IRF
Feeder Protection
(ZIV e-NET flex family)
Protection for distribution
feeders, transformers and
generators, transmission
line backup, and BCU (bay
control unit)
General characteristics
9 Powerful programable logic.
9 2000 event log. Up to 100 oscillography seconds. The IRF is applicable in any substation scheme.
9 Alphanumeric or graphic display. The protection functions are suitable for any
9 160 DI, 80 DO, and 22 LEDs. neutral configuration, solid-grounded, resistor-
9 Bonding, RSTP, PRP and HSR Redundancy. grounded, Petersen coil compensated, and
9 IEC 61850 Ed.2, DNP3.0, Modbus RTU and isolated.
PROCOME Protocols.
9 Native process bus. Analog input cards operate as The powerful programmable logic features
Merging Units for the CPU. Synchronized samples selectable execution times according to the
at 4800 Hz (as per IEC 61869-9). required priority (2 ms, 10 ms and 20 ms). Includes
9 Cybersecurity in accordance with IEC 62351, IEC many digital and analog operators, which allows
62443 and IEEE 1686-2013 standards. RBAC, the creation of complex protection and control
secure keys, physical and logical port disabling, functions.
cybersecurity event log, securing of management
protocols (PROCOME, HTTPS, SFTP, SSH),
remote authentication (LDAP, RADIUS) and digital
firmware securitization.
9 Time synchronization by IRIG-B, SNTP and PTP
(Ordinary Clock / Transparent Clock).
Making the Smart Grid Real
Characteristics
Saturation Detector Protection Schemes
CT saturation detection is based on the current Directional overcurrent units include DTT, PUTT, POTT,
derivative. The detector modifies the overcurrent units DCUB and DCB schemes, allowing instantaneous
operating principle when activated. Overcurrent units use operation for faults inside 100% of the line.
instantaneous voltage besides RMS voltage, allowing for
less strict CT requirements. Restricted Earth Fault
ZIV continually strives to improve products and services. The technical information included in this document is subject to change without prior notice.
The REF unit detects transformer winding faults located
Directional units very close to the neutral point. In addition to the neutral
Directional units determine the direction of the fault in differential unit, the Restricted Earth Fault Unit includes
complex scenarios such as: zero voltage faults, voltage a directional comparison unit that increases security
inversion faults in series compensated lines, faults in against external faults with CT saturation. The IED has
isolated or compensated neutral grids, and more. low and high impedance Restricted Earth Faults unit.
Protection Units
ANSI Function Uns. ANSI Function Uns.
50 Instantaneous Phase O/C 4 78 Out-of-Step 1
51 Time-delayed Phase O/C 4 Cold-Load 1
50N Instantaneous Neutral O/C 4 59V/Hz Overexcitation 1
51N Time-delayed Neutral O/C 4 87N Restricted Earth Faults Unit 1
50G Instantaneous Ground O/C 4 60VT VT Supervision and Fuse Failure Detector 1
51G Time-delayed Ground O/C 4 60CT CT Supervision 1
50Q Instantaneous Negative Sequence O/C 4 79 Recloser 1
51Q Time-delayed Negative Sequence O/C 4 Sequence Coordination 1
50Ns Instantaneous Sensitive Ground O/C 1 3 Coil Supervision (Depending on the Hard-
51Ns Time-delayed Sensitive Ground O/C 1 ware Selection)
51Ns Time-delayed Sensitive Ground O/C with 1 Breaker Supervision 1
EPTR_C EPTR_C Fault Locator 1
51Ni/c Ungrounded/Compensated Neutral O/C 1 Transducer Voltage Supervision 1
50V Instantaneous Voltage Dependent O/C 1 2 Pole Discrepancy 1
51V Time-delayed Voltage Dependent O/C 1 Open Pole Detector 1
67 Phase Directional 1 Dead Line Detector 1
67N Neutral Directional 1 Saturation Detector 1
67G Ground Directional 1 Harmonics Blocking 1
67Ns Sensible Neutral Directional 1
67P Positive-Sequence Directional 1
67Q Negative Sequence Directional 1
67Ni/c Isolated / Compensated Neutral Directional 1
85 Overcurrent Teleprotection Schemes 1 2 FRONT
50FD Fault Detector 1 USB PORTS 2 REAR SERIAL
PORTS
Phase Selector 1 H0IRFA1807Iv02
46 Open Phase Detector 1
37 Time-Delayed Phase Undercurrent 1
27 Phase Undervoltage 4
59 Phase Overvoltage 4
59N Neutral Overvoltage 4
64 Ground Overvoltage 4
47 Negative Sequence Overvoltage 1
49 Thermal Image 1
81M Overfrequency 4
81m Underfrequency 4
81D Rate of Change of the Frequency 4
Load Shedding 1
UP TO 4
25 Synchronism Check Unit 1 MODULAR ETHERNET
32P/Q Directional Power (active / reactive) 2 DESIGN PORTS
50BF Breaker Failure Protection 1