Instrument Questions
Instrument Questions
INSTRUMENT :
Instrument is a devices which is used to measure, monitor, display etc. of a process variable.
Que. :2 : Define all the process Variable and state their unit of measurement. ?
Ans. : FLOW : Kg / hr, litre/ min, Gallon / min. M3 / NM3 / HR. ( GASES )
PRESSURE : Force acting per unit Area. P = F/A
Units : Bar / Pascal / Kg / CM /, Pounds
LEVEL : Different between two heights.
UNITS : Meters, mm, cm, %.
TEMPERATURE : It is the degree of hotness or coldness of a body.
Units : Degree Centigrade, Degree Fahrenheit, Degree Kelvin, Degree
Rankine.
QUALITY : It deals with analysis
pH, % CO2, % 02, Conductivity, Viscosity.
Que.3 : What are the primary elements used for flow measurement. ?
Ans. : The primary elements used for flow measurement are :
1. Orifice Plate.
2. Venturi tube.
3. Pitot tube.
4. Annubars.
5. Flow Nozzle.
6. Weir & Flumes.
Que. :4 What are the different types of orifice plates and state their uses ?
Ans. : The different types of orifice plates are :
1. Concentric.
538895746.docx
Page 1 of 31
2. Segmental.
3. Eccentric.
CONCENTRIC :
The concentric orifice plate is used for ideal liquid as well as gases and steam service. This
orifice as a hole in concentric and hence known as concentric orifice.
The eccentric orifice plate has a hole eccentric. The use this is made in viscous and sherry flow
measurement.
The segmental orifice place has the hole in the form segment of a circle. This is used for colloidal
and sherry flow measurement.
Que. : How do you identify the H. P. side or inlet of an orifice plate in line. ?
Ans. : The marking is always done H. P. side of the orifice tab which gives an indication of the H.
P. side.
538895746.docx
Page 2 of 31
1. Adjust zero of the Xmtrs.
2. Static pressure test : Give equal pressure on both sides of the transmitter. Zero
should not shift. If it is shifting carry out static alignment.
3. Vacuum test : Apply equal vacuum to both the sides. The zero should not shift.
4. Calibration Procedure :
1. Give 20 psi air supply to the transmitter.
2. Vent the L.P. side to atmosphere.
3. Connect output of the Instrument to a standard test gauge. Adjust zero.
4. Apply required pressure to high pressure side of the transmitter and adjust the span.
5. Adjust zero again if necessary.
Que. : What is the seal liquid used for filling impulse lines on crude and viscous liquid ?
Ans. : Glycol.
Que. : How do you carry out piping for a Different pressure flow transmitter on liquids, Gas
and steam services ? Why ?
Ans. : Liquidlines: l
On liquid lines the transmitter is mounted below the orifice plate. Since liquids have a property
of self draining.
Gas Service :
On gas service the transmitter is mounted above the orifice plate because Gases have a
property of self venting and secondly condensate formation.
Steam Service :
On steam service the transmitter is mounted below the orifice plate with condensate pots. The
pots should be at the same level.
Que. : An operator tells you that flow indication is more ? How would you start checking ?
Ans. : 1. First flushing the transmitter. Flush both the impulse lines. Adjust the zero by
equalizing if necessary. If still the indication is more then.
2. Check L.P. side for choke. If that is clean then.
3. Check the leaks on L.P. side. If not.
4. Calibrate the transmitter.
Que. : How would you do Glycol filling or fill seal liquids in seal pots 7 Draw and explain.
Ans. : The procedure for glycol filling is :
01. Close the primary isolation valves.
02. Open the vent on the seal pots.
03. Drain the use glycol if present.
04. Connect a hand pump on L.P. side while filling the H.P. side with glycol.
538895746.docx
Page 3 of 31
05. Keep the equalizer valve open.
06. Keep the L.P. side valve closed.
07. Start pumping and fill glycol.
08. Same repeat for L.P. side by connecting pump to H.P. side, keeping equalizer open and
H.P. side isolation valve closed.
09. Close the seal pot vent valves.
10. Close equalizer valve.
11. Open both the primary isolation valves.
Que. : How do you calculate new factor from new range using old factor and old range. ?
Ans. : New Factor = _ / New Range
Old Factor = _ / Old Range
Flow = K _ / Range
Q = Factor X Unit Flow
New Factor = Old Factor / _/Old Range X _/New Range.
Que. : How will you vent air in the D.P. cell ? What if seal pots are used ?
Ans. :
1. Air is vented by opening the vent plugs on a liquid service transmitter.
2. On services where seal pots are used isolate the primary isolation valves and open the
vent valves. Fill the line from the transmitter drain plug with a pump.
directly indicate flow. The flow can be determined by taking the square root of the pen. Say the
pen reads 50% of chart.
D E F I N A T I O N.
ACCURACY :
A number or quantity which defines the limit of error under reference conditions.
ATTENUATION :
DEAD TIME :
The interval of time between initiation of an impact change or stimulus and the start of the
resulting response.
538895746.docx
Page 4 of 31
DRIFT :
As undesired change in output over a period of time, which change is unrelated to input,
operating conditions, or load.
ERROR :
The difference between the indication and the true value of the measured signal.
SPAN ERROR :
It is the difference between the actual span and the specified span and is expressed as the
percent of specified span.
ZERO ERROR :
It is the error of device operating under the specified conditions of use when the input is at the
lower range value.
STATIC GAIN :
It is the ratio of the output change to an input been change after the steady state has been
reached.
HYSTERESIS :
The maximum difference between the upscale and downscale indications of the measured signal
during a full range traverse for the same input.
INTERFERENCE :
Interference is any spurious voltage or current arising from external sources and appearing in the
circuits of a device.
It is the form of interference which appears between the measuring circuit terminals and ground.
LINEARITY :
538895746.docx
Page 5 of 31
RANGE :
The region between the limits within which a quantity is measured received or transmitted,
expressed by stating the lower and upper range values.
REPEATABILITY :
The closeness of agreement among a number of consecutive measurements of the output for
the same value of the measured signal under the same operating conditions.
REPRODUCIBILITY :
The closeness of agreement among repeated measurements of the output for the same value of
the input made under the same operating conditions.
RESPONSE :
It is the general behavior of the output of a device as a function of input both with respect to time.
TIME CONSTANT :
The time required for the output to complete 63.2 % of the total rise or decay.
SPAN :
ZERO SHIFT :
Any parallel shift of the input output curve.
P R E S S U R E.
PRESSURE CONVERSIONS :
538895746.docx
Page 6 of 31
1 10.000mm
Kg/cm2 of H20
=
1 Bar = 1.0197
Kg/cm2
1 0.98 Bar
Kg/cm2
=
1 Torr = 1 mm of Hg.
538895746.docx
Page 7 of 31
3. Helix.
Capsules : Two circular diaphragms are welded together to form a pressure capsule.
Material Used : phosphor bronze, Ni-spanc stainless steel.
Bellows : Bellows is a one - piece, collapsible, seamless metallic unit with deep folds formed from
very tin walled tubing.
Material used : Brass, phosphor bronze, stainless steel. Used for high pressure.
PRESSURE SPRINGS : Pressure springs of helical or spiral shape used for measuring high
pressures.
Que. : Draw and explain a pressure gauge ? What is the used of a Hair spring ?
Ans. : The parts of a pressure gauge are :
1. 'C' type Bourdon tube.
2. Connecting link.
3. Sector gear.
4. Pinion gear.
5. Hair Spring.
6. Pointer.
7. Dial.
Uses of Hair Spring : Hair spring serves two purposes name
1. To eliminate any play into linkages.
2. It serves as a controlling torque.
Que. : How will you calibrate an absolute pressure transmitter vacuum manometer
Range 0-400mm abs. ?
Ans. : The procedure for calibration is as follows :
1. Connect air supply to the transmitter.
2. Connect a test gauge of 0-1.4 Kg/cm2 to the output.
3. Connect Vacuum pump with tee off to the manometer.
4. Apply 760 mm Vacuum ( or nearest ) and adjust zero.
5. Apply 360 mm Vacuum adjust span. ( 760 - 360 = 400 mm abs. )
Que. : You are given a mercury manometer range 0 -760 mm ? A vacuum gauge reads 60 mm
vacuum. The test manometer reads 50 vacuum ? Which of the two in correct.
