FIRE-RATED ASSEMBLIES
IN COMMERCIAL CONSTRUCTION
These gypsum wallboard system details are intended solely as technical support incident to the sale and use of National
Gypsum Company products. They may be used as a reference by architects, engineers, other design professionals,
contractors, building code officials, or other competent construction industry trade personnel considering the selection,
specification and use of National Gypsum Company products in these systems.
Architects, engineers, designers or contractors involved should review these details with the governing code or inspection
official at the time of the job submittal to determine if there are any discrepancies with local code or regulatory
requirements. In any event, they must NOT be used without a complete evaluation by the owner's design professional to
verify the suitability of the system for a given application.
These system details may be printed and/or transferred electronically as needed by the user, subject to terms and
limitations of any applicable license agreement. Any unauthorized duplication or reuse of the material contained herein is
a violation of law.
For a guide to fire safety information relating to certain systems described in this PURPLE Book, please refer to the
information on National Gypsum Company's website at http://nationalgypsum.com/ng/resources/fire-safety.htm , or call
1-800-NATIONAL .
TABLE OF CONTENTS
Detail No. Title UL Design Head of Wall Firestop System Page
GN Series - General Information
GN 101 1
GN 102 ASTM and Gypsum Association Standards 2
GN 103 Wall Priority Legend 3
SS 201 2 Hour Partition to Steel Deck U411, V438 ProForm Quick-Set FS-90 Compound 17
SS 202 2 Hour Partition to Steel Deck (Castle Cut) U411, V438 Firestop Sealant 18
SS 203 2 Hour Partition to Steel Deck U411, V438 Elastomeric Spray Firestop 19
SS 204 2 Hour Partition to Steel Deck U411, V438 Firestop Sealant 20
SS 205 2 Hour Partition with Deflection Track U411, V438 Firestop Sealant, Double Top Track 21
SS 206 2 Hour Partition to Steel Deck U411, V438 Joint Forming Profile and Elastomeric Spray Firestop 22
SS 207 2 Hour Partition with Deflection Track U411, V438 Gypsum board, Fire Trak Shadowline 23
SS 208 2 Hour Partition to Steel Beam U411, V438 Elastomeric Spray Firestop 24
SS 209 2 Hour Partition Offset from Beam U411, V438 Elastomeric Spray Firestop 25
SS 210 2 Hour Partition to Concrete Slab U411, V438 Firestop Sealant 26
SS 211 2 Hour Partition to Steel Deck U411, V438 ProForm Quick-Set FS-90 Compound (1 Side) 27
SS 212 2 Hour Chase Wall to Steel Deck V488 ProForm Quick-Set FS-90 Compound 28
SS 213 2 Hour Cement Board Partition to Steel Deck V452 Elastomeric Spray Firestop 29
SW 301 3 Hour Shaftwall with Deflection Track W414, W419 Gypsum board, Fire Trak Shadowline 56
SW 401 4 Hour Shaftwall Partition V451, W419 57
Brand Sta-Smooth
Type FSW-G Brand Gridstone Gypsum Ceiling Panels
Gold Bond Brand Gridstone CleanRoom Gypsum Ceiling Panels
Type FSW-3 Brand Fire-Shield Gypsum Sheathing, Type X
Brand XP Fire-Shield Gypsum Board, Type X
Type FSW-5 Brand Hi-Impact XP Fire-Shield Gypsum Board, Type X
Brand Hi Abuse XP Fire-Shield Gypsum Board,Type X
Type FSW-6 Brand eXP Extended Exposure Sheathing, Type X
Brand eXP Interior Extreme Gypsum Panel, Type X
Brand eXP Fire-Shield Tile Backer, Type X
Brand eXP Interior Extreme IR Gypsum Panel, Type X
Brand eXP Interior Extreme AR Gypsum Panel, Type X
Type FSW-7 Brand eXP Extended Exposure Shaftliner, Type X
Type SoundBreak XP Brand SoundBreak XP Gypsum Board, Type X
Type FSL Brand High Strength Fire-Shield LITE , Type X
Type FSW-8 Brand Fire-Shield Gypsum Sheathing, Type X
HIGHEST PRIORITY
LOWEST PRIORITY
CONCRETE ON FLUTED
STEEL DECK
PROFORM QUICK-SET
FS-90 COMPOUND
GLASS FIBER INSULATION
HEAD OF WALL - 1 HR
WHI 495-PSV-1067
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX.
