Load Calculation 10

This document provides design analysis for two motor-compressor branch circuits for a project in Taganito, Surigao del Norte, Philippines. For Circuit 1 serving a 20-ton capacity, it specifies using 30.0mm2 THHN cable based on current and voltage drop calculations. For Circuit 2 serving a 4-ton capacity, it specifies using 5.5mm2 THHN cable. Both circuits specify conduit and ground wire sizes based on Philippine Electrical Code tables. Voltage drops were calculated to be within the allowable 3% limit.

Uploaded by

Royce Palada
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
301 views8 pages

Load Calculation 10

This document provides design analysis for two motor-compressor branch circuits for a project in Taganito, Surigao del Norte, Philippines. For Circuit 1 serving a 20-ton capacity, it specifies using 30.0mm2 THHN cable based on current and voltage drop calculations. For Circuit 2 serving a 4-ton capacity, it specifies using 5.5mm2 THHN cable. Both circuits specify conduit and ground wire sizes based on Philippine Electrical Code tables. Voltage drops were calculated to be within the allowable 3% limit.

Uploaded by

Royce Palada
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 8

TAGANITO HPAL PROJECT

TAGANITO, SURIGAO DEL NORTE

4- DESIGN ANALYSIS FOR Motor -Compressor Branch Circuits

A. Circuit No. 1
Capacity = 20 Tons Where : (As Per Carrier Specification)
Name PlateVoltage = 220V 1 Ton = 1,290 Watts
System Voltage 230V
Phase = 3P (3W+E) Therefore:
P. F. = 0.95 = 20 Ton x 1290 W /
= 25.80 kW
Capacity in kVA = 27.16 kVA
CALCULATED CURRENT:
= 27.16 kVA X 1000
1.732 X 230 V
FLC = 68.17 A

CB SETTING: = 68.17 X 1.75 = 119.30 A (Section 4.30.3.2 )


USE INDUSTRY STANDARD 125 AT 3P Article 2.40. Table 2.40.1.6 (A)
INVERSE TIME BREAKER 225 AF MCCB Standard Ampere ratings of Fuses and
Inverse Time Circuit Breakers.
CABLE SIZE SETTING : Branch Circuit Conductors (Section 4.30.2.PEC 1 2017 page 347)

CABLE AMPACITY : 68.17 X 1.25 = 85.2 A ≤ 55.0 A


1 SET/S 3- 8.0 mm² THHN
Refer to Article 3.10 Conductors for General Wiring, Table 3.10.2.6 (B)(16) PEC 1 2017 page 170

VOLTAGE DROP CALCULATION:


* Allowable Voltage Drop for Motor Circuit, from Panel to Motor is 3% that

VD = 30.8 X 71.96 X 60 LM
= 4.43 Volts
1000 X 30.0 X 1 SET/S
%VD = 4.43 Volts
230 Volts
%VD = 1.93 > 3.0% Article 2.10-Branch Circuits ,Section 2.10.2.2 (A) FPN N0. 4
USE: 1 SET/S 3- 30.0 mm² THHN

FOR SERVICE WIRE:


USE: 1 SET/S 3- 30.0 mm² THHN
Refer to Article 3.10 Conductors for General Wiring, Table 3.10.2.6 (B)(16) PEC 1 2017 page 170

FOR GROUND WIRE:


USE: 1- 5.5 mm² TW

Refer to Article 2.50. Minimum Size Equipment Ground


Table 2.50.6.13 PEC 1 2017 page 124
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE

FOR CONDUIT SIZING:

USE: 1- 30.0 mmØ IMC

Refer to Appendix C, Table C.4 PEC 1, 2017 page 986.


Maximum Number of Conductors in Intermediate Metallic Conduit

B. Circuit No. 2
Capacity = 4 Tons Where : (As Per Carrier Specification)
Voltage = 220V 1 Ton = 1,290 Watts
Phase = 3P (3W+E) Therefore:
P. F. = 0.80 = 4 Ton x 1290 W /
= 5.16 kW
Capacity in KVA = 6.45 kVA
CALCULATED CURRENT:
= 6.45 kVA X 1000
1.732 X 230 V
FLC = 16.19 A

CB SETTING: = 16.19 X 1.75 = 28.33 A


(inverse Time) USE: 30 AT 3P (Section 4.30.3.2 and Table 4.30.1
50 AF MCCB Article 2.40. Table 2.40.1.6 (A)
CABLE SIZE SETTING: Branch Circuit Conductors (Section 4.30.2.PEC 1, page 347)

16.19 X 1.25 = 20.2 A THHN


CABLE SIZE AMPACITY: 1 SET/S 3- 5.5 mm²
Refer to Article 3.10 Conductors for General Wiring, Table 3.10.2.6 (B)(16) PEC 1 2017 page 170

VOLTAGE DROP CALCULATION:


* Allowable Voltage Drop for Motor Circuit, from Panel to Motor is 3% that

= 6.35 Volts
VD = 30.8 X 16.19 X 70 LM
1000 X 5.5 X 1 SET/S
%VD = 6.35 Volts
230 Volts
%VD = 2.76 ≤ 3 % THHN Article 2.10-Branch Circuits Section 2.10.2.2 (A) FPN N
USE: 1 SET/S 3- 5.5 mm²

FOR SERVICE WIRE: THHN


USE: 1 SET/S 3- 5.5 mm²
Refer to Article 3.10 Conductors for General Wiring, Table 3.10.2.6 (B)(16) PEC 1 2017 page 170

FOR GROUND WIRE:


USE: 1- 3.5 mm² TW
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE

Refer to Article 2.50. Minimum Size Equipment Ground


Table 2.50.6.13 PEC 1 2017 page 124
FOR CONDUIT SIZING:
USE: 1- 16.0 mmØ IMC

Refer to Appendix C, Table C.4 PEC 1, 2017 page 986.


Maximum Number of Conductors in Intermediate Metallic Conduit
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE

Check P.E.C. Table Appendix C-Conduit & Tubing Fill Table :


USE: 1- 80.0 mmØ EMT
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE

1000

Volts
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE

1000

Volts

Article 2.10-Branch Circuits Section 2.10.2.2 (A) FPN N0. 4


TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE