin strip
For connection of the outputs and the external supply voltage
A DIP switch
For setting whether the outputs are to be set via pressing a key or via soft-
ware
Pin strips and DIP switches are located on the back of the OP.
DIP switch
DTM B DTM A
Pin strip
Figure 14-12 OP35: Location of the connection and setting elements of the direct key
modules (DTM)
Pin strips The pin strips of direct key module (DTM) A and direct key module B have
the following pin allocation:
1 2 3 4 5 6 7 8 9 10
10) Floating
The components to be controlled (e.g., relays, signal lamps, etc.) are connected
via the five-pin terminal blocks included.
Connect the lines to the terminal block
(wire cross section: 0.5 to 2.5 mm2).
Install terminal blocks on the pin strip of the direct key module.
DIP switches The setting of the DIP switch determines how the digital outputs of the direct
key module will be addressed.
Switch setting OFF: By pressing function keys
Switch setting ON: By the software
Setting of the DIP switch:
DTM A DTB A
S1 S2 S3 S4 S1 S2 S3 S4
ON
OFF
OFF ON
S3 F1/F3/F5/F7 DQ 1/DQ 3/DQ 5/DQ 7
TM A
Customized A set of blank label strips is included with the OP. You can use these to make
labelling your own labels for the OP keys.
Labelling Read and adhere to the following caution note before inserting the labelling
strips.
Caution
! Make sure that the labels are dry (i.e., do not smudge when wiped) before
being inserting them since a keyboard foil which is soiled from the inside
cannot be cleaned and must be replaced at the manufacturer’s plant.
Labelling strips
Opening the ope- You will have to open the housing of the operator panel to insert the labelling
rator panel strips.
Caution
! Only qualified personnel may perform work on this device.
Before performing work on the open device, be sure to read and adhere
to the ESD guidelines contained in the appendix of this manual.
1 1
1 1
Figure 15-2 OP35: Opening the housing of the OP (removing the housing screws)
Caution
! The OP housing and the display are connected by cables.
Some models have short connection cables to the display, and some have
long connection cables.
If your model has long connection cables, skip step 4.
Housing of the OP
Connection
cable to the
display
1
2
Figure 15-3 OP35: Opening the housing of the OP (lifting the housing)
Caution
! Make sure that the remaining connection cables (e.g., of the sealed key-
board) are not subjected to pull strain.
Housing of the OP
Figure 15-4 OP35: Opening the housing of the OP (laying the housing aside)
Labelling Before inserting the labelling strips, be sure to read and adhere to the caution
note.
Caution
! Make sure that the labels are dry (i.e., do not smudge when wiped) before
inserting them since a keyboard foil which is soiled from the inside cannot
be cleaned and must be replaced at the manufacturer’s plant.
Inserting the label Insert the finished label strips in the slits of the front plate with the writing
strips facing down.
Opening the ope- You will have to open the housing of the operator panel to insert the labelling
rator panel strips.
Warning
! Disconnect power plug before opening the device.
Caution
! Only qualified personnel may perform work on this device.
Before performing work on the open device, be sure to read and adhere
to the ESD guidelines contained in the appendix of this manual.
1 1
Figure 15-6 OP45: Opening the housing of the OP (removing the housing screws)
2. Pull front plate/frame out of the OP housing as far as it will go (the front
plate is connected to the OP housing with a hinge). Fold down the front
plate.
Housing
Figure 15-7 OP45: Opening the housing of the OP (folding down the front plate)
Labelling Before inserting the labelling strips, be sure to read and adhere to the caution
note.
Caution
! Make sure that the labels are dry (i.e., do not smudge when wiped) before
being inserting them since a keyboard foil which is soiled from the inside
cannot be cleaned and must be replaced at the manufacturer’s plant.
Inserting the label Insert the finished label strips in the slits of the front plate with the writing
strips facing down.
Closing the opera- To close the operator panel, proceed in reverse order.
tor panel again
Caution
! Commissioning is prohibited until it has been determined that the machine in
which these components are to be installed meets the regulations contained
in the 89/392/EEC guidelines.
Deciding on an You can install the OP25 in switching cabinets or consoles. You will need to
installation site make a cutout in the front panel.
and preparation
Width x height (in mm): 282-1 x 178-1
See “Technical Specifications” ( appendix) for information on the mount-
ing depth.
The thickness of the front panel may not exceed 16 mm.
Caution
! Protect the OP from overheating during operation:
Protect the device from direct sunlight. (This also helps to prevent the
foil sealed front from fading.)
Make sure that the ventilation slits are not obstructed after installation.
Note
The IP65 protection rating on the front cannot be ensured unless the sealing
is positioned correctly on the front plate of the OP.
Caution
! Provide suitable measures to prevent the OP from falling out of the front
panel before the device is permanently secured.
2. Secure the device in the front panel with the included screw-type clamps.
1 2
1
2
1 3
Screw-type clamps are not required for positions 2 and 3 unless the
front panel is not level and protection rating IP65 is to be achieved. Posi-
tion 3 requires that a mounting bracket be screwed to the mounting
strip.
Hook the screw-type clamps into the OP housing (see figure 16-2) and turn
the threaded spindles on the back against the front panel.