538895746.docx
Page 8 of 31
Ans. : The transmitter is correct because 760 - 50 = 710 mm abs.
LEVEL
2. SIGHT GLASS : This consists of a graduated glass tube mounted on the side of the vessel.
As the level of the liquid in the vessel change, so does the level of the liquid in the glass tube.
2. PURGE SYSTEM : In this method a pipe is installed vertically with the open and at zero level.
The other end of the pipe is connected to a regulated air r supply and to a pressure gauge. To
make a level measurement the air supply is adjusted so that pressure is slightly higher than the
pressure due to height of the liquid. This is accomplished by regulating the air pressure until
bubbles cab be seen slowly leaving the open end of the pipe.
The method above are suitable for open tank applications. when a liquid is in a pressure vessel,
the liquid column pressure can't be used unless the vessel pressure is balanced out. This is done
through the use of different pressure meters.
DIFF.PRESSURE METHOD : Connection are made at the vessel top and bottom, and to the two
columns of the D.P. meter. The top connection is made to the L.P. column of the transmitter and
the bottom to H.P. column of the transmitter. The difference in pressure in the vessel is balanced
out, since it is fed to both the column of the meter. The difference in pressure deducted by the
meter will be due only to the changing, level of the liquid.
538895746.docx
Page 9 of 31
Que. : Explain how you will measure level with a different pressure transmitter.
Ans. : The bottom connection of the vessel is connected to high pressure side of the transmitter.
Different Pressure = H X D
This difference pressure is applied to H.P. side of the transmitted and calibrated.
DISPLACER : It is consists of a cylindrical shape pipe sealed and filled inside with sand or some
weight. The purpose of this is to convert change in level to primary motion. The variation in
buoyancy resulting from a change in liquid level varies the net weight of the displacer increasing
or decreasing the load on the torque arm. This change is directly proportional to change in level
and specific gravity of the liquid.
538895746.docx
Page 10 of 31
PROPORTIONAL UNIT. : Converts primary motion to a proportional output air pressure.
538895746.docx
Page 11 of 31
Ans. : Wt. test calibration method :
1. Remove the displacer from the torque arm.
2. Apply equivalent weight on the torque arm that is equal to the wt. of the displacer. Adjust zero
% output.
3. For Span : V = TTr2h
Loss in weight = Wt. of float - wt. of the float immersed in liquid
Loss in weight = [ wt. of float - Vol. x d ]
Span wt. = (wt. of float - Loss in wt.)
r = radius of the displacer.
h = ht. of displacer.
4. Apply equivalent wt. equal to the (Wt. of float - Loss in weight). Adjust Span to get 100 % out
put.
5. To check linearity apply average of the two weights.
Que. : What will happen if the displacer has fallen down while in line ?
Ans. : The output will be minimum. ( wrong )
The output will be maximum (100 %) true.
Que. : What will happen if the displacer has a hole in it while in line ?
Ans. : The output will be maximum.
Que. : How will you commission D.P. transmitter in field in pressurized vessel.
Ans. : 1. Close both the isolation valves, Vent the H.P. side.
2. Fill it with the sealing liquid.
3. Open the L.P. side vent valve.
4. Adjust zero with suppression spring.
5. Close the L.P. side vent valve.
6. Open both the isolation valves.
Que. : How will you check zero of a level D.P. transmitter while is line ?
Ans. : 1. Close both the isolation valves.
2. Open the vent valve on L.P. leg and H.P. leg drain.
3. Check and adjust zero if necessary.
538895746.docx
Page 12 of 31
Ans. : The Enraf level precise level gauges are based on servo powered null balance technique.
A displacer serves as continuos level sensing element.
