Chapter 4. Constraints, Trade-Off, and Standards Constraints
Chapter 4. Constraints, Trade-Off, and Standards Constraints
Chapter 4. Constraints, Trade-Off, and Standards Constraints
Economical
In this constraint, the designers will find a way to lessen the expenses, by finding and comparing equipment
prices or finding a product substitute with the same output or even greater compared to the expensive
materials available. Moreover, the availability of the materials to be purchased was highly considered upon
the canvass. This constraint listed the actual cost of the components to be used in the project.
Mobility
Mobility is another important criterion of the design to consider. The weight of the prototype must also be
noted. The device should be lightweight that must weigh less than 10 kilograms (10 kg.). The design should
be convenient to use.
Efficiency
The efficiency design criteria consider the ratio of output power produced by the device with regards to the
input power applied to the device through conversion of the wind pressure and water flow. The device must
exhibit an efficiency of 40%-80% under wind velocity and 45%-80% when submerged in water flow.
Safety
The device is intended to be water-tight and equipped with protective components like circuit protection to
avoid internal damage that can cause harm to its user and the environment. The designers must ensure that
the prototype has proper protection since the device is also running underwater.
Trade-offs
Using the model on trade-off strategies in engineering design presented by Kirkwood and Sarin, the
importance of each criterion (on a scale of 0 to 5, 5 with the highest importance) was assigned and each
design technology’s ability to satisfy the criterion (on a scale from -5 to 5 with the highest ability to satisfy the
criterion).
Computation of ranking for the ability to satisfy the criterion of materials:
Kirkwood and Sarin 1980, Exponential Family Scoring Function
V - Lowest
Higher Preference Score Score =
Highest - Lowest
94
Criterion of Importance
Economic cost will be given a ranking of five (5) since the cost is the most significant in this design. The
economic (cost) is composed primarily of the materials, labor, and management, thus, the decision for the
next constraints dependent on it.
The next constraint is the mobility. An importance ranking of four (4) is given to this constraint because
mobility must be compact and lightweight to the user.
Another constraint is the efficiency. An importance ranking of four (4) also is given to this constraint for this
is about the ratio of the power output with respect to the power input at a given period as compared to the
other design. Using efficiency percentage, power losses can be determined.
Finally, the last constraint which is the safety constraint having an importance ranking of two (2). This
constraint justifies the assurance to the user that the device is safe to use.
Portability
Mobility is another important criterion of the design to consider. The weight of the prototype must also be
noted. The device should be lightweight that must weigh less than ten kilograms (12 kg). The design should
be lightweight and convenient to use.
95
Portability
0.8000
0.7000
0.6000
0.5000
0.4000
0.3000
0.2000
0.1000
0.0000
Horizontal Vertical-Darrieus Vertical-Savonius Multidirectional Vortex
Economic Cost
The total cost of the components for each sub-option to be used in the project. The total price of the project
must meet the client’s budget for the making of it.
96
Design Sub-Design Design Option Total Cost in Peso Ranking Score
Option 1 10050.00 0.1266
Vortex Option 2 11550.00 -0.0735
Option 3 14550.00 -0.4735
Economical
1.2000
1.0000
0.8000
0.6000
0.4000
0.2000
0.0000
Horizontal Vertical-Darrieus Vertical-Savonius Multidirectional Vortex
-0.2000
-0.4000
-0.6000
Efficiency
The efficiency design criteria consider the ratio of output power produced by the device with regards to the
input power applied to the device through conversion of the wind pressure and water flow.
97
Design Sub-Design Design Option Efficiency Ranking Score
Option 1 0.572 0.1440
Darrieus Option 2 0.6429 0.2858
Option 3 0.7448 0.4896
Vertical-Axis Turbine
Option 1 0.6115 0.2230
Savonius Option 2 0.6742 0.3484
Option 3 0.7683 0.5366
Option 1 0.5032 0.0064
Multidirectional Option 2 0.5712 0.1424
Option 3 0.6451 0.2902
Option 1 0.5152 0.0304
Vortex Option 2 0.5888 0.1776
Option 3 0.6424 0.2848
Efficiency
0.6
0.5
0.4
0.3
0.2
0.1
0
Horizontal Vertical-Darrieus Vertical-Savonius Multidirectional Vortex
Safety
The device is intended to be water-tight and equipped with protective components like circuit protection to
avoid internal damage that can cause harm to its user and the environment. The designers must ensure that
the prototype has proper protection since the device is also running underwater.
