ke-DP01-100A
Digital Protector VL1,VL2,VL3 Display Functions: Special Buttons:
Voltage – Current VL12,VL23,VL13
and Select: (Up direction)
IL1,IL2,IL3 when pressing continuously,
Frequency control Hz VL1 screen displays frequency of
0 -100A system. When button release
Phase Sequence Control L1 L2 L3
device continue to show voltage.
Over Voltage Protection

Under Voltage Protection VL2


Reset:
L1 L2 L3 If error case although disappeared
Unbalanced Voltage then device is not return to normal,
Protection latch-function occurred and it
makes locked device.
Over Current Protection VL3 Or Lock-function (only for currents)
may be occured.
Under Current Protection L1 L2 L3 After checking error in system then
restart device with pushing reset
Unbalanced Current button.
Protection VL12

Over Frequency L1 L2 L3
Protection

Under Frequency
Protection VL23

L1 L2 L3
Latch Function

TRUE RMS
VL13
AREAS OF OPERATION: L1 L2 L3

■ In-Elevator motors protection


■ on submersible pump and electric motors protection
■ Resistance in oven with
Phase Sequetion: (Seq)
General: In case of wrong phase order , Normal LED turned off and relay
In three phase systems, it measures RMS values of AC voltages, contact is not switch on. In this case seq warn appears on the
currents and system frequency sensitively. Using up direction button screen. If phase order is corrected , Normal LED turned on and out
(Select) phase-neutral voltages and phase-phase voltages monitor relay switch on.
sequentially.
ke-DP01 has many features. L1 L1,L2,L3 L1,L3,L2 L1,L2,L3 L2,L3
Those are; L2
- Phase Failure (seq) L3
- Phase Sequence (seq)
- Over Voltage Protection (o - U)
- Under Voltage Protection (u - U) Re
- Voltage Unbalance (asymmetry) Protection (unb)
- Over Current Protection (o - C) Voltage Unbalanced: (unb)
- Under Current Protection (u - C) The phase-phase voltage unbalance limit can be adjusted
- Current Unbalance (asymmetry) Protection (ubC) between(5% - 20%) . When it exceeds the adjusted limit , the device
- Over Frequency Protection (o - F) switched off its out contact at the end of t-1 delay. In this case unb
warn appears on the screen. For the returning normal state,
- Under Frequency Protection (u - F)
asymmetry values should under 20% (hysteresis value). In this case
When device is turn on if its adjusted voltages and frequency in its
at the end of t3 time Normal LED turned on and output contact switch
interval and if phase sequence is correct relay switch on.
on. If the phase-phase voltage unbalance, return adjusted value
If any of error occurred ( except phase failure and phase sequence )
shorter than t-1 time, output relay does not release its contact.
at the end of adjusted time relay switch off its contact. When system
Hysteresis is 20 %.
return normal values, at the end of time out relay switch on.
unb = 000(oFF) protection is disable .

Example: Let's say that asymmetry value is set to %15 for a


3 x 380VAC.
In this case, relay contact switch off at (220-(220x0.15))=187 V.
Switch on the contact is performed at 187+(220x%15x%20)= 194 V.
IMPORTANT: L1 - N is device supply inputs. Thus,the applied L1 – N (%20 is the hysteresis).
voltage must be rated voltage of system . Otherwise normal led makes
flash and the device switched off its output contact.
The measured frequency also must the frequency of the system.

Phase Failure: (u-U) (Vmax - Vmin)


Before starting system , it controls phase absence then if all phases % unb = x 100 Hys = 220 x (% Asm) x (% 20)
exits Normal LED turn on and relay contact switch on. In case of 220
missing of any L1,L2,L3 phases , Normal LED turn off and relay
switch off its contact .In this case u-U warn appears on display.
+ % unb
hys
L1 Vnom
L2 hys
- % unb
L3
Level
Re Re

