Effects of Segmented Shield Wires
Effects of Segmented Shield Wires
Abstract—Shield wire segmentation has been used for quite lines. Single-phase-to-ground coupling methods are most fre-
some time as an effective method for reducing transmission-line quently used for lower voltage level transmission lines [1], [2].
power losses, with most segmented shield wire applications on As efficiency becomes more important for electric utilities,
extra high-voltage lines utilizing phase-to-phase power-line car-
rier (PLC) coupling. As transmission system efficiency becomes shield wire segmentation has been used as an effective way
more of a priority, some utilities may consider applying segmented to reduce power loss from shield wires, and has been applied
shield wires to lower voltage lines, such as 115-kV and 230-kV to some high-voltage (HV) transmission lines [3], [4]. It was
lines, which most often utilize single-phase-to-ground PLC cou- concluded in [5] that the segmented shield wire system is not
pling. Thus, knowledge of the effects of segmented shield wires on suitable for use with PLC communications applications, which
PLC signal attenuation for various coupling methods would be
useful to relay engineers. The purpose of this paper is to present a are critical systems in transmission-line protection schemes.
generalized method to model transmission lines for signal attenu- From [5], the unsuitability of segmented shield wires with PLC
ation calculation at PLC frequencies, with special consideration applications results from pronounced resonance that can occur
given to shield wire connections. Terminating impedance and in a band of frequencies, resulting in excessively high PLC
phase wire transposition are considered as well. The modeling signal attenuation. However, the previous work described in
method presented is validated with field measurements. In a com-
panion paper, signal attenuation results considering the effects of [5] is based on a particular type of segmentation and coupling
various parameters are analyzed. method, which determines the particular frequency band where
the resonance occurs. For other frequencies, PLC coupling
Index Terms—Power-line carrier (PLC), signal attenuation,
methods, and shield wire segmentation methods, the resonance
transmission-line modeling.
effects could be much less severe. Therefore, a generalized
signal attenuation calculation model of the transmission line,
I. INTRODUCTION including the shield wires, was developed to analyze the effects
of shield wire segmentation on PLC signal attenuation.
Several papers have been written on transmission-line mod-
eling and modal analysis. References [6]–[10] provide gener-
TABLE I
BOUNDARY CONDITIONS FOR DIFFERENT SHIELD WIRE CONNECTIONS
(5)
where (8)
• is the phase domain voltage propaga- • is the chain parameter matrix of the phase conductors
tion constant matrix in per-unit length, and the series for the second half
impedance per-unit length matrix and shunt admit-
tance per-unit length matrix can be calculated by
following the steps stated in [10]; (9)
• is the phase domain characteristic
(surge) impedance of the line; C. Overall Chain Parameter Matrix
• is the line length between two towers or discontinuities. For transmission systems without termination as shown in
Fig. 4, all discontinuities are considered from the shield wire
B. Shield Wire Elimination discontinuities. After applying the boundary conditions to re-
The shield wires are either grounded or opened at the end of duce the shield wires from the transmission matrix, the overall
each section, or open at the middle point for the type A segmen- chain parameter matrix for the phase conductors that relates the
tation. Phase conductors are continuous without discontinuities sending end to the receiving end can be obtained as the product
430 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 1, JANUARY 2013
(17)
(18)
Fig. 4. Transmission system with sections.
where is the transmission system terminating impedance.
For the special case where the line is terminated in its char-
of the chain parameter matrices of each section in the proper acteristic impedance, the reflection coefficient in (18) is calcu-
order. The process is described as lated to be zero matrix. Thus, the overall equation between the
sending end and the receiving end voltages in (1) can be reduced
to
(10)
(19)
(11)
E. Including Transpositions in Phase Conductors
Phase conductor transposition is an effective way to equalize
(12) the phase impedances and reduce the induction from normal
operating currents and voltages [18]. However, transposition
(13) can cause additional attenuation of a PLC signal. As a result,
accounting for phase conductor transposition is necessary to
where model the PLC channel performance accurately. The defined
• is the chain parameter matrix of the phase conductors model can easily be extended to include the transpositions and
for the entire line; applied to the analysis of the effects.
• consists the elements of relating the re- For the two different phase conductor transposition types as
ceiving-end voltages to sending-end voltages; shown in Fig. 5, the relationship of the voltages after (at the
• consists of the elements of relating the receiving points ’ and ’) and before (at the points and ) transposi-
end voltages to sending end currents; tion can be expressed as
• consists of the elements of relating the receiving
end currents to sending end voltages; (20)
• consists of the elements of relating the receiving
end currents to sending end currents.