Threaded spindle
Deciding on the You can install/mount the OP35 in the following locations:
installation site
In 19” (48.26 cm) cabinets/racks
In front panels of switching cabinets and consoles
When installed correctly with the included screw-type clamps, the front
of the OP35 has an IP protection rating of IP65.
Caution
! To prevent the OP from overheating during operation:
– Protect the OP from direct sunlight. (This also keeps the sealed foil
front from fading.)
– Ensure that installation does not obstruct the ventilation slits of the
housing.
If you are using the OP35 with floppy disk drive, make sure of the fol-
lowing:
The angle of inclination of the OP to the vertical surface may not exceed
25°. Otherwise the floppy disk drive may malfunction.
To mount the OP35, use the cabinet braces available from the manufacturer
of your cabinet or rack.
Mounting dimensions of the OP35 for a standard, 19” cabinet:
Width: 19” (48.26 cm) Height: 7 “units of height”
The OP or the OP front plate is secured to the cabinet braces with four
screws.
Note
The IP65 protection rating on the front cannot be ensured unless the sealing
is positioned correctly on the front plate of the OP.
Caution
! Use suitable measures to prevent the OP from falling out of the front panel
before it is permanently secured.
2. Secure the OP to the front panel with the six screw-type clamps 1 in-
cluded.
To do this, hook the screw-type clamps into the housing of the OP, and
turn the threaded spindles on the back against the front panel.
Back of device
Deciding on the You can install/mount the OP45 in the following locations:
installation site
In 19” (48.26 cm) cabinets/racks
In front panels of switching cabinets and consoles
When installed correctly with the included screw-type clamps, the front
of the OP45 has an IP protection rating of IP65.
Caution
! To prevent the OP from overheating during operation:
– Protect the OP from direct sunlight. (This also keeps the sealed foil
front from fading.)
– Ensure that installation does not obstruct the ventilation slits of the
housing.
The OP45 may only be operated when mounted vertically.
Securing with Follow the steps shown below to secure the OP45 with mounting brackets.
mounting brackets
1 1
2. Pull front plate/frame out of the OP housing as far as it will go (the front
plate is connected to the OP housing with a hinge), and open.
2
3
Closing the OP Close the front plate again, and tighten the housing screws 1 .
again
Note
The IP65 protection rating on the front cannot be ensured unless the sealing
is positioned correctly on the front plate of the OP.
Caution
! Use suitable measures to prevent the OP from falling out of the front panel
before it is permanently secured.
2. Secure the OP to the front panel with the six screw-type clamps 1 in-
cluded.
To do this, hook the screw-type clamps into the housing of the OP, and
turn the threaded spindles on the back against the front panel.
Back of device
General installa- Interference-free operation is based on two factors: the interference-proof se-
tion notes tup of the controller hardware in accordance with EMC guidelines, and the use
of interference-proof cables.
EMC directives The directives defined in the description ”SIMATIC S5 Directives for the In-
terference-Proof Assembly of Programmable Logic Controllers” (Order No.
6ES5998-7AB11) apply to the interference-proof assembly and installation of
operator panels.
Caution
! The setup guidelines contained in your controller’s system manual also
apply to the OP.
Use only shielded cable for all signal connections.
Screw down or lock all plug connections.
Do not install signal lines in the same cable ducts as high voltage lines.
Overview Figure 17-1 shows several possible configurations for the OP, controller and
I/O devices.
SIMATIC S5
SIMATIC 500/505 SIMATIC 500/505
PC SIMATIC S7
Controllers of other mfgs Controllers of other mfgs
Choice of
OP25/OP35
Voltage supply
Choice of
Configuration Loop-through
Printer computer operation
Caution
! 24 V supply: Ensure safe electrical separation of the extra-low voltage.
Only use powerpacks which meet IEC 364–4–41 or HD 384.04.41 (part
410, VDE 0100) regulations.
The supply voltage must remain within the voltage range shown above. If
not, function failures may occur on the device.
GND
+24 V DC
Terminal block Use the included four-pin terminal block to connect the supply voltage.
Connect the lines (line cross section: 0.5 to 2.5 mm2).
Insert terminal block on the lower pin strip on the OP.
Ground connec- The grounding point on the back of the device (see figure 17-1) must be con-
tion nected with cabinet ground.
PC
V.24 COM1/2
OP25 (9-pin)
OP35
V.24
COM1/2
TTY passive (25-pin)
TTY/V.24 converter
IF2 PC 7xx
TTY passive COM1
(25-pin)
V.24 COM2
(9-pin)
Standard cables are available for the connections shown above (see ST80.1
catalog).
Standard cables are available for the connections shown below (see ST80.1
catalog).
SIMATIC S5
TTY active CPU
PG interface
OP25 TTY active
OP35 SI 2
TTY active
V.24 CP 523
Adapter PC
IF1 A11
V.24
COM1/2 (9-pin)
V.24
COM1/2
TTY passive (25-pin)
Other makes of
RS 422 controllers
RS 422/RS 485
* SINEC L2-DP
11) When using serial interfaces, either IF1 A (V.24/TTY) or IF1 B (RS 422/RS 485) can be connected
(but not both at the same time).
12) Use only approved cables when using the SIMATIC S7.
Printer
OP25
OP35 TTY
DR 215
IF2 DR 235
V.24
Printer settings The type of printer and the transmission parameters can be specified on the OP
with the Printer Settings standard screen.