< t-1 t-1 r-t t-1 r-t < t-1 t-1


Over and Under Voltage : (o-U),(u-U)
Under voltage (u-U) it can adjusted between Umin= (170 – 215 V). 2.6 Asymmetric Current Protection:
Over voltage (o-U) it can adjusted between Umax=(225 – 260 V). It can be set by the user between 5% and 40%. It controls the
If the voltage drops below the adjusted under voltage limit, when u-U asymmetric that may occur in the current of the three phases. That
shows on the screen and device switch off its output contact end of the may occur when one of the phases' voltage is low and the other one
t-1 time Normal LED turned on .In this case u-U warn appears on the is high. That may cause asymmetric current in the motor's bobbin.
screen. This way the motor's bobbin is protected. Furthermore it protects the
If the voltage exceed the adjusted over voltage limit, Normal LED motor from missing phase or a possible unplugged or cut wiring.
turned off and output relay switch off. In this case o-U warn appers on If the unbalance between the phases' current exceeds the adjusted
its screen. value the switch off occurs after t-1 delay.
Hysteresis is 6 V. If the current unbalance exceed the adjusted value, Normal LED
turned off and output relay switch off. In this case ubC warn appears
on its screen.
V This function can be disable if ubC value = 000 (oFF)
Over Voltage L1,L2,L3

Umax (o-U)
Normal
Normal
Umin (u-U)
Over and/or Under Frequency Protection : ( 40 – 70 Hz )
Under Frequency be able to set between(u-F) = 40 Hz ...[(o-F) -0,4]
Under Voltage
t
Over Frequency be able to set between (o-F) =[(u-F) + 0,4]...70 Hz
t-1 r-t t-1 r-t
If required , it can be set only under frequency or only over frequency
protection as well as both of protection can be disabled.
If o-F = 55 Hz and u-F = oFF set, device works as over
Re t
frequency protector only. (if system frequency above 55 Hz, under
screen displays o-F warning and end of time t-2 relay switch off its
Over and Under Current : (o-C),(u-C)
output contact )
Under Current (u-C)
if o-F = oFF and u-F = 45 Hz set , device works as under
Over Current (o-C)
frequency protector only . (if system frequency below 45 Hz, under
When the current of the protected system goes below the adjusted
screen displays u-F warning and end of time t-2 relay switch off its
value it switches off its output contact after d-t delay.
out contact.)
Normal LED turn off and relay switch off its contact .In this case
if o-F = oFF and u-F = oFF set, frequency protection is disabled.
u-C warn appears on display.
When any current passing through any phase of the protected system
exceeds the adjusted value the device switches off its output contacts
after a proper time (d-t).Normal LED turn off and relay switch off its
contact .In this case o-C warn appears on display. f(Hz)
Over Frequency L1,L2,L3
NOTE: Under current protection set value with its hysteresis must not
55 Hz (o-F)
overlap with over current protection set value with its hysteresis or, the Normal
Normal
under current protection set value must not be higher than the over 45 Hz (u-F)
current protection set value.
Under Frequency
t
t-2 r-t t-2 r-t
I(A)
VOC Re t

OC
LOCKING FUNCTION :
It can be controlled by two parameters. Locking time and
Locking counter. If the number of opening reaches the adjusted
o-C
%hYS
locking counter withing the adjusted locking time then device
switch off its contact and locks its functions until the user
%hYS
pressed Reset button.
u-C
If the locking counter is adjusted to oto then this function is
disable and device never locks itself.
t L-t : Locking Time ( 001 – 060 min. )
Sdt d-t r-t d-t r-t It is well know the frequently occurring faults may damage
r-t r-t system. For that the device when number of faults reaches the
Re t adjusted locking number within this locking time. This way the
system is protected and user has chance to investigate the
problem.
Start delay time: Sd-t L-C : Locking Counter ( oto , 001 – 010 piece )
It can be set between 1 and 60 seconds.It is used to prevent the switch The number of faults allowed within the period L-t. If number of
off from occurance because of the motor's inrush current. faults exceeds this adjusted counter value device locks itself.
This function can be disable if Sd-t value = 000 (oFF) In this case (- - -) warn appears on its screen. User must press
Return Time : r-t Reset button then the fault passes in order to unlock the device.
it shows the delay time that device will wait to switch on its output relay If L- C is set to oto then this property is disabled.
when failure ends after a switch off. It can be set between 0,5 and 99,9
seconds.
Very Over Current Coefficient : VOC (Current Very Sudden Switch
Off Protection) L- C (number of lock) = 2 piece
It can be set by the user between 2,1 and 6. L- t (lock time) = 3 min. if select ;
When the current value exceeds the adjusted value within the start V
Over Voltage Over Voltage
delay time, the device switches off, its output contact immediately. 1. Error 2. Error
L1,L2,L3