98
Table 4-4. Safety constraint ranking score
Safety
1.0000
0.9000
0.8000
0.7000
0.6000
0.5000
0.4000
0.3000
0.2000
0.1000
0.0000
Horizontal Vertical-Darrieus Vertical-Savonius Multidirectional Vortex
99
Table 4-5. Tabulation of final scores of design options
Sub- Constraints
Design Design Option
Design Economical Portability Efficiency Safety
Option 1 0.9267 0.7300 0.1520 0.5000
Horizontal-Axis
Option 2 0.7266 0.6967 0.3056 0.6667
Turbine
Option 3 0.6600 0.6633 0.4900 0.7500
Option 1 0.9400 0.7133 0.1440 0.8333
Darrieus Option 2 0.7400 0.6800 0.2858 0.8833
Option 3 0.6733 0.6467 0.4896 0.9167
Vertical-Axis Turbine
Option 1 0.9533 0.6967 0.2230 0.8333
Savonius Option 2 0.7533 0.7133 0.3484 0.8833
Option 3 0.6866 0.6300 0.5366 0.9167
Option 1 0.2599 0.5967 0.0064 0.0000
Multidirectional Option 2 0.0599 0.5800 0.1424 0.1667
Option 3 -0.0068 0.5300 0.2902 0.3333
Option 1 0.1266 0.3633 0.0304 0.1667
Vortex Option 2 -0.0735 0.3467 0.1776 0.3333
Option 3 -0.4735 0.2967 0.2848 0.5000
The decision matrix for the Turbine Design is constructed by knowing the Clients Requirements for the four
given options; this is known to be the value of the Weighting factor.
The Rating factor for each cell is defined as the Score in the Sensitivity Analysis multiplied by a factor of 10.
The Rating Factor is located at the upper in each cell. The concept with the highest Rated Weighting Factor
is the one that most closely satisfies the set design criteria by the client requirements
Sensitivity Analysis 1
Table 4-6. Level of importance for Turbine Design (Sensitivity Analysis 1)
100
Table 4-7. Sensitivity Analysis Number 1 for Turbine Design
Table 4-7 shows the Sensitivity Analysis Number 1 for Turbine Design. Based on the result of the data, Option
3: Ducted with Direct Input from the Vertical-Axis Turbine Sub-Design 1: Savonius Turbine won the design
having a score of 0.6741.
101
Design Matrix Summary
0.8000
0.7000
0.6000
0.5000
0.4000
0.3000
0.2000
0.1000
0.0000
-0.1000
-0.2000
The Decision Matrix Figure 4-5 shows the best design option for each criterion. The concept with the highest
RWF is the one that most closely satisfies the set design criteria by the client requirements. The highest RWF
summation for the variant is Option 3 Ducted with Direct Input Vertical-Axis Sub-Design 2- Savonius with
a total Rated Weighting Factor of 0.6741
Sensitivity Analysis 2
102
Table 4-9. Sensitivity Analysis Number 2 for Turbine Design
Table 4-9 shows the Sensitivity Analysis Number 2 for Turbine Design. Based on the result of the data, Option
3: Ducted with Direct Input from the Vertical-Axis Sub-Design Option 2- Savonius Turbine won the design
having a score of 0.7223.
103
Design Matrix Summary
0.8000
0.7000
0.6000
0.5000
0.4000
0.3000
0.2000
0.1000
0.0000
-0.1000
The Decision Matrix Figure 4-6 shows the best design option for each criterion. The concept with the highest
RWF is the one that most closely satisfies the set design criteria by the client requirements. The highest RWF
summation for the variant is Option 3 Ducted with Direct Input which is the Vertical-Axis Sub-Design 2-
Savonius with a total Rated Weighting Factor of 0.7223
Sensitivity Analysis 3
104
Table 4-11. Sensitivity Analysis Number 3 for Turbine Design
Table 4-11 shows the Sensitivity Analysis Number 3 for Turbine Design. Based on the result of the data,
option 1 Open type from the Vertical Axis Sub-Design 2 - Savonius Turbine won the design having a score
of 0.6926.
105
Design Matrix Summary
0.8000
0.7000
0.6000
0.5000
0.4000
0.3000
0.2000
0.1000
0.0000
-0.1000
-0.2000
The Decision Matrix Figure 4-7 shows the best design option for each criterion. The concept with the highest
RWF is the one that most closely satisfies the set design criteria by the client requirements. The highest RWF
summation for all variant is Option 1 Open type which is the Vertical Axis Sub-Design 2- Savonius Option
3: Ducted Type with Direct Inputs with a total Rated Weighting Factor of 0.6926.
106
Pareto Analysis
Design 1 Comparison:
107
Design 2.1 Comparison:
Table 4-17. Economical: Cost
Design 2 Sub-Design 1: Option 2: with Direct Option 3: Ducted Type
Option1: Open Type
Darrieus Input w/ Direct Input
Cost ₱3950.00 ₱5450.00 ₱5950.00
See Appendix A for the computation of Economical: Cost
Table 4-17 shows that the Design 2 Sub-Design 1 Option 1 Darrieus Open Type is the cheapest among the
other options stated.
