Transformer Protection 22-10-2020
Transformer Protection 22-10-2020
INCIPIENT FAULTS :
Incipient faults are one among the internal faults of power transformers. They are slowly occurring
uncommon faults in an electrical transformer. They are not serious at the beginning but they
gradually develop into severe faults and eventually longer outages. The incipient faults in
transformers are due to the following reasons.
Contamination of the insulating oil in the transformer.
Core bolt insulation failure.
Rust or other materials on the core.
Short circuits in the core lamination.
Moisture content in the insulating oil.
Common faults in transformer are:
(1) Inter turn fault.
(2) Insulation failure between HV winding and LV winding.
(3) Insulation failure between HV winding and earth.
(4) Insulation failure between LV winding and earth.
(5) Insulation failure of other winding, if any, e.g. tertiary winding.
(6) Bushing failure.
Major causes of faults in the transformer are:
1. Insulation Breakdown
2. Over heating due to over excitation/over flux
3. Fault due to deterioration in oil quality or loss of oil
4. Fault due to excessive temperature rise due to reduced /loss of cooling.
5. Transformer Overload.
6. System over voltages or surges due to lightning /switching.
7. External Fault Persist.
Insulation Breakdown:
The major reasons for the insulation breakdown are, ageing of insulation, Partial
discharges in the insulation, Transient over voltages due to lightning or switching in the
network, Current forces on the windings due to external faults with high current.
Insulation Breakdown of the windings will cause short circuits and /or earth faults. These
faults cause severe damaging on the windings and the transformer core.
Overheating:
The overexcited transformer flux is forced through metal tank and other un-laminated parts of the
transformer and result in heating up.
Phase to phase faults:
Short circuits between the phases will give rise to substantial fault current only limited by the source
impedance and the leakage impedance of the transformer.
Phase to ground faults:
When the fault current flows through earth return path, the fault is called ground fault.
Turn-to-turn or Inter Turn Faults:
Turn to turn faults between a few turns is difficult to detect by current measuring relays. Fault current
is of the order of rated current when 2 to 4% of the turns are short circuited. The current in the short
circuited loop is high (50-100 times In) and causes local damage and release of gas. Therefore rate of
rise of pressure relay may detect this fault.
Type 1(Self protection): Base on non-electrical Measurement Like Temperature, Pressure, Gas,
Oil Force.
1. PRD
2. Buchholz
3. WTT
4. OTT
Type 2: Base on Electrical Measurement Like Current, Voltage and Frequency.
1. Differential Protection.