2020 Time Delay Catalog 05 18 20
2020 Time Delay Catalog 05 18 20
2020 Time Delay Catalog 05 18 20
catalog of products
Time Delay
Input
Product Series Refer to: Setting & Functions Output Mounting
Voltages
Ranges
12VDC,
Analog-Set
THR-1 Series Pages Single- 24VAC/DC, 10A SPDT
0.1 SEC - 100
Relay Output 3-9 Function 120VAC/DC, Relay
HR
240VAC
Analog-Set
THR-3 Relay Pages Multi-Function 10A SPDT
0.1 SEC - 100 24-240VAC,
Output 10-11 (4) Relay
MIN 12-125VDC 2” x 2”
Encapsulated
THS-1 Series Analog-Set Panel
Pages Single- 24-240VAC, 1A SPNO
Solid State 0.01 SEC - 100 Mounted
12-15 Function 12-48VDC Solid State
Output HR with
time delay relays
Digital-Set 24-240VAC
TAD Series Multi-Function
Pages Multi-Range & 5A SPDT
Digital-Set (10)
40-41 0.01 SEC - 24-240VDC Relay
1/16 DIN
9,990 HR
1/16 DIN
5A DPDT & (48mm2)
Analog-Set 100-240VAC
TAA Series Multi-Function SPDT Timed
Pages Multi-Range &
Analog-Set (6)-2 Versions & SPDT
42-43 0.05 SEC - 24-240VDC
1/16 DIN Instantaneous
100 HR
Relay
Time Delays
THR-1 Series Products have three time delay options:
Onboard Adjustable Time Delay--complete
Product Number by adding two-digit Code from
Table at right, i.e., THR-10262-30 is an On Delay
with a time delay range of 0.1-10 seconds. * See ** TIMING RANGE TABLE
www.macromatic.com/onoff for information on Time Delay Range Code
how to order these functions with different ON & 0.05 - 5 Sec. 04
OFF time ranges. 0.1 - 10 Sec. 30
Onboard Fixed Time Delay--replace two-digit 1 - 100 Sec. 31
Code with suffix “F” followed by delay [0.1 ... 10 - 1,000 Sec. 36
0.1 - 10 Min. 32
100] followed by (S) seconds, (M) minutes or (H)
1 - 100 Min. 33
hours, i.e., THR-10262-F5S is an On Delay with a 10 - 1,000 Min. 37
time delay fixed at 5 seconds. 1 - 100 Hr. 35
Remote Time Delay--THR-1 Series products can
be built with two terminals for remote adjustable
800.238.7474
or fixed time delays. www.macromatic.com
Build your Time Delay Relays with the Online Product Builder [email protected]
3
ON DELAY, INTERVAL, FLASHER, CYCLE & DELAYED INTERVAL
Relay Output | THR-1 Series
INPUT CATALOG
FUNCTION VOLTAGE NUMBER ** WIRING
ON DELAY 120V AC/DC THR-10262-**J Onboard Adjustable or
12V DC THR-10266-**J Fixed Time Delay
24V AC/DC THR-10268-**J
240V AC THR-10261-**J
INTERVAL ON 120V AC/DC THR-10562-**J
12V DC THR-10566-**J
time delay relays | encapsulated
Time Delays
THR-1 Series Products have three time delay options:
Onboard Adjustable Time Delay--complete
Product Number by adding two-digit Code from
Table at right, i.e., THR-10262-30J is an On ** TIMING RANGE TABLE
Delay with a time delay range of 0.1-10 seconds. Time Delay Range Code
* See www.macromatic.com/onoff for informa- 0.05 - 5 Sec. 04
tion on how to order these functions with different 0.1 - 10 Sec. 30
ON & OFF time ranges. 1 - 100 Sec. 31
10 - 1,000 Sec. 36
Onboard Fixed Time Delay--replace two-digit
0.1 - 10 Min. 32
Code with suffix “F” followed by delay [0.1 ... 1 - 100 Min. 33
100] followed by (S) seconds, (M) minutes or (H) 10 - 1,000 Min. 37
hours, i.e., THR-10262-F5SJ is an On Delay with 1 - 100 Hr. 35
a time delay fixed at 5 seconds.
800.238.7474 Remote Adjustable Time Delay--THR-1 Series
products can be built with two terminals for
www.macromatic.com remote adjustable or fixed time delays.
[email protected] Build your Time Delay Relays with the Online Product Builder
4
OFF DELAY, SINGLE SHOT, WATCHDOG, SINGLE SHOT FALLING
EDGE, ON DELAY/OFF DELAY & DELAYED INTERVAL
Relay Output | THR-1 Series
Isolated Control Switch & Isolated Relay Common
INPUT CATALOG
FUNCTION VOLTAGE NUMBER ** WIRING
OFF DELAY 120V AC/DC THR-11662-** Onboard Adjustable or
12V DC THR-11666-** Fixed Time Delay
24V AC/DC THR-11668-**
240V AC THR-11661-**
SINGLE SHOT 120V AC/DC THR-11562-**
Time Delays
THR-1 Series Products have three time delay options:
Onboard Adjustable Time Delay--complete Product
Number by adding two-digit Code from Table at right,
i.e., THR-11662-30 is an Off Delay with a time delay ** TIMING RANGE TABLE
range of 0.1-10 seconds. Time Delay Range Code
* See www.macromatic.com/onoff for information 0.05 - 5 Sec. 04
on how to order these functions with different ON & 0.1 - 10 Sec. 30
OFF time ranges. 1 - 100 Sec. 31
Onboard Fixed Time Delay--replace two-digit Code 10 - 1,000 Sec. 36
with suffix “F” followed by delay [0.1 ... 100] followed 0.1 - 10 Min. 32
by (S) seconds, (M) minutes or (H) hours, i.e., THR- 1 - 100 Min. 33
11662-F5S is an Off Delay with a time delay fixed at 10 - 1,000 Min. 37
5 seconds. 1 - 100 Hr. 35
Remote Adjustable Time Delay--THR-1 Series
products can be built with two terminals for remote 800.238.7474
adjustable or fixed time delays. www.macromatic.com
Build your Time Delay Relays with the Online Product Builder [email protected]
5
OFF DELAY, SINGLE SHOT, WATCHDOG, SINGLE SHOT FALLING
EDGE, ON DELAY/OFF DELAY & DELAYED INTERVAL
Relay Output | THR-1 Series
Isolated Control Switch & Relay Common Internally Connected to Pin 2
INPUT CATALOG
FUNCTION VOLTAGE NUMBER ** WIRING
OFF DELAY 120V AC/DC THR-11662-**J Onboard Adjustable or
12V DC THR-11666-**J Fixed Time Delay
24V AC/DC THR-11668-**J
240V AC THR-11661-**J
SINGLE SHOT 120V AC/DC THR-11562-**J
12V DC THR-11566-**J
time delay relays | encapsulated
Time Delays
THR-1 Series Products have three time delay options:
Onboard Adjustable Time Delay--complete Product
Number by adding two-digit Code from Table at right,
i.e., THR-11662-30J is an Off Delay with a time delay ** TIMING RANGE TABLE
range of 0.1-10 seconds. Time Delay Range Code
* See www.macromatic.com/onoff for information 0.05 - 5 Sec. 04
on how to order these functions with different ON & 0.1 - 10 Sec. 30
OFF time ranges. 1 - 100 Sec. 31
10 - 1,000 Sec. 36
Onboard Fixed Time Delay--replace two-digit Code
0.1 - 10 Min. 32
with suffix “F” followed by delay [0.1 ... 100] followed 1 - 100 Min. 33
by (S) seconds, (M) minutes or (H) hours, i.e., THR- 10 - 1,000 Min. 37
11662-F5SJ is an Off Delay with a time delay fixed at 1 - 100 Hr. 35
5 seconds.
800.238.7474 Remote Adjustable Time Delay--THR-1 Series
products can be built with two terminals for remote
www.macromatic.com adjustable or fixed time delays.
[email protected] Build your Time Delay Relays with the Online Product Builder
6
OFF DELAY, SINGLE SHOT, WATCHDOG, SINGLE SHOT FALLING
EDGE, ON DELAY/OFF DELAY & DELAYED INTERVAL
Relay Output | THR-1 Series
Control Switch Common to Pin 2 & Isolated Relay Common
INPUT CATALOG
FUNCTION VOLTAGE NUMBER ** WIRING
OFF DELAY 120V AC/DC THR-11662-**T Onboard Adjustable or
12V DC THR-11666-**T Fixed Time Delay
24V AC/DC THR-11668-**T
240V AC THR-11661-**T
SINGLE SHOT 120V AC/DC THR-11562-**T
Time Delays
THR-1 Series Products have three time delay options:
Onboard Adjustable Time Delay--complete
Product Number by adding two-digit Code from
Table at right, i.e., THR-11662-30T is an Off Delay
** TIMING RANGE TABLE
with a time delay range of 0.1-10 seconds. * See
www.macromatic.com/onoff for information on Time Delay Range Code
how to order these functions with different ON & 0.05 - 5 Sec. 04
OFF time ranges. 0.1 - 10 Sec. 30
1 - 100 Sec. 31
Onboard Fixed Time Delay--replace two-digit 10 - 1,000 Sec. 36
Code with suffix “F” followed by delay [0.1 ... 100] 0.1 - 10 Min. 32
followed by (S) seconds, (M) minutes or (H) hours, 1 - 100 Min. 33
i.e., THR-11662-F5ST is an Off Delay with a time 10 - 1,000 Min. 37
delay fixed at 5 seconds. 1 - 100 Hr. 35
Remote Adjustable Time Delay--THR-1 Series
products can be built with two terminals for remote 800.238.7474
adjustable or fixed time delays. www.macromatic.com
Build your Time Delay Relays with the Online Product Builder [email protected]
7
OFF DELAY, SINGLE SHOT, WATCHDOG, SINGLE SHOT FALLING
EDGE, ON DELAY/OFF DELAY & DELAYED INTERVAL
Relay Output | THR-1 Series
Control Switch Common to Pin 2 &
Relay Common Internally Connected to Pin 2
INPUT CATALOG
FUNCTION VOLTAGE NUMBER ** WIRING
OFF DELAY 120V AC/DC THR-11662-**JT Onboard Adjustable or
12V DC THR-11666-**JT Fixed Time Delay
24V AC/DC THR-11668-**JT
240V AC THR-11661-**JT
SINGLE SHOT 120V AC/DC THR-11562-**JT
time delay relays | encapsulated
12V DC THR-11566-**JT
Cost effective design & 24V AC/DC THR-11568-**JT
compact 2” x 2” enclosure 240V AC THR-11561-**JT
are ideal for volume OEM
applications WATCHDOG 120V AC/DC THR-11362-**JT
(Retriggerable 12V DC THR-11366-**JT
Microprocessor-based design Single Shot) 24V AC/DC THR-11368-**JT
for greater performance & 240V AC THR-11361-**JT DIAGRAM 309
maximum flexibility
SINGLE SHOT 120V AC/DC THR-12262-**JT
Encapsulated for protection FALLING EDGE 12V DC THR-12266-**JT Remote Time Delay
against harsh environments (Retriggerable) 24V AC/DC THR-12268-**JT
240V AC THR-12261-**JT
10A SPDT relay output contacts
can handle most pilot duty & ON/OFF DELAY * 120V AC/DC THR-14162-**JT
fractional HP loads 12V DC THR-14166-**JT
24V AC/DC THR-14168-**JT
Relay Common internally 240V AC THR-14161-**JT
connected to Pin 2-makes
DELAYED 120V AC/DC THR-16562-**JT
wiring easier
INTERVAL * 12V DC THR-16566-**JT
Onboard & remote adjustable (Triggered) 24V AC/DC THR-16568-**JT
or fixed time delays from 0.05 240V AC THR-16561-**JT DIAGRAM 311
seconds to 100 hours See “Definitions of Timing Functions”.
* ON & OFF Time Ranges for these functions are the same. See
www.macromatic.com/onoff for information on how to order a unit with
different ON & OFF time ranges.
** Complete Product Number using two-digit Code from Table below.
Time Delays
THR-1 Series Products have three time delay options:
Onboard Adjustable Time Delay--complete Product
Number by adding two-digit Code from Table at right,
i.e., THR-11662-30JT is an Off Delay with a time
delay range of 0.1-10 seconds. ** TIMING RANGE TABLE
* See www.macromatic.com/onoff for information Time Delay Range Code
0.05 - 5 Sec. 04
on how to order these functions with different ON &
0.1 - 10 Sec. 30
OFF time ranges.
1 - 100 Sec. 31
Onboard Fixed Time Delay--replace two-digit Code 10 - 1,000 Sec. 36
with suffix “F” followed by delay [0.1 ... 100] followed 0.1 - 10 Min. 32
by (S) seconds, (M) minutes or (H) hours, i.e., THR- 1 - 100 Min. 33
11662-F5SJT is an Off Delay with a time delay fixed 10 - 1,000 Min. 37
at 5 seconds. 1 - 100 Hr. 35
Remote Adjustable Time Delay--THR-1 Series
800.238.7474 products can be built with two terminals for remote
adjustable or fixed time delays.
www.macromatic.com
[email protected] Build your Time Delay Relays with the Online Product Builder
8
THR-1 SERIES
Relay Output
Application Data
Voltage Tolerance: Temperature:
AC Operation: +10/-15% of nominal at 50/60 Hz Operate: -28o to 65oC (-18o to 149oF)
DC Operation: +10/-15% of nominal Storage: -45o to 85oC (-49o to 185oF)
Load (Burden): Maximum of 2 VA for all voltages Output Contacts:
10A @ 240VAC / 7A @ 28VDC SPDT, ¼hp @ 120VAC (N.O.)
