Air-Cooled Screw Chillers: Installation, Operation and Maintenance Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 48

Installation, Operation and Maintenance Manual

D – 510 C – 07/02 E – EN

Air-cooled screw chillers


EWAD 650-C18BJYNN
EWAD 550-C12BJYNN/Q
EWAD 650-C21BJYNN/A
EWAD 600-C10BJYNN/Z

50Hz – Refrigerant: R-134a

D – 510 C – 07/02 E – EN pag. 1/48


D – 510 C – 07/02 E – EN pag. 2/48
Introduction
General description
Each unit is completely assembled, wired, evacuated, charged, tested, and ready for installation. The main
components are air-cooled condensers with integral sub-cooler sections, accessible semi-hermetic single-screw
compressors, shell-and-tube evaporators, shell-and-tube water heat recovery condensers (optional), oil
separators, complete refrigerant piping and electrical panel (including control and power sections). Liquid line
components are shut-off valves, charging valves, filter-dryers, sight-glass/moisture indicators, electronic expansion
valves, liquid receivers (only with total heat recovery option). Other features are compressor heaters, evaporator
heater for low ambient water freeze protection, automatic pump-down during circuit shutdown and fully integrated
microprocessor control system.
The chiller uses R134a refrigerant and operates at positive pressures.

Purpose of the manual


The manual allows the installer and the operator to perform correctly all the required operations for unit installation
and maintenance without causing any damage to the chiller or injuries to qualified personnel.

Nomenclature
EWA D 600 BJ YN N **** /Z
Machine type
ERA: Air-cooled condensing unit
EWW: Water cooled packaged water chiller
EWL: Remote condenser water chiller
EWA: Air-cooled chiller, cooling only
EWY: Air-cooled chiller, heatpump
EWC: Air-cooled chiller, cooling only with centrifugal fan
EWT: Air-cooled chiller, cooling only with heat recovery

Refrigerant
D: R-134a
P: R-407C
Q: R-410A

Capacity class in kW (cooling)


Always 3-digit code
Cap < 50 kW: not round: example: 37 kW => 037
50 < Cap < 999 kW: round 0/5: 536 kW => 535
Cap > 999 kW use C-symbol (C=100): example: 2578 kW => C26

Model series
first character : letter A, B,…: major modification
second character : letter A,B,... : minor modification DENV
letter J-W… : minor modification New Series

Voltage
V1: ~ / 220 - 240 V / 50 Hz
V3: 1~ / 230 V / 50 Hz
T1: 3~ / 230 V / 50 Hz
W1: 3N~ / 400 V / 50 Hz
Y1: 3~ / 380-415 V / 50 Hz
YN: 3~ / 400 V / 50 Hz

Hydraulic module/Heat recovery version/Pump & electrical


options (Consult Selection software)
N: No Hydraulic components
M: Modular
A-V: Combination of specific options

Option code (Consult Selection software)


****: 4 digits

Option regarding efficiency version, sound version


/H: High ambient version
/A: High efficiency version
/Q: Extra low noise version
/Z: High efficiency and Extra low noise version

D – 510 C – 07/02 E – EN pag. 3/48


WARNING
This manual provides information about the features and standard procedure for the complete series.

All units are delivered from the factory complete with wiring diagrams and dimensional drawings including size and
weight for each model.

WIRING DIAGRAMS AND DIMENSIONAL DRAWINGS MUST BE CONSIDERED


ESSENTIAL DOCUMENTS OF THIS MANUAL

In case of any discrepancy between this manual and the equipment’s document please refer to the wiring diagram and
dimensional drawings.

Installation
Receiving and handling
The unit should be inspected immediately after receipt for possible damage.
All items on the bill of lading should be carefully checked to ensure a complete shipment. The unit should be
carefully checked and shipping damages should be reported to the carrier. The unit serial plate should be checked
before unloading the unit to ensure that it agrees with the power supply available. Physical damage to the unit
after acceptance is not DAIKIN’s responsibility.

Responsibilities
DAIKIN declines all present and future responsibilities referred to injuries to people and damages to things and to
the unit, caused by operator' s negligence, failure to respect installation/maintenance data from this manual, failure
to respect the current regulations regarding the safety of both the equipment and qualified personnel in charge of
the installation and the maintenance.

Servicing and maintenance personnel


Experienced personnel with specific training in refrigeration must carry out servicing and maintenance of the unit.
Regular checking of safety devices should be carried out, but routine maintenance should be carried out in line
with the recommendation list in the main section.
The simple design of the refrigeration circuit minimises potential problems during normal unit operation.

Safety
The unit must be suitably clamped to the ground.
It is necessary to follow these cautions and warnings.
- Lift the unit only using the proper tools that are able to support the weight of the unit fixed in the base frame on
the yellow holes.
- No admittance to unauthorised or unqualified personnel should be allowed.
- No operation on the electrical components is allowed without having switched off the power supply.
- No operation on the electrical components is allowed without using insulated platforms; no water or moisture
should be present.
- All operations on the refrigerant circuit and pressurised components are to be performed by qualified personnel
only.
- Replacing the compressor or adding oil may only be performed by qualified personnel.
- Sharp edges and coil surface are potential injury hazards. Avoid contact with them.
- Disconnect all electrical power supply to the unit while servicing the condenser fan motors. Failure to observe this
rule may cause bodily injuries.
- Avoid contamination with foreign bodies in the water piping when connecting the unit to the water system.
- Fit a mechanical filter to the piping connected to the evaporator inlet.
- The unit is equipped with safety relief valves installed on both high and low pressure side of the refrigerant
circuit.

D – 510 C – 07/02 E – EN pag. 4/48


Warning
Check the instructions for use before operating the unit.
Installation and maintenance must be performed only by qualified personnel with the required knowledge about
chillers, local codes and regulations. Unit installation must be avoided in areas that could be considered
dangerous for maintenance operations.

Transport
For transport in containers, the optional container kit is available on request, for preventing damage and to
facilitate the sliding of the chiller into the container during push-in and pull-out operations.
The kit includes:
- base frame bracing plus two lifting rings fixed on it;
- wood planks fixed below the unit base frame.
The additional lifting rings are on the same side of the control panel, therefore the chiller has to be loaded into the
container with the control panel on the container doors’ side.

Handling and lifting


Care should be taken to avoid rough handling or shocks due to the unit being dropped. Do not push or pull the unit
from anything else than the base, and block the pushing vehicle away from the unit to prevent damage to the
sheet metal cabinet and end frame.
Never allow any part of the unit to fall during unloading or moving as this may result in serious damage.
To lift the unit, suitable holes are provided in the unit base, and spreader bars and cables should be used to
prevent damage to the condenser coils or to the cabinet.

Suggested lifting arrangement for units with 2 compressors

Use spreader bars to avoid


damage to the unit

Suggested lifting arrangement for units with 3 & 4 compressors


D – 510 C – 07/02 E – EN pag. 5/48
Location
These units are produced for outdoor installation on roof floors or below ground level on the condition that the the
condenser air flow is not obstructed. The unit should be positioned on a solid foundation and perfectly leveled; in
case of installation on roofs or floors, it may be advisable to arrange the use of suitable weight distribution beams.
When the unit is installed on the ground, a concrete base, at least 250 mm wider and longer than the unit’s
footprint, should be laid. Furthermore, this base should withstand the unit weight mentioned in the technical data
table. When the unit is positioned in an area that is easily accessible by persons or animals, it is advisable to fit
guards for the condenser coil and, when necessary, guards for the evaporator area.
To obtain the best performance in the installation location, make sure the following requirements are met:
− Avoid a short airflow re-circulation.
− Ensure that obstacles do not obstruct proper airflow.
− To reduce noise and vibration, a stiff floor is required.
− Avoid a dusty environment in order to keep the condenser clean.
− Chiller water must be quite clean; oil traces and rust particles must be removed. Fit a water filter on the water
inlet pipes.

Space requirements
Since these units are air-cooled, it is important to ensure sufficient airflow across the condenser coils.
Two conditions must be avoided to achieve best performance: warm air re-circulation and coil starvation.
Both these conditions cause an increase in the condensing pressure, which reduces unit efficiency and capacity.
Each side of the unit must be accessible after installation for periodic service. Figure 3 shows the minimum
clearance requirements.
Vertical condenser air discharge must be unobstructed, because otherwise the unit efficiency and capacity would
be significantly reduced.
If the unit is positioned in a location surrounded by walls or obstacles of the same height as the unit, the unit
should be at least 2500 mm from any obstacle (figure 4). If the obstacles are higher than the unit, the unit should
be at least 3000 mm from the obstacles (figure 5). Units installed closer than the minimum recommended distance
to walls or other vertical risers may experience a combination of coil starvation and warm air re-circulation, thus
causing reduced unit capacity and efficiency.
When two or more units are positioned side by side it is recommended that the condenser coils of each unit be at
least at 3600 mm apart (figure 6).
For different installation solutions, consult DAIKIN technicians.

Picture 3 Picture 4

Picture 5 Picture 6

D – 510 C – 07/02 E – EN pag. 6/48


Acoustic protection
When the noise level must meet special requirements, it will be necessary to pay the maximum attention to ensure
perfect insulation of the unit from the support base by applying appropriate vibration-dampening devices, applying
vibration-dampening mounts on the water pipes and on the electrical connections.

Water piping
Due to the variety of piping practices, it is advisable to follow the recommendations of local authorities. They can
supply the installer with the proper building and safety codes required for a safe and proper installation.
Basically, the piping should be designed with a minimum number of bends and changes in elevation to keep
system cost down and performance up. It should contain:
1. Vibration eliminators to reduce vibration and noise transmission to the building.
2. Shutoff valves to isolate the unit from the piping system during unit servicing.
3. Manual or automatic air vent valves at the higher points of the system. Drains at the lower points of the
system. The evaporator and heat recovery condensers should not be the highest point in the piping system.
4. Devices to maintain adequate system water pressure (e.g. expansion tank or regulating valve).
5. Water temperature and pressure indicators located at the unit to aid in unit servicing.
6. A strainer or devices to remove foreign matter from the water before it enters the pump. The strainer should
be placed far enough upstream to prevent cavitations at the pump inlet (consult pump manufacturer for
recommendations). The use of a strainer will prolong pump life and help maintain high system performance
levels.
7. A strainer should be placed in the supply water line just prior to the inlet of the evaporator and heat recovery
condensers. This will aid in preventing foreign material from entering and decreasing the performance of the
heat exchangers.
8. The shell-and-tube evaporator has a thermostat and an electric heater to prevent freeze-up down to -28°C.
Any water piping to the unit must be protected to prevent freezing.
9. The shell-and-tube heat recovery condensers must be empty of water during the winter season, unless you fill
the water circuit with ethylene glycol.
10. If the unit is used as a replacement chiller on a previously existing piping system, the system should be
thoroughly flushed prior to unit installation and then regular chilled water analysis and chemical water
treatment is recommended immediately at equipment start-up.
11. In the event glycol is added to the water system, as an afterthought for freeze protection, recognize that the
refrigerant suction pressure will be lower, cooling performance less, and water side pressure drop greater.
System safety devices such as freeze protection and low pressure protection must be reset.

Prior to insulating the piping and filling the system, a preliminary leak check should be made.

Evaporator/Heat Recovery condenser freeze protection


All evaporators are equipped with a thermostatically controlled electric heater that provides freeze protection down
to -28°C. However, this should not be the only method of freeze protection. Unless the evaporator and heat
recovery condensers are flushed and drained as is described below in note 4, two or more of the remaining three
recommendations must be followed as part of the system design:
1. Continuous circulation of water through the piping and the heat exchanger.
2. Filling of glycol solution in the chilled water circuit.
3. Additional insulation and heating of the exposed piping.
4. Draining and flushing the chiller vessel with air during winter season.
It is the responsibility of the installing contractor and/or on-site maintenance personnel to ensure that this
additional protection is provided. Routine checks should be made to ensure adequate freeze protection is
maintained.
Failure to do so may result in damage to unit components. Freeze damage is not considered a warranty failure.

D – 510 C – 07/02 E – EN pag. 7/48


Flow switch
A water flow switch must be mounted in either the entering or leaving water line to insure adequate water flow
through the evaporator before starting the unit. This will safeguard against slugging the compressors on start-up. It
serves to shut down the unit in the event that water flow is interrupted to protect against evaporator freeze-up.
Whenever the unit is equipped with the heat recovery condensers a water flow switch must be mounted in either
the entering or leaving water line to ensure adequate water flow before switching the unit in “Heat recovery mode”.
It prevents the unit from shutting down due to high condensing pressure.
A flow switch is available from DAIKIN; this is a "paddle" type switch which may be adapted to any pipe size from
5" (127 mm) to 8" (203 mm) nominal.
Certain minimum flow rates are required to close the switch (Table 1).