108
Design 2.2 Comparison:
Table 4-22. Economical: Cost
Design 2 Sub-Design 2: Option 2: with Direct Option 3: Ducted Type
Option1: Open Type
Savonius Input w/ Direct Input
Cost ₱3850.00 ₱5350.00 ₱5850.00
See Appendix A for the computation of Economical: Cost
Table 4-22 shows that the Design 2 Sub-Design 2 Option 1 Horizontal Open type is the cheapest among
the other options stated.
109
Design 3 Comparison:
Table 4-27. Economical: Cost
Design 3: Option 2: with Direct Option 3: with Multiple
Option1: Open Type
Multidirectional Input Direct Input
Cost ₱9050.00 ₱10550.00 ₱11050.00
See Appendix A for the computation of Economical: Cost
Table 4-27 shows that the Design 3 Option 1 Horizontal Open type is the cheapest among the other options
stated.
110
Design 4 Comparison:
Table 4-32. Economical: Cost
Option 2: with Direct Option 3: Drag Force
Design 4: Vortex Option1: Ducted Type
Input Minimizer
Cost ₱10050.00 ₱11550.00 ₱14550.00
See Appendix A for the computation of Economical: Cost
Table 4-32 shows that the Design 4 Option 1 Vortex Ducted Type is the cheapest among the other options
stated.
111
Scaling, Linear Shift, and Normalization [5]
In applications, it is usually meaningful to rank order the importance of the various performance criteria.
Moreover, it is meaningful to assign percent (%) importance to each criterion. It is customary to form a
weighted linear combination of the numerical values of the criteria. When criteria have different dimensions,
it does not make sense to add them directly, so we need to normalize to convert all to be dimensionless.
When raw low numerical values are associated with more desirable values. Use:
Maxraw - PCraw
PCnorm = 9 ( )+ 1
Maxraw - Minraw
Where:
PCnorm= Performance criterion normalization
PCraw= Performance criterion raw
Maxraw= Maximum values for raw performance criterion
Minraw= Minimum values for raw performance criterion
When raw high numerical values are associated with more desirable values. Use:
PCraw - Minraw
PCnorm = 9 ( )+ 1
Maxraw - Minraw
Where:
PCnorm= Performance criterion normalization
PCraw= Performance criterion raw
Maxraw= Maximum values for raw performance criterion
Minraw= Minimum values for raw performance criterion
In Table 4-16 for raw values for performance criterion 3 in column 4, the normalized values are: Option 1,
4.96; Option 2, 6.69; Option 3, 4.95, as shown in column 4 of table 4-37. The complete normalization of the
data in Table 4-16 is shown in Table 4-37. The relative rank ordering of the values of each Performance
Criterion is preserved. The pairwise comparison of rows in Table 4-37 will result in the same conclusion as
the one in Table 4-16, whereby Option 3 dominates most of the performance criterion compare to the other
two options.
112
Table 4-38. Pairwise Comparison of Design 2.1 in all Constraints
Performance Performance Performance Performance
Option Number
Criterion 1 Criterion 2 Criterion 3 Criterion 4
1 8.93 5.92 4.87 8.50
2 7.24 7.42 6.46 8.95
3 6.68 6.82 8.76 9.25
In Table 4-21 for raw values for performance criterion 3 in column 4, the normalized values are: Option 1,
4.87; Option 2, 6.46; Option 3, 8.76, as shown in column 4 of table 4-38. The complete normalization of the
data in Table 4-21 is shown in Table 4-38. The relative rank ordering of the values of each Performance
Criterion is preserved. The pairwise comparison of rows in Table 4-38 will result in the same conclusion as
the one in Table 4-21, whereby Option 3 dominates most of the performance criterion compare to the other
two options.
In Table 4-26 for raw values for performance criterion 3 in column 4, the normalized values are: Option 1,
5.76; Option 2, 7.17; Option 3, 9.29, as shown in column 4 of table 4-39. The complete normalization of the
data in Table 4-26 is shown in Table 4-39. The relative rank ordering of the values of each Performance
Criterion is preserved. The pairwise comparison of rows in Table 4-38 will result in the same conclusion as
the one in Table 4-26, whereby Option 3 dominates most of the performance criterion compare to the other
two options.
In Table 4-31 for raw values for performance criterion 3 in column 4, the normalized values are: Option 1,
3.32; Option 2, 4.85; Option 3, 6.51, as shown in column 4 of table 4-40. The complete normalization of the
data in Table 4-31 is shown in Table 4-40. The relative rank ordering of the values of each Performance
Criterion is preserved. The pairwise comparison of rows in Table 4-40 will result in the same conclusion as
the one in Table 4-31, whereby Option 3 dominates most of the performance criterion compare to the other
two options.