Setting Accuracy:
Maximum Setting (Adjustable): +5%, -0% Life:
Minimum Setting (Adjustable): +0%, -50% Mechanical: 10,000,000 operations
10
PROGRAMMABLE
MULTI-FUNCTION | MULTI-TIME RANGE | MULTI-VOLTAGE
Relay Output | THR-3 Series
Application Data
Voltage Tolerance: Temperature: Operating: -28o to 65oC (-18o to 149oF)
AC Operation: +10/-15% of nominal at 50/60 Hz Storage: -40o to 85oC (-40o to 185oF)
DC Operation: +10/-15% of nominal
Output Contacts:
Load (Burden): Maximum of 2 VA for all voltages 10A @ 240VAC / 7A @ 28VDC SPDT, ¼hp @ 120VAC (N.O.)
Setting Accuracy: Life:
Maximum Setting (Adjustable): +5%, -0% Mechanical: 10,000,000 operations
Minimum Setting (Adjustable): +0%, -50%
Dimensions
All Dimensions in
Inches (Millimeters)
INPUT CATALOG
FUNCTION VOLTAGE NUMBER ** WIRING v
ON DELAY p 24-240V AC THS-1024A-** Onboard Adjustable or
12-125V DC THS-1024D-** Fixed Time Delay
INTERVAL ON 24-240V AC THS-1054A-**
12-125V DC THS-1054D-**
time delay relays | encapsulated
Cost effective design &
compact 2” x 2” enclosure FLASHER 24-240V AC THS-1094A-**
are ideal for volume OEM (ON Time 1st) 12-125V DC THS-1094D-**
applications DIAGRAM 317
Microprocessor-based design
for greater performance &
maximum flexibility REPEAT CYCLE * 24-240V AC THS-1314A-** Remote Time Delay
(OFF Time 1st) 12-125V DC THS-1314D-**
Encapsulated for protection
against harsh environments
Output rated 1A continuous/10A
inrush is perfect for high duty REPEAT CYCLE * 24-240V AC THS-1514A-**
cycle/long life applications (ON Time 1st) 12-125V DC THS-1514D-**
Onboard & remote adjustable
or fixed time delays from 0.01
seconds to 100 hours DELAYED 24-240V AC THS-1614A-**
Built-in load suppression INTERVAL * 12-125V DC THS-1614D-**
eliminates need for separate
protection DIAGRAM 320
Time Delays
THS-1 Series Products have three time delay options:
Onboard Adjustable Time Delay--complete
Product Number by adding two-digit Code from
Table at right, i.e., THS-1054A-30 is an Interval On ** TIMING RANGE TABLE
with a time delay range of 0.1-10 seconds. * See
Time Delay Range Code
www.macromatic.com/onoff for information on
0.01 - 1 Sec. 02
how to order these functions with different ON &
0.05 - 5 Sec. 04
OFF time ranges. 0.1 - 10 Sec. 30
Onboard Fixed Time Delay--replace two-digit 1 - 100 Sec. 31
Code with suffix “F” followed by delay [0.1 ... 100] 10 - 1,000 Sec. 36
followed by (S) seconds, (M) minutes or (H) hours, 0.1 - 10 Min. 32
i.e., THS-1054A-F5S is an Interval On with a time 1 - 100 Min. 33
delay fixed at 5 seconds. 10 - 1,000 Min. 37
Remote Time Delay--THS-1 Series products can 1 - 100 Hr. 35
800.238.7474 be built with two terminals for remote adjustable or
fixed time delays.
www.macromatic.com
[email protected] Build your Time Delay Relays with the Online Product Builder
12
OFF DELAY, SINGLE SHOT, WATCHDOG, SINGLE SHOT FALLING
EDGE, ON DELAY/OFF DELAY & DELAYED INTERVAL
Solid State Output | THS-1 Series
Isolated Control Switch
INPUT CATALOG
FUNCTION VOLTAGE NUMBER ** WIRING v
OFF DELAY 24-240V AC THS-1164A-** Onboard Adjustable or
12-125V DC THS-1164D-** Fixed Time Delay
SINGLE SHOT 24-240V AC THS-1154A-**
Time Delays
THS-1 Series Products have three time delay options:
Onboard Adjustable Time Delay--complete
Product Number by adding two-digit Code from ** TIMING RANGE TABLE
Table at right, i.e., THS-1164A-30 is an Off Delay
Time Delay Range Code
with a time delay range of 0.1-10 seconds. * See
0.01 - 1 Sec. 02
www.macromatic.com/onoff for information on
0.05 - 5 Sec. 04
how to order these functions with different ON &
0.1 - 10 Sec. 30
OFF time ranges. 1 - 100 Sec. 31
Onboard Fixed Time Delay--replace two-digit 10 - 1,000 Sec. 36
Code with suffix “F” followed by delay [0.1 ... 0.1 - 10 Min. 32
100] followed by (S) seconds, (M) minutes or (H) 1 - 100 Min. 33
hours, i.e., THS-1164A-F5S is an Off Delay with a 10 - 1,000 Min. 37
time delay fixed at 5 seconds. 1 - 100 Hr. 35
Remote Time Delay--THS-1 Series products can
be built with two terminals for remote adjustable 800.238.7474
or fixed time delays. www.macromatic.com
Build your Time Delay Relays with the Online Product Builder [email protected]
13
OFF DELAY, SINGLE SHOT, WATCHDOG, SINGLE SHOT FALLING
EDGE, ON DELAY/OFF DELAY & DELAYED INTERVAL
SOLID STATE OUTPUT | THS-1 SERIES
Control Switch Common to Pin 2
INPUT CATALOG
FUNCTION VOLTAGE NUMBER ** WIRING v
OFF DELAY 24-240V AC THS-1164A-**T Onboard Adjustable or
12-125V DC THS-1164D-**T Fixed Time Delay
SINGLE SHOT 24-240V AC THS-1154A-**T
12-125V DC THS-1154D-**T
time delay relays | encapsulated
14
THS-1 SERIES
Solid State Output
INPUT CATALOG
FUNCTION VOLTAGE NUMBER ** WIRING
ON DELAY 24-240V AC & THL-1024U-** Onboard Adjustable or
12-48V DC Fixed Time Delay
time delay relays | encapsulated
Time Delays
THL-1 Series Products have three time delay options:
Onboard Adjustable Time Delay--complete Prod-
uct Number by adding two-digit Code from Table ** TIMING RANGE TABLE
at right, i.e., THL-1024U-30 is an On Delay with a Time Delay Range Code
time delay range of 0.1-10 seconds. 0.01 - 1 Sec. 02
Onboard Fixed Time Delay--replace two-digit 0.05 - 5 Sec. 04
Code with suffix “F” followed by delay [0.1 ... 100] 0.1 - 10 Sec. 30
followed by (S) seconds, (M) minutes or (H) hours, 1 - 100 Sec. 31
10 - 1,000 Sec. 36
i.e., THL-1024U-F5S is an On Delay with a time 0.1 - 10 Min. 32
delay fixed at 5 seconds. 1 - 100 Min. 33
Remote Time Delay--THL-1 Series products can 10 - 1,000 Min. 37
be built with two terminals for remote adjustable or 1 - 100 Hr. 35
fixed time delays.