Flow direction marked on switch

NPT flow switch connection

Tee

NOMINAL PIPE MINIMUM REQUIRED FLOW


SIZE INCHES (MM) TO ACTIVATE SWITCH –
LITERS PER SECONDS
5 (127) 3.7
6 (152) 5.0
8 (203) 8.8
Table 1

Table 2 – Operating limits – EWAD-BJYNN - EWAD-BJYNN/Q


EWAD-BJYNN EWAD-BJYNN
Unit version BJYNN with Option with Option BJYNN/Q
OPRN OPLN
Max ambient temperature °C +44 +40 +40 +40 (1)
Min ambient temperature °C +10 (2) +10 (2) +10 (2) -10 (3)
Max leaving evaporator water temperature °C +9 +9 +9 +9
Min leaving evap. water temp. (without glycol) °C +4 +4 +4 +4
Min leaving evap. water temp. (with glycol) °C -8 -8 -8 -8
Max evaporator ∆T °C 8 8 8 8
Min evaporator ∆T °C 4 4 4 4
Notes:
(1) When the air temperature is higher than +32°C fan speed control device (OPFS) (standard on BJYNN/Q units) sets
up speed rotation increasing cooling capacity and sound pressure level.
(2) When the air temperature is lower than +10°C you need the fan speed control device (OPFS). It allows the unit to
operate with air temperature down to –10°C. Low ambient operation (OPLA) allows to reach –18°C.
(3) Fan speed control device (OPFS)is standard furnished on the BJYNN/Q units.

Table 3 – Operating limits – EWAD-BJYNN/A - EWAD-BJYNN/Z


EWAD- EWAD-
BJYNN/A BJYNN/A
Unit version BJYNN/A with Option with Option BJYNN/Z
OPLN OPRN
Max ambient temperature °C +48 +44 +44 +40
Min ambient temperature °C +10 (2) +10 (2) +10 (2) -10 (3)
Max leaving evaporator water temperature °C +9 +9 +9 +9
Min leaving evap. water temp. (without glycol) °C +4 +4 +4 +4
Min leaving evap. water temp. (with glycol) °C -8 -8 -8 -8
Max evaporator ∆T °C 8 8 8 8
Min evaporator ∆T °C 4 4 4 4
Notes:
(2) When the air temperature is lower than +10°C you need the fan speed control device(OPFS). It allows the unit to
operate with air temperature down to –10°C. Low ambient operation (OPLA) allows to reach –18°C.
(3) Fan speed control device (OPFS) is standard furnished on the BJYNN/Z units.
D – 510 C – 07/02 E – EN pag. 8/48
Physical data EWAD-BJYNN R-134a
Unit size 650 700 750 850 900
Cooling capacity (1) kW 640 700 761 817 886
Power input (1) kW 217 233 253 270 282
COP 2,94 3,01 3,01 3,03 3,15
Screw compressors N° 2 2 2 2 2
Refrigerant circuits N° 2 2 2 2 2
Refrigerant charge R-134a kg 97 104 114 124 124
Oil charge kg 40 40 40 40 40
Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5
Condenser fans
No. of fans / nominal power fan kW 9/1,7 10/1,7 11/1,7 12/1,7 12/1,7
Fan speed rpm 860 860 860 860 860
Diameter mm 800 800 800 800 800
3
Total air flow m /s 47,5 52,8 58,1 63,3 64,5
Evaporator
Evaporators / water volume N°/l 1/254 1/254 1/246 1/246 1/246
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 168,3 168,3 168,3 168,3 168,3
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 4910 4990 5256 5480 5580
Standard unit operating weight kg 5130 5200 5520 5734 5834
Unit length mm 5310 5310 6210 6210 6210
Unit width mm 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520

Unit size Note (2) 950 C10 C11 C12 C13


Cooling capacity (1) kW 988 1057 1109 1166 1226
Power input (1) kW 334 345 369 386 404
COP 2,96 3,06 3,01 3,02 3,04
Screw compressors N° 3 3 3 3 3
Refrigerant circuits N° 3 3 3 3 3
Refrigerant charge R-134a kg 144 160 164 180 186
Oil charge kg 60 60 60 60 60
Min % of capacity reduction % 8,3 8,3 8,3 8,3 8,3
Condenser fans
No. of fans / nominal power fan kW 14/1,7 16/1,7 16/1,7 18/1,7 18/1,7
Fan speed rpm 860 860 860 860 860
Diameter mm 800 800 800 800 800
3
Total air flow m /s 73,9 86,0 84,5 89,7 95,0
Evaporator
Evaporators / water volume N°/l 1/415 1/415 1/402 1/402 1/402
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 219,1 219,1 219,1 219,1 219,1
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 7550 7830 7830 8420 8420
Standard unit operating weight kg 7970 8250 8250 8830 8830
Unit length mm 7400 8270 8270 9200 9200
Unit width mm 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520
Notes: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 35°C air ambient temp.
Power input is for compressor only.
(2) For cooling capacity in the middle of 886kW and 988kW, select EWAD-BJYNN/A unit.

D – 510 C – 07/02 E – EN pag. 9/48


Physical data EWAD-BJYNN R-134a
Unit size C14 Note (2) C15 C16 C18
Cooling capacity (1) kW 1322 1520 1641 1772
Power input (1) kW 421 503 539 564
COP 3,14 3,02 3,05 3,15
Screw compressors N° 3 4 4 4
Refrigerant circuits N° 3 4 4 4
Refrigerant charge R-134a kg 186 236 256 256
Oil charge kg 60 80 80 80
Min % of capacity reduction % 8,3 6,25 6,25 6,25
Condenser fans
No. of fans / nominal power fan kW 18/1,7 22/1,7 24/1,7 24/1,7
Fan speed rpm 860 860 860 860
Diameter mm 800 800 800 800
3
Total air flow m /s 96,7 116,1 126,7 129
Evaporator
Evaporators / water volume N°/l 1/402 2/254+246 2/246+246 2/246+246
Max operating pressure bar 10,5 10,5 10,5 10,5
Water connection diameter mm 219,1 168,3 168,3 168,3
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 8570 9552 10632 10832
Standard unit operating weight kg 8980 10024 11140 11340
Unit length mm 9200 11000 11900 11900
Unit width mm 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520
Notes: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 35°C air ambient temp.
Power input is for compressor only.
(2) For cooling capacity in the middle of 1322kW and 1520kW, select EWAD-BJYNN/A unit.

Electrical data EWAD-BJYNN R-134a


Unit size 650 700 750 850
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 414 436 471 502
Max compressor current (3) A 435 460 501 542
Fans current A 36 40 44 48
Max unit current (3) A 471 500 545 590
Max unit inrush current (4) A 814 834 838 867
Max unit current for wires sizing (5) A 530 582 625 668
Unit size 900 950 C10 C11 C12
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 497 632 658 688 726
Max compressor current (3) A 548 664 687 730 773
Fans current A 48 56 64 64 72
Max unit current (3) A 596 720 751 794 845
Max unit inrush current (4) A 867 998 1022 1022 1055
Max unit current for wires sizing (5) A 668 821 877 916 963
Unit size C13 C14 C15 C16 C18
Standard voltage (1) 400 V – 3ph – 50 Hz
Nominal unit current (2) A 756 744 938 1004 994
Max compressor current (3) A 816 820 1002 1084 1096
Fans current A 72 72 88 96 96
Max unit current (3) A 888 892 1090 1180 1192
Max unit inrush current (4) A 1079 1079 1284 1292 1292
Max unit current for wires sizing (5) A 1002 1002 1250 1336 1336
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current is based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current is based on: 14/9 °C entering/leaving evaporator water temperature and 44°C ambient temp.
(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.
(5) Compressor FLA + fans current.

D – 510 C – 07/02 E – EN pag. 10/48


Physical data EWAD-BJYNN with option OPRN R-134a
Unit size 650 700 750 850 900
Cooling capacity (1) kW 606 670 730 784 868
Power input (1) kW 235 250 269 289 305
COP 2,58 2,68 2,71 2,71 2,84
Screw compressors N° 2 2 2 2 2
Refrigerant circuits N° 2 2 2 2 2
Refrigerant charge R-134a kg 97 104 114 124 128
Oil charge kg 40 40 40 40 40
Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5
Condenser fans
No. of fans / nominal power fan kW 9/1 10/1 11/1 12/1 12/1
Fan speed rpm 680 680 680 680 680
Diameter mm 800 800 800 800 800
3
Total air flow m /s 36,4 40,5 44,5 48,6 48,6
Evaporator
Evaporators / water volume N°/l 1/254 1/254 1/246 1/246 1/246
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 168,3 168,3 168,3 168,3 168,3
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 4910 4990 5256 5480 5580
Standard unit operating weight kg 5130 5200 5520 5734 5834
Unit length mm 5310 5310 6210 6210 6210
Unit width mm 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520

Unit size Note (2) 950 C10 C11 C12 C13


Cooling capacity (1) kW 945 1016 1062 1116 1175
Power input (1) kW 360 371 395 414 432
COP 2,63 2,74 2,69 2,70 2,72
Screw compressors N° 3 3 3 3 3
Refrigerant circuits N° 3 3 3 3 3
Refrigerant charge R-134a kg 149 160 160 180 186
Oil charge kg 60 60 60 60 60
Min % of capacity reduction % 8,3% 8,3% 8,3% 8,3% 8,3
Condenser fans
No. of fans / nominal power fan kW 14/1 16/1 16/1 18/1 18/1
Fan speed rpm 680 680 680 680 680
Diameter mm 800 800 800 800 800
3
Total air flow m /s 56,7 66,0 64,8 68,8 72,9
Evaporator
Evaporators / water volume N°/l 1/415 1/415 1/402 1/402 1/402
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 219,1 219,1 219,1 219,1 219,1
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 7550 7830 7830 8420 8420
Standard unit operating weight kg 7970 8250 8250 8830 8830
Unit length mm 7400 8270 8270 9200 9200
Unit width mm 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520
Notes: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 35°C air ambient temp.
Power input is for compressor only.
(2) For cooling capacity in the middle of 868kW and 945kW, select EWAD-BJYNN/A unit.

D – 510 C – 07/02 E – EN pag. 11/48


Physical data EWAD-BJYNN with option OPRN R-134a
Unit size C14 Note (2) C15 C16 C18
Cooling capacity (1) kW 1296 1457 1553 1735
Power input (1) kW 456 546 573 610
COP 2,84 2,67 2,71 2,84
Screw compressors N° 3 4 4 4
Refrigerant circuits N° 3 4 4 4
Refrigerant charge R-134a kg 186 228 248 248
Oil charge kg 60 80 80 80
Min % of capacity reduction % 8,3 6,25 6,25 6,25
Condenser fans
No. of fans / nominal power fan kW 18/1 22/1 24/1 24/1
Fan speed rpm 680 680 680 680
Diameter mm 800 800 800 800
3
Total air flow m /s 73,6 89,0 97,1 98,0
Evaporator
Evaporators / water volume N°/l 1/402 2/254+246 2/246+246 2/246+246
Max operating pressure bar 10,5 10,5 10,5 10,5
Water connection diameter mm 219,1 168,3 168,3 168,3
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 8570 9552 10632 10832
Standard unit operating weight kg 8980 10024 11140 11340
Unit length mm 9200 11000 11900 11900
Unit width mm 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520
Notes: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 35°C air ambient temp.
Power input is for compressor only.
(2) For cooling capacity in the middle of 1296kW and 1457kW, select EWAD-BJYNN/A unit.

Electrical data EWAD-BJYNN with option OPRN R-134a


Unit size 650 700 750 850
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 416 438 474 510
Max compressor current (3) A 443 470 504 538
Fans current A 18 20 22 24
Max unit current (3) A 461 490 526 562
Max unit inrush current (4) A 797 815 817 846
Max unit current for wires sizing (5) A 512 562 603 644
Unit size 900 950 C10 C11 C12
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 508 638 662 701 733
Max compressor current (3) A 549 678 705 739 773
Fans current A 24 28 32 32 34
Max unit current (3) A 573 706 737 771 807
Max unit inrush current (4) A 846 971 992 992 1021
Max unit current for wires sizing (5) A 644 793 845 884 925
Unit size C13 C14 C15 C16 C18
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 765 760 948 1020 1016
Max compressor current (3) A 807 821 1008 1076 1097
Fans current A 36 36 44 48 48
Max unit current (3) A 843 857 1052 1124 1145
Max unit inrush current (4) A 1050 1050 1249 1253 1253
Max unit current for wires sizing (5) A 966 966 1206 1288 1288
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current is based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current is based on: 14/9 °C entering/leaving evaporator water temperature and 40°C ambient temp.
(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.
(5) Compressor FLA + fans current.