113
Table 4-41. Pairwise Comparison of Design 4 in all Constraints
Performance Performance Performance Performance
Option Number
Criterion 1 Criterion 2 Criterion 3 Criterion 4
1 2.07 4.12 3.32 1.00
2 0.38 4.27 4.85 2.50
3 -2.99 3.67 6.51 4.00
In Table 4-36 for raw values for performance criterion 3 in column 4, the normalized values are: Option 1,
3.32; Option 2, 4.85; Option 3, 6.51, as shown in column 4 of table 4-41. The complete normalization of the
data in Table 4-36 is shown in Table 4-41. The relative rank ordering of the values of each Performance
Criterion is preserved. The pairwise comparison of rows in Table 4-41 will result in the same conclusion as
the one in Table 4-36, whereby Option 3 dominates most of the performance criterion compare to the other
two options.
Table 4-42. Summary of winning Option per Design using Pairwise Comparison
Performance Performance Performance Performance
Design Options
Criterion 1 Criterion 2 Criterion 3 Criterion 4
D1 – O3 6.57 6.97 8.76 7.75
D2-SD1 – O3 6.68 6.82 8.76 9.25
D2-SD2 – O3 6.79 5.77 9.29 9.25
D3 – O3 0.94 5.77 6.51 4.00
D4 - O3 -2.99 3.67 6.51 4.00
*Reference: Cruz, J., Almario, E. (n.d.), “When is the Pareto Choice from a Finite Set Invariant to Variations in Weights and Values of Multiple
Performance Criteria”, Philippine Science Letters
Table 4-42 shows the dominated design option in Table 4-37 for design 1, the normalized values are the
following: Performance Criterion 1, 6.57; Performance Criterion 2, 6.97; Option 3, 8.76; Performance Criterion
4, 7.75. In Table 4-38 for design 2.1, the normalized values are: Performance Criterion 1, 6.68; Performance
Criterion 2, 6.82; Performance Criterion 3, 8.76; Performance Criterion 4, 9.25. In Table 4-39 for design 2.2,
the normalized values are: Performance Criterion 1, 6.79; Performance Criterion 2, 5.77; Performance
Criterion 3, 9.29; Performance Criterion 4, 9.25. In Table 4-40 for design 3, the normalized values are:
Performance Criterion 1, 0.94; Performance Criterion 2, 5.77; Performance Criterion 3, 6.51; Performance
Criterion 4, 4.00 and in Table 4-41 for design 4, the normalized values are: Performance Criterion 1, -2.99;
Performance Criterion 2, 3.67; Performance Criterion 3, 6.51; Performance Criterion 4, 4.00.
114
Trade-off Design between Two Constraints
Economical and Mobility Constraints
Table 4-43. Trade off Design between Economical vs Mobility Values
Design Option Economical Mobility
Design 1 Option 3 (x1) 6050 2010
Design 2.1 Option 3 (x2) 5950 2060
Design 2.2 Option 3 (x3) 5850 2050
Design 3 Option 3 (x4) 11050 2410
Design 4 Option 3 (x5) 14550 3110
In Figure 4-8, the maximum and minimum values of Economical Constraints are 11,000 and 3,000 and for
the maximum and minimum values of Mobility Constraints are 4,000 and 1,000. It explained that the area
bounded by Design 2.2 Option 3, Design 3 Option 3 and Design 4 Option 3 are the accepted design options
with respect to the Economical and Mobility constraints.
115
Economical and Efficiency Constraints
Table 4-44. Trade off Design between Economical vs Efficiency Values
Design Option Economical Efficiency
Design 1 Option 3 (x1) 6050 74.5
Design 2.1 Option 3 (x2) 5950 74.48
Design 2.2 Option 3 (x3) 5850 76.83
Design 3 Option 3 (x4) 11050 64.51
Design 4 Option 3 (x5) 14550 64.51
In Figure 4-9, the maximum and minimum values of Economical Constraints are 11,000 and 3,000 and for
the maximum and minimum values of Efficiency Constraints are 80 and 40. It explained that the area bounded
by Design 2.2 Option 3, Design 3 Option 3 and Design 4 Option 3 are the accepted design options with
respect to the Economical and Efficiency constraints.
116
Economical and Safety Constraints
Table 4-45. Trade off Design between Economical vs Safety Values
Design Option Economical Safety
Design 1 Option 3 (x1) 6050 85.00
Design 2.1 Option 3 (x2) 5950 95.00
Design 2.2 Option 3 (x3) 5850 95.00
Design 3 Option 3 (x4) 11050 60.00
Design 4 Option 3 (x5) 14550 60.00
In Figure 4-10, the maximum and minimum values of Economical Constraints are 11,000 and 3,000 and for
the maximum and minimum values of Safety Constraints are 100 and 40. It explained that the area bounded
by Design 2.2 Option 3 and Design 4 Option 3 are the accepted design options with respect to the Economical
and Safety constraints.
117
Mobility and Efficiency Constraints
Table 4-46. Trade off Design between Mobility vs Efficiency Values
Design Option Mobility Efficiency
Design 1 Option 3 (x1) 2010 74.5
Design 2.1 Option 3 (x2) 2060 74.48
Design 2.2 Option 3 (x3) 2050 76.83
Design 3 Option 3 (x4) 2410 64.51
Design 4 Option 3 (x5) 3110 64.51
In Figure 4-11, the maximum and minimum values of Mobility Constraints are 4,000 and 1,000 and for the
maximum and minimum values of Efficiency Constraints are 80 and 40. It explained that the area bounded
by Design 1 Option 3, Design 2.1 Option 3 and Design 2.2 Option 3 are the accepted design options with
respect to the Mobility and Efficiency constraints.