5/8" FIRE-SHIELD
GYPSUM BOARD
CONCRETE ON FLUTED
STEEL DECK
5/8" FIRE-SHIELD
GYPSUM BOARD
3 5/8" STEEL STUD
24" O.C. MAX.
GLASS FIBER INSULATION
(OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
ELASTOMERIC SPRAY
FIRESTOP
MINERAL WOOL
INSULATION
1" MAX.
HEAD OF WALL - 1 HR
UL DESIGN: HW-D-0043
UL DESIGN: HW-D-0292
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX. (SLOTTED
TRACK OPTIONAL)
5/8" FIRE-SHIELD
GYPSUM BOARD
CONCRETE ON FLUTED
STEEL DECK
FIRESTOP SEALANT
MINERAL WOOL
INSULATION
HEAD OF WALL - 1 HR
UL DESIGN: HW-D-0034
UL DESIGN: HW-D-0045 STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX. (SLOTTED
TRACK OPTIONAL)
5/8" FIRE-SHIELD
GYPSUM BOARD
3 5/8" STEEL STUD 24"
O.C. MAX.
GLASS FIBER INSULATION
(OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
FIRESTOP SEALANT
MINERAL WOOL
INSULATION
HEAD OF WALL - 1 HR
UL DESIGN: HW-D-0034
UL DESIGN: HW-D-0045 MECHANICALLY FASTEN
DEFLECTION TRACK 24"
O.C. MAX. (OPTIONAL)
5/8" FIRE-SHIELD
GYPSUM BOARD
3 5/8" STEEL STUD 24"
O.C. MAX.
GLASS FIBER INSULATION
(OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
ELASTOMERIC SPRAY
FIRESTOP
MINERAL WOOL
INSULATION
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX. (SLOTTED
TRACK OPTIONAL)
5/8" FIRE-SHIELD
GYPSUM BOARD
3 5/8" STEEL STUD 24"
O.C. MAX.
GLASS FIBER INSULATION
(OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
2 1/2"
MIN.
1/4" MAX.
MAX.
3"
PROFORM QUICK-SET
FS-90 COMPOUND
MINERAL WOOL
INSULATION
HEAD OF WALL - 1 HR
1"
5/8" FIRE-SHIELD
GYPSUM BOARD
3 5/8" STEEL STUD
24" O.C. MAX.
GLASS FIBER INSULATION
(OPTIONAL)
STEEL BEAM
SPRAY-APPLIED FIRE
RESISTIVE MATERIAL
HEAD OF WALL - 1 HR 20 GA. Z-CLIPS @ 16" O.C.
UL DESIGN: HW-D-0252 MAX., FASTEN BEFORE
UL DESIGN: HW-D-0259 APPLICATION OF SPRAY ON
FIREPROOFING
FASTEN STEEL TRACK TO
Z-CLIPS
MINERAL WOOL
INSULATION
ELASTOMERIC SPRAY
FIRESTOP
5/8" FIRE-SHIELD
GYPSUM BOARD
3 5/8" STEEL STUD
24" O.C. MAX.
GLASS FIBER INSULATION
(OPTIONAL)
O.C. MAX.
FLEXIBLE SEALANT
(OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
STEEL BEAM
SPRAY-APPLIED FIRE
HEAD OF WALL - 1 HR RESISTIVE MATERIAL
UL DESIGN: HW-D-0617
UL DESIGN: HW-D-0635 3/8" DIAMOND MESH
EXPANDED METAL LATH
MINERAL WOOL
INSULATION
1 1/2" Z FURRING OR
CHANNELS 24" O.C.
ELASTOMERIC SPRAY
FIRESTOP
5/8" FIRE-SHIELD
GYPSUM BOARD
3 5/8" STEEL STUD
24" O.C. MAX.
GLASS FIBER INSULATION
(OPTIONAL)
5/8" FIRE-SHIELD
PARTITION - 1 HR GYPSUM BOARD
UL DESIGN: U465 STEEL TRACK -
UL DESIGN: V438 MECHANICALLY FASTEN 24"
1/4" MIN.
O.C. MAX.
FLEXIBLE SEALANT
(OPTIONAL)
3/4" MAX.
HEAD OF WALL - 1 HR
UL DESIGN: HW-D-0079 FIRESTOP SEALANT
UL DESIGN: HW-D-0083
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX. (SLOTTED
TRACK OPTIONAL)
5/8" FIRE-SHIELD
GYPSUM BOARD
3 5/8" STEEL STUD
24" O.C. MAX.