800.238.7474
www.macromatic.com
[email protected] Build your Time Delay Relays with the Online Product Builder
16
ON DELAY | INLINE (SERIES CONNECTION)
Solid State Output | Analog-Set | THL-1 Series
Application Data
Voltage Tolerance: Output Contacts:
AC Operation: +10 to -15% of nominal voltage, 50/60 Hz Normally Open Solid State 1A Continuous, 10A Inrush @ 65o C, Pilot Duty
DC Operation: +10 to -15% of nominal voltage
Life:
Load (Burden): Maximum of 1 VA for all voltages No predictable failure if used within operating parameters.
Setting Accuracy: Leakage Current (OFF-State): < 5ma @ 240V AC
Maximum Setting (Adjustable): +5%, -0%
Minimum Load Current: 20ma
Minimum Setting (Adjustable): +0%, -50%
The THL-8 On Delay Inline (Series Connection) offers an easy and accurate method
to select any time delay. The THL-8 Series is a compact 2” x 2” encapsulated enclo-
sure with a universal input voltage. It is connected in series with the load requiring
only 2 terminals/connections.
Three time ranges are available: 0.1 – 102.3 seconds, 1 – 1,023 seconds and 10
– 10,230 seconds. Programming is accomplished through the use of a 10-position
DIP-switch. Each position is marked with a binary time increment. The required
delay is selected by moving the switch of each increment to the ON position and
adding their corresponding values (see examples below). This method provides a
time delay relays | encapsulated
greater setting accuracy than is found on other units with an analog potentiometer.
Universal input voltage:
24-240V AC & 12-48V DC These products feature a universal input voltage of 24-240V AC and 12-48V DC.
The inline two-terminal output is rated 1A continuous/10A inrush pilot duty, and is
DIP-switch for accurate digital- ideal for high duty cycle and long life applications. The enclosure is encapsulated for
set of any time delay from protection against harsh environments.
100ms to 10,230 seconds
Two-terminal series-connection For similar products with choices of onboard and remote analog-set or fixed time
with the load delay, see the THL-1 Series.
Time Delays
www.macromatic.com
[email protected] Build your Time Delay Relays with the Online Product Builder
18
ON DELAY | INLINE (SERIES CONNECTION)
Solid State Output | Dip-Switch Digital-Set | THL-8 Series
Application Data
Voltage Tolerance: Temperature: Operating: -40o to 65oC (-40o to 149oF)
AC Operation: +10 to -15% of nominal voltage, 50/60 Hz +5% Storage: -40o to 85oC (-40o to 185oF)
DC Operation: +10 to -15% of nominal voltage
Output Contacts:
Load (Burden): Maximum of 1 VA for all voltages Normally Open Solid State 1A Continuous, 10A Inrush @ 65o C, Pilot Duty
Setting Accuracy: Life:
Constant Voltage & Temperature w/i specifications: No predictable failure if used within operating parameters.
+2% of set time or +50ms, whichever is greater
Leakage Current (OFF-State): < 5ma @ 240V AC
Dimensions
All Dimensions in
Inches (Millimeters)
Time Delays
TR-5 Series Products have three time delay options:
Onboard Adjustable Time Delay--complete
Product Number by adding two-digit Code from ** TIMING RANGE TABLE
Table at right, i.e., TR-50222-05 is an On Delay Time Delay Range Code
with a time delay range of 0.1-10 seconds. 0.05 - 5 Sec. 04
Onboard Fixed Time Delay--replace two-digit 0.1 - 10 Sec. 05
Code with suffix “F” followed by delay [0.1 ... 0.3 - 30 Sec. 07X
0.6 - 60 Sec. 08
100] followed by (S) seconds, (M) minutes or (H) 1.2 - 120 Sec. 09
hours, i.e., TR-50222-F5S is an On Delay with a 1.8 - 180 Sec. 10
time delay fixed at 5 seconds. 3 - 300 Sec. 12
Remote Adjustable Time Delay--Selected TR-5 0.1 - 10 Min. 22
Series products can be built with two terminals 0.3 - 30 Min. 15
for remote adjustable or fixed time delays. See 0.6 - 60 Min. 16X
20
NON-PROGRAMMABLE | OFF DELAY, SINGLE SHOT,
WATCHDOG & SINGLE SHOT FALLING EDGE
TR-5 Series
INPUT
VOLTAGE CATALOG WIRING/
FUNCTION 50/60Hz. NUMBER ** SOCKETS
Time Delays
TR-5 Series Products have three time delay options:
Onboard Adjustable Time Delay--complete
Product Number by adding two-digit Code from ** TIMING RANGE TABLE
Table at right, i.e., TR-51622-05 is an Off Delay Time Delay Range Code
with a time delay range of 0.1-10 seconds. 0.05 - 5 Sec. 04
0.1 - 10 Sec. 05
Onboard Fixed Time Delay--replace two-digit 0.3 - 30 Sec. 07
Code with suffix “F” followed by delay [0.1 ... 0.6 - 60 Sec. 08
100] followed by (S) seconds, (M) minutes or (H) 1.2 - 120 Sec. 09
hours, i.e., TR-51622-F5S is an Off Delay with a 1.8 - 180 Sec. 10
time delay fixed at 5 seconds. 3 - 300 Sec. 12
Remote Time Delay--Selected TR-5 Series 0.1 - 10 Min. 22
products can be built with two terminals for 0.3 - 30 Min. 15
remote adjustable or fixed time delays. See 0.6 - 60 Min. 16
www.macromatic.com/remote for information.
1.2 - 120 Min. 17
800.238.7474
Sockets & Accessories available www.macromatic.com
Build your Time Delay Relays with the Online Product Builder [email protected]
21
NON-PROGRAMMABLE | REPEAT CYCLE, ON/OFF DELAY,
& DELAYED INTERVAL
TR-5 Series
INPUT
VOLTAGE CATALOG WIRING/
FUNCTION 50/60Hz. NUMBER ** SOCKET
Time Delays
TR-5 Series Products have three time delay options:
Onboard Adjustable Time Delay--complete Product ** TIMING RANGE TABLE
Number by adding two-digit Code from Table at
right, i.e., TR-53122-05 is a Repeat Cycle with both Time Delay Range Code
an ON & OFF time delay range of 0.1-10 seconds. 0.05 - 5 Sec. 04
See www.macromatic.com/onoff for information 0.1 - 10 Sec. 05
on how to order a unit with different ON & OFF time 0.3 - 30 Sec. 07X
ranges. 0.6 - 60 Sec. 08
Onboard Fixed Time Delay--replace two-digit Code 1.2 - 120 Sec. 09
with suffix “F” followed by delay [0.1 ... 100] followed 1.8 - 180 Sec. 10
by (S) seconds, (M) minutes or (H) hours, i.e., TR- 3 - 300 Sec. 12
53122-F5S is a Repeat Cycle with a time delay fixed 0.1 - 10 Min. 22
0.3 - 30 Min. 15
at 5 seconds.