The IF2 interface of the OP25/OP35 is available for looping through a pro-
grammer or an additional TD/OP. This provides the following advantages.
Access to the controller during operation
Inexpensive way to connect a second TD/OP to a controller
Figure 17-5 gives you an overview of the connections in AS 511 loop-through
operation.
OP25 PG 685/7xx
OP35
IF2
Operator panel
V.24 OP25, OP35
TTY passive IF1 A
V.24 OP45
COM1
Standard cables are available for the connections shown above (see ST80.1
catalog).
Overview Figure 17-6 shows several possible configurations for the OP45, controller and
I/O devices.
Power supply
230 V/115 V AC
Monitor
External
VGA
VGA monitor
COM2 Printer
DR 215
Choice of
DR 230
COM1
Configuration
computer
PC
PG 7xx
Controller
SIMATIC S5
(only AS 511)
Keyboard
External MF2
keyboard
Safety notes Before connecting the OP45 to the power supply, read and adhere to the fol-
lowing safety notes.
Warning
! This device may only be operated on power networks with grounded pro-
tective conductors or electrical outlets with protective conductors.
Do not connect the device if it shows signs of exterior damage.
Important when using the OP outside Germany:
If another power cable is substituted for the one included with the OP, this
cable must meet the safety regulations and standards of the country in
which the OP is being used.
230/115 V voltage Check to determine whether the nominal voltage set on the voltage selector
selector switch switch corresponds to your local power voltage. 230 V has been set at the fac-
tory.
Caution
! Changing the voltage also changes the voltage on the power connection for the
monitor. (If necessary, adjust the voltage selector switch on the monitor.)
PC
V.24 COM1/2
OP45 (9-pin)
V.24 COM1/2
(25-pin)
COM2
PG 7xx
V.24 COM1
(25-pin)
COM2
(9-pin)
Standard cables are available for the connections shown above (see ST80.1
catalog).
Standard cables are available for the connections shown above (see ST80.1
catalog).
OP45
Printer
DR 215
COM2 DR 230
Printer settings The type of printer and the transmission parameters can be specified on the OP
with the Printer Settings standard screen.
An external MF2 keyboard can be operated on the OP45 at the same time as a
built-in sealed keyboard.
A choice of two ways to connect the MF2 keyboard is available.
To the keyboard connection under the front flap
To the keyboard connection on the right side of the OP45
Note
Two external keyboards cannot be used at the same time.
Key assignment Some OP keys do not exist on an MF2 keyboard. Combinations of keys must
be used for these entries. The following table shows which key combinations
on the MF2 Keyboard correspond to the OP keys.
Purpose The backup battery of the OP25/OP35 ensures the following when the supply
voltage is switched off.
The operating data in the SRAM of the OP are retained.
The hardware clock continues to run.
Lifespan The OP is equipped with a lithium battery which has already been installed
on delivery. Under normal conditions, the battery has an average life of
approximately 5 years.
Battery status An empty battery is indicated by a system message while the OP is running.
You should replace the backup battery as soon as possible after this message
occurs.
Supply sources New batteries can be obtained from the replacement part department of Sie-
mens. The batteries are ready to be installed (with cable and connection
plug).
Warning
! Improper handling of the lithium battery may cause an explosion.
Batteries:
– – Never charge.
– – Do not open.
– – Do not short circuit.
– – Do not reverse poles.
– – Do not expose to temperatures of over 100° C.
– – Protect from direct sunlight.
Do not allow moisture to condense on the batteries.
If transportation is required, regulations pertaining to dangerous freight
must be adhered to for the carrier (obligation to identify).
Battery covering The next two figures show the location of the battery covering on the OP25
and OP35.
Battery
covering
Before changing Before changing the battery, read and adhere to the following.
the battery
Caution
! The battery may only be changed by qualified personnel.
Before changing the battery, read and adhere to the ESD guidelines con-
tained in the appendix of this manual.
Note
To prevent data loss, always change the battery with the voltage supply
switched on.
Caution
! Used lithium batteries require special waste disposal. Wrap them individu-
ally in a leakproof plastic bag before disposing of them.
18.2 Display
The following subsections describe how to replace the display of the OP25,
OP35 and OP45.
Notes on safety Before replacing the display, adhere to the following notes.
Warning
! Maintenance on the device may only be performed by qualified and au-
thorized trained personnel.
Unauthorized opening of the device and incorrect repairs can create sub-
stantial danger to the user.
Crystal liquid can escape from a display which has been damaged.
Do not under any circumstances permit this liquid to come in contact
with your skin or breathe in its fumes. If you do come in contact with
the crystal liquid, wash the affected area with alcohol and consult a doc-
tor immediately.
Warning
! LC displays do not belong in ordinary household trash.
Adhere to the applicable regulations of your country or locality pertaining to
the disposal of special wastes.
Before opening the Before opening the OP, read and adhere to the following caution note:
OP
Caution
! Make sure that the OP is separated from the voltage supply.
Before beginning work on the open device, read and adhere to the ESD
guidelines contained in the appendix of this manual.
Figure 18-3 OP25: Opening the OP housing (removing the housing screws)
Caution
! The backup battery on the back panel cover is connected to the electronics
module with a plug-in line.
Do not disconnect this connection or all operating data stored in the SRAM
will be lost.