Due to the discontinuities from the shield wires and the
(21)
nonuniform distribution of section lengths, the phase domain
propagation constant for the entire line should be recalculated
from the transmission matrix generated in (12). By comparing So the phase transposition matrices of the two different types of
(12) and (4), the following equations can be used to derive the transpositions are
equivalent phase domain propagation parameters:
(14) (22)
(15)
and
where the equivalent phase domain characteristic impedance
matrix can be calculated through
(23)
(16)
YANG AND FRANKLIN: EFFECTS OF SEGMENTED SHIELD WIRES ON SIGNAL ATTENUATION OF PLC CHANNELS—PART I 431
B. Measurement Description
Fig. 6. Section distribution of the transmission line used for tests.
Two tests were performed on the test line with the frequency
at 100 kHz and 300 kHz with the signal applied to the center
phase. Phase-to-ground coupling equipment is installed on the
The or matrices can be inserted into the original trans- center phase, which made it possible to measure voltages at the
mission chain matrices to generate the modified chain matrix for receiving-end. The 500-kV test line has 1000- wideband line
the PLC channel traps that present almost purely resistive impedance to frequen-
cies within their stopband. The frequencies of the test signal,
which were 100 kHz and 300 kHz, were within the stopband of
(24) the line trap.
For the case in which several transpositions are present, the The tests consisted of applying a signal at one end of the line
chain matrix can be generated by inserting each corresponding and measuring the magnitude of the signal at the other end of
transposition matrix into (24). the line using a frequency-selective voltmeter. At the sending
end of the line, the signals were applied after the IMT, which is
direct to the line-tuning unit. As a result, when the series LC unit
IV. FIELD MEASUREMENT
was tuned to resonate at the test frequency, the phase-to-ground
voltage level applied to the transmission line should approxi-
A. Test Line Description
mately be the voltage level measured at the terminals of the
The field tests were performed on a nontransposed 500-kV signal generator. The applied voltage to the center phase was
transmission line with segmented shield wires as shown in 5 V for both tests. At the receiving end of the line, the voltage
Fig. 6. The shield wires have six segmentations along the total was measured across the drain coil, which was approximately
line length. The segmentation here is recognized as type A the phase-to-ground voltage level on the line. However, the only
segmentation. So the shield wires are opened at the towers parameters known at the receiving end are the line trap imped-
which are at the ends of each segmentation, including the very ances, which are 1000 on the center phase and one outer
beginning and very end of the line. The total line length is phase. The bus impedance can only be approximated.
around 49.6 km with the actual value of each section shown
in Fig. 6. The shield wires are only grounded at the towers C. Calculation Procedure
which are in the middle of each segmentation and insulated at
all remaining towers. The receiving end voltages can be calculated using the mod-
The test line is a delta configuration as shown in Fig. 7. Re- eling method described in Section III. Using 100 kHz as an ex-
ferring to Fig. 7: ample, the calculation steps are as follows:
• phase conductors are Ortolan 1033.5 kcm 45/7 ACSR; the 1) Calculate the series impedance and shunt admittance
geometric mean radius (GMR) of the phase conductors is of the line at 100 kHz using the steps stated in [10]. The
137 mm; ground resistivity in this example calculation is considered
432 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 1, JANUARY 2013
to be 100 -m. The calculated and are shown in the D. Comparison of Measured and Calculated Voltages
equation at the bottom of the page. The phase-to-ground line terminating impedance consists of
2) Generate the chain parameter matrix for each section with the line trap impedance in series with a capacitive reactance
phase conductors and shield wires included. All of the representing the phase-to-ground bus capacitance. The line
chain parameter matrices are 10 10 matrices. trap impedance value is the only parameter known. As recom-
3) Apply boundary conditions to reduce the shield wires. The mended in [19], the bus impedance used at PLC frequencies
reduced chain parameter matrices are 6 6 matrices. below 100 kHz is approximately , and for frequencies
4) Combine the chain parameter matrix of each section to- above 100 kHz, a value of to should be used.
gether to obtain the phase conductors’ chain parameter ma- Four different sets of terminating impedance networks were
trix for the entire line. compared as follows: is the characteristic impedance of
5) Calculate the phase domain propagation constant and char- the line, is the recommended [19] phase-to-ground bus
acteristic impedance from elements of the chain parameter impedance in series with the line trap impedance with short cir-
matrix using (12) and (13). The calculated results are as cuits between phases, is the recommended phase-to-ground
follows. bus impedance in series with the line trap impedance with open
1) Characteristic Impedance: circuits between phases, and is the line trap impedance
only with short circuits elsewhere
2) Propagation Constant:
TABLE II [4] B. Foehner and P. Thomas, “Sectionalizing static wire prevents 500-kV
MEASURED AND CALCULATED VOLTAGE LEVELS AT THE RECEIVING END outages,” Transm. Distrib., pp. 56–57, Sep. 1978.
OF LINE [5] J. A. B. Faria, “Broadband resonance effects in power lines with
sectionalized shield wires,” in Proc. IEEE Southeast Conf., 1990, pp.
654–658.