D – 510 C – 07/02 E – EN pag. 12/48


Physical data EWAD-BJYNN with option OPLN R-134a
Unit size 650 700 750 850 900
Cooling capacity (1) kW 606 670 730 784 868
Power input (1) kW 235 250 269 289 305
COP 2,58 2,68 2,71 2,71 2,84
Screw compressors N° 2 2 2 2 2
Refrigerant circuits N° 2 2 2 2 2
Refrigerant charge R-134a kg 97 104 114 124 128
Oil charge kg 40 40 40 40 40
Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5
Condenser fans
No. of fans / nominal power fan kW 9/1 10/1 11/1 12/1 12/1
Fan speed rpm 680 680 680 680 680
Diameter mm 800 800 800 800 800
3
Total air flow m /s 36,4 40,5 44,5 48,6 48,6
Evaporator
Evaporators / water volume N°/l 1/254 1/254 1/246 1/246 1/246
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 168,3 168,3 168,3 168,3 168,3
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 5150 5230 5496 5720 5820
Standard unit operating weight kg 5370 5440 5760 5974 6074
Unit length mm 5310 5310 6210 6210 6210
Unit width mm 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520

Unit size Note (2) 950 C10 C11 C12 C13


Cooling capacity (1) kW 945 1016 1062 1116 1175
Power input (1) kW 360 371 395 414 432
COP 2,63 2,74 2,69 2,70 2,72
Screw compressors N° 3 3 3 3 3
Refrigerant circuits N° 3 3 3 3 3
Refrigerant charge R-134a kg 149 160 160 180 186
Oil charge kg 60 60 60 60 60
Min % of capacity reduction % 8,3 8,3 8,3 8,3 8,3
Condenser fans
No. of fans / nominal power fan kW 14/1 16/1 16/1 18/1 18/1
Fan speed rpm 680 680 680 680 680
Diameter mm 800 800 800 800 800
3
Total air flow m /s 56,7 66,0 64,8 68,8 72,9
Evaporator
Evaporators / water volume N°/l 1/415 1/415 1/402 1/402 1/402
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 219,1 219,1 219,1 219,1 219,1
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 7910 8190 8190 8780 8930
Standard unit operating weight kg 8330 8610 8610 9190 9340
Unit length mm 7400 8270 8270 9200 9200
Unit width mm 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520
Notes: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 35°C air ambient temp.
Power input is for compressor only.
(2) For cooling capacity in the middle of 868kW and 945kW, select EWAD-BJYNN/A unit.

D – 510 C – 07/02 E – EN pag. 13/48


Physical data EWAD-BJYNN with option OPLN R-134a
Unit size C14 Note (2) C15 C16 C18
Cooling capacity (1) kW 1296 1457 1553 1735
Power input (1) kW 456 546 573 610
COP 2,84 2,67 2,71 2,84
Screw compressors N° 3 4 4 4
Refrigerant circuits N° 3 4 4 4
Refrigerant charge R-134a kg 186 228 248 248
Oil charge kg 60 80 80 80
Min % of capacity reduction % 8,3 6,25 6,25 6,25
Condenser fans
No. of fans / nominal power fan kW 18/1 22/1 24/1 24/1
Fan speed rpm 680 680 680 680
Diameter mm 800 800 800 800
Total air flow m3/s 73,6 89,0 97,1 98,0
Evaporator
Evaporators / water volume N°/l 1/402 2/254+246 2/246+246 2/246+246
Max operating pressure bar 10,5 10,5 10,5 10,5
Water connection diameter mm 219,1 168,3 168,3 168,3
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 9080 10032 11112 11312
Standard unit operating weight kg 9490 10504 11620 11820
Unit length mm 9200 11000 11900 11900
Unit width mm 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520
Notes: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 35°C air ambient temp.
Power input is for compressor only.
(2) For cooling capacity in the middle of 1296kW and 1457kW, select EWAD-BJYNN/A unit.

Electrical data EWAD-BJYNN with option OPLN H134a


Unit size 650 700 750 850
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 416 438 474 510
Max compressor current (3) A 443 470 504 538
Fans current A 18 20 22 24
Max unit current (3) A 461 490 526 562
Max unit inrush current (4) A 797 815 817 846
Max unit current for wires sizing (5) A 512 562 603 644
2

Unit size 900 950 C10 C11 C12


Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 508 638 662 701 733
Max compressor current (3) A 549 678 705 739 773
Fans current A 24 28 32 32 34
Max unit current (3) A 573 706 737 771 807
Max unit inrush current (4) A 846 971 992 992 1021
Max unit current for wires sizing (5) A 644 793 845 884 925
Unit size C13 C14 C15 C16 C18
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 765 760 948 1020 1016
Max compressor current (3) A 807 821 1008 1076 1097
Fans current A 36 36 44 48 48
Max unit current (3) A 843 857 1052 1124 1145
Max unit inrush current (4) A 1050 1050 1249 1253 1253
Max unit current for wires sizing (5) A 966 966 1206 1288 1288
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current is based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current is based on: 14/9 °C entering/leaving evaporator water temperature and 40°C ambient temp.
(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.
(5) Compressor FLA + fans current.

D – 510 C – 07/02 E – EN pag. 14/48


Physical data EWAD-BJYNN/Q R-134a
Unit size 550 600 650 700 750 800
Cooling capacity (1) kW 539 597 650 709 759 812
Power input (1) kW 229 246 262 285 307 340
COP 2,35 2,43 2,48 2,48 2,47 2,39
Screw compressors N° 2 2 2 2 2 3
Refrigerant circuits N° 2 2 2 2 2 3
Refrigerant charge R-134a kg 104 114 124 132 140 160
Oil charge kg 40 40 40 40 40 60
Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 8,3
Condenser fans
No. of fans / nominal power fan kW 10/0,3 11/0,3 12/0,3 13/0,3 14/0,3 16/0,3
Fan speed rpm 500 500 500 500 500 500
Diameter mm 800 800 800 800 800 800
3
Total air flow m /s 25,6 28,2 30,8 33,3 35,9 42,1
Evaporator
Evaporators / water volume N°/l 1/261 1/254 1/254 1/246 1/246 1/424
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 168,3 168,3 168,3 168,3 168,3 219,1
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 5230 5445 5659 5900 6030 8190
Standard unit operating weight kg 5440 5650 5864 6150 6280 8610
Unit length mm 5310 6210 6210 7110 7110 8300
Unit width mm 2230 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520 2520

Unit size 850 900 950 C10 C11 C12


Cooling capacity (1) kW 869 921 974 1055 1086 1152
Power input (1) kW 361 377 393 406 438 449
COP 2,41 2,45 2,48 2,60 2,48 2,57
Screw compressors N° 3 3 3 3 3 3
Refrigerant circuits N° 3 3 3 3 3 3
Refrigerant charge R-134a kg 160 180 186 199 202 215
Oil charge kg 60 60 60 60 60 60
Min % of capacity reduction % 8,3 8,3 8,3 8,3 8,3 8,3
Condenser fans
No. of fans / nominal power fan kW 16/0,3 18/0,3 18/0,3 20/0,3 20/0,3 22/0,3
Fan speed rpm 500 500 500 500 500 500
Diameter mm 800 800 800 800 800 800
3
Total air flow m /s 41,0 43,6 46,1 51,3 51,3 56,4
Evaporator
Evaporators / water volume N°/l 1/415 1/415 1/415 1/402 1/402 1/402
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 219,1 219,1 219,1 219,1 219,1 219,1
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 8190 8725 8725 9310 9310 9750
Standard unit operating weight kg 8610 9150 9150 9720 9720 10160
Unit length mm 8300 9200 9200 10100 10100 11000
Unit width mm 2230 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520 2520
Note: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 32°C air ambient temp.
Power input is for compressor only.

D – 510 C – 07/02 E – EN pag. 15/48


Electrical data EWAD-BJYNN/Q R-134a
Unit size 550 600 650 700 750 800
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 414 439 468 512 556 605
Max compressor current (3) A 440 473 506 558 610 660
Fans current A 10 11 12 13 14 16
Max unit current (3) A 450 484 518 571 624 676
Max unit inrush current (4) A 796 797 819 820 854 958
Max unit current for wires sizing (5) A 456 505 554 594 634 685

Unit size 850 900 950 C10 C11 C12


Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 640 666 702 733 791 818
Max compressor current (3) A 693 726 759 811 863 895
Fans current A 16 18 18 20 20 22
Max unit current (3) A 709 744 777 831 883 917
Max unit inrush current (4) A 958 980 1000 1002 1035 1070
Max unit current for wires sizing (5) A 733 783 831 872 911 952
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current is based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current is based on: 14/9 °C entering/leaving evaporator water temperature and 40°C ambient temp.
(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.
(5) Compressor FLA + fans current.

D – 510 C – 07/02 E – EN pag. 16/48


Physical data EWAD-BJYNN/A R-134a
Unit size 650 700 800 850 900 950
Cooling capacity (1) kW 667 723 800 855 903 926
Power input (1) kW 204 217 237 255 268 260
COP 3,27 3,33 3,38 3,36 3,37 3,57
Screw compressors N° 2 2 2 2 2 2
Refrigerant circuits N° 2 2 2 2 2 2
Refrigerant charge R-134a kg 114 124 128 132 132 144
Oil charge kg 40 40 40 40 40 40
Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 12,5
Condenser fans
No. of fans / nominal power fan kW 11/1,7 12/1,7 13/1,7 14/1,7 14/1,7 16/1,7
Fan speed rpm 860 860 860 860 860 860
Diameter mm 800 800 800 800 800 800
3
Total air flow m /s 58,1 63,3 68,6 73,9 75,2 86,0
Evaporator
Evaporators / water volume N°/l 1/254 1/254 1/246 1/246 1/246 1/244
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 168,3 168,3 168,3 168,3 168,3 168,3
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 5205 5419 5660 5790 5890 6333
Standard unit operating weight kg 5410 5624 5910 6040 6140 6589
Unit length mm 6210 6210 7110 7110 7110 8300
Unit width mm 2230 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520 2520

Unit size C10 C11 C12 C13 C14 C15 C16


Cooling capacity (1) kW 974 1038 1094 1177 1222 1282 1354
Power input (1) kW 267 312 325 343 365 378 396
COP 3,65 3,33 3,37 3,43 3,35 3,40 3,42
Screw compressors N° 2 3 3 3 3 3 3
Refrigerant circuits N° 2 3 3 3 3 3 3
Refrigerant charge R-134a kg 144 180 186 196 194 204 204
Oil charge kg 40 60 60 60 60 60 60
Min % of capacity reduction % 12,5 8,3 8,3 8,3 8,3 8,3 8,3
Condenser fans
No. of fans / nominal power fan kW 16/1,7 18/1,7 18/1,7 20/1,7 20/1,7 22/1,7 22/1,7
Fan speed rpm 860 860 860 860 860 860 860
Diameter mm 800 800 800 800 800 800 800
3
Total air flow m /s 86,0 100,6 95,0 105,6 105,6 116,1 118,3
Evaporator
Evaporators / water volume N°/l 1/392 1/415 1/415 1/402 1/402 1/402 1/402
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 219,1 219,1 219,1 219,1 219,1 219,1 219,1
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 6563 8420 8420 8950 8950 9390 9540
Standard unit operating weight kg 6967 8830 8830 9360 9360 9800 9950
Unit length mm 8300 9200 9200 10100 10100 11000 11000
Unit width mm 2230 2230 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520 2520 2520
Note: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 35°C air ambient temp.
Power input is for compressor only.

D – 510 C – 07/02 E – EN pag. 17/48


Physical data EWAD-BJYNN/A R-134a
Unit size C17 C18 C19 C20 C21
Cooling capacity (1) kW 1430 1557 1710 1806 1920
Power input (1) kW 386 476 510 536 555
COP 3,70 3,27 3,35 3,37 3,46
Screw compressors N° 3 4 4 4 4
Refrigerant circuits N° 3 4 4 4 4
Refrigerant charge R-134a kg 232 256 264 264 264
Oil charge kg 60 80 80 80 80
Min % of capacity reduction % 8,3 6,25 6,25 6,25 6,25
Condenser fans
No. of fans / nominal power fan kW 26/1,7 26/1,7 28/1,7 28/1,7 28/1,7
Fan speed rpm 860 860 860 860 860
Diameter mm 800 800 800 800 800
3
Total air flow m /s 140 137,2 147,8 150,5 150,5
Evaporator
Evaporators / water volume N°/l 1/533 2/254+246 2/246+246 2/246+246 2/392+392
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 219,1 168,3 168,3 168,3 219,1
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 10355 10960 11168 11368 12144
Standard unit operating weight kg 10931 11420 11678 11878 13036
Unit length mm 12800 12800 13670 13670 13670
Unit width mm 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520
Note: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 35°C air ambient temp.
Power input is for compressor only.

Electrical data EWAD-BJYNN/A R-134a


Unit size 650 700 800 850 900
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 412 434 464 494 485
Max compressor current (3) A 442 468 511 554 547
Fans current A 44 48 52 56 56
Max unit current (3) A 486 516 563 610 603
Max unit inrush current (4) A 821 842 846 872 872
Max unit current for wires sizing (5) A 538 590 633 676 676
Unit size 950 C10 C11 C12 C13 C14
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 480 491 631 651 686 713
Max compressor current (3) A 532 545 670 696 742 788
Fans current A 64 64 72 72 80 80
Max unit current (3) A 596 609 742 768 822 868
Max unit inrush current (4) A 872 872 1012 1029 1037 1059
Max unit current for wires sizing (5) A 684 684 837 885 932 971
Unit size C15 C16 C17 C18 C19 C20 C21
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 748 722 723 928 988 970 998
Max compressor current (3) A 834 810 791 1022 1108 1095 1130
Fans current A 88 88 104 104 112 112 112
Max unit current (3) A 922 898 895 1126 1220 1207 1242
Max unit inrush current (4) A 1090 1090 1090 1291 1299 1299 1299
Max unit current for wires sizing (5) A 1018 1018 1034 1266 1352 1352 1352
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current is based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current is based on: 14/9 °C entering/leaving evaporator water temperature and 48°C ambient temp.
(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.
(5) Compressor FLA + fans current.