GLASS FIBER INSULATION
(OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
HEAD OF WALL - 1 HR
WHI-495-PSV-1325
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX.
PROFORM QUICK-SET
SETTING COMPOUND
3 5/8" STEEL STUD
24" O.C. MAX.
GLASS FIBER INSULATION
(OPTIONAL)
PARTITION - 1 HR
UL DESIGN: V497
PARTITION RATED STEEL TRACK -
FROM BOTH SIDES MECHANICALLY FASTEN
24" O.C. MAX.
FLEXIBLE SEALANT
(OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
PROFORM QUICK-SET
FS-90 COMPOUND
HEAD OF WALL - 1 HR
WHI 495-PSV-1067
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX.
5/8" FIRE-SHIELD
GYPSUM BOARD
2 1/2" MIN. STEEL STUD
CONCRETE ON FLUTED
STEEL DECK
ELASTOMERIC SPRAY
FIRESTOP
MINERAL WOOL
INSULATION
1" MAX.
HEAD OF WALL - 1 HR
UL DESIGN: HW-D-0043
UL DESIGN: HW-D-0292
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX. (SLOTTED
TRACK OPTIONAL)
1/2" PERMABASE
CEMENT BOARD
CONCRETE ON FLUTED
STEEL DECK
PROFORM QUICK-SET
FS-90 COMPOUND
GLASS FIBER INSULATION
HEAD OF WALL - 2 HR
WHI 495-PSV-1068
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX.
CONCRETE ON FLUTED
STEEL DECK
FIRESTOP SEALANT
CONCRETE ON FLUTED
STEEL DECK
ELASTOMERIC SPRAY
FIRESTOP
MINERAL WOOL
INSULATION
1" MAX.
HEAD OF WALL - 2 HR
UL DESIGN: HW-D-0043
UL DESIGN: HW-D-0292
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX. (SLOTTED
TRACK OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
FIRESTOP SEALANT
MINERAL WOOL
INSULATION
HEAD OF WALL - 2 HR
UL DESIGN: HW-D-0034
UL DESIGN: HW-D-0045
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX. (SLOTTED
TRACK OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
FIRESTOP SEALANT
MINERAL WOOL
INSULATION
HEAD OF WALL - 2 HR
UL DESIGN: HW-D-0034
UL DESIGN: HW-D-0045 MECHANICALLY FASTEN
DEFLECTION TRACK 24"
O.C. MAX. (OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
ELASTOMERIC SPRAY
FIRESTOP
MINERAL WOOL
INSULATION
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX. (SLOTTED
TRACK OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
2 1/2"
MIN.
1/4" MAX.
PROFORM QUICK-SET
MAX.
3"
FS-90 COMPOUND
MINERAL WOOL
INSULATION
MECHANICALLY FASTEN
24" O.C. MAX.
STEEL BEAM
SPRAY-APPLIED FIRE
RESISTIVE MATERIAL
HEAD OF WALL - 2 HR 20 GA. Z-CLIPS @ 16" O.C.
UL DESIGN: HW-D-0252 MAX., FASTEN BEFORE
UL DESIGN: HW-D-0259 APPLICATION OF SPRAY ON
FIREPROOFING
FASTEN STEEL TRACK TO
Z-CLIPS
MINERAL WOOL
INSULATION
ELASTOMERIC SPRAY
FIRESTOP
O.C. MAX.
FLEXIBLE SEALANT
(OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
STEEL BEAM
SPRAY-APPLIED FIRE
HEAD OF WALL - 2 HR RESISTIVE MATERIAL
UL DESIGN: HW-D-0617
UL DESIGN: HW-D-0635 3/8" DIAMOND MESH
EXPANDED METAL LATH
MINERAL WOOL
INSULATION
1 1/2" Z FURRING OR
CHANNELS 24" O.C.
ELASTOMERIC SPRAY
FIRESTOP
O.C. MAX.
FLEXIBLE SEALANT
(OPTIONAL)
FIRESTOP SEALANT
3/4" MAX.
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX. (SLOTTED
TRACK OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
HEAD OF WALL - 2 HR
WHI-495-PSV-1326
HEAD OF WALL RATED STEEL TRACK -
FROM BOTH SIDES MECHANICALLY FASTEN
24" O.C. MAX.
CONCRETE ON FLUTED
STEEL DECK
PROFORM QUICK-SET
FS-90 COMPOUND
HEAD OF WALL - 2 HR
WHI 495-PSV-1068
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX.