Electronics
module
Backup battery
Figure 18-4 OP25: Opening the OP housing (removing the back panel
cover)
2. Remove the five screws 4 . Lift out the electronics module and place on
an ESD surface.
4
4
3
2
Display
Before opening Before opening the OP, read and adhere to the following caution note:
the OP
Caution
! Make sure that the OP is separated from the voltage supply.
Before beginning work on the open device, read and adhere to the ESD
guidelines contained in the appendix of this manual.
1 1
1 1
Housing
of the OP
3
2
Figure 18-8 OP35: Opening the housing (disconnectiog the display cables)
Caution
! Make sure that the remaining connection cables (e.g., the cable of the sealed
keyboard) are not subjected to pulling.
5
6
Figure 18-9 OP35: Opening the housing of the OP (putting the housing aside)
Before opening the Before opening the OP, read and adhere to the following notes:
OP
Warning
! Make sure that the power plug of the OP has been pulled.
Caution
! Before beginning work on the open device, read and adhere to the ESD
guidelines contained in the appendix of this manual.
1 1
2
3
5 Display
Housing
Exterior dimensions (W x H) in mm 296 x 192 482 x 310 482 x 310
Mounting cutout (W x H) in mm 282–1 x 178–1 436–1.5 x 295–1.5 438–1 x 297–1
Mounting depth without options in 59 85 180
mm – 138 180
With floppy disk drive 79 158 –
With direct key module and cable
Protection rating
Front IP65 IP65 IP65
Back IP20 IP20 IP20
Weight 1.85 kg 6.35 kg 14 kg
With floppy disk drive 7.2 kg
Processor
Type F8680 386SL DX2-66
Clock pulse frequency 14 MHz 25 MHz 33 MHz
Memory
FLASH 1 Mbyte 2 Mbytes –
DRAM 2 Mbytes 4 Mbytes 8 Mbytes
(can be expanded to
64 Mbytes)
SRAM (buffered) 128 Kbytes 128 Kbytes –
Floppy disk drive – 1.44 Mbytes 1.44 Mbytes
(optional)
Hard disk – – 425 Mbytes 13
Display
Type STN-LCD STN-LCD TFT-LCD
Resolution (hor. x vert.) 320 x 240 mm 640 x 480 640 x 480 mm
Active monitor screen area 115 x 86 mm 192 x 144 mm 211 x 158 mm
Background illumination CCFL tube CCFL tube 2 CCFL tube
Lifespan 14 Approx. 10,000 hours
Keyboard
Type Sealed keyboard Sealed keyboard Sealed keyboard
System keys 24 32 32
Function keys 24 (18 with LED) 36 (28 with LED) 36 (28 with LED)
Voltage Supply
Nominal voltage 24 V DC 24 V DC 115/230 V AC
(50/60 Hz)
Permissible range 18 V to 30 V 18 V to 30 V ±10%
Max. permissible transients 35 V (500 msec) 35 V (500 msec) –
Time between transients Min. of 50 sec Min. of 50 sec –
Current consumption (without
options)
Typical 0.4 A 0.8 A 0.3 A
Max. continuous current 0.6 A 1.0 A 1.4 A
Fuse Internal, electronic Internal, electronic Internal, safety fuse
Relay Contact
Switching capacity 24 V DC, 0.4 A 24 V DC, 0.4 A –
(no inductive load) (no inductive load)
14) The background illumination tube of the display is subject to wear, and is not included in the warranty. Depending
on the operating temperature, the tube has a life span of approximately 10, 000 hours. Under unfavorable operating
conditions, we recommend replacing the tube after this time. The tube is available as a spare part. The actual re-
placement must be performed by SIEMENS service personnel.
Number of outputs 8 2 x 8 17 2 x 8 17
Maximum output current 300 mA per output 300 mA per output 300 mA per output
External voltage supply 24 V DC 24 V DC 24 V DC
Permissible range 18 V to 30 V 18 V to 30 V 18 V to 30 V
Environmental Requirements
Environmental temperature
Operation
Vertical installation 0° to 50° C 4° to 45° C 5° to 40° C 18
Horizontal installation 0° to 40° C 4° to 35° C –
(Floppy disk drive not permitted)
Transportation, storage –20° to 60° C –20° to 60° C –25° to 60° C
Mounting position with floppy disk – Max. of 25° inclination Max. of 25° inclination
drive to front or back to front or back
Relative humidity
Operation v 85%, 20% to 80%, 5% to 85%,
no condensation no condensation no condensation
Transportation, storage 5% to 90%, 5% to 85%,
no condensation no condensation
Shock load
Operation 15 g / 11 ms 5 g/ 11 ms for floppy 5 g/11 ms
disk access
15 g / 11 ms otherwise
Transportation, storage 50 g 50 g 50 g
Vibration
Operation 0.055 mm (10 – 85 Hz) 0.075 mm (10 – 58 Hz) 0.035 mm (to 58 Hz)
2 g (30 – 500 Hz) 1 g (58 – 500 Hz) or 0.4 g (58 to 500 Hz)
0.5 g for floppy disk
drive
Transportation, storage 3.5 mm (5 – 12 Hz) 3.5 mm (5 – 8.5 Hz) 1g
2 g (12 – 500 Hz) 1 g (8.5 – 500 Hz)
Maximum pressure difference 2 hPa – –
(front, back)
Air pressure
Operation 706 to 1030 hPa 706 to 1030 hPa 706 to 1030 hPa
Transportation, storage 581 to 1030 hPa 581 to 1030 hPa 581 to 1030 hPa
This product meets the regulations of EEC guideline 89/336 if the standards
listed below are fulfilled.