D – 510 C – 07/02 E – EN pag. 18/48


Physical data EWAD-BJYNN/A with option OPRN R-134a
Unit size 650 700 800 850 900 950
Cooling capacity (1) kW 640 703 769 822 881 907
Power input (1) kW 216 232 254 271 286 275
COP 2,97 3,02 3,03 3,04 3,08 3,30
Screw compressors N° 2 2 2 2 2 2
Refrigerant circuits N° 2 2 2 2 2 2
Refrigerant charge R-134a kg 114 124 128 132 132 144
Oil charge kg 40 40 40 40 40 40
Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 12,5
Condenser fans
No. of fans / nominal power fan kW 11/1 12/1 13/1 14/1 14/1 16/1
Fan speed rpm 680 680 680 680 680 680
Diameter mm 800 800 800 800 800 800
3
Total air flow m /s 44,5 48,6 52,6 56,7 57,2 65,4
Evaporator
Evaporators / water volume N°/l 1/254 1/254 1/246 1/246 1/246 1/244
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 168,3 168,3 168,3 168,3 168,3 168,3
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 5205 5419 5660 5790 5890 6333
Standard unit operating weight kg 5410 5624 5910 6040 6140 6589
Unit length mm 6210 6210 7110 7110 7110 8300
Unit width mm 2230 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520 2520

Unit size C10 C11 C12 C13 C14 C15 C16


Cooling capacity (1) kW 953 998 1053 1135 1177 1238 1323
Power input (1) kW 283 332 347 362 389 402 421
COP 3,36 3,00 3,03 3,14 3,03 3,08 3,14
Screw compressors N° 2 3 3 3 3 3 3
Refrigerant circuits N° 2 3 3 3 3 3 3
Refrigerant charge R-134a kg 144 180 186 196 194 204 204
Oil charge kg 40 60 60 60 60 60 60
Min % of capacity reduction % 12,5 8,3 8,3 8,3 8,3 8,3 8,3
Condenser fans
No. of fans / nominal power fan kW 16/1 18/1 18/1 20/1 20/1 22/1 22/1
Fan speed rpm 680 680 680 680 680 680 680
Diameter mm 800 800 800 800 800 800 800
3
Total air flow m /s 65,4 77,1 72,8 80,9 80,9 89,0 89,9
Evaporator
Evaporators / water volume N°/l 1/392 1/415 1/415 1/402 1/402 1/402 1/402
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 219,1 219,1 219,1 219,1 219,1 219,1 219,1
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 6563 8420 8420 8950 8950 9390 9540
Standard unit operating weight kg 6967 8830 8830 9360 9360 9800 9950
Unit length mm 8300 9200 9200 10100 10100 11000 11000
Unit width mm 2230 2230 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520 2520 2520
Note: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 35°C air ambient temp.
Power input is for compressor only.

D – 510 C – 07/02 E – EN pag. 19/48


Physical data EWAD-BJYNN/A with option OPRN R-134a
Unit size C17 C18 C19 C20 C21
Cooling capacity (1) kW 1401 1512 1618 1762 1871
Power input (1) kW 408 501 541 572 594
COP 3,44 3,02 2,99 3,08 3,15
Screw compressors N° 3 4 4 4 4
Refrigerant circuits N° 3 4 4 4 4
Refrigerant charge R-134a kg 232 256 264 264 264
Oil charge kg 60 80 80 80 80
Min % of capacity reduction % 8,3 6,25 6,25 6,25 6,25
Condenser fans
No. of fans / nominal power fan kW 26/1 26/1 28/1 28/1 28/1
Fan speed rpm 680 680 680 680 680
Diameter mm 800 800 800 800 800
3
Total air flow m /s 106,3 105,2 113,3 114,4 114,4
Evaporator
Evaporators / water volume N°/l 1/533 2/254+246 2/246+246 2/246+246 2/392+392
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 219,1 168,3 168,3 168,3 219,1
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 10355 10960 11168 11368 12144
Standard unit operating weight kg 10931 11420 11678 11878 13036
Unit length mm 12800 12800 13670 13670 13670
Unit width mm 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520
Note: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 35°C air ambient temp.
Power input is for compressor only.

Electrical data EWAD-BJYNN/A with option OPRN R-134a


Unit size 650 700 800 850 900
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 403 428 459 490 484
Max compressor current (3) A 443 470 510 550 547
Fans current A 22 24 26 28 28
Max unit current (3) A 465 494 536 578 575
Max unit inrush current (4) A 796 815 817 843 843
Max unit current for wires sizing (5) A 516 566 607 648 648
Unit size 950 C10 C11 C12 C13 C14
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 472 484 614 633 669 705
Max compressor current (3) A 528 543 678 705 745 785
Fans current A 32 32 36 36 40 40
Max unit current (3) A 560 575 714 741 785 825
Max unit inrush current (4) A 843 843 971 988 992 1015
Max unit current for wires sizing (5) A 652 652 801 849 892 931
Unit size C15 C16 C17 C18 C19 C20 C21
Standard voltage (1) 400 V – 3ph – 50 Hz
Nominal unit current (2) A 729 716 704 918 980 967 1000
Max compressor current (3) A 825 807 783 1020 1100 1094 1116
Fans current A 44 44 52 52 56 56 56
Max unit current (3) A 869 851 835 1072 1156 1150 1172
Max unit inrush current (4) A 1043 1043 1043 1234 1238 1238 1238
Max unit current for wires sizing (5) A 974 974 982 1214 1296 1296 1296
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current is based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current is based on: 14/9 °C entering/leaving evaporator water temperature and 44°C ambient temp.
(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.
(5) Compressor FLA + fans current.

D – 510 C – 07/02 E – EN pag. 20/48


Physical data EWAD-BJYNN/A with option OPLN R-134a
Unit size 650 700 800 850 900 950
Cooling capacity (1) kW 640 703 769 822 881 907
Power input (1) kW 216 232 254 271 286 275
COP 2,97 3,02 3,03 3,04 3,08 3,30
Screw compressors N° 2 2 2 2 2 2
Refrigerant circuits N° 2 2 2 2 2 2
Refrigerant charge R-134a kg 114 124 128 132 132 144
Oil charge kg 40 40 40 40 40 40
Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 12,5
Condenser fans
No. of fans / nominal power fan kW 11/1 12/1 13/1 14/1 14/1 16/1
Fan speed rpm 680 680 680 680 680 680
Diameter mm 800 800 800 800 800 800
3
Total air flow m /s 44,5 48,6 52,6 56,7 57,2 65,4
Evaporator
Evaporators / water volume N°/l 1/254 1/254 1/246 1/246 1/246 1/244
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 168,3 168,3 168,3 168,3 168,3 168,3
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 5445 5659 5900 6030 6130 6573
Standard unit operating weight kg 5650 5864 6150 6280 6380 6829
Unit length mm 6210 6210 7110 7110 7110 8300
Unit width mm 2230 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520 2520

Unit size C10 C11 C12 C13 C14 C15 C16


Cooling capacity (1) kW 953 998 1053 1135 1177 1238 1323
Power input (1) kW 283 332 347 362 389 402 421
COP 3,36 3,00 3,03 3,14 3,03 3,08 3,14
Screw compressors N° 2 3 3 3 3 3 3
Refrigerant circuits N° 2 3 3 3 3 3 3
Refrigerant charge R-134a kg 144 180 186 196 194 204 204
Oil charge kg 40 60 60 60 60 60 60
Min % of capacity reduction % 12,5 8,3 8,3 8,3 8,3 8,3 8,3
Condenser fans
No. of fans / nominal power fan kW 16/1 18/1 18/1 20/1 20/1 22/1 22/1
Fan speed rpm 680 680 680 680 680 680 680
Diameter mm 800 800 800 800 800 800 800
3
Total air flow m /s 65,4 77,1 72,8 80,9 80,9 89,0 89,9
Evaporator
Evaporators / water volume N°/l 1/392 1/415 1/415 1/402 1/402 1/402 1/402
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 219,1 219,1 219,1 219,1 219,1 219,1 219,1
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 6803 8780 8780 9310 9310 9750 9900
Standard unit operating weight kg 7207 9190 9190 9720 9720 10160 10310
Unit length mm 8300 9200 9200 10100 10100 11000 11000
Unit width mm 2230 2230 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520 2520 2520
Note: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 35°C air ambient temp.
Power input is for compressor only.

D – 510 C – 07/02 E – EN pag. 21/48


Physical data EWAD-BJYNN/A with option OPLN R-134a
Unit size C17 C18 C19 C20 C21
Cooling capacity (1) kW 1401 1512 1618 1762 1871
Power input (1) kW 408 501 541 572 594
COP 3,44 3,02 2,99 3,08 3,15
Screw compressors N° 3 4 4 4 4
Refrigerant circuits N° 3 4 4 4 4
Refrigerant charge R-134a kg 232 256 264 264 264
Oil charge kg 60 80 80 80 80
Min % of capacity reduction % 8,3 6,25 6,25 6,25 6,25
Condenser fans
No. of fans / nominal power fan kW 26/1 26/1 28/1 28/1 28/1
Fan speed rpm 680 680 680 680 680
Diameter mm 800 800 800 800 800
3
Total air flow m /s 106,3 105,2 113,3 114,4 114,4
Evaporator
Evaporators / water volume N°/l 1/533 2/254+246 2/246+246 2/246+246 2/392+392
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 219,1 168,3 168,3 168,3 219,1
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 10715 11440 11648 11848 12624
Standard unit operating weight kg 11291 11900 12158 12358 13516
Unit length mm 12800 12800 13670 13670 13670
Unit width mm 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520
Note: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 35°C air ambient temp.
Power input is for compressor only.

Electrical data EWAD-BJYNN/A with option OPLN R-134a


Unit size 650 700 800 850 900
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 403 428 459 490 484
Max compressor current (3) A 443 470 510 550 547
Fans current A 22 24 26 28 28
Max unit current (3) A 465 494 536 578 575
Max unit inrush current (4) A 796 815 817 843 843
Max unit current for wires sizing (5) A 516 566 607 648 648
Unit size 950 C10 C11 C12 C13 C14
Standard voltage (1) 400 V – 3f – 50 Hz
Nominal unit current (2) A 472 484 614 633 669 705
Max compressor current (3) A 528 543 678 705 745 785
Fans current A 32 32 36 36 40 40
Max unit current (3) A 560 575 714 741 785 825
Max unit inrush current (4) A 843 843 971 988 992 1015
Max unit current for wires sizing (5) A 652 652 801 849 892 931
Unit size C15 C16 C17 C18 C19 C20 C21
Standard voltage (1) 400 V – 3ph – 50 Hz
Nominal unit current (2) A 729 716 704 918 980 967 1000
Max compressor current (3) A 825 807 783 1020 1100 1094 1116
Fans current A 44 44 52 52 56 56 56
Max unit current (3) A 869 851 835 1072 1156 1150 1172
Max unit inrush current (4) A 1043 1043 1043 1234 1238 1238 1238
Max unit current for wires sizing (5) A 974 974 982 1214 1296 1296 1296
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current is based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current is based on: 14/9 °C entering/leaving evaporator water temperature and 44°C ambient temp.
(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.
(5) Compressor FLA + fans current.

D – 510 C – 07/02 E – EN pag. 22/48


Physical data EWAD-BJYNN/Z R-134a
Unit size 600 650 700 850 900 950 C10
Cooling capacity (1) kW 569 631 668 840 914 953 1013
Power input (1) kW 216 237 264 323 336 361 361
COP 2,64 2,66 2,53 2,61 2,72 2,64 2,80
Screw compressors No. 2 2 2 3 3 3 3
Refrigerant circuits No. 2 2 2 3 3 3 3
Refrigerant charge R-134a kg 124 128 132 186 196 194 204
Oil charge kg 40 40 40 60 60 60 60
Min % of capacity reduction % 12,5 12,5 12,5 8,3 8,3 8,3 8,3
Condenser fans
No. of fans / nominal power fan kW 12/0,3 13/0,3 14/0,3 18/0,3 20/0,3 20/0,3 22/0,3
Fan speed rpm 500 500 500 500 500 500 500
Diameter mm 800 800 800 800 800 800 800
3
Total air flow m /s 30,8 33,3 35,9 46,1 51,3 51,3 56,4
Evaporator
Evaporators / water volume No./l 1/254 1/246 1/246 1/415 1/402 1/402 1/402
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 168,3 168,3 168,3 219,1 219,1 219,1 219,1
Condenser coil
Coil type Lanced fins – internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 5659 5900 6030 8725 9310 9310 9750
Standard unit operating weight kg 5864 6150 6280 9150 9720 9720 10160
Unit length mm 6210 7110 7110 9200 10100 10100 11000
Unit width mm 2230 2230 2230 2230 2230 2230 2230
Unit height mm 2520 2520 2520 2520 2520 2520 2520
Note: (1) Cooling capacity and power input are based on 12/7 °C entering/leaving water temp. and 35°C air ambient temp.
Power input is for compressor only.

