DM33
DM33
DM33
27,50/51,50N/51N,51BF,59,59Uo,67,67N,68,I2t
DM33 · Three Overcurrent levels
· Three Earth-fault levels
· Zero sequence overvoltage level
N37 -R2
· Two over / under voltage level
· Blocking Output and Blocking Input for pilot wire
selectivity coordination
· Breaker Failure protection
M
LINE
· Breaker Interruption Energy SI2t
· Time tagged multiple event recording
· Modbus Communication Protocol
· UL / CSA listed
Three-phase directional and non directional overcurrent plus directional earth fault relay with
programmable time-current curves suitable for protection of radial and ring HV, MV, LV power distribution
systems with insulated, resistance earthed or compensated neutral.
Zero sequence current and voltage circuits includes a 3rd harmonic active filter
Connection Diagram
32
DM33
1F - 67/50/51 (I>): 1st Overcurrent Level
- Operation Mode : F1a = Non Directional - Directional Supervision - Total Directional
- Characteristic sensivity direction : aI> =(0 - 359 - Dis)°, step 1°
- Current setting range : I> = (0.1 - 4)In, step 0.01In
- Instantaneous output : £ 0.04s
- Definite trip time delay in the independent time operation mode
- Trip time delay at 10x[I>] in inverse time operation modes } tI> = (0.05 - 65)s, step 0.01s
- Operation mode F(I>): F(I>) = D : Independent definite time F(I>) = MI : IEEE moderate inverse time curve
F(I>) = A : IEC curve type A F(I>) = VI : IEEE very inverse time curve
F(I>) = B : IEC curve type B F(I>) = I : IEEE inverse time curve
F(I>) = C : IEC curve type C F(I>) = EI : IEEE extremely inverse time curve
F(I>) = SI : IEEE standard inverse time curve
2F & 3F - 67/50/51 (I>> & I>>>): 2nd & 3rd Overcurrent Element - Individually Programmable
- Operation Mode : Non Directional - Directional Supervision - Total Directional
- Characteristic sensivity direction : aI>>, aI>>>=(0 - 359 - Dis)°, step 1°
- Current setting range : I>>, I>>> = (0.1 - 40) In, step 0.01 In
- Instantaneous output : £ 0.04s
- Independent time delay : tI>> & tI>>> = (0.05 - 65)s, step 0.01s
- Operation mode F(O>): F(O>) = D : Independent definite time F(O>) = MI : IEEE moderate inverse time curve
F(O>) = A : IEC curve type A F(O>) = VI : IEEE very inverse time curve
F(O>) = B : IEC curve type B F(O>) = I : IEEE inverse time curve
F(O>) = C : IEC curve type C F(O>) = EI : IEEE extremely inverse time curve
F(O>) = SI : IEEE standard inverse time curve
2F & 3F - 67N/50N/51N (O>> & O>>): 2nd & 3rd Earth Fault Elements - Individually programmable
- Operation Mode : Non Directional - Directional Supervision - Total Directional
- Characteristic sensivity direction : aO>>, aO>>>=(0 - 359 - Dis)°, step 1°
- Current setting range : O>>, O>>> = (0.002 - 0.8)On, step 0.01 On
- Instantaneous output : £ 0.04s
- Independent time delay : tO>> & tO>>> = (0.05 - 65)s, step 0.01s
F - 59Uo : Zero Sequence Voltage Element
- Setting range : Uo> = (1 - 50)V step 1V
- Instantaneous output : £ 0.03s
- Trip time delay : tUo> = (0.05 - 9.99)s, step 0.01s
1F & 2F - 27, 59, 27+59 (U< / U>) : 1st & 2nd Under/Over Voltage Element - Individually Programmable
- Operation mode : Over - Under - Over/Under - Disabled
- Operation level : u = (5 - 90)%Un, step 1%Un
- Instantaneous output : £ 0.03s
- Trip time delay : tu = (0.05 - 65)s, step 0.01s
Breaker Interrupption Energy
- Conventional interruption current : Ic = (0.1 - 9.99)In, step 0.01In
- Max Energy before maintenance : W = (1 - 9999)Ic2t, step 1Ic2t
Breaker Failure Element
- Alarm time delay : tBF = (0.05 - 0.75)s, step 0.01s
33