CONCRETE ON FLUTED
STEEL DECK
ELASTOMERIC SPRAY
FIRESTOP
MINERAL WOOL
INSULATION
1" MAX.
HEAD OF WALL - 2 HR
UL DESIGN: HW-D-0043
UL DESIGN: HW-D-0292
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX. (SLOTTED
TRACK OPTIONAL)
1/2" PERMABASE
CEMENT BOARD
5/8" FIRE-SHIELD
GYPSUM BOARD
CONCRETE ON FLUTED
STEEL DECK
ELASTOMERIC SPRAY
FIRESTOP
MINERAL WOOL
INSULATION
1" MAX.
HEAD OF WALL - 3 HR
UL DESIGN: HW-D-0043
UL DESIGN: HW-D-0292
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX. (SLOTTED
TRACK OPTIONAL)
CONCRETE ON FLUTED
STEEL DECK
ELASTOMERIC SPRAY
FIRESTOP
MINERAL WOOL
INSULATION
1" MAX.
HEAD OF WALL - 4 HR
UL DESIGN: HW-D-0043
UL DESIGN: HW-D-0292
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX. (SLOTTED
TRACK OPTIONAL)
VERTICAL JOINTS
STAGGERED ONE STUD
CAVITY ON OPPOSITE
SIDES OF PARTITION
HORIZONTAL BASE
LAYER JOINTS NEED NOT
BE STAGGERED OR
BACKED BY FRAMING
5/8" FIRE-SHIELD
GYPSUM BOARD
PARTITION - 1 HR
UL DESIGN: U465
UL DESIGN: V438
VERTICAL JOINTS
STAGGERED ONE STUD
ON OPPOSITE SIDES OF
PARTITION
HORIZONTAL BASE
LAYER JOINTS NEED NOT
BE STAGGERED OR
BACKED BY FRAMING
VERTICAL JOINTS
STAGGERED ONE STUD
CAVITY BETWEEN BASE
AND FACE LAYERS
HORIZONTAL JOINTS
STAGGERED 12" MIN.
BETWEEN BASE AND
FACE LAYERS
PARTITION - 2 HR
UL DESIGN: U411
UL DESIGN: V438
VINYL OR METAL
CONTROL JOINT
5/8" FIRE-SHIELD
1/2" MAX. GYPSUM BOARD
1 5/8" TYPE S SCREWS
24" O.C.
5/8"
STEEL STUDS
2 LAYERS 5/8"
FIRE-SHIELD
FIRE TEST - 1 HR GYPSUM BOARD
WHI-647-3024
VINYL OR METAL
CONTROL JOINT
2 LAYERS 5/8"
1/2" MAX. FIRE-SHIELD
GYPSUM BOARD
1 5/8" TYPE S SCREWS
24" O.C.
5/8"
STEEL STUDS
2 LAYERS 5/8"
FIRE-SHIELD
GYPSUM BOARD
FIRE TEST - 2 HR
WHI-651-0318.1
CORNER BEAD
PARTITION - 1 HR
UL DESIGN: U465
UL DESIGN: V438
PARTITION - 1 HR
UL DESIGN: U465
UL DESIGN: V438
PARTITION - 2 HR
UL DESIGN: U411
UL DESIGN: V438
1 HOUR RATED
PARTITION
TAPE AND JOINT
COMPOUND (TYP.)
1 LAYER REQUIRED
AT 1 HOUR SMOKE
PARTITION
2 HOUR RATED
PARTITION (HIGHER
PRIORITY)
1 HOUR CORRIDOR
PARTITION
NON-RATED STEEL
STUD PARTITION
1 LAYER REQUIRED AT
1 HOUR SMOKE PARTITION
2 HOUR RATED
PARTITION (HIGHER
PRIORITY)
5/8" FIRE-SHIELD
GYPSUM BOARD
1 HR PARTITION
FLEXIBLE SEALANT
(OPTIONAL)
5/8" FIRE-SHIELD
GYPSUM BOARD
1 HR PARTITION
FLEXIBLE SEALANT
(OPTIONAL)
5/8" FIRE-SHIELD
GYPSUM BOARD
CONTINUOUS STEEL TRACK
CLIPPED TO RECEIVE
TAPE AND JOINT
GYPSUM BOARD
COMPOUND
2 LAYERS 5/8" FIRE-SHIELD
GYPSUM BOARD
2 HR PARTITION
CONCRETE ON FLUTED
STEEL DECK
UNSUPPORTED LENGTH
FLEXIBLE SEALANT
(OPTIONAL)
STEEL J TRACK -
MECHANICALLY FASTEN
24" O.C. MAX.