Very Over Current value = (o – C) x (VOC) (o-U)


This function can be disable if VOC = 000 (oFF) Normal Normal
Over Current Coefficient : OC (Current Sudden Switch Off Protection) (u-U)
It can be set by the user between 1,1 and 2.
When the current value exceeds the adjusted value without the start
delay time, the device switches off, its output contact immediately. t
Over Current value = (o – C) x (OC) t-1 r-t t-1 r-t
This function can be disable if OC = 000 (oFF) Re Locked occurred

t
< 3 minutes Pushed to Reset button
and Lock have reseted.
ACCESSING PARAMETER MENU:
Push the SET button
SET
during 3 seconds.

Accessing
Current
SET
Parameter

+ +
Over Voltage Over Current
Accessing
( o – U) ( o – C)
Voltage
SET SET phase - phase SET
Parameter oFF:function is disabled
225 - 260 (V)
oFF:function is disabled
_ _

+ + +
Return time Under Voltage Under Current
(r-t) ( u – U) ( u – C)
SET
return time from error SET phase - phase SET
00,5 – 99,9 (sec.) 170 - 215 (V) oFF:function is disabled
oFF:function is disabled
_ _ _

+ + +
Locking Counter Unbalance for Voltage Unbalance for Current
(L - C) ( unb ) ( unb )
SET [oto, (001–010 pieces)] SET 0,05 – 0,40 SET 0,05 – 0,40
oto: function is disabled (5% - 40% ) (5% - 40%)
oFF:function is disabled oFF:function is disabled

_ _ _

+ + +
Locking Time Delay Time for Voltage Hysteresis Value
(L – t ) ( t - 1) ( hYS )
SET 001 – 060 (minutes) SET SET
00.3(3%) – 0.50 (50%)
00,1 – 99,9 (sec.)

_ _ _

+ +
Delay Time for Frequency Delay Time for Current

SET
quit SET
( t - 2)
SET
( d - t)
(0,1 – 60 sec.)
00,1 – 99,9 (sec.)

_ _

+ +
Over Frequency Start Delay Time
(o–F) ( Sdt )
SET [(u-F) + 0,4] ≤...≤ 70 Hz SET (0,1 – 60 sec.)
oFF:function is disabled oFF:function is disabled

_ _

+ +
Under Frequency Very Over Current
(u–F) Coefficient
SET 40 Hz ≤...≤ [(o-F) – 0,4] SET (VOC)
oFF:function is disabled VOC = 2,1 - 6,0
oFF:function is disabled
_ _

+
Over Current
Coefficient
SET Return from SET (OC)
VOLTAGE Menu OC = 1,1 - 2,0
oFF:function is disabled

+
Lock :
Locking function for
SET
currents.
on : function is inabled
oFF: function is disabled
_

Return from
SET CURENT Menu
Connection :
TECHNICAL INFORMATION:

Rated Voltage (Un) : 127 Vac (L1-N)


Operating Range : (0,8-1,1) x Un
Frequency : 50 / 60 Hz
L1 Supply Power Consumption : < 4VA
L2 Current Transformer Ratio : X / 5A
L3 Current Measurement Range : 0 - 100 Amp AC
Voltage Measurement Range : (Phase-Phase)15 - 280 Vac, 45 - 65Hz
N
: (Phase-Neutral )15 -170 Vac, 45 - 65Hz
For power supply(L1 - N) 102V –140V
1A 1A 1A Voltage Measurement
Power Consumption : <1VA (for one phase)
Measurement Sensitivity : %1±1 digit
Contact Current : Max. 3A / 240Vac
Device Protection Class : IP 20
Connector Protection Class : IP 00
Temperature : - 5 °C .... + 50 °C
Connection Type : To connection rail in electrical panel
Dimension :

58mm 53mm

90mm

36mm

45mm

62mm
32mm
48mm

Fault
lamp

100A

100A

100A

Load
15

18 16

ATTENTION !!!

- Clean the device using dry dust cloth after turned off device.
- Read and follow the instruction on this manual and attached label.