[6] M. C. Perz, “Natural modes of power line carrier on horizontal three
phase lines,” IEEE Trans. Power App. Syst., vol. PAS-83, no. 7, pp.
679–686, Jul. 1964.
[7] M. C. Perz, “A method of analysis of power line carrier problems on
three-phase lines,” IEEE Trans. Power App. Syst., vol. PAS-83, no. 7,
pp. 686–691, Jul. 1964.
[8] L. M. Wedepoh and S. E. T. Mohamed, “Multiconductor transmission
lines: Theory of natural modes and fourier integral applied to transient
analysis,” Proc. Inst. Elect. Eng., vol. 116, no. 9, Sep. 1969.
[9] L. M. Wedepohl, “Electrical characteristics of polyphase transmission
systems, with special reference to boundary value calculations at power
line carrier frequencies,” Proc. Inst. Elect. Eng., vol. 112, no. 11, pp.
2103–2112, Nov. 1965.
[10] G. A. Franklin, “Using modal analysis to estimate received signal
levels for a power-line carrier channel on a 500-kV transmission line,”
IEEE Trans. Power Del., vol. 24, no. 4, pp. 2446–2454, Oct. 2009.
[11] L. M. Wedepohl and R. G. Wasley, “Wave propagation in polyphase
transmission systems: Resonance effects due to discretely bonded earth
wires,” Proc. Inst. Elect. Eng., vol. 112, no. 11, Nov. 1965.
[12] J. A. B. Faria and J. F. B. da Silva, “The effect of randomly earthed
ground wires on PLC transmission: A simulation experiment,” IEEE
Trans. Power Del., vol. 5, no. 4, pp. 1669–1677, Oct. 1990.
[13] S. Yang and G. A. Franklin, “Modeling of overhead transmission lines
with segmented shield wires for signal attenuation calculation in power
line carrier systems,” in Proc. IEEE Southeast Conf., 2011, pp. 12–16.
[14] S. Cristina and M. D’Amore, “Propagation on polyphase lossy power
Table II shows a comparison of calculated versus measured lines: A new parameter sensitivity model,” IEEE Trans. Power App.
received signal levels for the aforementioned terminating im- Syst., vol. PAS-98, no. 1, pp. 35–44, Jan. 1979.
pedances, with three different values of ground resistivity of [15] S. Cristina and M. D’Admore, “Performance sensitivity of a power line
carrier channel,” IEEE Trans. Power App. Syst., vol. PAS-98, no. 4, pp.
100, 200, and 300 -m. As shown in Table II, the characteristic 1337–1344, Jul. 1979.
impedance, which is the reflectionless terminating impedance, [16] S. Cristina and M. D’Amore, “A new efficient method to evaluate
produced the least accurate results. It can be expected since the carrier channel performances on long EHV power lines with trans-
positions,” IEEE Trans. Power App. Syst., vol. PAS-101, no. 9, pp.
actual line termination was far from being that of the charac- 3053–3060, Sep. 1982.
teristic impedance of the line. The other three termination im- [17] C. R. Paul, Analysis of Multiconductor Transmission Lines, 2nd ed.
pedances resulted in much better estimates of the receiving end Hoboken, NJ: Wiley/IEEE.
[18] P. D. Morgan and S. Whitehead, “The impedance and power losses of
signal levels. three-phase overhead lines,” J. Inst. Elect. Eng., vol. 68, no. 399, pp.
367–408, Mar. 1930.
V. CONCLUSION [19] Relaying Communications Channels Application Guide. Markham,
ON, Canada: Pub. No. GET-8034, GE Power Management, 2001.
A generalized phase domain signal attenuation calculation [20] J. A. B. Faria, “On the resonance effects due to ground wires in trans-
method for a PLC channel on overhead transmission lines with mission lines with non-uniform soil conductivity and non-uniform
tower resistances,” IEEE Trans. Power Del., vol. 7, no. 1, pp. 29–38,
segmented shield wires was described in this paper. A group Jan. 1992.
of field measurement data along with the model calculation re-
sults is provided to verify the modeling method. The method Shanshan Yang (S’10) received the B.S. and M.S. degrees in electrical power
presented herein can be used by relay engineers or PLC appli- system and power system protection from Shandong University, Jinan, China,
in 2005 and 2008, respectively, and the Ph.D. degree in computer engineering
cation engineers to help select appropriate PLC frequencies and from the University of Alabama at Birmingham in 2012, with research in the
coupling methods for PLC applications on overhead transmis- area of computer-based modeling and analysis of power system protection and
sion lines with continuous or segmented shield wires. power-line carrier applications on overhead transmission lines.
Currently, she is an Applications and Development Engineer with Electrocon
Future work will be on the analysis of other effects that seg- International, Inc. Ann Arbor, MI. Her responsibilities include the development
mented shield wires may bring into the transmission system, of detailed models of protective relays.
such as influences to transient overvoltage studies.