118
Mobility and Safety Constraints
Table 4-47. Trade off Design between Mobility vs Safety Values
Design Option Mobility Safety
Design 1 Option 3 (x1) 2010 85.00
Design 2.1 Option 3 (x2) 2060 95.00
Design 2.2 Option 3 (x3) 2050 95.00
Design 3 Option 3 (x4) 2410 60.00
Design 4 Option 3 (x5) 3110 60.00
In Figure 4-12, the maximum and minimum values of Mobility Constraints are 4,000 and 1,000 and for the
maximum and minimum values of Safety Constraints are 100 and 40. It explained that the area bounded by
Design 2.2 Option 3 and Design 4 Option 3 are the accepted design options with respect to the Mobility and
Safety constraints.
119
Efficiency and Safety Constraints
Table 4-48. Trade off Design between Efficiency vs Safety Values
Design Option Efficiency Safety
Design 1 Option 3 (x1) 74.5 85.00
Design 2.1 Option 3 (x2) 74.48 95.00
Design 2.2 Option 3 (x3) 76.83 95.00
Design 3 Option 3 (x4) 64.51 60.00
Design 4 Option 3 (x5) 64.51 60.00
In Figure 4-13, the maximum and minimum values of Efficiency Constraints are 80 and 40 and for the
maximum and minimum values of Safety Constraints are 100 and 40. It explained that the area bounded by
Design 2.1 Option 3 and Design 2.2 Option 3 are the accepted design options with respect to the Efficiency
and Safety constraints.
120
Weighted Sum of Performance Criteria and Level of Importance
Table 4- 49. The level of importance and the weighting factor of each constraint.
Design Criteria Level of Importance Weighting Factor
Economical (Cost) 5 0.3333
Mobility (Form Factor) 4 0.2667
Efficiency (Power Ratio) 4 0.2667
Safety (Protection Rating) 2 0.1333
Total 15 1
Table 4-49 shows the level of importance and the weighting factor for each constraint.
Weight Variation and Sensitivity Analysis 5[11]
i i i i i
Form WPC = x1 PC1 + x2PC2 + x3PC3+ x4PC4
j = 1, 2, 3, 4 and i = 1, 2, 3, 4, 5
Where:
PCij = Performance Criterion
xi = Normalized values of constraints, xi ≥ 0
j = Number of constraints
i = Number of options
1
WPC = 6.57x1 + 6.97x2 + 8.76x3 + 7.75x4
2
WPC = 6.68x1 + 6.82x2 + 8.76x3 + 9.25x4
3
WPC = 6.79x1 + 5.77x2 + 9.29x3 + 9.25x4
4
WPC = 0.94x1 + 5.77x2 + 6.51x3 + 4.00x4
5
WPC = -2.99x1 + 3.67x2 + 6.51x3 + 4.00x4
Weighted Factor Values (non-negative and total of 1.00)
Level of Importance
Weighted Factor =
Total level of Importance
5
x1 = = 0.3333, Where x1 is for Efficiency (Power Ratio)
15
4
x2 = = 0.2667, Where x2 is for Safety (Protection Rating)
15
4
x3 = = 0.2667, Where x3 is for Economical (Cost)
15
2
x4 = = 0.1333, Where x4 is for Mobility (Form Factor)
15
Therefore, the total score for each design:
1
WPC = 6.57(0.3333) + 6.97( 0.2667) + 8.76( 0.2667) + 7.75(0.1333) = 7.42
2
WPC = 6.68(0.3333) + 6.82( 0.2667) + 8.76( 0.2667) + 9.25(0.1333) = 7.62
3
WPC = 6.79(0.3333) + 5.77( 0.2667) + 9.29( 0.2667) + 9.25(0.1333) = 7.80
4
WPC = 0.94(0.3333) + 5.77( 0.2667) + 6.51( 0.2667) + 4.00(0.1333) = 4.12
5
WPC = -2.99(0.3333) + 3.67( 0.2667) + 6.51( 0.2667) + 4.00(0.1333) = 2.25
121
Table 4-50. Total rating of each design
Level Design Options
of Weighting D1-O3 Rating D2-SD1 Rating D2-SD2 Rating D3 – 03 Rating D4 - 03 Rating
Constraints
Impor Factor O3 O3
tance
Economical
5 0.3333 6.57 2.19 6.68 2.23 6.79 2.26 0.94 0.31 -2.99 -1
(Cost)
Mobility (Form
4 0.2667 6.97 1.86 6.82 1.82 6.85 1.83 5.77 1.54 3.67 0.98
