E560 Cmu02 CS
E560 Cmu02 CS
Application, characteristics and technical data The connection to the RTU560 serial peripheral
have to be taken from the hardware data sheet: bus is done via 48 pole DIN-F socket connector
according to DIN 41612. The serial peripheral bus
is not available on the RJ45 connectors on the
560CMU02 R0001 1KGT 150 595 front plate.
CPA Interface
Operation The CPA interface is available on the RJ45
The communication unit 560CMU02 is one of the connector on the front plate. It can interface
CMU boards (CMU = communication unit) of the RS485 signals. The Bus can be terminated by a 1
remote terminal unit. The 560CMU02 controls kΩ resistor with jumper x_485 (Position 1-2)(see
process events and communications with control Fig. 5).
centers and local MMI systems via up to three
The settings have to be done by RTUtil560
serial interfaces (CP1, CP2, CPA) and the
configuration tool. The signals are used according
Ethernet 10BaseT/100BaseT LAN interface (E).
to Fig. 2:
Pin Signal
1 - Not used
2 TA Data - RJ45
3 TB Data + 1
4 - Not used 8
7 - Not used
8 -
Signalling
CP1 and CP2 Interface RS232C Mode
The LEDs of the 560CMU02 are under software
control (exception T and R). The definition and
Pin Signal Input/Output operation of the LED “ERR" must be taken from
the release specific function description. The
1 DCD Input LEDs “Tx” and “Rx” are directly connected to the
receiver / transmitter of the communication line.
2 RxD Input RJ45
The LEDs “A" and “L" are directly connected to
1 the Ethernet-controller.
3 TxD Output
8
4 DTR Output LED Colour Meaning
Jack
ERR red Warning / Error
5 GND -
T (3x) green Transmit data (CP1, 2, A)
7 RTS Output R (3x) green Receive data (CP1, 2, A)
A (1x) green Ethernet Activity
8 CTS Input
L (1x) green Ethernet Link
Shield Connected with housing Table 1: Meaning of LEDs
Fig. 3: CP1- and CP2 Interface RS232C Mode
Firmware Version
Ethernet Interface The actual firmware version will be delivered on a
CompactFlash memory card. A new firmware file
The Ethernet interfaces on the Front plate
can be loaded with the Web diagnostic tool into
supports different functions.
the removable CompactFlash memory card.
• Webserver-diagnostic with download of
Changing of CompactFlash memory cards is
configuration files and firmware
possible.
• Protocol IEC 60870-5-104, DNP3.0, …
• Integrated HMI Settings
The signals are used according to Fig. 4. The settings of the hardware and for operation of
the communication interface of the 560CMU02
have to be taken with the RTUtil560 configuration
Ethernet Interface tool.
The settings of the communication parameters
Pin Signal Input/Output
can be done in the “Hardware Tree" of the
1 TD + Output RTUtil560.
For RTU I/O bus protocol the settings are
2 TD - Output RJ45 predefined. For other protocols the parameters
have to be defined according to the protocol type.
3 RD + Input 1
4 Not used 8
5
Jack
6 RD - Input
7 Not used
The following parameters have to be defined for The settings of the Ethernet interface are
all protocols:
• node name
• Baudrate: 50 to 19 200 baud
• IP address
Modem control:
• connected stations
• Direct link (TxD/RxD only)
• the number of the host interface.
• WT link full duplex (23WT21-23, 25 no
handshake)
• WT link half duplex (23WT22/25, with
CTS handshake)
• WT link half duplex (23WT21-23, 25 with
RTS / DCD)
• Dial up (external modem without
handshake, without RTS / CTS)
• Loop switch unit (RP570/71 Host interface
only)
• Link with collision avoidance (TxD, RxD,
DCD, without handshake (DNP 3.0 only)
ABB
ABB AG
ABB
Power Technologies Division
Power Technology Systems
ABB AG
Kallstadter Str.1, D 68309
Power Technologies Mannheim
Division
Telephone: +49 (0) 621 381-7592
Power
Fax:
Technology Systems
+49 (0) 621 381-7622
www.abb.com/pt
Kallstadter Str.1, D 68309 Mannheim
Telephone: +49 (0) 621 381-7592
Fax: +49 (0) 621 381-7622
www.abb.com/pt