Principle :
A displacer A with a relative density higher than that of a product to be measured, is suspended
from a stainless steal wire B tat is attached to a measuring drum. A two phase servo motor
controlled by a capacitive balance system winds unwinds the measuring wire until the tension on
the weight springs is in balance with the wt. of the displace part immersed in the liquid. The
sensing system in principle measures the two capacitance formed by the moving central sensing
rod E provided with two capacitor plates and the si plates. In balance position the capacitance
are of equip value. A level variation will cause a difference in buoyancy of the displacer. The
center sensing rod will move in to direction of one of the side capacitor plates. This causes
difference in value of this capacitance. By an electrolyte rotation of the servo motors the can
driven transmitter continuously change the voltage pattern to remote indicate of which the
receiver motor drives a counter indicating low variation.
TEMPRETURE
enclosed. When the thermometer is heated the mercury expands much more than the glass and
is therefore forced to rise up in the tubing A scale is fixed at the side.
2. Bimetallic Thermometer : Two metals whose coefficient of linear expansion is different are
welded and rolled together to the desire thickness. The actual movement of a bimetal is its
flexibility with one end fixed, a straight bimetal strip deflects in proportion to its temperature, to
the square of its length and inversely with its thickens.
538895746.docx
Page 13 of 31
Compensations are provided in order to nullify the effect of changes in ambient temperature. The
compensation in liquid filled expansions thermal system consists of the second tubing and helical
element, both liquid filled. The two elements are so constructed that the measuring helical floats
on a movable base the position of which is governed by the compensating helical. The two tubing
and helicals are matched in volume so that variation in temperature at the instrument case and
along the capillary tubing produce equal motion from both helicals. Such motion nullity each
other so that only motion produced by varying the bulb temperature actuates the recorder pen.
temperature charge is small, at higher temperature the vapor pressure change is much greater.
538895746.docx
Page 14 of 31
x = Co. off of thermal (expansion).
t = Temperature to be measured.
These metals have a positive temperature co-efficient of expansion. Therefore resistance
increases as the temperature increases.
OPERATION :
The input to the instrument is a measurement of some in the processes using a sensing element
( such as thermocol ) or a device to produce direct voltage, which is the voltage (signal). This
voltage is subtracted from a voltage developed by a known constant voltage in a potentiometric
measuring circuit. The subtraction occurs by connecting two voltages in series with the opposing
polarity, difference between these two voltages produces signal, the voltage going to the
amplifier. The error will positive or negative depending on which of the two voltages greater.
When amplified, the error signal will drive servo balancing motor in appropriate direction to adjust
circuit ( actually drive the slide wire ) until the difference between the feedback voltage and the
input voltage is balance out. An error signal equal to zero results ( null point ) the balancing
( servo motor is be longer driven )
538895746.docx
Page 15 of 31
zener CR3, R1 and R2 combine provide relatively constant current to zener CR4, Thus
variations. Resisters R2 and R3 form a bridge that any remoment line voltage effects.
Selecting a thermowell :
The significant properties considered in selecting a material for the well are as follows :
1. Resistance to corrosion and oxidation.
2. Resistance to mechanical and thermal shock.
3. Low permeability ( Resistance to gas leakage ).
538895746.docx
Page 16 of 31
4. Mechanical strength.
5. Thermal conductivity.
4. While feeding subtract the ambient temp. m v s from the corresponding temp. every time.
5. Adjust the necessary adjustments.
Que. : What type of sensing element would you use to measure very low temperature ?
Ans. : The sensing element used for measuring very low temperature is R. T. D.
538895746.docx
Page 17 of 31
calibrated slide wire. Variations in temp. of the measured medium cause a change in resistance
of the bulb and a consequent unbalance of the bridge circuit. A self balancing wheatstone bridge
recognizes the condition of unbalance, determines its direction and magnitude and position the
slide wire contractor to rebalance the bridge and indicate the temp. on the scale.
The polarity of the signal at AA determines the phase of the alternating voltage at BB which in
turn determines the direction of rotation of the balancing motor.
Que. : How is automatic Reference junction compensation carried out in temp. ? Recorders
etc.
Ans. : For automatic reference junction compensation a variable nickel resister is used. As the
temperature changes, so does its resistance. This reference junction compensatory is located,
so that it will be at the temperature of the reference junction. The reference junction is at the
position where the dissimilar wire of the thermocouple is rejoined, which invariably is at the
terminal strip of the instrument.