Factor)
Efficiency (Power
4 0.2667 8.76 2.34 8.76 2.34 9.29 2.48 6.51 1.74 6.51 1.74
Ratio)
Safety (Protection
2 0.1333 7.75 1.03 9.25 1.23 9.25 1.23 4.00 0.53 4.00 0.53
Rating)
Total 15 1 7.42 7.62 7.80 4.12 2.25
*Reference: Cruz, J., Almario, E., “When is the Pareto Choice from a Finite Set Invariant to Variations in Weights and Values of Multiple Performance Criteria”, Philippine Science
Letters
Table 4-50 shows that Design 2 Sub-Design 2 Option 3 Savonius Ducted Type with Direct Input
Design Options Rating
3
2.5
2
1.5
1
0.5
0
-0.5
-1
-1.5
D1 O3 D2.1 O3 D2.2 O3 D3 O3 D4 O3
Economical (Cost) 2.19 2.23 2.26 0.31 -1
Mobility (Form Factor) 1.86 1.82 1.83 1.54 0.98
Efficiency (Power Ratio) 2.34 2.34 2.48 1.74 1.74
Safety (Protection Rating) 1.03 1.23 1.23 0.53 0.53
122
Weight Variation and Sensitivity Analysis Test A
Table 4-51. The level of importance and weighting factor of each constraints
Design Criteria Level of Importance Weighting Factor
Economical (Cost) 5 0.3333
Mobility (Form Factor) 2 0.1333
Efficiency (Power Ratio) 4 0.2667
Safety (Protection Rating) 4 0.2667
Total 15 1
Table 4-51 shows the level of importance and weighting factor for each constraint
Weight Variation and Sensitivity Analysis
i i i i i
Form WPC = x1 PC1 + x2PC2 + x3PC3+ x4PC4
j = 1, 2, 3, 4 and i = 1, 2, 3, 4, 5
Where:
PCij = Performance Criterion
xi = Normalized values of constraints, xi ≥ 0
j = Number of constraints
i = Number of options
1
WPC = 6.57x1 + 6.97x2 + 8.76x3 + 7.75x4
2
WPC = 6.68x1 + 6.82x2 + 8.76x3 + 9.25x4
3
WPC = 6.79x1 + 5.77x2 + 9.29x3 + 9.25x4
4
WPC = 0.94x1 + 5.77x2 + 6.51x3 + 4.00x4
5
WPC = -2.99x1 + 3.67x2 + 6.51x3 + 4.00x4
Weighted Factor Values (non-negative and total of 1.00)
Level of Importance
Weighted Factor =
Total level of Importance
5
x1 = = 0.3333, Where x1 is for Economical (Cost)
15
2
x2 = = 0.1333, Where x2 is for Mobility (Form Factor)
15
4
x3 = = 0.2667, Where x3 is for Efficiency (Power Ratio)
15
4
x4 = = 0.2667, Where x4 is for Safety (Protection Rating)
15
Therefore, the total score for each design:
1
WPC = 6.57(0.3333) + 6.97( 0.1333) + 8.76( 0.2667) + 7.75(0.2667) = 7.53
2
WPC = 6.68(0.3333) + 6.82( 0.1333) + 8.76( 0.2667) + 9.25(0.2667) = 7.95
3
WPC = 6.79(0.3333) + 5.77( 0.1333) + 9.29( 0.2667) + 9.25(0.2667) = 8.12
4
WPC = 0.94(0.3333) + 5.77( 0.1333) + 6.51( 0.2667) + 4.00(0.2667) = 3.89
5
WPC = -2.99(0.3333) + 3.67( 0.1333) + 6.51( 0.2667) + 4.00(0.2667) = 2.3
123
Table 4-52. Total rating of each design
Level Design Options
of Weighting D1-O3 Rating D2-SD1 Rating D2-SD2 Rating D3 – 03 Rating D4 - 03 Rating
Constraints
Impor Factor O3 O3
tance
Economical
5 0.3333 6.57 2.19 6.68 2.23 6.79 2.26 0.94 0.31 -2.99 -1
(Cost)
Mobility (Form
2 0.1333 6.97 0.93 6.82 0.91 6.85 0.91 5.77 0.77 3.67 0.49
Factor)
Efficiency (Power
4 0.2667 8.76 2.34 8.76 2.34 9.29 2.48 6.51 1.74 6.51 1.74
Ratio)
Safety (Protection
4 0.2667 7.75 2.07 9.25 2.47 9.25 2.47 4.00 1.07 4.00 1.07
Rating)
Total 15 1 7.53 7.95 8.12 3.89 2.3
*Reference: Cruz, J., Almario, E., “When is the Pareto Choice from a Finite Set Invariant to Variations in Weights and Values of Multiple Performance Criteria”, Philippine Science
Letters
Table 4-52 shows that Design 2 Sub-Design 2 Option 3 Savonius Ducted Type with Direct Input
Sensitivity Analysis Test A
3
2.5
2
1.5