TOP ROW OF
FASTENERS
5/8" FIRE-SHIELD
GYPSUM BOARD
CONCRETE ON FLUTED
STEEL DECK
HEAD OF WALL - 1 HR
UL DESIGN: HW-D-0194
FIRESTOP SEALANT
SLOTTED TRACK -
MECHANICALLY FASTEN
24" O.C. MAX.
5/8" FIRE-SHIELD
GYPSUM BOARD
CONCRETE ON FLUTED
STEEL DECK
HEAD OF WALL - 1 HR
UL DESIGN: HW-D-0572 MINERAL WOOL
INSULATION
ELASTOMERIC SPRAY
FIRESTOP
STEEL TRACK -
MECHANICALLY FASTEN
24" O.C. MAX.
5/8" FIRE-SHIELD
GYPSUM BOARD
CONCRETE ON FLUTED
STEEL DECK
MINERAL WOOL
INSULATION
HEAD OF WALL - 1 HR
UL DESIGN: HW-D-0548 ELASTOMERIC SPRAY
FIRESTOP
5/8" FIRE-SHIELD
GYPSUM BOARD
CT, CH, OR I STUDS
24" O.C.
CONCRETE ON FLUTED
STEEL DECK
MINERAL WOOL
INSULATION
HEAD OF WALL - 1 HR
UL DESIGN: HW-D-0569 ELASTOMERIC SPRAY
FIRESTOP
5/8" FIRE-SHIELD
GYPSUM BOARD
CT, CH, OR I STUDS
24" O.C.
CONCRETE ON FLUTED
STEEL DECK
PROFORM QUICK-SET
FS-90 COMPOUND
MINERAL WOOL
INSULATION
2 1/2"
MIN.
MAX.
3"
STEEL BEAM
SPRAY-APPLIED FIRE
RESISTIVE MATERIAL
20 GA. Z-CLIPS @ 24" O.C.
HEAD OF WALL - 1 HR
MAX., FASTEN BEFORE
UL DESIGN: HW-D-0642
APPLICATION OF SPRAY ON
UL DESIGN: HW-D-0571
FIREPROOFING
MINERAL WOOL
INSULATION
ELASTOMERIC SPRAY
FIRESTOP
5/8" FIRE-SHIELD
GYPSUM BOARD
CT, CH, OR I STUDS
24" O.C.
1" FIRE-SHIELD
SHAFTLINER
PARTITION - 1 HR
UL DESIGN: U499 STEEL TRACK -
UL DESIGN: W419 MECHANICALLY FASTEN 24"
O.C. MAX.
FLEXIBLE SEALANT
(OPTIONAL)
1/4" MIN.
CONCRETE ON FLUTED
STEEL DECK
STEEL BEAM
SPRAY-APPLIED FIRE
HEAD OF WALL - 1 HR RESISTIVE MATERIAL
UL DESIGN: HW-D-0645
UL DESIGN: HW-D-0636 3/8" DIAMOND MESH
EXPANDED STEEL LATH
MINERAL WOOL
INSULATION
1 1/2" Z FURRING OR
CHANNELS 24" O.C.
ELASTOMERIC SPRAY
FIRESTOP
5/8" FIRE-SHIELD
GYPSUM BOARD
CT, CH, OR I STUDS
24" O.C.
1" FIRE-SHIELD
SHAFTLINER
PARTITION - 1 HR STEEL J TRACK -
UL DESIGN: U499 MECHANICALLY FASTEN
UL DESIGN: W419 24" O.C. MAX.
FLEXIBLE SEALANT
(OPTIONAL)
1/4" MIN.
CONCRETE ON FLUTED
STEEL DECK
UNSUPPORTED LENGTH
FLEXIBLE SEALANT
(OPTIONAL)
STEEL J TRACK -
MECHANICALLY FASTEN
24" O.C. MAX.
TOP ROW OF
FASTENERS
2 LAYERS 5/8"
FIRE-SHIELD GYPSUM
BOARD
HORIZONTAL CONTROL
JOINT 30'-0" O.C.
CONCRETE ON FLUTED
STEEL DECK
UNSUPPORTED LENGTH
FLEXIBLE SEALANT
(OPTIONAL)
STEEL J TRACK -
MECHANICALLY FASTEN
24" O.C. MAX.