CONTROL SYSTEMS
AUTOMATIC CONTROLLER :
It is a device which measured the value of variable quantity or condition and operates to correct
or lie it deviation of this measured value from a selected reference.
PROCESS :
A process comprises the collective function performed in and by the equipment in which a
variable is to be controlled.
SELF REGULATION :
538895746.docx
Page 18 of 31
It is an inherent characteristic of the process which aids in limiting the deviation of the controlled
variable.
CONTROLLED VARIABLE :
The controlled variable is that quantity and condition which is measured and controlled.
CONTROLLED MIDIUM :
It is that process energy or material in which a variable is controlled. The controlled variable is a
condition or characteristic of the controlled medium. For e.g. where temperature of water in a
tank is automatically controlled, the controlled variable is temperature and controlled medium is
water.
MANIPULATED VARIABLE :
It is that quantity or condition which is varied by the automatic controller so as to affect the value
of the controlled variable.
CONTROL AGENT :
It is that process energy or material of which the manipulated variation is a condition or
characteristic. The manipulated variable is a condition or characteristic of the control agent. For
e.g. when a final control element changes the fuel gas flow to burner the manipulated variable is
flow the control agent is fuel gas.
ACTUATING SIGNAL :
The actuating signal is the difference at anytime between the reference input and a signal related
to the controlled variable. This basically known as error signal.
DEVIATION :It is the difference between the actual value of the controlled variable and the value
of the controlled variable corresponding with set point.
OFFSET :
It is the steady state difference between the control point and the value of the controlled variable
corresponding with setpoint
CORRECTIVE ACTION :
It is the variation of the manipulated variable produced by the controlling means. The controlling
means operates the final control element ( control value ) which in turn varies the manipulated
variable.
REFERENCE INPUT :
It is the reference signal in an automatic controller.
SET POINT :
It is the position to which the control point setting mechanism is set.
CONTROL POINT :
538895746.docx
Page 19 of 31
It is the value of the controlled variable which under any fixed set of conditions the automatic
controller operates to maintain.
PRIMARY FEEDBACK :
538895746.docx
Page 20 of 31
It is the signal which is related to the
€_‚Ò_ÖM_ith the reference input to obtain the actuating signal. Simply stated primary feedback
is the actual measurement of the controlled variable which when compared with the desired
measurement of the controlled variable produces the actuating signal.
POSITIONING ACTION :
It is that in which there is a predetermined relation between the value of the controlled variable
and the position of the final control element.
PROPORTIONAL ACTION :
It is that in which there is a continuous linear relationship between the value of the actual
measurement of the controlled variable and the value position.
FLOATING ACTION :
It is that in which there is a predetermined relation between the deviation and speed of final
control element.
DERIVATIVE ACTION :
It is that in which there is a predetermined relation between a time derivative of the controlled
variable and position of final control element.
REST ACTION :
It is the value movement at a speed proportional to the magnitude of deviation.
RATE ACTION :
It is that in which there is a continuos linear relation between the rate of change of controlled
variable and position of final control element. Rate action produces value motion proportional to
the rate of change of actual measurement.
PROPORTIONAL BAND :
It is the range of values of the controlled variable which correspond to the full operating range of
the final control element.
RESET RATE :
It is the number of times/minute that the effect of proportional position action upon the final
control element is repeated by proportional speed floating action.
538895746.docx
Page 21 of 31
b) The travel as a result of the effect of proportional position action with the same deviation in
both cases.
2. Reset Time : It is the time interval by which the rate is commonly expressed in minutes. It is
determined by subtracting.
a) The time required for a selected motion of the final control element resulting from combined
effect of the proportional position plus rate action.
b) The time required for the same motion as a result of the effect of proportional position action
alone with the same rate of change of controlled variable in both cases or expressed in another
way. It is the time lead in terms of air pressure on the control value produced by rate action
compared with proportional position action for the same rate of change of actual measurement in
both cases.
538895746.docx
Page 22 of 31
Que. : Where is ON / OFF control used ?
Ans. : On off control is used when
1. Precise control is not needed.
2. Processes that have sufficient capacity to allow the final operator to keep up with the
measurement cycle.