1
0.5
0
-0.5
-1
-1.5
D1 O3 D2.1 O3 D2.2 O3 D3 O3 D4 O3
Economical (Cost) 2.19 2.23 2.26 0.31 -1
Mobility (Form Factor) 0.93 0.91 0.91 0.77 0.49
Efficiency (Power Ratio) 2.34 2.34 2.48 1.74 1.74
Safety (Protection Rating) 2.07 2.47 2.47 1.07 1.07
124
Weight Variation and Sensitivity Analysis Test B
Table 4-53. The level of importance and weighting factor of each constraints
Design Criteria Level of Importance Weighting Factor
Economical (Cost) 2 0.1333
Mobility (Form Factor) 4 0.2667
Efficiency (Power Ratio) 4 0.2667
Safety (Protection Rating) 5 0.3333
Total 15 1
Table 4-53 shows the level of importance and weighting factor for each constraint
Weight Variation and Sensitivity Analysis
i i i i i
Form WPC = x1 PC1 + x2PC2 + x3PC3+ x4PC4
j = 1, 2, 3, 4 and i = 1, 2, 3, 4, 5
Where:
PCij = Performance Criterion
xi = Normalized values of constraints, xi ≥ 0
j = Number of constraints
i = Number of options
1
WPC = 6.57x1 + 6.97x2 + 8.76x3 + 7.75x4
2
WPC = 6.68x1 + 6.82x2 + 8.76x3 + 9.25x4
3
WPC = 6.79x1 + 5.77x2 + 9.29x3 + 9.25x4
4
WPC = 0.94x1 + 5.77x2 + 6.51x3 + 4.00x4
5
WPC = -2.99x1 + 3.67x2 + 6.51x3 + 4.00x4
Weighted Factor Values (non-negative and total of 1.00)
Level of Importance
Weighted Factor =
Total level of Importance
2
x1 = = 0.1333, Where x1 is for Economical (Cost)
15
4
x2 = = 0.2667, Where x2 is for Mobility (Form Factor)
15
4
x3 = = 0.2667, Where x3 is for Efficiency (Power Ratio)
15
5
x4 = = 0.3333, Where x4 is for Safety (Protection Rating)
16
Therefore, the total score for each design:
1
WPC = 6.57(0.1333) + 6.97( 0.2667) + 8.76( 0.2667) + 7.75(0.3333) = 7.66
2
WPC = 6.68(0.1333) + 6.82( 0.2667) + 8.76( 0.2667) + 9.25(0.3333) = 8.13
3
WPC = 6.79(0.1333) + 5.77( 0.2667) + 9.29( 0.2667) + 9.25(0.3333) = 8.30
4
WPC = 0.94(0.1333) + 5.77( 0.2667) + 6.51( 0.2667) + 4.00(0.3333) = 4.74
5
WPC = -2.99(0.1333) + 3.67( 0.2667) + 6.51( 0.2667) + 4.00(0.3333) = 3.65
125
Table 4-54. Total rating of each design
Level Design Options
of Weighting D1-O3 Rating D2-SD1 Rating D2-SD2 Rating D3 – 03 Rating D4 - 03 Rating
Constraints
Impor Factor O3 O3
tance
Economical
2 0.1333 6.57 0.88 6.68 0.89 6.79 0.91 0.94 0.13 -2.99 -0.4
(Cost)
Mobility (Form
4 0.2667 6.97 1.86 6.82 1.82 6.85 1.83 5.77 1.54 3.67 0.98
Factor)
Efficiency (Power
4 0.2667 8.76 2.34 8.76 2.34 9.29 2.48 6.51 1.74 6.51 1.74
Ratio)
Safety (Protection
5 0.3333 7.75 2.58 9.25 3.08 9.25 3.08 4.00 1.33 4.00 1.33
Rating)
Total 15 1 7.66 8.13 8.3 4.74 3.65
*Reference: Cruz, J., Almario, E., “When is the Pareto Choice from a Finite Set Invariant to Variations in Weights and Values of Multiple Performance Criteria”, Philippine Science
Letters
Table 4-54 shows that Design 2 Sub-Design 2 Option 3 Savonius Ducted Type with Direct Input
Sensitivity Analysis Test B
3.5
3
2.5
2
1.5
1
0.5
0
-0.5
-1
D1 O3 D2.1 O3 D2.2 O3 D3 O3 D4 O3
Economical (Cost) 0.88 0.89 0.91 0.13 -0.4
Mobility (Form Factor) 1.86 1.82 1.83 1.54 0.98
Efficiency (Power Ratio) 2.34 2.34 2.48 1.74 1.74
Safety (Protection Rating) 2.58 3.08 3.08 1.33 1.33
126
Weight Variation and Sensitivity Analysis Test C
Table 4-55. The level of importance and weighting factor of each constraints
Design Criteria Level of Importance Weighting Factor
Economical (Cost) 4 0.2667
Mobility (Form Factor) 5 0.3333
Efficiency (Power Ratio) 4 0.2667