TOP ROW OF
FASTENERS
5/8" FIRE-SHIELD
GYPSUM BOARD
CT, CH, OR I STUDS
24" O.C.
1" FIRE-SHIELD
SHAFTLINER
5/8" FIRE-SHIELD
GYPSUM BOARD
PARTITION - 2 HR STEEL J TRACK -
UL DESIGN: U498 MECHANICALLY FASTEN
UL DESIGN: W419 24" O.C. MAX.
FLEXIBLE SEALANT
(OPTIONAL)
1/4" MIN.
CONCRETE ON FLUTED
STEEL DECK
HEAD OF WALL - 2 HR
UL DESIGN: HW-D-0194
UL DESIGN: HW-D-0342
FIRESTOP SEALANT
2 LAYERS 5/8"
FIRE-SHIELD GYPSUM
BOARD
CONCRETE ON FLUTED
STEEL DECK
MINERAL WOOL
INSULATION
HEAD OF WALL - 2 HR
UL DESIGN: HW-D-0548 ELASTOMERIC SPRAY
FIRESTOP
CONCRETE ON FLUTED
STEEL DECK
MINERAL WOOL
INSULATION
HEAD OF WALL - 2 HR
UL DESIGN: HW-D-0569 ELASTOMERIC SPRAY
FIRESTOP
CONCRETE ON FLUTED
STEEL DECK
PROFORM QUICK-SET
FS-90 COMPOUND
MINERAL WOOL
INSULATION
2 1/2"
MIN.
MAX.
3"
STEEL BEAM
SPRAY-APPLIED FIRE
RESISTIVE MATERIAL
20 GA. Z-CLIPS @ 24" O.C.
HEAD OF WALL - 2 HR
MAX., FASTEN BEFORE
UL DESIGN: HW-D-0642
APPLICATION OF SPRAY ON
UL DESIGN: HW-D-0571
FIREPROOFING
MINERAL WOOL
INSULATION
ELASTOMERIC SPRAY
FIRESTOP
CONCRETE ON FLUTED
STEEL DECK
STEEL BEAM
SPRAY-APPLIED FIRE
HEAD OF WALL - 2 HR RESISTIVE MATERIAL
UL DESIGN: HW-D-0645
UL DESIGN: HW-D-0636 3/8" DIAMOND MESH
EXPANDED STEEL LATH
MINERAL WOOL
INSULATION
1 1/2" Z FURRING OR
CHANNELS 24" O.C.
ELASTOMERIC SPRAY
FIRESTOP
CONCRETE ON FLUTED
STEEL DECK
PROFORM QUICK-SET
FS-90 COMPOUND
MINERAL WOOL
INSULATION
CONCRETE OR FLUTED
STEEL DECK
FIRESTOP SEALANT
STEEL J TRACK -
MECHANICALLY FASTEN
24" O.C. MAX.
1" FIRE-SHIELD
SHAFTLINER
1/2" GYPSUM BOARD
5/8"
5/8" FIRE-SHIELD
GYPSUM BOARD
STEEL STUDS
1/2" MAX.
FIRE TEST - 1 HR
BASED ON WHI-647-3024 2 LAYERS 5/8" FIRE-SHIELD
GYPSUM BOARD
VINYL OR METAL
CONTROL JOINT
1" FIRE-SHIELD
SHAFTLINER
1/2" GYPSUM BOARD
1 5/8" TYPE S SCREWS
24" O.C.
5/8"
1" FIRE-SHIELD
2 LAYERS 5/8" FIRE-SHIELD SHAFTLINER
GYPSUM BOARD
STEEL J TRACK
STEEL J TRACK
1" FIRE-SHIELD
SHAFTLINER
1" FIRE-SHIELD
SHAFTLINER
12" MAX.
1" FIRE-SHIELD
SHAFTLINER
1" FIRE-SHIELD
SHAFTLINER
STEEL J TRACK
PAN-HEAD SCREW
24" O.C.
STEEL J TRACK
2 LAYERS 5/8"
FIRE-SHIELD
GYPSUM BOARD
STEEL J TRACK
1" FIRE-SHIELD
SHAFTLINER
2 LAYERS 5/8"
FIRE-SHIELD
GYPSUM BOARD
1" FIRE-SHIELD
SHAFTLINER
1" FIRE-SHIELD
1" FIRE-SHIELD SHAFTLINER
SHAFTLINER
STEEL J TRACK
STEEL J TRACK
PAN-HEAD SCREW
24" O.C.