Remote Time Delay--Selected TR-5 Series products 0.6 - 60 Min. 16 X
can be built with two terminals for remote adjustable 1.2 - 120 Min. 17X
800.238.7474 or fixed time delays.
See www.macromatic.com/remote for information.
X Not offered on TR-546
www.macromatic.com Sockets & Accessories available
[email protected] Build your Time Delay Relays with the Online Product Builder
22
TR-5 SERIES
Non-Programmable
Application Data
Voltage Tolerance: Life:
AC Operation: +10/-15% of nominal at 50/60 Hz. Mechanical: 10,000,000 operations (2,000,000 operations
DC Operation: +10/-15% of nominal. on TR-506 & TR-546 Series only)
Full Load: 100,000 operations
Load (Burden):
Maximum of 2 VA for all voltages Compatibility:
Using a solid state switch to initiate the time sequence is
Setting Accuracy:
acceptable. See www.macromatic.com/leakage or contact
Maximum Setting (Adjustable): +5%, -0% Macromatic for information regarding leakage current limits and
Minimum Setting (Adjustable): +0%, -50% other solid state design considerations.
Fixed Time Delay: +2% or 50ms, whichever is greater
Triggering Off Delay, Single Shot or Watchdog Units:
Repeat Accuracy (constant voltage and temperature):
Dimensions
2.4
(60)
2.9
(74)
1.7 3.5
(43) (89)
All Dimensions in
Inches (Millimeters)
Time Delays
TR-5 Series Products have three time delay options:
Onboard Adjustable Time Delay--complete
** TIMING RANGE TABLE
Product Number by adding two-digit Code from
Time Delay Range Code
Table at right, i.e., TR-51662-05 is an Off Delay
0.05 - 5 Sec. 04
with a time delay range of 0.1-10 seconds. 0.1 - 10 Sec. 05
Onboard Fixed Time Delay--replace two-digit 0.3 - 30 Sec. 07
Code with suffix “F” followed by delay [0.1 ... 0.6 - 60 Sec. 08
100] followed by (S) seconds, (M) minutes or (H) 1.2 - 120 Sec. 09
hours, i.e., TR-51662-F5S is an Off Delay with a 1.8 - 180 Sec. 10
time delay fixed at 5 seconds. 3 - 300 Sec. 12
0.1 - 10 Min. 22
Remote Time Delay--Selected TR-5 Series
0.3 - 30 Min. 15
products can be built with two terminals for 0.6 - 60 Min. 16
remote adjustable or fixed time delays. See 1.2 - 120 Min. 17
800.238.7474 www.macromatic.com/remote for information.
24
NON-PROGRAMMABLE | OFF DELAY, SINGLE SHOT
& WATCHDOG
8 Pin | SPDT Versions | TR-5 Series
Application Data
Voltage Tolerance: Temperature: Operating: -28o to 65oC (-18o to 149oF)
AC Operation: +10/-15% of nominal at 50/60 Hz. Storage: -40o to 85oC (-40o to 185oF)
DC Operation: +10/-15% of nominal.
Output Contacts:
Load (Burden):
SPDT 10A @ 240V AC/30V DC,
Maximum of 2 VA for all voltages 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.)
Setting Accuracy: B300 & R300; AC15 & DC13
Maximum Setting (Adjustable): +5%, -0% Life:
Minimum Setting (Adjustable): +0%, -50% Mechanical: 10,000,000 operations
Fixed Time Delay: +2% or 50ms, whichever is greater Full Load: 100,000 operations
Compatibility:
Dimensions
2.4
(60)
2.9
(74)
1.7 3.5
(43) (89)
All Dimensions in
Inches (Millimeters)
The TR-681 & TR-682 Series offer the flexible programmability of a multi-function and
multi-range time delay relay together with a universal input voltage. These products
provide an easy method to select one of eight (TR-681) or four (TR-682) time delay
functions and any time range between 0.05 seconds and 100 hours. Programming is
accomplished through the use of two rotary switches to select function and time range.
The actual time delay is then set by using the potentiometer to adjust within the select-
ed time range. This product can literally replace hundreds of different catalog numbers,
thereby
reducing inventory requirements.
INPUT
VOLTAGE CATALOG WIRING/
FUNCTION OUTPUT 50/60Hz. NUMBER SOCKETS
Four or eight timing functions in
one unit easily selectable with 11 Pin 24-240V AC & TR-6812U 11 PIN OCTAL
ON DELAY DPDT 12-125V DC 70170-D
time delay relays | plug-in
rotary switch
INTERVAL ON
Each unit has 16 timing ranges OFF DELAY
built-in covering 0.05 seconds-100 SINGLE SHOT
hours FLASHER (ON 1st)
Selecting a range is easy using a SINGLE SHOT
16-position rotary switch (Falling Edge)
(no math is required or DIP WATCHDOG DIAGRAM 210
switches to set) ON DELAY (Triggered)
8 Pin 24-240V AC & TR-6816U 8 PIN OCTAL
Universal input voltage: 24-240V SPDT 12-125V DC 70169-D
AC & 12-125V DC
Utilizes industry-standard 8
or 11 pin octal sockets
10A SPDT or DPDT output
contacts can handle most pilot
DIAGRAM 211
duty and fractional HP loads
8 Pin 24-240V AC & TR-6822U 8 PIN OCTAL
ON DELAY DPDT 12-125V DC 70169-D
INTERVAL ON
FLASHER
(OFF 1st)
FLASHER
(ON 1st).
DIAGRAM 1
See “Definitions of Timing Functions”.
Timing Ranges
Select one of the 16 Dial Setting Timing Range Dial Setting Timing Range
built-in time ranges A 0.05 - 0.5 Sec. I 1 - 10 Min.
by setting the rotary B 0.1 - 1 Sec. J 3 - 30 Min.
switch per a chart on C 0.5 - 5 Sec. K 6 - 60 Min.
the unit (see right) D 1 - 10 Sec. L 0.2 - 2 Hr.
and then adjust within E 3 - 30 Sec. M 0.5 - 5 Hr.
F 6 - 60 Sec. N 1 - 10 Hr.
that range using the
G 0.2 - 2 Min. O 2.4 - 24 Hr.
knob on top. H 0.5 - 5 Min. P 10 - 100 Hr.
