CH2 Application of Distribution Transformers
CH2 Application of Distribution Transformers
Application of Distribution
Transformers
1. Introduction
In general, distribution transformers are used to reduce primary-system
voltages (2.4 to 34.5 kV) to utilization voltages (120 to 600 V).
Other voltages are also available, for example, 2400 × 7200, which is used on a
2400-V system that is to be changed later to 7200 V.
To reduce installation costs to a minimum, small distribution transformers are
made for pole mounting in overhead distribution.
To reduce size and weight, preferred oriented steel is commonly used in their
construction.
Transformers 100 kVA and below are attached directly to the pole, transformers
larger than 100 up to 500 kVA are hung on crossbeams or support lugs.
If three or more transformers larger than 100 kVA are used, they are installed
on a platform supported by two poles.
In underground distribution, transformers are installed in Street vaults, in
manholes direct-buried, on pads at ground level, or within buildings. Transformer
type may depend upon soil content, lot location, public acceptance, or cost.
×), a winding is
When two voltages are separated by a cross (×
used for 120 V multiple connection and for 240 V series connection, but
smooth-surfaced, oil-filled tank. Oil absorbs the coil heat and transfers
For transformers 25 kVA and larger, the size of smooth tank surface
enclose coils.
(1) dry-type
(2) liquid-filled-type
1. Subway transformers
2. Low-cost residential transformers
3. Network transformers
These are made from 10 to 500 kVA for delta and wye
Figure 2.2 .b
Various types of
transformers
For an emergency outage this unit is simply driven to the site, hooked
up, and the power to the site is restored.
Dr. Sadek DHBAIBI 17
3. Types Of distribution transformers
Figure 2.3c shows a typical power
transformer.
and
or
or
where θ is the power factor angle of the load, VR is the percent resistance
voltage = (copper loss/output)× ×100, SL is the apparent load power, ST is
the rated apparent power of the transformer, Iop is the operating
current, Ira is the rated current, Vx is the percent leakage reactance
voltage (VZ2 − VR2)1/2, and Vz is the percent impedance voltage.
Note that the percent regulation at unity power factor is:
The total losses include the losses in, the electric circuit, magnetic
circuit, and dielectric circuit. Stigant and Franklin state that a
transformer has its highest efficiency at a load at which the iron loss and
copper loss are equal.
Therefore the load at which the efficiency is highest can be found from
Figure 2.7 annual cost per unit load vs. load level.
Dr. Sadek DHBAIBI 29
4. Transformer Efficiency
Of course, the cost of investment is the largest cost component, and
it includes the cost of the transformer itself and the costs of material
and labor involved in the transformer installation.
Figure 2.7 shows the annual cost per unit load versus load level. At
low-load levels, the relatively high costs result basically from the
investment cost, whereas at high-load levels, they are due to the cost
of additional loss of life of the transformer, the cost of lost energy, and
the cost of demand loss in addition to the investment cost. Figure 2.7
indicates an operating range close to the bottom of the curve.
or x.
is located on the right-hand side when facing the high-voltage side of the
transformer.
winding.
right.
Dr. Sadek DHBAIBI 32
6. Transformer Polarity
which two adjacent terminals of the high and low-voltage windings are
winding, as shown in Figure 2.9, and then the voltage between the high
and low-voltage winding terminals that are not connected together are
measured.
The polarity is subtractive if the voltage read is less than the voltage
The polarity is additive if the voltage read is greater than the applied
°C
These curves indicate a minimum life expectancy of 20 years at 95°
°C hot-spot temperatures, for 55°
and 110° °C and 65°
°C rise
transformers.