PROJECT:
PANEL NAME: PP-FIRE PUMP VOLT
LOCATI0N:
TOTAL
COMPUTATION:
Page 1 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
CB RATING: = 30 X 4.5 = 360 A
%V = 3.24
230
%V = 1.41 IF ≤ = 2
USE: 38 0THWmm²
FOR SERVICE WIRE:
USE: 38 0 mm² THW
FOR GROUND WIRE:
SEE ARTICLE 2.50 . MINIMUM SIZE OF EQUIPMENT GROUND TAB
USE : 1- 30 SQ. MM TW
FOR CONDUIT SIZING:
SEE APPENDIX C, TABLE C.4 PEC 1, 2017 PAGE 985
USE: 50
For Reference:
Page 2 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
e (V) = Voltage Drop, (volts)
% VD = Voltage Drop, (%)
L = Single Length of Conductor, (meters)
I = Current, (amperes)
S = Single Conductor Cross Section multiplied
V = System Voltage, (volts)
(1) The conductors being protected are not part of the multioutlet branch
supplying receptacles for cord-and plug-connected portable loads.
(2) The ampacity of the conductors does not correspond with the standa
of a fuse or a circuit breaker without overload trip adjustments abov
(but that shall be permitted to have other trip or rating adjustments).
(3) The next higher standard rating selected does not exceed 800 amper
Page 3 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
AGE DROP
System RATING
Voltage % Full Load
(V) k kVA CN 3ø
Multiplier
Pole
Current
W
230 31.87 31.87 4.5 3 80
0.00 0.00
0.00 0.00
0.00
0.00
0.00
0.00
0.00
31.87 ### 31.87
31.87
Phase 3
System Voltage
100.00(V) 230
Transformer
31.87
(kVA)
80
Page 4 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
ING TABLE 3.10.2.6
LCULATION:
17.8 x L x I
1000 x S
Page 5 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
meters)
mpacity of the
of the overcurrent
Page 6 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
ING GROUND WIRE
MCCB Rating AT AF mm² Type
360 350 400 30 TW
MAIN PROTEC
MAIN FEEDER
Page 7 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
Page 8 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
Page 9 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
CA
CONDUIT
Full Load
PF DF K L
mmØ Type Current
50 IMC 1 1 30.8 60 80
Page 10 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
Page 11 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
Page 12 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
CABLE AMPACITY
System
SERVICE WIRE PERMITTED
Voltage
CV %
Rating Number mm² Type
Multiplier
1000 1.25 100 38 THW 230 2%
MCB
THW FIRE RATED TYPE
in 50 mmØ IMC
Page 13 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
Page 14 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
Page 15 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
PERMITTED VD VOLTAGE DROP REMARKS
% Voltage
e(V) %V
Allowable Drop
4.6 3.11 1.35% OK
Page 16 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
Page 17 file:///conversion/tmp/activity_task_scratch/538399887.xlsx
Page 18 file:///conversion/tmp/activity_task_scratch/538399887.xlsx