800.238.7474
www.macromatic.com Sockets & Accessories available
[email protected] Build your Time Delay Relays with the Online Product Builder
26
PROGRAMMABLE | MULTI-FUNCTION
TR-6 Series Time Ranger tm
t
N D 1
to select a function, each function can be selected M
L
E
F RANGE
4 2
5 Watchdog
with the same number in two positions. NOTE: K
J I H
G 3 3 FUNCTION
6 Single Shot
Function cannot be changed with power applied 2
1
4
to unit.
SEE CHART
7 Off Delay
t
FOR SETUP
P A B
O C 8 One Shot Falling Edge
t
ADJUST N D
Setting Time Delay and Time Range: To set the M E
Application Data
Voltage Tolerance: Temperature:
AC Operation: 20.4 – 264V at 50/60 Hz Operating: -28o to 65oC (-18o to 150oF)
DC Operation: 10.2 – 137.5V Storage: -40o to 85oC (-40o to 185oF)
Load (Burden): Functions Triggered By A Control Switch:
Maximum of 3 VA for all voltages Minimum required trigger switch closure time is 50ms.
Setting Accuracy: Compatibility:
Maximum Setting (Adjustable): +5%, -0% Using a solid state switch to initiate the time sequence is
Minimum Setting (Adjustable): +0%, -50% acceptable. See www.macromatic.com/leakage or contact
Macromatic for information regarding leakage current limits and
Repeat Accuracy (constant voltage and temperature):
other solid state design considerations.
+0.1% or +50ms, whichever is greater
Output Contacts:
Reset Time: 10A @ 240V AC/30V DC,
Functions Triggered with Input Voltage: 0.1 Seconds 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.)
Functions Triggered with Control Switch: 0.04 Seconds B300 & R300 (N.O.); AC15 & DC13
Start-up Time: (Time from when power is applied until unit is Life:
timing): 50ms Mechanical: 10,000,000 operations
Full Load: 100,000 operations
Maintain Function Time: (Time unit continues to operate after
power is removed): 0.01 Seconds Approvals:
File #E109466 Low Voltage &
EMC Directives
EN60947-1, EN60947-5-1
Dimensions
All Dimensions in
Inches (Millimeters)
hours
12-125V DC
Selecting a range is easy using a
rotary switch (no math is required
or DIP switches to set)
FLASHER 24-240V AC & TR-6082U
Universal input voltage: 24-240V (OFF 1st) 12-125V DC DIAGRAM 1
AC & 12-125V DC
Uses industry-standard 8 pin
octal sockets FLASHER 24-240V AC & TR-6092U
(ON 1st) 12-125V DC
10A DPDT output contacts can
handle most pilot duty & fractional
HP loads
See “Definitions of Timing Functions”.
Timing Ranges
Select one of the 16 built-in time ranges by setting the rotary switch per a chart on the
unit (see below) and then adjust within that range using the knob on top.
800.238.7474
www.macromatic.com Sockets & Accessories available
[email protected] Build your Time Delay Relays with the Online Product Builder
28
PROGRAMMABLE | MULTI-RANGE
OFF DELAY, TR-6
SINGLE SHOT & WATCHDOG
Series Time Ranger tm
The TR-6 Series offers the flexible programmability of a multi-range time delay
relay together with a universal input voltage. These products provide an easy
method to select one of 16 time ranges between 0.05 seconds and 100 hours
using a rotary switch. The actual time delay is then set by using the potentiometer
to adjust within the selected time range.
INPUT
CATALOG
FUNCTION VOLTAGE WIRING/SOCKETS
NUMBER
50/60Hz..
OFF DELAY 24-240V AC & TR-6162U 11 PIN OCTAL
Control Switch Trigger 12-125V DC 70170-D
Each unit has 16 timing ranges
built-in covering 0.05 seconds-100
SINGLE SHOT 24-240V AC & TR-6152U
hours
Timing Ranges
Select one of the 16 built-in time ranges by setting the rotary switch per a chart on
the unit (see below) and then adjust within that range using the knob on top.
29
PROGRAMMABLE | MULTI-RANGE
REPEAT CYCLE & DELAYED INTERVAL
TR-6 Series Time Ranger tm
The TR-6 Series offers the flexible programmability of a multi-range time delay
relay together with a universal input voltage. These products provide an easy
method to select one of 16 time ranges between 0.05 seconds and 100 hours
using a rotary switch. The actual time delay is then set by using the potentiometer
to adjust within the selected time range.
INPUT
VOLTAGE CATALOG WIRING/
FUNCTION 50/60Hz. NUMBER SOCKET
DIAGRAM 212
* These units have independently selectable & adjustable ON & OFF times. See
www.macromatic.com/onoff for more information.
See “Definitions of Timing Functions”.
Timing Ranges
Select one of the 16 built-in time ranges by setting the rotary switch per a chart on
the unit (see below) and then adjust within that range using the knob on top.
800.238.7474
O
P
2.4 - 24 Hr.
10 - 100 Hr.
www.macromatic.com Sockets & Accessories available
[email protected] Build your Time Delay Relays with the Online Product Builder
30
PROGRAMMABLE | MULTI-RANGE
TR-6 Series Time Ranger tm
Application Data
Voltage Tolerance: Triggering Off Delay, Single Shot or Watchdog Units:
AC Operation: 20.4 – 264V at 50/60 Hz Timing sequence must be initiated only after input voltage is
DC Operation: 10.2 – 137.5V applied to unit. Minimum required trigger switch closure time is
Load (Burden): 0.1 seconds.
Maximum of 3 VA for all voltages Compatibility:
Setting Accuracy: Using a solid state switch to initiate the time sequence is
Maximum Setting (Adjustable): +5%, -0% acceptable. See www.macromatic.com/leakage or contact
Minimum Setting (Adjustable): +0%, -50% Macromatic for information regarding leakage current limits and
other solid state design considerations.
Repeat Accuracy (constant voltage and temperature):
Output Contacts:
+0.1% or +50ms, whichever is greater
Temperature:
Operating: -28o to 65oC (-18o to 150oF)
Storage: -40o to 85oC (-40o to 185oF)
Dimensions
All Dimensions in
Inches (Millimeters)
The Macromatic TR-606 Series is a perfect product to use when a trigger switch is not
available in the circuit or when the application is to replace the functionality of a pneu-
matic time delay relay. These products come with 8 separate timing ranges covering
0.5 seconds – 30 minutes which are easy to select & setup with one rotary switch &
Each unit has 8 timing built-in potentiometer.
covering 0.05 seconds - 30 minutes
time delay relays | plug-in
DIAGRAM 1
See “Definitions of Timing Functions”.
Timing Ranges
Select one of the 8 built-in time ranges by setting the rotary switch per a chart on
the unit (see below) and adjust within that range using the knob on top:
Dial Timing
Setting Range
A 0.05 - 5 Sec.