Electrical data EWAD-BJYNN/Z R-134a


Unit size 600 650 700 850 900 950 C10
Standard voltage (1) 400 V – 3ph – 50 Hz
Nominal unit current (2) A 392 420 444 585 604 636 652
Max compressor current (3) A 416 447 474 618 640 678 705
Fans current A 12 13 14 18 20 20 22
Max unit current (3) A 428 460 488 636 660 698 727
Max unit inrush current (4) A 790 791 812 943 945 965 986
Max unit current for wires sizing (5) A 458 507 556 687 737 785 835
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current is based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current is based on: 14/9 °C entering/leaving evaporator water temperature and 40°C ambient temp.
(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.
(5) Compressor FLA + fans current.

D – 510 C – 07/02 E – EN pag. 23/48


Sound pressure level EWAD-BJYNN and EWAD-BJYNN/A
-5
Sound pressure level at 1 m from the unit in free field ( ref. 2 x 10 )
EWAD-BJYNN EWAD-BJYNN/A
63 125 250 500 1000 2000 4000 8000
Hz Hz Hz Hz Hz Hz Hz Hz dBA
650 650 77,0 77,5 79,0 75,0 74,5 72,0 63,0 54,5 79,0
700 700 77,0 77,5 79,0 75,0 74,5 72,0 63,0 54,5 79,0
750 800 77,5 78,0 79,5 75,5 75,0 72,5 63,5 55,0 79,5
850 850 77,5 78,0 79,5 75,5 75,0 72,5 63,5 55,0 79,5
900 900 78,0 78,5 80,0 76,0 75,5 73,0 64,0 55,5 80,0
- 950 77,5 78,0 79,5 75,5 75,0 72,5 63,5 55,0 79,5
- C10 77,5 78,0 79,5 75,5 75,0 72,5 63,5 55,0 79,5
950 C11 77,0 77,5 79,0 75,0 74,5 72,0 63,0 54,5 79,0
C10 C12 77,0 77,5 79,0 75,0 74,5 72,0 63,0 54,5 79,0
C11 C13 77,5 78,0 79,5 75,5 75,0 72,5 63,5 55,0 79,5
C12 C14 77,5 78,0 79,5 75,5 75,0 72,5 63,5 55,0 79,5
C13 C15 77,5 78,0 79,5 75,5 75,0 72,5 63,5 55,0 79,5
C14 C16 78,0 78,5 80,0 76,0 75,5 73,0 64,0 55,5 80,0
- C17 78,0 78,5 80,0 76,0 75,5 73,0 64,0 55,5 80,0
C15 C18 77,5 78,0 79,5 75,5 75,0 72,5 63,5 55,0 79,5
C16 C19 77,5 78,0 79,5 75,5 75,0 72,5 63,5 55,0 79,5
C18 C20 78,0 78,5 80,0 76,0 75,5 73,0 64,0 55,5 80,0
C21 78,0 78,5 80,0 76,0 75,5 73,0 64,0 55,5 80,0
Notes: Average sound pressure level rated in accordance to ISO 3744, at free field semispherical conditions.
Sound pressure levels are referred to units furnished without water pump and/or high lift fans.

Sound pressure level EWAD-BJYNN + option OPRN and EWAD-BJYNN/A + option


OPRN
-5
Sound pressure level at 1 m from the unit in free field ( ref. 2 x 10 )
EWAD-BJYNN EWAD-BJYNN/A
63 125 250 500 1000 2000 4000 8000
+ option OPRN + option OPRN
Hz Hz Hz Hz Hz Hz Hz Hz dBA
650 650 74,0 70,5 73,5 70,0 69,0 66,5 58,0 50,5 73,5
700 700 74,0 71,0 74,0 70,5 69,0 67,0 58,0 50,5 74,0
750 800 74,5 71,5 74,5 71,0 69,5 67,5 58,5 51,0 74,5
850 850 75,0 72,0 75,0 71,5 70,0 68,0 59,0 52,0 75,0
900 900 76,0 73,0 76,5 72,5 71,0 69,0 60,0 52,5 76,0
- 950 76,0 73,0 76,5 72,5 71,0 69,0 60,0 52,5 76,0
- C10 76,0 73,0 76,5 72,5 71,0 69,0 60,0 52,5 76,0
950 C11 74,5 71,5 74,0 71,0 69,5 67,5 58,5 51,0 74,5
C10 C12 74,5 71,5 74,0 71,0 69,5 67,5 58,5 51,0 74,5
C11 C13 75,0 72,0 75,0 71,5 70,0 68,0 59,0 51,5 75,0
C12 C14 75,5 72,0 75,0 71,5 70,5 68,0 59,5 52,0 75,0
C13 C15 76,0 72,5 75,5 72,0 71,0 68,5 60,0 52,5 75,5
C14 C16 76,5 73,5 77,0 73,0 71,5 69,5 60,5 53,0 76,5
- C17 76,5 73,5 77,0 73,0 71,5 69,5 60,5 53,0 76,5
C15 C18 75,5 72,5 75,5 72,0 70,5 68,5 59,5 52,0 75,5
C16 C19 76,0 73,0 76,5 72,5 71,0 69,0 60,0 52,5 76,0
C18 C20 76,5 73,5 77,0 73,0 71,5 69,5 60,5 53,0 76,5
C21 76,5 73,5 77,0 73,0 71,5 69,5 60,5 53,0 76,5
Notes: Average sound pressure level rated in accordance to ISO 3744, at free field semispherical conditions.
Sound pressure levels are referred to units furnished without water pump and/or high lift fans.

D – 510 C – 07/02 E – EN pag. 24/48


Sound pressure level EWAD-BJYNN + option OPLN and EWAD-BJYNN/A + option
OPLN
-5
Sound pressure level at 1 m from the unit in free field ( ref. 2 x 10 )
EWAD-BJYNN EWAD-BJYNN/A
63 125 250 500 1000 2000 4000 8000
+ option OPLN + option OPLN
Hz Hz Hz Hz Hz Hz Hz Hz dBA
650 650 75,0 72,5 72,0 69,5 66,5 61,5 54,5 46,5 71,5
700 700 75,0 73,0 72,0 69,5 66,5 62,0 54,5 46,5 71,5
750 800 75,0 73,0 72,5 69,5 66,5 62,0 54,5 46,5 71,5
850 850 75,0 73,0 72,5 70,0 66,5 62,0 55,0 47,0 71,5
900 900 76,0 74,0 73,0 70,5 67,5 63,0 55,5 47,5 72,5
- 950 76,0 74,0 73,0 70,5 67,5 63,0 55,5 47,5 72,5
- C10 76,0 74,0 73,0 70,5 67,5 63,0 55,5 47,5 72,5
950 C11 75,0 73,0 72,5 69,5 66,5 62,0 54,5 46,5 71,5
C10 C12 75,0 73,0 72,5 69,5 66,5 62,0 54,5 46,5 71,5
C11 C13 75,0 73,0 72,5 70,0 66,5 62,0 55,0 47,0 71,5
C12 C14 75,0 73,0 72,5 70,0 66,5 62,0 55,0 47,0 71,5
C13 C15 75,5 73,0 72,5 70,0 67,0 62,0 55,0 47,0 72,0
C14 C16 76,5 74,5 73,5 71,0 68,0 63,5 56,0 48,0 73,0
- C17 76,5 74,5 73,5 71,0 68,0 63,5 56,0 48,0 73,0
C15 C18 75,5 73,0 72,5 70,0 67,0 62,0 55,0 47,0 72,0
C16 C19 75,5 73,5 72,5 70,0 67,0 62,5 55,0 47,0 72,0
C18 C20 76,5 74,5 73,5 71,0 68,0 63,5 56,0 48,0 73,0
C21 76,5 74,5 73,5 71,0 68,0 63,5 56,0 48,0 73,0
Notes: Average sound pressure level rated in accordance to ISO 3744, at free field semispherical conditions.
Sound pressure levels are referred to units furnished without water pump and/or high lift fans.

Sound pressure level EWAD-BJYNN/Q and EWAD-BJYNN/Z


-5
Sound pressure level at 1 m from the unit in free field ( ref. 2 x 10 )
EWAD-BJYNN/Q EWAD-BJYNN/Z 63 125 250 500 1000 2000 4000 8000
Hz Hz Hz Hz Hz Hz Hz Hz dBA
550 600 61,5 63,5 66,0 64,5 57,5 54,0 50,0 42,5 65,0
600 650 61,5 64,0 66,0 64,5 58,0 54,5 50,0 43,0 65,0
650 700 62,0 64,0 66,0 65,0 58,0 54,5 50,5 43,0 65,0
700 - 62,5 64,5 66,5 65,5 58,5 55,0 50,5 43,5 65,5
750 - 62,5 65,0 67,0 65,5 59,0 55,5 51,0 44,0 66,0
800 850 62,0 64,0 66,5 65,0 58,0 54,5 50,5 43,0 65,5
850 900 62,0 64,0 66,5 65,0 58,0 54,5 50,5 43,0 65,5
900 950 62,0 64,5 66,5 65,0 58,5 55,0 50,5 43,5 65,5
950 C10 62,0 64,5 66,5 65,0 58,5 55,0 50,5 43,5 65,5
C10 - 62,5 64,5 67,0 65,5 59,0 55,5 51,0 44,0 66,0
C11 - 63,0 65,0 67,0 66,0 59,0 55,5 51,0 44,0 66,0
C12 - 63,0 65,5 67,5 66,0 59,5 56,0 51,5 44,5 66,5
Notes: Average sound pressure level rated in accordance to ISO 3744, at free field semispherical conditions.
The data for EWAD-BJYNN/Q and EWAD-BJYNN/Z units are referred to 32 °C air ambient temperature.
Sound pressure levels are referred to units furnished without water pump and/or high lift fans.

D – 510 C – 07/02 E – EN pag. 25/48


Relief Valves
As a safety precaution and to meet code requirements, each chiller is equipped with pressure relief valves
located on the condenser coil, evaporator, heat recovery condenser (if supplied) and liquid receiver, for the
purpose of releasing excessive refrigerant pressure (caused by equipment malfunctioning, fire etc.) to the
atmosphere.

Oil Heater
The oil separator is equipped with an immersion electric heater that is installed in a tube and can be
removed without disturbing the oil or opening the refrigerant circuit.

Evaporator water flow and pressure drop


Adjust the chilled water flow through the evaporator. The flow rates must remain between the minimum and
maximum values. Flow rates below the minimum values shown will result in laminar flow that will reduce efficiency,
cause erratic operation of the electronic expansion valve and could cause low temperature cut-out. On the other
hand flow rates exceeding the maximum values shown may cause erosion, vibration and possible breakage of
evaporator water connections and tubes. Measure the chilled water pressure drop across the evaporator at field
installed pressure taps. It is important not to include any pressure drop due to valves or strainers in the
measurement. Variable chilled water flow through the evaporator while the compressors are operating is not
recommended. Set points are valid for a constant flow and a variable temperature.

Heat Recovery Condenser water flow and pressure drop


Heat recovery condensers are supplied without the connection headers for both inlet and outlet water sides. These
headers, including the well pockets for microprocessor control sensors, must be provided locally by the installer.
Adjust the hot water flow through the heat recovery condenser. The flow rates must remain between the minimum
and maximum values. Flow rates below the minimum values shown will result in laminar flow that will reduce
efficiency, cause erratic operation of the unit and could cause high pressure cut-out. On the other hand, flow rates
exceeding the maximum values shown can cause erosion on the condenser water connections and tubes.
Measure the hot water pressure drop across the condenser at field installed pressure taps. It is important not to
include in the measurement any pressure drop due to valves or strainers. Variable hot water flow through the
condenser while the compressors are operating is not recommended. Set points are valid for a constant flow and a
variable temperature.

Leaving Connections

Installer must provide the Headers


between the heat recovery
condenser to have only one supply
water connection and one return
water connection

Heat Recovery Condensers Entering Connections

D – 510 C – 07/02 E – EN pag. 26/48


Table for matching unit size
Unit size BJYNN BJYNN/A BJYNN/Q BJYNN/Z
A - - 550 600
B 650 650 600 650
C 700 700 650 700
D 750 800 700 -
E 850 850 750 -
F - - 800 850
G 900 900 - -
H - 950 - -
I - - 850 950
J - C10 - C10
K 950 C11 900 -
L C10 C12 950 -
M C11 C13 C10 -
N C12 C14 C11 -
O C13 C15 C12 -
P C14 C16 - -
Q - C17 - -
R C15 C18 - -
S C16 C19 - -
T C18 C20 - -
U - C21 - -
Note:
Unit size matching system used for evaporator pressure drop curves and pressure drop curves for partial and total heat recovery.