3. It is mainly used in refrigeration and are conditioning systems.
Que. :
Ans. : When reset action is applied in controllers Where the measurement is away from the set
point for long periods the rest may drive the output to its maximum resulting in rest wind up.
When the process starts again the output will no come off its maximum until the measurement
crosses the so point causing large overshoots. This problem can be avoid by including antireset
wind up circuit which eliminates the problem of output saturation.
538895746.docx
Page 23 of 31
5. With controller on manual, impose a step changes in the output of controller, which is an
signal to value.
6. Record the response of controlled variable.
7. Return the controller output to its previous value and return the controller to auto operation.
ANALOGUE DIFFERENTIATER :
538895746.docx
Page 24 of 31
or cone shaped, actually more dense than the fluid being measured, creates an annular passage
between its maximum circumference and the weight of the tapered tube. As the flow varies the
"float" rises or falls to vary the area of the passage so that the differential across it just balances
the gravitational force on the "float" i.e. the differential pressure is maintained constant. The
position of the "float" is the measured of the rate of flow.
PRINCIPLE : If a tube is placed with its open and facing into a stream of fluid, then the fluid
impinging on the open end will be brought to rest, and the kinetic energy converted to pressure
energy. This the pressure built up in the tube will be greater than that in the free stream by the
impact pressure or pressure produced by loss of kinetic energy. The increase in pressure will
depend upon the square of the velocity of the stream. The difference is measured between the
pressure in the tube and static pressure of the stream. The static pressure is measured by a
tapping in the wall of the main or by a tapping incorporated in the pitot static tube itself. The
difference between the pressure in the tube and static pressure will be a measure of the impact
pressure and therefore of the velocity of the stream oil.
538895746.docx
Page 25 of 31
Ans. : Integral orifice is used to measure small flow rates. It is mounted directly on the secondary
device. The integral orifice diameter varies between 0.020 inch and 0.250 inch diameter. The
integral orifice finds considerable use in laboratory and pitot plants.
Calculation of flow rate :
Qn / Fc = Ks x Cwi x Fa x Fm x ( Gp / Ge ) hw
{ Wm } 2
F = {------------------------------ }
{ Cst Fa Fm Fc cf }
2. CORNER TAPS :
On pipe sizes less than 2 inches corner taps located directly at the face of the orifice plate.
538895746.docx
Page 26 of 31
Face flow taps are located at 2 1/2 pipe diameter upstream and B pipe diameter downstream.
Full flow taps at 2 1/2 and B pipe diameter have the same advantage as vena contracta or radius
taps.
538895746.docx
Page 27 of 31
7. Oval Gear type.
$$ CONTROL VALVES $$
A control valve consists of an operator and valve body. The operator provides the power
to vary the position of the valve plug inside the body. The plug is connected to the
operator by a stem, which slides through a stuffing box. The air signal from the controller
is applied above the diaphragm. The increasing air signal from the controller is applied
above the diaphragm. An increasing air signal will push the operator stem downwards
against the force exerted by the spring on the diaphragm plate. The valve is adjusted in
such a way that the plug starts moving when 3 psi is applied to the diaphragm and
touches the seat when 15 psi is applied
gm. Thus an increase in air pressure will close the valve. Hence the home "Air to Close".
Another type is "Air to open", such that 3 psi on the diaphragm the value is closed and 15
psi air signal it in fully open.
538895746.docx
Page 28 of 31
Que. : What is Cv of a valve ?
Ans. : Cv is the capacity of a valve and is defined as :
"No of gallons per minute of water which passes through a fully open valve at a pressure drop of
1 psi.
The valve coefficient Cv is proportional to the area 'A' between the plug and valve seat measured
perpendicularly to the direction of flow.
Que. : What types of bonnets would you use of high temp. and low temp. ?
Ans. :
HIGH TEMP. : Bonnets are provided with radiation fins to prevent glad packing from getting
damaged.
ON VCF LOW TEMP. : Extended bonnets are used to prevent gland packing from getting
frcored.
538895746.docx
Page 29 of 31
link in turn senses this change and the positioner will produce an output which will operate the
valve to the original position.
