ke-DP01-100A: Digital Protector
ke-DP01-100A: Digital Protector
ke-DP01-100A
Digital Protector VL1,VL2,VL3 Display Functions: Special Buttons:
Voltage – Current VL12,VL23,VL13
and Select: (Up direction)
IL1,IL2,IL3 when pressing continuously,
Frequency control Hz VL1 screen displays frequency of
0 -100A system. When button release
Phase Sequence Control L1 L2 L3
device continue to show voltage.
Over Voltage Protection
Over Frequency L1 L2 L3
Protection
Under Frequency
Protection VL23
L1 L2 L3
Latch Function
TRUE RMS
VL13
AREAS OF OPERATION: L1 L2 L3
Umax (o-U)
Normal
Normal
Umin (u-U)
Over and/or Under Frequency Protection : ( 40 – 70 Hz )
Under Frequency be able to set between(u-F) = 40 Hz ...[(o-F) -0,4]
Under Voltage
t
Over Frequency be able to set between (o-F) =[(u-F) + 0,4]...70 Hz
t-1 r-t t-1 r-t
If required , it can be set only under frequency or only over frequency
protection as well as both of protection can be disabled.
If o-F = 55 Hz and u-F = oFF set, device works as over
Re t
frequency protector only. (if system frequency above 55 Hz, under
screen displays o-F warning and end of time t-2 relay switch off its
Over and Under Current : (o-C),(u-C)
output contact )
Under Current (u-C)
if o-F = oFF and u-F = 45 Hz set , device works as under
Over Current (o-C)
frequency protector only . (if system frequency below 45 Hz, under
When the current of the protected system goes below the adjusted
screen displays u-F warning and end of time t-2 relay switch off its
value it switches off its output contact after d-t delay.
out contact.)
Normal LED turn off and relay switch off its contact .In this case
if o-F = oFF and u-F = oFF set, frequency protection is disabled.
u-C warn appears on display.
When any current passing through any phase of the protected system
exceeds the adjusted value the device switches off its output contacts
after a proper time (d-t).Normal LED turn off and relay switch off its
contact .In this case o-C warn appears on display. f(Hz)
Over Frequency L1,L2,L3
NOTE: Under current protection set value with its hysteresis must not
55 Hz (o-F)
overlap with over current protection set value with its hysteresis or, the Normal
Normal
under current protection set value must not be higher than the over 45 Hz (u-F)
current protection set value.
Under Frequency
t
t-2 r-t t-2 r-t
I(A)
VOC Re t
OC
LOCKING FUNCTION :
It can be controlled by two parameters. Locking time and
Locking counter. If the number of opening reaches the adjusted
o-C
%hYS
locking counter withing the adjusted locking time then device
switch off its contact and locks its functions until the user
%hYS
pressed Reset button.
u-C
If the locking counter is adjusted to oto then this function is
disable and device never locks itself.
t L-t : Locking Time ( 001 – 060 min. )
Sdt d-t r-t d-t r-t It is well know the frequently occurring faults may damage
r-t r-t system. For that the device when number of faults reaches the
Re t adjusted locking number within this locking time. This way the
system is protected and user has chance to investigate the
problem.
Start delay time: Sd-t L-C : Locking Counter ( oto , 001 – 010 piece )
It can be set between 1 and 60 seconds.It is used to prevent the switch The number of faults allowed within the period L-t. If number of
off from occurance because of the motor's inrush current. faults exceeds this adjusted counter value device locks itself.
This function can be disable if Sd-t value = 000 (oFF) In this case (- - -) warn appears on its screen. User must press
Return Time : r-t Reset button then the fault passes in order to unlock the device.
it shows the delay time that device will wait to switch on its output relay If L- C is set to oto then this property is disabled.
when failure ends after a switch off. It can be set between 0,5 and 99,9
seconds.
Very Over Current Coefficient : VOC (Current Very Sudden Switch
Off Protection) L- C (number of lock) = 2 piece
It can be set by the user between 2,1 and 6. L- t (lock time) = 3 min. if select ;
When the current value exceeds the adjusted value within the start V
Over Voltage Over Voltage
delay time, the device switches off, its output contact immediately. 1. Error 2. Error
L1,L2,L3
t
< 3 minutes Pushed to Reset button
and Lock have reseted.
ACCESSING PARAMETER MENU:
Push the SET button
SET
during 3 seconds.
Accessing
Current
SET
Parameter
+ +
Over Voltage Over Current
Accessing
( o – U) ( o – C)
Voltage
SET SET phase - phase SET
Parameter oFF:function is disabled
225 - 260 (V)
oFF:function is disabled
_ _
+ + +
Return time Under Voltage Under Current
(r-t) ( u – U) ( u – C)
SET
return time from error SET phase - phase SET
00,5 – 99,9 (sec.) 170 - 215 (V) oFF:function is disabled
oFF:function is disabled
_ _ _
+ + +
Locking Counter Unbalance for Voltage Unbalance for Current
(L - C) ( unb ) ( unb )
SET [oto, (001–010 pieces)] SET 0,05 – 0,40 SET 0,05 – 0,40
oto: function is disabled (5% - 40% ) (5% - 40%)
oFF:function is disabled oFF:function is disabled
_ _ _
+ + +
Locking Time Delay Time for Voltage Hysteresis Value
(L – t ) ( t - 1) ( hYS )
SET 001 – 060 (minutes) SET SET
00.3(3%) – 0.50 (50%)
00,1 – 99,9 (sec.)
_ _ _
+ +
Delay Time for Frequency Delay Time for Current
SET
quit SET
( t - 2)
SET
( d - t)
(0,1 – 60 sec.)
00,1 – 99,9 (sec.)
_ _
+ +
Over Frequency Start Delay Time
(o–F) ( Sdt )
SET [(u-F) + 0,4] ≤...≤ 70 Hz SET (0,1 – 60 sec.)
oFF:function is disabled oFF:function is disabled
_ _
+ +
Under Frequency Very Over Current
(u–F) Coefficient
SET 40 Hz ≤...≤ [(o-F) – 0,4] SET (VOC)
oFF:function is disabled VOC = 2,1 - 6,0
oFF:function is disabled
_ _
+
Over Current
Coefficient
SET Return from SET (OC)
VOLTAGE Menu OC = 1,1 - 2,0
oFF:function is disabled
+
Lock :
Locking function for
SET
currents.
on : function is inabled
oFF: function is disabled
_
Return from
SET CURENT Menu
Connection :
TECHNICAL INFORMATION:
58mm 53mm
90mm
36mm
45mm
62mm
32mm
48mm
Fault
lamp
100A
100A
100A
Load
15
18 16
ATTENTION !!!
- Clean the device using dry dust cloth after turned off device.
- Read and follow the instruction on this manual and attached label.