Interference Immunity
Static discharge IEC 801–2 IEC 801–2 IEC 801–2
(contact discharge) class 3 class 3 class 3
RF irradiation ENV 50140 ENV 50140 ENV 50140
10 V/m, 80% AM, 10 V/m, 80% AM, 10 V/m, 80% AM,
1 kHz 1 kHz 1 kHz
Pulse modulation ENV 50204 ENV 50204 ENV 50204
900 MHz "5 MHz 900 MHz "5 MHz 900 MHz "5 MHz
10 V/mr.m.s., 50% ED, 10 V/mr.m.s., 50% ED, 10 V/mr.m.s., 50% ED,
200 Hz 200 Hz 200 Hz
RF conduction – ENV 50141 ENV 50141
150 kHz – 80 MHz 150 kHz – 80 MHz
10 V, 80% AM, 1 kHz 10 V, 80% AM, 1 kHz
Burst interference IEC 801–4 IEC 801–4 IEC 801–4
Power lines
Supply lines 2 kV 2 kV 2 kV
Process data lines 2 kV 2 kV 2 kV
Signal lines 1 kV 1 kV 1 kV
Interference Emission
Radio supression class EN 55022 (VDE 0878) EN 55022 (VDE 0878) EN 55022 (VDE 0878)
class B class B class B
IF1 B Assignment:
5 1
9-pin sub D socket
9 6
IF3 Assignment:
8 1
COM1 Assignment:
13 1
25-pin sub D socket
25 14
COM2 Assignment:
5 1
MPI Assignment:
5 1
Calling the test While turning on the power supply of the OP, press the
program
cursor keys simultaneously, and keep them
Test sequence The test program provides a series of individual tests each of which can be
started with a function key (F9 to F14 and K1 to K10).
The test results appear on the display after an individual test is concluded.
OK : No errors
DEF : The tested function unit is defective.
Exiting the test The test program can only be exited by switching off the power supply of the
program OP.
Internal/external The memory chips of the OP are tested with read-write tests.
memory
When an error occurs, the faulty memory address is indicated on the display.
Note
Since the contents of the SRAM, EEPROM and Flash memories are stored in
the DRAM before the test is performed, we recommend testing the DRAM
for errors first.
Since the saved data are not reloaded, the contents of the tested memory are
destroyed when an error occurs. The same applies to a power failure.
Serial interfaces These tests can only be performed when homemade adapters are installed on
the applicable connections. See appendix C.1.3 for circuiting of the adapter.
F14 IF1 test
An adapter must be installed on both the IF1 A and the IF1 B for the IF1 test.
V.24 signals: Adapter 1 on IF1 A and
Adapter 4 on IF1 B
TTY signals: Adapter 2 on IF1 A and
Adapter 4 on IF1 B
K2 IF2 test
V.24 signals: Adapter 1
TTY signals: Adapter 2
K3 IF3 test
RS 485 signals: Adapter 1
TTY signals: Adapter 3
K4 MPSS test
Internal test of the component for the multipoint interface
Adjust contrast
Adjust brightness
Indicate font
The pins specified below must be connected or circuited together for the test
adapters.
Pin 1 2 3 4 5 6 7 8 9 10
8x
2.2 kOhm
+24 V DC 0V
Message number
0 Driver error
1 Startup message
2 Warning
3 Note
4 Operator error
5 Miscellaneous messages
6 Configuring error
7 Internal error
The category of a message gives you a rough idea of what caused the system
message.
A selection of important system messages follows stating when they occur
and, if applicable, how to correct the cause of the error.
The following system messages are not included.
S Self-explanatory system messages
S System messages caused by a mistake in configuring
Message Cause/Remedy
040 The OP is not able to establish a connection to the controller.
Possible causes can be:
The connection cable between OP and controller is not plugged in.
Free ASCII protocol (FAP):
The character delay time may be configured too short.
041, 044 The connection to the controller is faulty.
Possible causes:
Fault in the transmission route (e.g. connection cable defective)
Interface parameters set incorrectly on the OP or on the coupling partner
210, 212 See no. 7xx
250 Impossible to switch to desired OP operating mode via job
This message can occur, for example, when an attempt is made to switch to loop-
through operation during communication via FAP.
252 OP recipe functions cannot be executed simultaneously.
Two examples of situations in which message 252 occurs:
The selected function is already active (e.g., is being used in the background by the
controller).
You attempt to transfer or delete a data record while a data record is being selected.
256 Not enough free system memory space to execute the selected function
⇒ Select the function again.
If the message appears again anyway, “simplify” the configuration of the screen caus-
ing the problem (i.e., use fewer screen elements/functions). Examples:
Move the function causing the message to another screen.
Do not use curves in the screen together with this function.
257 A data record was not stored with the recipe version which is currently loaded.
You must enter the old version in the configuration of the recipe if you want to con-
tinue using these data records.
The assignment of the values of a data record is specified by the recipe structure.
An “old” data record may be interpreted incorrectly if the structure was changed in a
new configuration.
259 The transfer of a data record to the controller must be performed within a certain
amount of time. This time has been exceeded.