D – 510 C – 07/02 E – EN pag. 27/48


Evaporator pressure drop
EWAD-BJYNN - EWAD-BJYNN/Q
EWAD-BJYNN/A

520.4
U
495.4
T

392.3
Q
J
273.2
R
426.4
S
355.4 - 460.4
312.3-327.3-344.3-358.3
M-N-O-P
258.2
H
241.2
G
240.3
F
260.3 - 279.3
I - -K296.3
-L
178.2 -B196.2
-C
212.2 -D229.2
-E
163.2
A

 
 







Pressure drop (kPa)








    
       

Water flow rate (l/s)

D – 510 C – 07/02 E – EN pag. 28/48


Evaporator pressure drop
EWAD-BJYNN/Z

260.3 - 279.3 I-- 296.3


K-L
F
240.3
163.2
A
178.2 - 196.2
B-C


 

 







 

(kPa)
drop(l/s)


Pressuredrop


Pressure





           

 

Water flow rate (l/s) 

D – 510 C – 07/02 E – EN pag. 29/48


Pressure drop across partial heat recovery exchanger (plate
exchanger)
EWAD-BJYNN - EWAD-BJYNN/Q
EWAD-BJYNN/A - EWAD-BJYNN/Z

46587:9SK=PF@ KNIF46587<9EKDLF@ AJI4M587<9OLHAP@ K


460.4 – 495.4 S –- 520.4
T-U
4M587<9EKA=@ K
426.4R

46587:9G?8KKQ@ ?RIF46587<9O?LCF@ ?RI4M587<9O?DHAF@ ?


344.3 – 358.3 O -– P392.3
-Q
46587:9G?HAB@ ?
327.3N
46587:9G?Q;-AF@ ?
312.3 M
46587:9EAD=@ ?
296.3
L

46587:9EABD@ ?
279.3K
46587:9EA=P@ ?
260.3J
46587:9EAAD@ AJIF46587:9EAHK;H@ AJIF46587<9GALCF@ AJI4M587<9GAB?@ ANI4M587OAKP@ ?
229.2 – 241.2 – 258.2 E -– F 273.2 - G–-240.3
H-I
46587:9EA;-AF@ A
212.2D
46587:9<;>D=@ A
196.2C
46587:9<;>BC@ A
178.2B
46587:9<;>=?@ A
163.2A
(+*/*
&1*
$1*
"/*
r
!1*
g
qp m
(kPa)

31*
drop (kPa)

o
2-*
di carico

kn
i
m
jk n .1*
Pressure
Perdita

jk l m

g hi ,-*

(0*
( , . 2 3 !#"%$'&)(+* ,-* ./*
T:UWV/XYZX-Y[YG\^]W_NYab ` cdfe
Water
Portata
flow
acqua
rate (l/s)
(l/s)

D – 510 C – 07/02 E – EN pag. 30/48


Pressure drop across total heat recovery exchanger
EWAD-BJYNN - EWAD-BJYNN/Q
EWAD-BJYNN/A - EWAD-BJYNN/Z

Ž^›‘WœQ” – œGfŽ^›‘WœQšž– œGfŽ^›‘<ž—F – œ


F F460.4 – 495.4 S F–- 520.4
T-U
ŽR’‘ŸœF—f”Q– œ
F 426.4R
Ž^›‘<•œœ– •SfŽ^›‘<•Fž™– •SfŽ^›‘<•š—– •
F F344.3 – 358.3 O F-– P -Q
392.3
ŽR’‘:•—f˜Q– •
F 327.3N
ŽR’‘:•“>—– •
F 312.3 M
ŽR’‘<—FšF”Q– •
F 296.3L
ŽR’‘<—F˜FšQ– •
F 279.3K
Ž^’‘Ÿ—F—Fš– —FfŽ^›‘Ÿ—œ¡“– —EfŽ^›‘Ÿ—FžF™Q– —EfŽ¢›‘Ÿ—F”F Q– •SfŽ¢’‘Ÿ—f˜•Q– —
F F F
229.2 – 241.2 –F258.2 F -– G 260.3 - H–F-273.2
I-J
Ž^’‘<—œf Q– •
F 240.3E
Ž^’‘<—“—– —
F 212.2D
Ž^’‘“8š”Q– —
F 196.2
C
Ž^’‘“8˜™Q– —
F 178.2B
Ž^’‘“8”•Q– —
F 163.2
A
v0x-x
t-x
s-x
-x

 }-x
ˆ
‚
|-x
Œ‹
(kPa)
drop (kPa)

Š
{x
di carico

†‰
ˆ
„
z-x
…† ‰
Pressure

ˆ
Perdita

…† ‡
y-x
‚ ƒ„

v0x
sutwv0x y-x z-x {x |-x~}-x€-x)s-xt-xWv0x-x y-x-x

 

Portata
Water acqua
flow 
rate (l/s)
(l/s)

D – 510 C – 07/02 E – EN pag. 31/48


System Pre-start Checklist
Yes No N/A

Chilled water
Piping complete
Water system filled and vented
Pump installed, (rotation checked), strainers cleaned
Controls (3-way valves, face and bypass dampers, by-pass valves, etc.) operative
Water system operated and flow adjusted to meet unit design requirements

Heat recovery Condensers


Piping and headers complete
Water system filled and vented
Temperature sensors installed in the water well pockets
Pump installed, (rotation checked), strainers cleaned
Controls (3-way valves, face and bypass dampers, by-pass valves, etc.) operative
Water system operated and flow adjusted to meet unit design requirements

Electrical
Power leads connected to starter
All interlock wiring to the control panel complete and in accordance with specification
Pump starter and interlock wired
Wiring complies with local codes

Miscellaneous
Thermometer wells, thermometers, gauges, control wells, controls, etc., installed
A minimum 60% of system capacity is available for tests and control adjustments

Note: This check list must be completed and sent to the local DAIKIN service center two weeks prior to start-up.

Operation
Operator Responsibilities
It is important that the operator become familiar with the equipment and the system before attempting to operate the
chiller. In addition to reading this manual, the operator should study the operating manual for the control panel (latest
edition) and the electrical wiring diagram furnished with the unit before starting, operating, or shutting it down.
During the initial start up of the chiller, the DAIKIN technician will be available to answer any questions and advise
procedures for a correct operation.
It is recommended that the operator maintain a separate operation log for each chiller unit. In addition, a separate
maintenance log, specific for periodic maintenance and service activities, should be kept in place.
If the operator encounters abnormal or unusual operating conditions, it is recommended that a DAIKIN service technician
be consulted.

Refrigeration Cycle
The low-pressure refrigerant gas from the evaporator enters the screw compressor through the motor, thus cooling motor
windings. The compressor compresses the refrigerant from low to high pressure and during this process oil is injected
into the screw chamber for cooling, lubrication and sealing purposes. As a result of the injection of oil, a mixture of oil and
refrigerant reaches the high efficiency oil separator where both elements are separated by the combined action of
centrifugal force and low velocity,
As the gas leaves from the top of the oil separator, the oil flows down the receiver walls and is forced, by the effect of the
differential pressure between suction and discharge sides, back into the compressor injection port.
After leaving the oil separator, the high pressure and hot gas goes through the “four-way valve” and, depending on the
unit operation mode, enters either the air-cooled coil condenser (cooling mode) or the heat recovery water condenser
(heat recovery mode).

D – 510 C – 07/02 E – EN pag. 32/48


In either heat exchanger, the hot gas is cooled by the ambient air in the first case or by the water in the second case,
changing from gas to liquid phase.
Before leaving the condensing section, the liquid refrigerant is led into the sub-cooler where it is cooled below its
saturation temperature, thus compensating for the pressure drop along the liquid line and improving the capacity of the
evaporator.
After leaving the sub-cooler, the liquid refrigerant enters the liquid receiver, where the exceeding charge is accumulated
during the “cooling mode” in order to compensate for the different volume (refrigerant side) between the coil condenser
and the heat recovery condenser. The liquid refrigerant goes through the filter dryer, where any existing particles of
humidity are removed, and then through the expansion valve.
At that point, there will be a mixture of low-pressure liquid and gas refrigerant which enters the evaporator and takes the
heat load from the chilled water, thus completing the process and allowing a new cycle to start.

Refrigerant circuit
EWAD-BJYNN - EWAD-BJYNN/Q
EWAD-BJYNN/A - EWAD-BJYNN/Z

ST1 WL1

Y6

EVAPORATOR

ST2 WL2

Y6

D – 510 C – 07/02 E – EN pag. 33/48


D – 510 C – 07/02 E – EN pag. 34/48
Refrigerant circuit
EWAD-BJYNN – EWAD-BJYNN/Q
EWAD-BJYNN/A – EWAD-BJYNN/Z
with Heat Recovery Option
Controller
The controller can be used to modify the setpoints of the unit and to check control parameters. A display
shows the machine' s operating status, programming values and setpoints (e.g. temperatures and pressures
of fluids such as water and refrigerant). This control device maximizes the DAIKIN chiller energy efficiency
and reliability. It uses sophisticated software with predictive logic to select the most energy-efficient
combination of compressor, electronic expansion valve and condenser fan to keep stable operating
conditions and maximize energy efficiency. The compressors are automatically used on a rotation basis to
ensure even operating hours. The controller protects critical components in response to external signals
received from the system field sensors measuring: motor temperatures, refrigerant gas and oil pressures,
correct phase sequence and phase failure.

Control section - main features:


• Management of the compressor capacity slide and the electronic expansion valve in accordance with
the distributed multiprocessor logic system
• Chillers enabled to work in partial failure condition thanks to the distributed multiprocessor logic
system
• Full operational routines for following conditions:
- High ambient temperature
- High thermal load
- High evaporator inlet water temperature (start-up)
• Display of evaporator inlet/outlet water temperature
• Display of both condensing and evaporating temperatures and pressures, and both suction and
discharge superheat temperatures for each circuit
• Regulation of cooled water outlet temperature. Temperature tolerance ± 0,1°C
• Compressors and evaporator pump hour counters
• Display of status of safety devices
• Equalization of the number of running sessions and working hours of the different compressors
• Excellent management of compressors load
• Management of cooling tower fans according to condensing pressure
• Automatic re-start in case of power supply interruption (adjustable)
• Soft load
• Return temperature reset
• Reset according to air outside temperature value
• Setpoint Reset
• Demand limit or Current limit
• Speedtrol control (optional)

Safety - each refrigerant circuit


High pressure (pressure switch)
Low pressure (pressure switch)
Compressor overload
Condenser fan magneto-thermal protection
High discharge temperature on the compressor
Phase monitor
Star / Delta transition failure
Low delta (differential) pressure between suction and discharge
Low pressure ratio
High oil pressure drop
Low oil pressure

D – 510 C – 07/02 E – EN pag. 35/48


Safety - system
Phase monitor
Freeze protection
One evaporator flow input to controller (stops the unit)
Remote on/off input.

Regulation type
Proportional + integral + derivative regulation with feed-back input taken from the temperature sensor at the
evaporator water outlet.

Condensation
The condensation control can be based on temperature or on pressure. The fans can be managed according
to ON/OFF mode or with a 0/10 V modulating signal.

Controller terminal
The controller terminal has following features:
• 4-line by 20-character backlit liquid crystal display
• Key-pad consisting of 15 keys using a “clear language presentation”
• Memory to protect the data
• General faults alarm LED
• 4-level password access to modify settings
• Service report displaying all running hours and general conditions
• Memorized alarm history to facilitate fault analysis.

Tele-maintenance and supervisory system


The controller can be monitored locally or via modem using the supervisory program.

The supervision system is the best solution:


• To centralize all the information in just one local and/or remote PC
• To check all the parameters for each unit connected
• Temperature – pressure data logging
• Printouts of alarms, parameters and graphs
• To control several plants, located in different geographical areas, from a central station
• To manage the Service centers

The supervisory system allows:

• Displaying all working conditions for each controller


• Displaying their graphics
• Displaying and printing current alarms
• Connection between local and remote computer via telephone line (Modem)
• Switching units ON / OFF
• Changing setpoint.

Remote control
Compatibility with supervisory systems is becoming increasingly important in the HVAC industry. The unit
controller allows easy interfacing with BMS (Building Management Systems), the external world that may be:

• fully compatible with Siemens, Johnson;


• any MODBUS compatible system (Satchwell, Honeywell);
• BacNet point to point, ECHELON FTT10 (available on request).
D – 510 C – 07/02 E – EN pag. 36/48
Heat Recovery Microprocessor Control
All the units equipped with heat recovery water condensers have an additional “microprocessor control” to manage
the heat recovery function of the unit.
The microprocessor is installed inside the main control box, below the key pad. (see the picture below)

HEAT RECOVERY
OPERATION
Key Pad
Chiller Operation Switch Selector “Q7”
“0” Cooling Mode
“1” Heat Recovery
Mode

Heat Recovery
Microprocessor
Control
Carel type “ IR32”

We use two different models of microprocessor control.