B 0.1 - 10 Sec.
C 0.3 - 30 Sec.
D 0.6 - 60 Sec.
E 1.8 - 180 Sec.
F 3 - 300 Sec.
G 0.1 - 10 Min.
H 0.3 - 30 Min.
800.238.7474
www.macromatic.com Sockets & Accessories available
[email protected] Build your Time Delay Relays with the Online Product Builder
32
PROGRAMMABLE | MULTI-RANGE
TRUE OFF DELAY
TR-6 Series Time Ranger tm
Application Data
Voltage Tolerance: Output Contacts:
AC Operation: +10/-15% of nominal at 50/60 Hz DPDT 10A @ 240V AC; 8A @ 28V DC,
DC Operation: +10/-15% of nominal 1/2 HP @ 240V AC, 1/4HP @ 120V AC
B300 & R300
Load (Burden):
Maximum of 2 VA for all voltages. These products draw a brief Life:
inrush current on power-up of 1A to charge the internal circuitry. Mechanical: 2,000,000 operations
Full Load: 100,000 operations
Setting Accuracy:
Maximum Setting (Adjustable): +5%, -0% IMPORTANT: These relays are shipped from the factory in the
Minimum Setting (Adjustable): +0%, -50% OFF state. A shock to the relay during shipping or installation
may cause it to change to the ON state. It is recommended that
Repeat Accuracy (constant voltage and temperature): input voltage be applied to the product for at least 0.1 second
Temperature:
-28o to 65oC (-18o to 150oF)
Compatibility:
Using a solid state switch to initiate the time sequence is
acceptable. See www.macromatic.com/leakage or contact
Macromatic for information regarding leakage current limits and
other solid state design considerations.
Dimensions
All Dimensions in
Inches (Millimeters)
* These are the only functions requiring use of the Control Switch shown in Wiring
Diagrams below.
DIAGRAM 121
8 Pin 120V AC/DC TD-88162 8 PIN OCTAL
SPDT 12V DC TD-88166 70169-D
24V AC/DC TD-88168
240V AC TD-88161
DIAGRAM 169
800.238.7474 See “Definitions of Timing Functions”.
www.macromatic.com Sockets & Accessories available
[email protected] Build your Time Delay Relays with the Online Product Builder
34
PROGRAMMABLE | SINGLE FUNCTION
DIP-Switch | Digital-Set | TD-8 Series
The TD-8 Series time delay relays offer an easy and accurate method to select any
time delay between 100ms and 1,023 hours. Programming is accomplished through
the use of a 10-position DIP-switch. Each position is marked with a binary time
increment. The required delay is selected by moving the switch of each increment
to the ON position and adding their corresponding values (see examples below).
This method provides a greater setting accuracy than is found on other units with an
analog potentiometer. An LED indicates relay status.
INPUT
VOLTAGE CATALOG WIRING/
FUNCTION 50/60Hz. NUMBER ** SOCKETS
ON DELAY 120V AC/DC TD-80222-** Single Mode Dual Mode
12V DC TD-80226-** DIP-Switches for accurate
24V AC/DC TD-80228-** 8 PIN OCTAL digital set of time delay
DIAGRAM 2
See “Definitions of Timing Functions”.
* ON & OFF Time Ranges for these functions are the same. See
www.macromatic.com/onoff for information on how to order a unit with different ON &
OFF time ranges.
Time Delays
**TIMING RANGE TABLE
COMPLETE PRODUCT NUMBER
USING TWO DIGIT CODE BELOW:
i.e., TD-80222-40
800.238.7474
Sockets & Accessories available www.macromatic.com
Build your Time Delay Relays with the Online Product Builder [email protected]
35
ME BASE
FUNCTIONS
N ON ON
N OFF ON
N ON OFF
N ON ON
N OFF OFF
N OFF ON
N ON OFF
N OFF OFF
F OFF ON
F ON OFF
F OFF ON
F ON OFF
F ON ON
F OFF OFF
F OFF OFF
F ON ON
J K
F G
TD-8 SERIES
DIP-Switch | Digital-Set
MODE (t)
SINGLE
MODE
DUAL
ON OFF ON
used to select a function (see the descriptions of how each function A- -1 1
FUNCTION
1ST DELAY
operates in “Definition of Timing Functions” in this catalog). Switch- B-
C-
-2
-4
2
t1 4
TIME BASE
2ND DELAY
G- - 64 2
H- - 128 t2 4
Switches H, J & K are used to select the time base (t2) for dual J -
K-
- 256
- 512 16
8
mode functions. A convenient chart is on the side of the product to SEE CHART ON SIDE COMBINE FOR
clearly illustrate how to set both the function and time base.
FOR FUNCTION & TOTAL TIME
TIME BASE SETUP
time delay relays | plug-in
2.4 (60)
All Dimensions in
Inches (Millimeters)
2.9
(74)
1.7 3.0
(43) (76)
The TD-781 Series offers an easy and accurate way to select a function and any
time delay between 50ms and 999 hours. Programming is accomplished by using
a pushbutton thumbwheel to select one of seven built-in time ranges and three
pushbutton thumbwheels to digitally set the time delay required. This method
provides a greater setting accuracy than is found on other units with an analog
potentiometer. These units have a fifth pushbutton thumbwheel to select one of
ten built-in functions. An LED indicates timing mode and time out condition.
Multi-Function Product
Ten user-selectable modes in
INPUT CATALOG WIRING/ one unit
800.238.7474
www.macromatic.com
Build your Time Delay Relays with the Online Product Builder [email protected]
37
PROGRAMMABLE | MULTI-RANGE
Digital-Set | TD-7 Series Time Rangertm
The TD-7 series of time delay relays offer an easy and accurate way to select any
time delay between 50ms and 999 hours. Programming is accomplished by using
a pushbutton thumbwheel to select one of seven built-in time ranges and three
pushbutton thumbwheels to digitally set the time delay required. This method
provides a greater setting accuracy than is found on other units with an analog
potentiometer. An LED indicates timing mode and time out condition.
800.238.7474
www.macromatic.com
[email protected] Build your Time Delay Relays with the Online Product Builder
38
TD-7 SERIES TIME RANGERTM
Application Data
Voltage Tolerance: Output Contacts:
AC Operation: +10/-15% of nominal at 50/60 Hz. DPDT 10A @ 240V AC/30V DC,
DC Operation: +10/-15% of nominal. 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.)