Possible causes:
The controller (user program) did not acknowledge receipt of the data record.
The data record is very long.
The data record is transferred in its entirety although the time was exceeded.
260 Operating mode of the controller (e.g., manual operation, automatic, STOP) does not
correspond to the configuration.
261 The data record can no longer be used since the data are no longer reliable.
306 See no. 7xx.
340 Entries cannot be made on the OP while status processing is running on the PG.
Message Cause/Remedy
385/386 This message is indicated until one of the following happens.
The data record is transferred.
The data record is acknowledged by the controller (only for transfer to controller).
During the transmission (message is indicated), no further entries can be made on the
OP.
500 to 505 The controller is temporarily overloaded, or more than 1.5 seconds have passed since
the standard function block was last called.
506 The controller has sent too many “fetch message area” jobs with the same block num-
ber within a certain period of time (i.e., the OP is overloaded).
507 The controller (user program) did not acknowledge the recipe within 10 seconds.
510 The controller acknowledged the recipe as faulty.
This error can occur, for example, when a process link to a nonexisting DB is config-
ured in a recipe.
541 to 550 The specified variable does not exist in the controller.
613 The specified data block with DB no. (starting DW and end DW) does not exist in the
controller or is too short.
(Values in parentheses: First data word, last data word)
645, 649 See no. 7xx.
670 Too many variables were requested at the same time.
Remedy: – Configure basic clock pulse longer.
– Configure fewer variables in the screen.
681 The connection between OP and controller is faulty.
The interface parameters may be set incorrectly.
682 Configure the indicated screen with fewer process links.
7xx Proceed in steps as shown below when one of these errors occurs.
a) – Switch the voltage supply of the OP off and on again.
– Perform a new start of the controller.
b) – Switch to transfer mode during the OP startup
(press + simultaneously).
ESC
– Transfer configuration again.
– Perform a new start of the controller.
c) Contact your nearest Siemens office if the error continues to
occur. Be sure to give the message number and any variables in
the message text.
ESDs can be destroyed by voltages and energy far below those perceived by
human beings. Such voltages are created just by touching a component or mo-
dule if the person has not discharged himself/herself electrostatically. In most
cases, components subjected to such overvoltages cannot be identified immedi-
ately as faulty since they may not malfunction until they have been in opera-
tion for a longer period of time.
Important precau- Since most plastics have a strong tendency to charge themselves, it is impera-
tions against static tive that they be kept away from sensitive components.
charging
Make sure that workers, workplace and packaging are well grounded when
electrostatic sensitive components are in the vicinity.
Handling ESD Never touch electronic modules unless the work required makes this unavoid-
modules able. Never under any circumstances touch component pins or printed circuits
when handling PCBs.
Components should not be touched unless
you are continuously grounded with an ESD bracelet
you are wearing ESD shoes or shoes with ESD protective grounding strips
and are walking on ESD flooring.
Before touching an electronic module, you must discharge your own body first.
The easiest way to accomplish this is to touch a conductive, grounded object
(e.g., the bare metal surfaces of switching cabinets, water pipes, etc.) immedi-
ately before touching the module.
Never allow modules to come in contact with chargeable and highly insulating
materials (e.g., plastic foil, insulating tabletops, and synthetic fiber clothing).
Always place modules on conductive surfaces (e.g., tables with ESD covering,
conductive ESD foam, ESD bags or ESD shipping containers).
Keep modules at least 10 cm away from CRTs, monitors and television sets.
Measuring and mo- Measurements may not be performed on the modules unless
difying ESD mod-
the measuring device is grounded (e.g., via a protective conductor) or
ules
the measuring head is briefly discharged (e.g., by touching the bare metal
surface of the controller housing) when using a potential-free measuring
device.
Always use a grounded soldering iron for soldering work.
Shipping ESD Always store or ship modules and components in conductive packaging (e.g.,
modules metallized plastic boxes and metal containers).
If packaging is not conductive, the modules must first be wrapped in conduc-
tive material. Examples of wrapping materials which can be used include con-
ductive foam rubber, ESD bags, household aluminum foil or paper. Never un-
der any circumstances use plastic bags or foils.
When packing modules equipped with built-in batteries, make sure that the
conductive packaging does not touch or short circuit the battery connections.
If necessary, cover the connections with insulating tape or material beforehand.
Siemens Sales The following table lists all Siemens Sales Offices in the Federal Republic of
Offices in the FRG Germany.
Aachen Kassel
Augsburg Kempten/Allg.
Bayreuth Kiel
Berlin Laatzen
Bielefeld Leipzig
Bonn Lingen
Bremen Magdeburg
Brunswick Mainz
Chemnitz Mannheim
Coblenz Munich
Cologne Münster/Westf.
Constance Nuremberg
Darmstadt Osnabrück
Dortmund Regensburg
Dresden Rostock
Duisburg Saarbrücken
Düsseldorf Siegen
Erfurt Stuttgart
Essen Ulm
Frankfurt am Main Wetzlar
Freiburg Wilhelmshaven
Hamburg Wuppertal
Heilbronn Würzburg
Karlsruhe
European The following table lists all European Siemens Companies and
Companies and Representatives.
Representatives
Austria Finland
Siemens AG Österreich Siemens Oy
Bregenz Espoo, Helsinki
Graz France
Innsbruck Siemens S.A.