IR32W units with two heat recovery condensers
IR32Z units with three or four heat recovery condensers

Both models are equipped with NTC PT100 temperature sensors to control the inlet water temperature of the
heat recovery condenser and to measure the hot outlet water temperature.
The temperature sensors are supplied electrically connected to the microprocessor but not fitted in the pipe
well pockets; the installation must be done locally by the installer.

The identification of the sensors goes as follows:


“W10” to be installed at the condenser inlet
“W11” to be installed at the condenser outlet
Function
When the heat recovery mode is enabled by the selector switch Q7, if the sensor “W10” reads a water
temperature value below the current setpoint, the control will allow the first stage to switch the four-way valve
from chiller to heat recovery position.
If the setpoint temperature is not achieved, the microprocessor will activate the rest of control stages that,
depending on the number of refrigerant circuits, are available. On the contrary, if the water temperature
exceeds the setpoint value, the microprocessor will switch off control stages until the temperature is within
the regulation band.
Of course it is mandatory that the heat recovery condenser flow switch is on, otherwise the unit will not
enable the heat recovery cycle.
The Microprocessor control is normally set at the factory. To verify or change the setpoints, please refer to
the user manual supplied with the unit.

Heat Recovery Operation


The units supplied with heat recovery condensers are equipped with an additional microprocessor (TC10, see
electrical wiring diagram) for hot water temperature control, featuring two, three or four control stages depending
on the number of heat exchangers installed on the unit (one stage per compressor). For information on how to set
this microprocessor see the Specific manual supplied with the unit. The heat recovery mode is available only when
D – 510 C – 07/02 E – EN pag. 37/48
there is a request for cooling while the system load can be balanced by adjusting the number of compressors
running and their load condition.
To run the unit in heat recovery mode follow the points listed below:
1) Verify that the installation of the water flow switch was done by the installer and check the electrical
connection at M3.426 and M3.427 terminal blocks inside the electrical panel
2) Check that the microprocessor sensor is fitted in the pocket well of the water return common header (done by
the installer)
3) Check the set point of the return water temperature on the display of the microprocessor “TC10” (Carel IR32).
Do not exceed the max allowed water temperature (see the operating limits) to avoid the shut-down of the unit
on high pressure.
4) Switch on the water pump
5) Switch “ON” the selector “Q7” that allows the unit to run in heat recovery mode. If the microprocessor TC10
demands hot water, the 4 way-valve in the refrigerant circuit will switch from condenser coil function to heat
recovery condenser function (first control stage) and continue to activate additional circuits until the hot water
return temperature reaches the set point. In that scenario, the fan motors of the respective condenser coils are
switched “OFF”. Vice-versa, when the microprocessor is reducing the number of control stages, the 4 way-
valve changes the refrigerant circuit from the heat recovery condenser to the condenser coil, while also
switching on the respective fan motors.
6) In case of lack of water in the heat recovery condenser, the unit is automatically put in cooling mode only.

Standard controls
High pressure control
The high pressure switch will shut-down the compressor when the discharge pressure exceeds the setting point
value.

Phase/voltage monitor
The phase/voltage monitor is a device which provides protection against three-phase electrical motor fault
conditions such as power failure, phase failure, and phase reversal. Whenever any of these conditions occur, an
open contact signal is sent to the microprocessor which then de-energizes all inputs. Once power is restored,
contacts close and the microprocessor enables compressors for operation. When three-phase power has been
applied, the output relay should close and the "run light" should turn on. If the output relay does not close, perform
the following tests:

1. Check the voltages between L1-L2, L1-L3 and L2-L3 (L1, L2, L3 are the three phases). These voltages should
be even and within + 10% of the rated three-phase line-to-line voltage.

2. If these voltages are extremely low or widely unbalanced check the power system to determine the cause of the
problem.

3. If the voltages are good, using a phase tester, verify that phases are in A, B, C sequence for L1, L2 and L3.
Correct rotation is required for compressor operation. If it is necessary to correct the phase sequence, turn off the
power supply and interchange any two of the supply power leads wired to the main disconnect switch. This may be
necessary as the phase voltage monitor is sensitive to phase reversal. Turn on the power. The output relay should
now close after the appropriate delay.

Heat Recovery Microprocessor Set-up


The units supplied with heat recovery condensers are equipped with an additional microprocessor (TC10, see
electrical wiring diagram) for hot water temperature control, featuring two, three or four control stages depending
on the number of heat exchangers installed on the unit (one stage per compressor). For information on how to set
this microprocessor see the specific manual supplied with the unit.

D – 510 C – 07/02 E – EN pag. 38/48


The most important set-up values are given below. Please see the microprocessor manual for further details.

ITEM Description Setpoint


St1 Inlet water temperature set point Max 50
St2 N/A
CO Operating Mode 1
P1 Differential Set point 2
P2 N/A
C4 Authority 0.5
C5 1
C6 0
C7 3
C8 5
C9 0
C10 0
C11 0
C12 20”
C13 1
C14 0
C15 0
C16 100
C17 5
C18 0
C19 0
C21 30
C22 43
C23 N/A
C24 N/A
P25 8
P26 55
P27 2
P28 20
C29 4
C30 N/A
C31 0
C32 1
C33 0
C50 4
C51 0

System Maintenance
General
To ensure proper operation at peak capacity and to avoid damage to system components, a periodic inspections
program should be set up and followed. The information given below is intended as a guide to be used during
inspection and must be combined with observation of compressor sound and good electrical practices to ensure
trouble-free performance. The sight-glass indicator in the liquid line of every circuit must be checked to verify the
glass is full and clear. If the indicator shows a wet condition and/or there are bubbles in the sight-glass, even when
the system has a full refrigerant charge, the filter-dryer element must be changed.

Compressor maintenance
The screw compressor does not required frequent maintenance. However, a vibration test is an excellent check for
proper mechanical operation. Compressor vibration indicates that maintenance is required as it adversely affects
the performance and efficiency of the unit. It is recommended that the compressor be checked with a vibration
analyser at or shortly after start-up and again on an annual basis. When performing the test, the load should be
maintained as close to the rated load as possible. The vibration analysis provides a fingerprint of the compressor

D – 510 C – 07/02 E – EN pag. 39/48


and, if performed on a routinely basis, can give a warning on impending problems. The compressor is supplied
with a cartridge oil filter. It is a good practice to replace this filter anytime the compressor is opened for service.

Electrical control
Warning: Electric shock hazard. Turn off all electrical power supplies before attempting electrical service as
described below.

Caution: It is necessary to de-energize the complete electrical panel, including crankcase heater, before doing
any servicing inside.
Prior to attempting any service on the control panel, it is advisable to study the wiring diagram and understand the
operation system of the water chiller. Electrical components do not require any special maintenance other than a
monthly tightening of cable connections.

Warning: The warranty becomes void if the wiring connection to the unit is not in accordance with the
specification. A blown fuse or tripped protector indicates that a short, ground or overload condition exists.
Before replacing the fuse or restarting the compressor, the cause of the problem must be found and corrected. It is
important to have a qualified electrician service this panel. Unqualified tampering with the controls may cause
serious damage to the equipment and makes the warranty void.

Refrigerant sight-glass
The refrigerant sight-glasses should be observed periodically (a weekly observation should be adequate). A clear
liquid sight-glass indicates that the system is charged with the correct amount of refrigerant to ensure proper feed
through the expansion valve. Bubbling refrigerant in the sight-glass, during stable running conditions, indicates that
the system may be short of refrigerant charge. Refrigerant gas flashing in the sight-glass might also indicate an
excessive pressure drop in the liquid line, possibly due to a clogged filter-dryer or a restriction elsewhere in the
liquid line. If sub-cooling is low add refrigerant to make the sight-glass clear. If sub-cooling is normal and flashing
is visible in the sight-glass, replace the filter-dryer. The moisture condition of the refrigerant is indicated by the
changing color of the element inside the sight-glass. If the sight-glass does not indicate a dry condition after about
3 hours of operation, the unit should be pumped down and the filter-dryers changed.
The following table is a guide to determinate the dry or wet condition of the system:

COLOUR MEANS
Green (Sky Blue) Dry
Yellow (Pink) Wet

Filter-dryers
A replacement of the filter-dryer is recommended during scheduled service maintenance of the unit when, even if
sub-cooling temperature is normal, bubbles can be seen in the sight-glass. The filter-dryer should also be changed
if the colour of the moisture indicator in the sight-glass shows excessive humidity content. During the first few
months of operation, it might be necessary to replace the filter dryer if bubbles appear in the liquid line as
explained before. Any residual particles from the unit working process, compressor and miscellaneous
components are carried over by the refrigerant into the liquid line and retained by the filter-drier.
To change the filter drier, close the manual liquid line shutoff valve and pump the unit down by opening the
switches Q1, Q2 (ON/OFF switches of compressors) in “off” position.
Move the ON/OFF unit switch Q0 to the “off” position.
Close the suction line valve. Remove and replace the filter-drier. Evacuate the liquid line through the manual
shutoff valve to remove non-condensable that may have entered during filter replacement.
Open the suction line valve; open the liquid line manual shutoff valve. A leak check is recommended before putting
the unit in operation.

Electronic expansion valve


The air-cooled chiller is equipped with the most advanced electronic expansion valve, thus achieving precise
control of refrigerant mass flow. As today’s systems require improved energy efficiency, tighter temperature
control, and wider range of operating conditions, and incorporate features like remote monitoring and diagnostics,
the application of electronic expansion valves becomes mandatory. The electronic expansion valve has features
that make it unique: short opening and closing time, high accuracy, positive shut-off function that eliminates the
need for an additional solenoid valve, highly linear flow capacity, continuous modulation of mass flow without
stress in the refrigerant circuit and corrosion-resistant stainless steel body.

D – 510 C – 07/02 E – EN pag. 40/48


Evaporator
The units are supplied with optimized counter-flow evaporator, single refrigerant pass. It is direct expansion type (2
evaporators for units with 4 compressors), with refrigerant inside the tubes and water outside (shell side), carbon
steel tube sheets, and straight copper tubes, that are spirally wound internally for higher efficiency, expanded on
the tube plates. The external shell is linked to an electrical heater that prevents freezing at ambient temperatures
as low as -28ºC and is energized by a thermostat and covered with a closed cell insulation material. Each
evaporator has 2, 3 or 4 refrigerant circuits, one for each compressor. Each evaporator is manufactured in
accordance with PED standards. Normally, no service work is required on the evaporator.

D – 510 C – 07/02 E – EN pag. 41/48


Heat Recovery Condensers
Condensers are easy-to-clean shell and through-tube type. Standard configuration is 2 passes. The unit has
completely assembled independent exchangers, one per circuit. Each heat recovery condenser has integrally-
finned high-efficiency seamless copper tubes, roll-expanded into heavy carbon steel tube sheets. Water heads are
removable and include vent and drain plugs. The condensers are equipped with spring-loaded relief valves.
The condenser is designed to comply with PED standards. Waterside working pressure is designed as 10.5 bar.
Standard configuration on water connection side is 2 passes.
The installer must provide both inlet and outlet water connection headers for all heat recovery condensers installed
on the unit, and provide the flow switch as well. All the heat recovery condensers must be connected together in
parallel. A temperature sensor, supplied with the unit, must be installed on the inlet water pipe for control of the
heat recovery cycle.

Condenser coil fans


The condenser fans are helical type with wing-profile blades for a better performance. The direct coupling to the
electrical motor helps reduce vibrations during operation. The three-phase motors are supplied with IP54
protection as standard (Insulation class F); they are protected against overloading and short circuits by circuit
breakers located inside the electrical control panel.

Air-cooled condenser (Condensing coil)


The condensing coils are made of internally enhanced seamless copper tubes arranged in a staggered row pattern
and mechanically expanded into DAIKIN lanced and rippled aluminum condenser fins with full fin collars. An
integral sub-cooler circuit provides sub-cooling to effectively eliminate liquid flashing and increase cooling capacity
without increasing the power input.
No maintenance is normally required except for occasional removal of dirt and debris from the outside surface of
the fins. DAIKIN recommends the use of foaming coil cleaners available at air conditioning supply outlets. Use
caution when selecting such cleaners as some may contain potentially harmful chemical. Care should be taken not
to damage the fins during cleaning.

Lubricating oils
In addition to lubricating the bearing and other moving parts, the oil has the equally important task of sealing the
clearances between the rotors and other potential leakage paths, thus improving pumping efficiency; the oil also
helps dissipate the heat of compression. The amount of oil injected is therefore well in excess of that required for
lubrication alone. To reduce the oil circulation in the refrigerant circuit, the oil separator is installed on the
compressor discharge line
Lubricating oil approved by DAIKIN is mentioned on the compressor label.
The oil pressure transducer monitors the oil injection pressure in the compressor. If the oil pressure value is below
the setpoint for microprocessor control, the compressor stops.
The oil pressure is generated by the discharge pressure; therefore this must maintain a minimum value, which will
increase as the suction pressure increases, so that the required pressure difference is maintained.