1" FIRE-SHIELD
SHAFTLINER
5/8" FIRE-SHIELD
GYPSUM BOARD
STEEL J TRACK -
MECHANICALLY FASTEN
24" O.C. MAX.
CONCRETE ON FLUTED
STEEL DECK
3" MAX.
4
FLEXIBLE SEALANT
(OPTIONAL)
STEEL J TRACK -
MECHANICALLY
FASTEN 24" O.C. MAX.
5/8" FIRE-SHIELD
GYPSUM BOARD
J TRACK
SW 702
CEILING LINE
J TRACK
DETAIL A DETAIL B
DUCT SURFACE
MOUNTING ANGLES
DUCT SURFACE
FLEXIBLE SEALANT AS
REQUIRED FOR SMOKE
SEAL
J TRACK
1" FIRE-SHIELD
SHAFTLINER
2 LAYERS 5/8" FIRE-SHIELD
GYPSUM BOARD
CONCRETE OR FLUTED
STEEL DECK
1" FIRE-SHIELD
SHAFTLINER
4" CT STUDS 20 GA.
C TRACK
2 HR RATED
FLOOR-CEILING
ASSEMBLY
MECHANICALLY FASTEN
STEEL J TRACK 24" O.C.
FLEXIBLE SEALANT
(OPTIONAL)
1/2" TYPE S OR S-12
PAN-HEAD SCREWS
(TWO PER STUD)
DUCT
1" FIRE-SHIELD
SHAFTLINER
VERTICAL - 2 HR
UL DESIGN: U497
HORIZONTAL - 2 HR
UL DESIGN: G586
DETAIL: ST 102
2 HOUR SHAFTWALL
ASSEMBLY -
UL DESIGN: U498
DETAIL: ST 104
NON-RATED STEEL
STUD PARTITION
2 HOUR SHAFTWALL
ASSEMBLY -
UL DESIGN: U497
LATERAL STEEL
BRACE
STEEL COLUMN
DETAIL: ST 103
2 HR SHAFTWALL
ASSEMBLY - COL.
UL DESIGN: U498
10" 10"
1" SHAFTLINER
FILLER STRIP STEEL COLUMN
FASTEN J TRACKS
WITH 1" TYPE S
SCREWS 24" O.C. NON-RATED STEEL STUD
PARTITION
2 HR SHAFTWALL ASSEMBLY
WITH LINER PANEL ORIENTED
TOWARD LATERAL BRACE -
UL DESIGN: U497
10" 10"
2 HR SHAFTWALL ASSEMBLY
WITH LINER PANEL ORIENTED
TOWARD LATERAL BRACE -
UL DESIGN: U497
FASTEN J TRACKS
WITH 1 5/8" TYPE S
SCREWS 24" O.C.
1" SHAFTLINER
FILLER STRIP
2 HR SHAFTWALL
ASSEMBLY WITH LINER
PANEL ORIENTED TOWARD
LATERAL BRACE -
UL DESIGN: U497
NON-RATED STEEL STUD
PARTITION
STEEL COLUMN
CONTROL JOINT
2 HR SHAFTWALL ASSEMBLY
WITH LINER PANEL ORIENTED
TOWARD LATERAL BRACE
UL DESIGN: U497
STEEL BEAM
STEEL J TRACK
4" x 4" STEEL TUBE
30" x 6" x 1/2" STEEL
1 1/2" x 6" x 1/2" STEEL ATTACHMENT PLATE FOR
PLATE GUIDE RAILS
DETAIL A
2" 2"
MINIMUM HOISTWAY WIDTH
2 HR SHAFTWALL
ASSEMBLY -
ELEVATOR CAB
UL DESIGN: U497
MINIMUM HOISTWAY DEPTH
DETAIL A
GUIDERAIL BRACKET
ASSEMBLY
PIT LADDER
5/8" FIRE-SHIELD
OR 1/2" FIRE-SHIELD
C GYPSUM
WALLBOARD
SECTION C-C
25 GA. 3" x 28"
SHEET STEEL
16" x 30" x1" RIGID ELBOW 1" FIRE-SHIELD
FIRE-SHIELD AND CONDUIT SHAFTLINER
SHAFTLINER
1/2" FIRE-SHIELD C
GYPSUM BOARD
1/2" FIRE-SHIELD C
GYPSUM BOARD
1 HR RATED
FLOOR-CEILING ASSEMBLY
1 1/2 HR FIRE-RATED
DAMPER
DUCT
NON-RATED SUSPENDED
CEILING
1 HR RATED PARTITION -