B300 & R300; AC15 & DC13
Load (Burden):
3 VA Life:
Mechanical: 10,000,000 operations
Setting Accuracy:
Full Load: 100,000 operations
Constant Voltage & Temperature w/i specifications:
+0.1% of set time or +50ms, whichever is greater Compatibility:
For Variable Voltage & Temperature w/i specifications: Using a solid state switch to initiate the time sequence is
+1% of set time or +50ms, whichever is greater acceptable. See www.macromatic.com/leakage or contact
Macromatic for information regarding leakage current limits and
Dimensions
2.4
(60)
2.9
(74)
1.7 3.0
(43) (77)
All Dimensions in
Inches (Millimeters)
40
DEFINITION OF TIMING FUNCTIONS
Digital-Set | TAD Series
DIAGRAM 171
Includes Six (6) Functions 100-240V AC TAA2U SEE DIAGRAMS
Built-in (See “Definitions of 50/60Hz NEXT PAGE
Timing Functions”.)
& 24-240V DC 11 Pin Octal
6 field-selectable functions in
one unit
See “Definitions of Timing Functions”.
Large dial for setting of time See below for Sockets & Accessories.
delay
Application Data
50ms to 100 Hours Voltage Tolerance: LED Indicators: One red LED indicates
programmable timing range +10% of rated voltage. Input Voltage/Timing (flashing) & a sec-
ond red LED indicates relay status.
Load (Burden):
Universal 100-240V AC/ 24-
Less than 2.5 VA Output Contacts:
240V DC input voltage
5A DPDT Resistive @ 250V AC
Repeat Accuracy:
Panel, track or surface mounting +0.01%, +0.05 seconds (includes variation Enclosure Protection Rating:
due to voltage and temperature changes). IP40 (front face)
1/16 DIN style case (comes with
panel-mounting adapter) Recycle Time: Life:
0.2 seconds maximum. Mechanical: 10,000,000 operations
Temperature: Full Load: 100,000 operations
Operating: -10o to 55oC (14o to 131oF) Approvals:
Storage: -40o to 85oC (-40o to 185oF)
File #E170213
Sockets & Accessories
PRODUCT
DESCRIPTION NUMBER
8 Pin Octal Socket 70169-Dv
8 Pin Octal Socket (Back Mounting) OR08-PC OR08-PC
11 Pin Octal Socket 70170-Dv
11 Pin Octal Socket (Back Mounting) SR6P-M11G
Panel-Mounting Adaptor Included
v For Surface or Track Mounting-See Sockets & SR6P-M11G
Accessories for additional information
Dimensions PANEL CUTOUT
42
DEFINITION OF TIMING FUNCTIONS
Analog-Set | TAA Series
Universal Input Voltage: Operating Range -15% of 12V, +10% of 240V -15% of 12V, +10% of 240V
12-240V AC/DC Burden 3VA (AC), 1.7W (DC) 3VA (AC), 1.7W (DC)
0.1 second - 10 days Output
programmable time delay Configuration SPDT DPDT
15A SPDT or DPDT output Rating 15A @ 240V AC
contacts 1/3HP @ 120V AC, 3/4HP @ 240V AC, B300
Minimum Switching 100mA @ 5V AC or 5V DC
LEDs indicate output relay
status & timing mode Contact Material Silver Alloy
Life 10 million operations mechanical; 70,000 electrical
Compact 17.5mm enclosure
mounts on 35mm DIN track Timing
Number of Functions 10 (see descriptions on Page 44)
Pilot duty rating
Time Ranges 8 different time ranges built-in:
100 ms - 1 Sec. 0.1 - 1 Hr.
1 - 10 Sec. 1 - 10 Hr.
0.1 - 1 Min. 0.1 - 1 Day
1 - 10 Min. 1 - 10 Days
Repeat Accuracy +0.2%
Setting Accuracy 5%
Reset Time 150ms maximum
Trigger Pulse Length 50ms maximum
Other
Mounting 35mm DIN Rail only
800.238.7474
www.macromatic.com
[email protected]
REPEAT CYCLE *
ON DELAY A F
(ON 1ST)
PULSE
REPEAT CYCLE
B GENERATOR G
* (OFF 1ST)
(PULSE=0.5 SEC)
t i m e d e l a y r e l a y s | 1 7. 5 m m
INTERVAL C ONE SHOT H
RETRIGGERABLE
MEMORY LATCH
ONE SHOT E J
(Latching Relay)
(Watchdog)
TE-8816U TE-8812U
SPDT DPDT
All Dimensions in
Inches (Millimeters)
12 in-lbs
Catalog Number:
70169-D
12 in-lbs
Catalog Number:
70170-D
10A @ 300V
Pressure Wire Clamp Terminations
Recommended Tightening Torque
7 in-lbs
Catalog Number:
File #E60008
OR08-PC
10A @ 300V
Pressure Wire Clamp Terminations
Recommended Tightening Torque
7 in-lbs
Catalog Number:
File #E60008
SR6P-M11G
Panel-Mounted Sockets
Sockets Mounted to 35mm DIN Rail *
Typically, time delay relays are initiated or triggered by one of two methods, depending on the function:
application of input voltage
application of a trigger
time delay relays | definition of timing functions
These triggers can be one of two signals: a control switch (dry contact), i.e., limit switch, push button, float switch, etc., or volt-
age (commonly known as a power trigger).
CAUTION: any time delay relay that is designed to be initiated with a dry contact control switch trigger could be dam-
aged if voltage is applied to the trigger switch terminals. Only products that have a “power trigger” should be used
with voltage as the trigger.
Below and on the following pages are both written and visual descriptions on how the common timing functions operate. A Tim-
ing Chart shows the relationship between Input Voltage, Trigger (if present) and Output. If you cannot find a product to fit your
requirements or have any questions, Macromatic’s Application Engineers offer technical information along with product selection
and application assistance. Call us at 800-238-7474 or e-mail us [email protected].
OFF DELAY Upon application of input voltage, the time delay relay
Delay on is ready to accept a trigger. When the trigger is applied,
Release the output is energized. Upon removal of the trigger, the
time delay (t) begins. At the end of the time delay (t),
Delay on Break
the output is de-energized. Any application of the trigger
Delay on during the time delay will reset the time delay (t) and the
De-Energization output remains energized.
SINGLE SHOT Upon application of input voltage, the time delay relay
One Shot is ready to accept a trigger. When the trigger is applied,
Momentary the output is energized and the time delay (t) begins.
During the time delay (t), the trigger is ignored. At the
Interval
end of the time delay (t), the output is de-energized and
the time delay relay is ready to accept another trigger.
ON/OFF DELAY Upon application of input voltage, the time delay relay
is ready to accept a trigger. When the trigger is applied,
the time delay (t1) begins. At the end of the time delay
(t1), the output is energized. When the trigger is re-
moved, the output contacts remain energized for the time
delay (t2). At the end of the time delay (t2), the output is
de-energized & the time delay relay is ready to accept
another trigger. If the trigger is removed during time
delay period (t1), the output will remain de-energized and
time delay (t1) will reset. If the trigger is reapplied during
time delay period (t2), the output will remain energized
and the time delay (t2) will reset.
Specifications subject to change without notice | Macromatic and Time Ranger are registered tradenames of Macromatic Industrial Controls, Inc.