Linz Haguenau
Salzburg Lille, Seclin
Vienna Lyon, Caluire-et-Cuire
Belgium Marseille
Siemens S.A. Metz
Brussels Paris, Saint-Denis
Liège Strasbourg
Siemens N. V. Toulouse
Antwerp Great Britain
Bosnia-Herzegovina Siemens plc
Generalexport Predstavnistvo Sarajevo Birmingham, Walsall
Sarajevo Bristol, Clevedon
Bulgaria Congleton
Sofia Glasgow
Leeds
Croatia
Liverpool
Siemens d. o. o.
London, Sunbury-on-Thames
Zagreb
Manchester
Cyprus
Newcastle
GEVO Ltd.
Greece
or
Siemens A.E.
Jolali Ltd.
Athens, Amaroussio
Nicosia
Thessaloniki
Czech Republic
Hungaria
Siemens AG
Siemens Kft
Brno
Budapest
Mladá Boleslav
Iceland
Prague
Smith & Norland H/F
Denmark
Reykjavik
Siemens A/S
Ireland
Copenhagen, Ballerup
Siemens Ltd.
Dublin
Italy Romania
Siemens S.p.A. Siemens birou de consultatii tehnice
Bari Bukarest
Bologna Russia
Brescia Siemens AG
Casoria or
Florence Mosmatic
Genoa Moscow
Milan Siemens AG
Padua Ekaterinburg
Rome
Slovak Republic
Turin
Siemens AG
Luxemburg
Bratislava
Siemens S.A.
Slovenia
Luxemburg
Siemens d. o. o.
Malta
Ljubljana
J. R. Darmanin & Co. Ltd.
Spain
Valletta
Siemens S.A.
Netherlands
Barcelona
Siemens Nederland N.V. Bilbao
The Hague Gijón
Rijswijk Granada
Norway La Coruña
Siemens A/S Las Palmas de Gran Canaria
Bergen León
Oslo Madrid
Stavanger Málaga
Trondheim Murcia
Poland Palma de Mallorca
Siemens GmbH Pamplona
Gdansk-Letnica Sevilla
Katowice Valencia
Warsaw Valladolid
Portugal
Vigo
Zaragoza
Siemens S.A.
Albufeira Sweden
Coímbra Siemens AB
Lisbon, Amadora Göteborg
Matosinhos Jönköping
Porto Malmö
Sundsvall
Upplands Väsby, Stockholm
Switzerland Turkey
Siemens-Albis AG SIMKO
Basel Adana
Bern Ankara
Zürich Bursa
Siemens-Albis S.A. Istanbul
Renens, Lausanne Izmir
Samsun
Ukraine
Siemens AG
Kiev
Non-European The following table lists all non-European Siemens Companies and
Companies and Representatives of Siemens AG.
Representatives
Africa The following table lists all Siemens Companies and Representatives of
Siemens AG in Africa.
Algeria Morocco
Siemens Bureau d’Alger SETEL
Alger Société Electrotechnique et de Télécommunications S.A.
Angola Casablanca
TECNIDATA Mozambique
Luanda Siemens Liaison Office
Bophuthatswana Maputo
Siemens Ltd. Namibia
Mafekeng Siemens (Pty.) Ltd.
Egypt Windhoek
Siemens Technical Office Nigeria
Cairo-Mohandessin Electro Technologies Nigeria Ltd. (ELTEC)
Siemens Technical Office Lagos
Alexandria Rwanda
EGEMAC S.A.E. Etablissement Rwandais
Cairo-Mattaria Kigali
Ethiopia Sambia
Addis Electrical Engineering Ltd. Electrical Maintenance Lusaka Ltd.
Addis Abeba Lusaka
Ivory Coast Simbabwe
Siemens AG Electro Technologies Corporation (Pvt.) Ltd. (ETC)
Abidjan Harare
Libya
Siemens AG, Branch Libya
Tripoli
America The following table lists all Siemens Companies and Representatives of
Siemens AG in America.
Argentina Canada
Siemens S.A. Siemens Electric Ltd.
Bahía Blanca Montreal, Québec
Buenos Aires Toronto
Còrdoba Chile
Mendoza INGELSAC
Rosario Santiago de Chile
Bolivia Colombia
Sociedad Comercial é Industrial Hansa Ltda. Siemens S.A.
La Paz Barranquilla
Brazil Bogotá
Siemens S.A. Cali
Belém Medellín
Belo Horizonte Costa Rica
Brasilia Siemens S.A.
Campinas Panama
Curitiba San José
Fortaleza
Cuba
Pôrto Alegre
Respresentación
Recife
Consult iva EUMEDA
Rio de Janeiro
La Habana
Salvador de Bahia
Ecuador
São Paulo
Vitória Siemens S.A.
Quito
El Salvador Paraguay
Siemens S.A. Rieder & Cia. S.A.C.I.
San Salvador Asunción
Guatemala Peru
Siemens S.A. Siemsa
Ciudad de Guatemala Lima
Honduras United States of America
Representaciones Electroindustriales S de R.L. - Siemens Industrial Automation Inc.
Relectro Automation Division
Tegucigalpa Alpharetta, GA
Mexico Numeric Motion Control
Siemens S.A. de CV Elk Grove Village, Illinois
Culiacán Uruguay
Gómez Palacio Conatel S.A.