ADVANTAGE :
1. Actuator forces required are very less.
2. Extended bonnet and hence can be used on any service i.e. on high temp. and very low temp.
3. Variations in flow.
4. Light weight.
538895746.docx
Page 30 of 31
V. PORT PLUG :
Ported plug are generally used on double seated valves. This is because ported plugs, have a
more constant off balance area.
CONTOURED PLUGE :
Contoured plugs are generally used on single seated valve with small trim sizes.
EQUAL PERCENTAGE :
For equal increments of valve opening it will give equal increment in flow rate range. At small
opening the flow will also be small.
QUICK OPENING :
At small opening the increments in flow rate is more. At higher opening the flow rate becomes
steady.
Que. : How will you change the valve characteristics with positioner ?
Ans. : The positioner contains different types of came in it. selection of the proper can the valve
opening characteristics can be changed.
538895746.docx
Page 31 of 31
Que. : How will you select the control valve characteristics ?
Ans. : The graphic display of flow various lift shows then the Desired or inherent characteristic is
changed by variations pressure drop. This occurs as the process changes from condition where
most of pressure drop takes place at the control valve is a condition where most of the pressure
drop is generally distributed through rest of the system.
% Flow : This variation in where most of the total drop take place is one of the most important
aspects is choosing the proper valve characteristics for give process.
Flow control : Normally Equal percentage valve is used.
Pressure Control : Normally linear valve is used to maintain a constant pressure drop.
Temp. Control : Normally equal percentage valve is used.
Liquid Level Control : Normally linear valve is used.
Basically in selecting a valve characteristic two important point have to be taken into account.
a) There should be a linear relationship between the position of the plug and the flow through the
valve in a wide range of change in the pressure drop across the valve.
b) The pressure drop across a valve should be as low as possible.
Que. : An operator tells you that a control valve in a stuck ? How will you start checking ?
Ans. :
1. First of all get the control valve is passed from operation.
2. Check the lingual to the diaphragm of the control valve.
3. Disconnect it possible the actuator stem from the control valve stem.
4. Stroke the actuator and see whether the actuator operates or not. It not then the diaphragm
may be punctured.
5. If the actuator operates connect it back to the plug stem stroke the control valve. If it does not
operate loosen the gland nuts a bit and see if it operates. If it does not then the control valve has
to be removed from the line to w/shop.
Que. : Where is an Air to close and Air to open control valves used ?
Ans. :
AIR TO CLOSE :
1. Reflux lines.
2. Cooling water lines.
3. Safety Relief services.
AIR TO OPEN :
1. Feed lines.
2. Steam Service.
538895746.docx
Page 32 of 31
Force produced = 15 psi x 25" pounes.
$$ GENERAL QUESTIONS. $$
Que. : Explain Cascade Control system with a diagram. What would happier if a single controller
were used ?
Ans. : Cascade means two controllers is series. One of them is the Master or Primary and the
second is the secondary of slave controller. The output of the secondary controller operates the
final control element, that is the valve.
LOOP EXPLANATION :
The output of the temp. transmitter goes as measurement signal to the TIC which is the master
controller. Similarly the output of pressure transmitter goes as measurement signal to the PIC
which is the secondary controller.
The output of TIC comes at set point to PIC which is turn operates the valve. The reqd. temp. is
set on the TIC.
538895746.docx
Page 33 of 31
Ans. : Balanced draft boilers are generally used negative furnace pressure. When both forced
draft and induced draft are used together, at some point in the system the pressure will be the
same as that of atmosphere. Therefore the furnace pressure must be negative to prevent hot
gas leakage. Excessive vacuum in the furnace however produces heat losses through air
infiltration. The most desirable condition is that the one have is a very slight ( about 0.1" H20 )
negative pressure of the top of furnace.
Que. : What is feed back control ? What is feed forward control ? Discuss its application ?
Ans. :
FEEDBACK CONTROL :
Feed back control involves the detection of the controlled variable and counteracting of charges
its it’s value relative to set point, by adjustment of a manipulated variable. This mode of control
necessities that the disturbance variable must affect the controlled variable itself before
correction can take place. Hence the term 'feedback' can imply a correction 'back' in terms of
time, a correction that should have taken place earlier when the disturbance occurred.
$$ GENERAL QUESTION - II $$
"Defn. :" Intrinsically safe circuit is one in which any spark or thermal effect produce either
normally or under specified fault conditions is incapable of causing ignition of a specified gas or
vapor in air mixture at the most easily ignited concentration.