UL DESIGN: U465 OR V438
RATED OR NON-RATED
FLOOR-CEILING ASSEMBLY
BRACING AS REQUIRED
DUCT
1 HR RATED PARTITION -
UL DESIGN: U465 OR V438
RATED OR NON-RATED
FLOOR-CEILING ASSEMBLY
BRACING AS REQUIRED
DUCT
1 HR RATED PARTITION -
UL DESIGN: U465 OR V438
2 HR RATED
FLOOR-CEILING ASSEMBLY
1 1/2 HR FIRE-RATED
DAMPER
DUCT
NON-RATED SUSPENDED
CEILING
2 HR RATED PARTITION -
UL DESIGN: U411 OR V438
RATED OR NON-RATED
FLOOR-CEILING ASSEMBLY
BRACING AS REQUIRED
DUCT
2 HR RATED PARTITION -
UL DESIGN: U411 OR V438
RATED OR NON-RATED
FLOOR-CEILING ASSEMBLY
BRACING AS REQUIRED
DUCT
2 HR RATED PARTITION -
UL DESIGN: U411 OR V438
RATED OR NON-RATED
FLOOR-CEILING ASSEMBLY
BRACING AS REQUIRED
DUCT
HORIZONTAL SHAFTWALL
ASSEMBLY - UL DESIGN:
G586
NOTE:
FOR SPANS GREATER THAN
8'-0" REFER TO DETAIL SW 703
FOR INTERMEDIATE SUPPORTS
2 HR RATED PARTITION -
UL DESIGN: U411 OR V438
1/2" FIRE-SHIELD C OR
5/8" FIRE-SHIELD
GYPSUM BOARD
COLUMN - 1 HR
UL DESIGN: X528
1 5/8" STEEL STUD
CORNER BEAD
COLUMN - 2 HR
UL DESIGN: X528
1 5/8" STEEL STUD
CORNER BEAD
3 LAYERS
5/8" FIRE-SHIELD
GYPSUM BOARD
COLUMN - 3 HR
UL DESIGN: X510
1 5/8" STEEL STUD
CORNER BEAD
4 LAYERS
5/8" FIRE-SHIELD C
GYPSUM BOARD
COLUMN - 4 HR
UL DESIGN: X501
1 5/8" STEEL STUD
CORNER BEAD
CONCRETE ON FLUTED
STEEL DECK
1/4"
BEAM - 2 HR
UL DESIGN: N501
WALL PENETRATION
F RATING - 2 HR
T RATING - 0 HR
UL DESIGN: W-L-1041
OF OPENING
WALL PENETRATION
F RATING - 2 HR
T RATING - 0 HR
UL DESIGN: W-L-3035
FLOOR PENETRATION
F RATING - 3 HR
T RATING - 0 HR
UL DESIGN: C-AJ-1163
6" MAX.
MIN. 1" THICKNESS PROFORM
QUICK-SET FS-90 COMPOUND
MIN. 4 1/2" THICK LIGHTWEIGHT
OR NORMAL WEIGHT
CONCRETE FLOOR OR MIN. 5"
THICK CONCRETE WALL
NOM. 6" DIAMETER OR
SMALLER SCHEDULE 40
STEEL EMT, CONDUIT OR
PIPE GROUTED FLUSH WITH
FLOOR OR WALL ASSEMBLY
(OPTIONAL)
3" THICKNESS OF GLASS FIBER
INSULATION FIRMLY PACKED
INTO OPENING
MAX. 100 PAIR NO. 24 AWG
CABLES MIN. 10% TO MAX.
40% OF AGGREGATE
CROSS-SECTIONAL AREA
OF OPENING
NOTE: WALL ASSEMBLIES MAY ALSO
BE CONSTRUCTED OF ANY UL
CLASSIFIED CONCRETE
BLOCKS
FLOOR PENETRATION
F RATING - 3 HR
T RATING - 1/4 HR
UL DESIGN: C-AJ-3073
VOID ASSEMBLY
F RATING - 3 HR
T RATING - 1/2 HR
UL DESIGN: C-AJ-0038
10" MAX.
NOTES:
FOR MULTIPLE LAYER SYSTEMS STAGGER VERTICAL
AND HORIZONTAL PATCH JOINTS 12" MINIMUM AND
FASTEN VERTICAL EDGES TO STUD FRAMING