Guadalajara Montevideo
León Venezuela
México, D.F.
Siemens S.A.
Monterrey
Caracas
Puebla
Valencia
Nicaragua
Siemens S.A.
Managua
Asia The following table lists all Siemens Companies and Representatives of
Siemens AG in Asia.
Bahrain India
Transitec Gulf Siemens Limited
Manama Ahmedabad
Bangladesh Bangalore
Siemens Bangladesh Ltd. Bombay
Dhaka Calcutta
Brunei Madras
New Delhi
Brunei Darussalam
Secúnderabad
Hong Kong
Indonesia
Siemens Ltd.
P.T. Siemens Indonesia, P.T. Siemens Dian-Grana
Hong Kong Elektrika, Representative Siemens AG
Jakarta
Australia The following table lists all Siemens Companies and Representatives of
Siemens AG in Australia
Alarm message Indicates a particularly urgent operating state and must be acknowledged
Controller Check for devices/systems with which the OP communicates (e.g., SIMATIC
programmable controllers and PC)
Event message Indicates certain operating states of machines or systems connected to the
controller
Forced printout Automatic printout of the alarm or event messages that will be deleted from
the message buffer during a buffer overflow
Icon Graphic symbol assigned to the individual softkeys showing the softkey’s
function
Loop-through op- Operating mode of the OP. Permits normal operation. Also permits commu-
eration nication via the OP between a PG or an additional OP and the PLC. Requires
that the link to the controller use the
AS 511 protocol.
Message logging Configurable printout of alarm and event messages parallel to the printout of
the contents of the display
Pop-up window Contains a list of entries from which one entry can be selected
Process screen Representation of process values and sequences in the form of screens which
can contain graphics, texts, and values.
Programmable lo- SIMATIC S5 series controllers (e.g., SIMATIC S5-115U and S5-135U)
gic controller
Softkeys Function keys can have softkey functionality (i.e., can have different mean-
ings depending on which screen is active).
Startup test Checks the status of the central processing unit and memory each time volt-
age is applied
Transfer mode Operating mode of the OP in which data from the configuration computer are
transferred to the OP
Abbreviations
OP Operator Panel
PC Personal computer
PG Programmer
M
J Main screen, 4-6
Jeida / PCMCIA standard, 13-2 Main screen area, 3-1
Memory, 1-4
Memory test, OP25, C-4
K Message buffer, 5-3, 5-8
Deletion, 5-8
Key assignment, User-specific, 11-8
Message buffer page, 5-8
Key characteristic, 11-8
Message indication, 11-2
Key code, 11-8
Message indicator, 5-4
Key codes, Check, 11-11
Message line, 5-3, 5-5
Key definition, 11-8
Message logging, 5-7, 7-2, 11-2
Key functions, 3-4
Switching off, 11-2
Key mode, 11-10
Switching on, 11-2
Keyboard, 3-2
Message number, system messages, D-1
Cleaning of, 18-1
Message page, 5-3
Function keys, 3-2
Message processing, 5-10
System keys, 3-3
Message status, 5-4
Keyboard connection, 14-5
Message window, 5-3, 5-5
Keyboard, sealed, 1-3
Messages, 1-6
Keys, labelling of
Logging, 5-7
Customized, 15-1
Stored, 5-8
OP25, 15-2
MF2 keyboard, connection to OP45, 17-12
OP35, 15-3
MF2 keyboard, external, 14-10
OP45, 15-6
Models, device, 1-3
Monitor, external, 14-10
MPI bus, 10-5
L MPI transfer, 11-2, 12-2
Languages, 1-6
Languages, switching of, 11-2
Login, 8-2
As superuser, 8-3
N OP35
Commissioning, initial, 10-2
Normal operation, 11-2, 12-2
Configuration computer, connection of, 17-4
Numeric fields, 3-6
Connections, 14-6
Controller, link to, 17-5
Digital outputs, 14-6
O Dimensions, 14-7
OP25 Direct key module, 14-16
Commissioning, initial, 10-2 Display, 14-5
Configuration computer, connection of, 17-4 Display, replacing of, 18-10
Connections, 14-3 Electrical installation, 17-2
Controller, link to, 17-5 Floppy disk drive, 14-5
Digital outputs, 14-3 Front flap, 14-5
Dimensions, 14-4 Function keys, 14-5
Direct key module, 14-14 Installation, 16-5
Display, 14-2 Installation in 19”cabinets/racks, 16-5
Display, replacing of, 18-6 Installation in switching cabinets/consoles,
Electrical installation, 17-2 16-6
Function keys, 14-2 Interface assignment, B-1
Hardware test, C-2 Keys, labelling of, 15-3
Installation, 16-2 Loop–through operation, 17-7
Interface assignment, B-1 Module slot, 14-6
Keys, labelling of, 15-2 Operating and indicating elements, 14-5
Loop–through operation, 17-7 Operating indicators, 14-5
Module slot, 14-3 Printer, connection of, 17-6
Operating and indicating elements, 14-2 Relay contacts, 17-3
Printer, connection of, 17-6 Relay output, 14-6
Relay contacts, 17-3 Serial interfaces, 14-6
Relay output, 14-3 System keys, 14-5
Serial interfaces, 14-3 Voltage supply, 17-3
System keys, 14-2
Test adapters, C-7
Voltage supply, 17-3