Safety (Protection Rating) 2 0.1333
Total 15 1
Table 4-55 shows the level of importance and weighting factor for each constraint
Weight Variation and Sensitivity Analysis
i i i i i
Form WPC = x1 PC1 + x2PC2 + x3PC3+ x4PC4
j = 1, 2, 3, 4 and i = 1, 2, 3, 4, 5
Where:
PCij = Performance Criterion
xi = Normalized values of constraints, xi ≥ 0
j = Number of constraints
i = Number of options
1
WPC = 6.57x1 + 6.97x2 + 8.76x3 + 7.75x4
2
WPC = 6.68x1 + 6.82x2 + 8.76x3 + 9.25x4
3
WPC = 6.79x1 + 5.77x2 + 9.29x3 + 9.25x4
4
WPC = 0.94x1 + 5.77x2 + 6.51x3 + 4.00x4
5
WPC = -2.99x1 + 3.67x2 + 6.51x3 + 4.00x4
Weighted Factor Values (non-negative and total of 1.00)
Level of Importance
Weighted Factor =
Total level of Importance
4
x1 = = 0.2667, Where x1 is for Economical (Cost)
15
5
x2 = = 0.3333, Where x2 is for Mobility (Form Factor)
15
4
x3 = = 0.2667, Where x3 is for Efficiency (Power Ratio)
15
2
x4 = = 0.1333, Where x4 is for Safety (Protection Rating)
15
Therefore, the total score for each design:
1
WPC = 6.57(0.2667) + 6.97( 0.3333) + 8.76( 0.2667) + 7.75(0.1333) = 7.44
2
WPC = 6.68(0.2667) + 6.82( 0.3333) + 8.76( 0.2667) + 9.25(0.1333) = 7.62
3
WPC = 6.79(0.2667) + 5.77(0.3333) + 9.29( 0.2667) + 9.25(0.1333) = 7.80
4
WPC = 0.94(0.2667) + 5.77( 0.3333) + 6.51( 0.2667) + 4.00(0.1333) = 4.44
5
WPC = -2.99(0.2667) + 3.67( 0.3333) + 6.51( 0.2667) + 4.00(0.1333) = 2.69
127
Table 4-56. Total rating of each design
Level Design Options
of Weighting D1-O3 Rating D2-SD1 Rating D2-SD2 Rating D3 – 03 Rating D4 - 03 Rating
Constraints
Impor Factor O3 O3
tance
Economical
4 0.2667 6.57 1.75 6.68 1.78 6.79 1.81 0.94 0.25 -2.99 -0.8
(Cost)
Mobility (Form
5 0.3333 6.97 2.32 6.82 2.27 6.85 2.28 5.77 1.92 3.67 1.22
Factor)
Efficiency (Power
4 0.2667 8.76 2.34 8.76 2.34 9.29 2.48 6.51 1.74 6.51 1.74
Ratio)
Safety (Protection
2 0.1333 7.75 1.03 9.25 1.23 9.25 1.23 4.00 0.53 4.00 0.53
Rating)
Total 15 1 7.44 7.62 7.8 4.44 2.69
*Reference: Cruz, J., Almario, E., “When is the Pareto Choice from a Finite Set Invariant to Variations in Weights and Values of Multiple Performance Criteria”, Philippine Science
Letters
Table 4-56 shows that Design 2 Sub-Design 2 Option 3 Savonius Ducted Type with Direct Input
Sensitivity Analysis Test C
3
2.5
2
1.5
1
0.5
0
-0.5
-1
D1 O3 D2.1 O3 D2.2 O3 D3 O3 D4 O3
Economical (Cost) 1.75 1.78 1.81 0.25 -0.8
Mobility (Form Factor) 2.32 2.27 2.28 1.92 1.22
Efficiency (Power Ratio) 2.34 2.34 2.48 1.74 1.74
Safety (Protection Rating) 1.03 1.23 1.23 0.53 0.53
128
The proponents conducted 3 sensitivity analysis tests to determine the best design option. Based on the
sensitivity analysis test with a random constraints level of importance Design 2.2 Option 3 Vertical
Savonius Turbine Ducted Type with Direct Input dominates all the other 4 design options. Therefore,
Design 2.2 Option 3 is the best design option.
129
Design Standards
IEC 61400-1(Class S): Air Density of 1.225 kg/m3, average annual wind below 8.5 m/s
IEC 61400-2 Ed. 3.0 b: 2013 – requirements for the safety of small wind turbines
UKAS ISO/IEC 17025 and ISO Guide 34 certified, density: 998.2 kg/m^3 at 20 degrees Celsius
ISA standard atmosphere: sea level condition air density is 1.225 kg/m3
Philippine Electrical Code Table 3.10.1.16 Article 3.10- Conductors for General Wiring, Page 350,
2009
130