538895746.docx
Page 34 of 31
HAZARDOUS AREAS :
The specification of products or systems sold as intrinsically safe must state in what hazardous
areas they are infect intrinsically safe. Universal cooling of hazardous areas has not,
unfortunately, been adopted in all countries. However two sets of codes in common use are.
Que. : What does a transmitter output start from 3-15 psi or (0.2 - 1 Kg/Cm2) or 4 - 20 ma. etc. ?
Ans. : The transmitter output stance from what is known as "live zero". This system has specific
advantages :
1. The systems automatically alarms when the signal system becomes inoperative.
2. The output areas is linear ( Ratio of 1 : 5 ).
The input force is applied on the input bellows which novas the beam. This crackles nozzle back
pressure. The nozzle back pressure is sensed by the balancing bellows which brings the beam to
balance. The baffle movement is very less about 0.002" for full scale output.
The increase in input signal will cause the baffle to move towards the nozzle. The nozzle back
pressure will increase. This increase in back pressure acting on the balancing bellows, will
expands the bellows, there by moving the nozzle upward. The nozzle will move untill motion
(almost) equals the input (baffle) motion.
Advantages of force Balance :
1. Moving parts are fever.
2. Baffle movement is negligible.
3. Frictional losses are less.
ELECTRONICS
538895746.docx
Page 35 of 31
A diode is the most basic solid state (semi conductor) device. The above figure shows a P.N.
junction. The P. material has holes and the N. material has electrons.
FORWARD BIAS :
REVERSE BIAS :
( 1 ) Where the applied voltage overcomes the barrier potential (the p side is more positive than
the n side) the current produce is large because majority carriers cross the junction in large
numbers. This condition is called forward bias.
( 2 ) When the applied voltage aids the barrier potential (n side + ve than p side) the current in
small. This state is known as Reverse Bias.
BRIDGE RECTIFIER :
PEAK INVERSE VOLTAGE : Maximum Reverse voltage across the diode during the cycle.
A Zener diodes operating in the breakdown region is equivalent to a battery. Because of this
current through Zener diode can change but the voltage remains constant. It is this constant
voltage that has made the zever diode an important device in voltage regulation.
VOLTAGE REGULATOR :
The output remains constant despite changes in input voltage due to Zever effect.
538895746.docx
Page 36 of 31
Whether the transistor is pnp or npn it resembles two diodes (back to back). The one of the left is
called bipolar devices.
Biasing the transistor :
Emitter - Base - Forward Bias.
Collector - Base - Reverse Bias.
On the other hand , if something causes the 02 base current to decrease, the 02 collector current
will decrease. This reduces the 01 base current. In turn, there is less 01 collector current, which
reduces the 01 base current even more. This regeneration continues until both transistors are
driven into cut off. At this time the latches like a open switch. This latch will always stay in open
or close position.
538895746.docx
Page 37 of 31
1. OR - GATE :
SYMBOL :
TRUTH A B Y
TABLE :
0 0 0
0 1 0
1 0 0
1 1 1
Define : An OR Gate has one output if any or all of its input are 1's.
2. AND GATE :
Define : An AND Gate has output when all inputs are present.
SYMBOL :
TRUTH A B Y
TABLE :
0 0 0
0 1 0
1 0 0
1 1 1
3. NOT GATE :
A not gate is also known as an inverter. This circuit has one input and one out put . All it does is
invert the input signal; if the input is high, the output is low and vice versa.
Buffer : This is a non inverting gate, used to drive low impedance loads.
SYMBOL :
TRUTH A B Y
TABLE :
0 0 1
0 1 0
1 0 0
1 1 0
538895746.docx
Page 38 of 31
Exclusiv A B Y
e OR
GATE
0 0 0
0 1 1
1 0 1
1 1 0
TRUTH A B Y
TABLE :
0 0 1
0 1 1
1 0 1
1 1 0
538895746.docx
Page 39 of 31