Crankcase and oil separator heaters


The function of the Oil separator heaters is to prevent oil dilution with refrigerant during compressor shutdown,
which would cause foaming and consequent reduction in lubricating oil flow to the moving parts. Electric heaters
are energized every time the compressors shuts-down.

Warning: Make sure that the heaters have been energized at least 12 hours prior to the start-up.

Refrigerant

Refrigerant charging
These air-cooled screw chillers have been factory-charged with a full operating charge of refrigerant; however,
there might be times when the unit must be recharged at the jobsite. Follow these recommendations when
charging in the field. Refer to the unit operating charge found in the table of physical data, pages 9 through 15,
according to the version of the unit, either chiller or heat recovery . The optimum charge is the charge that allows
the unit to run with no flashing in the liquid line at any operating conditions. When the liquid line temperature does
not drop with the addition of 2,0-4,0 kg of charge and the discharge pressure goes up by 20-35 kPa then the sub-
cooler is nearly full and proper charge has been reached. Unit can be charged at any steady load condition, at any
outdoor ambient temperature. Unit must be allowed to run for 5 minutes or longer so that the condenser fan

D – 510 C – 07/02 E – EN pag. 42/48


staging is stabilized at normal operating discharge pressure. For best results charge the unit with 2 or more
condenser fans operating per refrigerant circuit.
In case moisture is detected in the moisture indicator, the system must be evacuated to eliminate the cause of
trouble. After the problem has been solved, the system must be dried by making an almost perfect vacuum. For
this purpose, a displacement vacuum pump should be used.
When the system has been opened for extensive repairs, such as an overhaul, the following evacuation procedure
is advised:
1. Evacuate the refrigerant system by means of a vacuum pump until the value 200 Pa (1,5 mm Hg) is reached.
2. Break the vacuum with nitrogen until the atmospheric pressure is reached.
3. Repeat operations 1 and 2 for two times.
4. Evacuate the refrigerant system until the value of 66,5 Pa is reached.
The dry nitrogen, used to break the vacuum, will absorb any moisture and air left in the system, and they will be
almost completely removed after three evacuations. If burnt oil or sludge are found in the refrigerant circuit
(caused by the compressor motor burn-out), it will be necessary to carefully clean the system, before attempting
the vacuum operation, by using the filter dryer clean-out method, which basically involves the use of special filter
dryers including a suitable desiccant in both the liquid and suction lines.
Excessive refrigerant losses can also cause leak of oil from the system. Check the oil level during operation and
ensure that oil is visible in the top sight-glass of the oil separator.
1. If the unit is slightly undercharged, it will show bubbles in the sight-glass. Recharge the unit.
2. If the unit is moderately undercharged, it will, most likely, trip on freeze protection. Recharge the unit as
described in the charging procedure below.

Procedure to charge a moderately undercharged unit


1. If a unit is low on refrigerant, you must first determine the cause before attempting to recharge the unit. Locate
and repair any refrigerant leak. Evidence of oil is a good indicator of leakage; however, oil might not be visible
in all cases. Liquid leak detector fluids work well to show bubbles in medium size leaks but electronic leak
detector may be needed to locate small leaks.
2. Add the charge to the system through the valve on the evaporator inlet pipe, between the expansion valve and
the evaporator head. Follow the procedure described in “Refrigerant charging”.
3. The charge can be added at any load condition.

Charging the refrigerant


1. Connect the refrigerant bottle with a filling pipe to the filling valve on the evaporator head. Before firmly
tightening the refrigerant bottle valve, open it and force the air out of the filling pipe. Tighten the charging valve
connection and fill the refrigerant.
2. When the refrigerant stops flowing into the system, start the compressor and complete the refrigerant charge.
3. If you do not know how much refrigerant has to be added, shut off the bottle valve every 5 minutes and continue
to charge the refrigerant until the sight glass is clear and free of bubbles.

Note: Do not discharge the refrigerant into the atmosphere. To recover it, use empty, clean and dry bottles. The
liquid refrigerant recovery can be made through the valve provided on the condenser coil sub-cooler outlet. To
facilitate the recovery of refrigerant, put the bottle inside a container full of ice; avoid excessive filling of the bottle
(70÷80% max).

D – 510 C – 07/02 E – EN pag. 43/48


Preventive maintenance schedule
SCHEDULE
Operation
TYPE OF OPERATION Six-
Ref. No. Weekly Monthly Yearly
Monthly
1 Reading and recording of suction pressure x
2 Reading and recording of discharge pressure x
3 Reading and recording of supply voltage x
4 Reading and recording of current intensity x
Check the circuit for refrigerant charge and possible
5 x
moisture by observing the liquid sight glass
6 Check the suction temperature and the superheating x
7 Check setting and operation of safety devices x
8 Check setting and proper operation of control devices x
9 Inspect the condenser for possible scaling or damages x

Start-up and shut-down

Start-up
− Verify that all shut-off valves are open.
− Prior to starting the unit, open the water circulation pump(s) and regulate the flow through the evaporator
and through the heat recovery condensers (if supplied) in accordance with the working conditions of the
unit. If no flow meter is available in the water system, it is recommended to adjust the water flow, as a first
step, by establishing the corresponding differential pressure drop across the heat exchangers as specified
in the pressure drop diagram. The final set up will be done, when the unit is running, by adjusting the
water flow to reach the water "∆Τ” at full load.
− Verify that both evaporator inlet and outlet water temperature sensors indicate the same temperature as
the local thermometers, or the discrepancy does not exceed 0,1°C.
− Verify that the inlet water temperature sensor of the heat recovery condenser (if supplied) has been
installed in a well pocket on the common pipe and indicates the same temperature as the local
thermometer, or the discrepancy does not exceed 0,1°C.
− Verify that the flow switch(es) is(are) connected to the electrical panel at the terminal blocks M3.8 – M3.23
for the evaporator and M3.426 – M3.427 for heat recovery condensers (if supplied).
− Check the electrical power connection to the electrical panel and put all the switches in “OFF” position.
Switch “ON” the main switch isolator “Q10” and the selector “Q12”. In this way the electric heaters of the
compressors and the oil separators are energized.
− Check if the software installed on the microprocessor corresponds to the unit type and make sure that the
setpoints are correct. See the controller operating manual for instructions
− Turn the selector switch Q0 to ”Local” position. For normal unit operation, if the unit is controlled remotely,
switch Q0 to “remote” position.
− Push the “on/off” button on the keypad and wait for the green light.
− Before turning the Q1 selector to ON position, check that the Q10 and Q12 have been switched ON at
least 12 hours before. The controller, if there is a cooling load demand, will start the corresponding
compressor. Repeat the sequence for Q2, Q3, Q4 selectors depending on the number of compressors
installed.

Operational Shut-down
− Push the “On/Off” button on the keypad, or use remote switch, to de-energize the unit. The green light will
turn off and all the compressors will carry out their pump-down cycle and then stop.
− Switch off the water pumps

Seasonal Shut-down
− Turn the Q1 selector to Off position. The compressor will carry out its pump-down cycle and then stop.
− Repeat the sequence for all the selectors Q2, (Q3 and Q4) to stop all the other compressors.
− Switch the “Q0” selector from “Local” to off position.
D – 510 C – 07/02 E – EN pag. 44/48
− Push the “On/Off” button on the keypad to de-energize the unit, green light becomes off.
− Open the circuit breaker Q12 to stop the auxiliary circuit.
− Open the main switch Q10 to disconnect the power supply to the unit. In this condition the oil electric
heater is off. When you restart the unit, before switching on the compressors, wait for at least 12 hours to
warm up the oil.
− Close the shut-off valves of the refrigerant circuits.
− Switch off the water pumps
− Empty the water heat exchangers or fill them with glycol for freeze protection.

Maintenance Shut-down
− Turn the Q1 selector to Off position. The compressor will carry out its pump-down cycle and then stop.
− Repeat the sequence for all the selectors Q2, (Q3 and Q4) to stop all the other compressors.
− Switch the “Q0” selector from “Local” to off position.
− Push the “On/Off” button on the keypad to de-energize the unit, green light become off.
− Open the circuit breaker Q12 to stop the auxiliary circuit.
− Open the main switch Q10 to disconnect the power supply to the unit. In this condition the oil electric
heater is off. When you restart the unit, before switching on the compressors, wait for at least 12 hours to
warm up the oil.
− Close the shut-off valves of the refrigerant circuits.
− Switch off the water pumps
− Service the unit in accordance with the program

Procedure to return materials under warranty


Material may not be returned except with permission from DAIKIN Service department. A "Returned Goods" tag
will be included with the returned material to expedite handling at our factory. Return of the parts does not
constitute an order for replacement. Therefore, a purchase order must be entered through our nearest Sales
Representative. The order should include part name, part number, model number and serial number of the unit
involved. After DAIKIN inspection of the returned part, if the failure is due to faulty material or workmanship, credit
will be issued on the customer' s purchase order. All defective parts shall be returned to DAIKIN factory,
transportation charges prepaid.

Service & replacement parts


Always report the model number, acknowledgement number and the unit serial number stamped on the
nameplate, whenever ordering maintenance service or replacement parts.
When ordering replacement parts, state the installing date of the machine and the date of the failure. For an exact
definition of the replacement part requested, please mention the respective code number or, should this not be
possible, attach a description of the part being requested.

D – 510 C – 07/02 E – EN pag. 45/48


Troubleshooting chart
PROBLEM POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS
1. Main power switch open. 1. Close switch.
2. Unit system switch open. 2. Check unit status on Control Panel. Close
switch.
3. Circuit switch in pump-down position. 3. Check circuit status on Control Panel.
Close switch.
4. Evaporator flow switch not closed. 4. Check unit status on Control Panel. Close
switch.
5. Circuit breakers open. 5. Close circuit breakers.
6. Fuse blown or circuit breakers tripped. 6. Check electrical circuits and motor
windings for shorts or grounds.
Investigate the possibility of overload.
Check for loose or corroded connections.
Reset breakers or replace fuses after fault
is corrected.
Compressor will
7. Unit phase voltage monitor not satisfied. 7. Check unit power wiring to unit for correct
not run
phasing. Check voltage.
8. Compressor overload tripped. 8. Overloads are reset manually. Reset
overload button.
Clear alarm on Microprocessor.
9. Defective compressor contactor or 9. Check wiring. Repair or replace contactor.
contactor coil.
10. System shut down by safety devices. 10. Determine type and cause of shutdown
and correct problem before attempting to
restart.
11. No cooling required. 11. Check control settings. Wait until unit calls
for cooling.
12. Motor electrical trouble. 12. See 6, 7, 8 above.
13. Loose wiring. 13. Check circuits for voltage at required
points. Tighten all power wiring terminals.
1. Low voltage during high load condition. 1. Check supply voltage for excessive
Compressor voltage drop.
Overload Relay 2. Loose power wiring. 2. Check and tighten all connections.
Tripped or 3. Power line fault causing unbalanced 3. Check supply voltage.
Circuit Breaker voltage.
Tripped or Fuses 4. Defective or grounded wiring in the motor. 4. Check motor and replace if defective.
Blown 5. High discharge pressure. 5. See corrective steps for high discharge
pressure.
Compressor
1. Compressor internal problem. 1. Contact DAIKIN.
noisy or
2. Oil injection not adequate. 2. Contact DAIKIN.
vibrating
Compressor will 1. Defective capacity control. 1. See Capacity control section.
not load or 2. Unloader mechanism defective. 2. Replace.
unload 3. Control solenoids defective. 3. Replace.

D – 510 C – 07/02 E – EN pag. 46/48


Troubleshooting chart
PROBLEM POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS
1. Discharge shutoff valve partially closed. 1. Open shutoff valve.
2. Non condensable in the system. 2. Purge the non condensable from the
condenser coil after shutdown.
3. Fans not running. 3. Check fan fuses and electrical circuits.
4. Fan control out of adjustment. 4. Check that unit set-up in Microprocessor
matches the unit model number. Check
Microprocessor condenser pressure
High discharge
sensor for proper operation.
pressure.
5. Heat recovery condensers dirty. 5. Clean the condenser tubes by mechanical
or chemical tools
6. System overcharged with refrigerant. 6. Check for excessive sub-cooling. Remove
the excess charge.
7. Dirty condenser coil. 7. Clean the condenser coil.
8. Air re-circulation from outlet into unit coils. 8. Remove the cause of re-circulation.
9. Air restriction in the unit. 9. Remove obstructions near unit.
1. Wind effect at low ambient temperature. 1. Protect unit against excessive wind into
vertical coils.
2. Condenser fan control not correct. 2. Check that unit set-up in Microprocessor
Low discharge
matches the unit model number.
pressure
3. Low suction pressure. 3. See Corrective steps for low suction
pressure.
4. Compressor operating unloaded. 4. See Corrective steps for failure to load.
1. Inadequate refrigerant charge quantity. 1. Check liquid line sight-glass. Check unit
for leaks.
2. Evaporator dirty. 2. Carry out chemical cleaning.
3. Clogged liquid line filter-drier. 3. Replace.
4. Expansion valve malfunctioning. 4. Check expansion valve superheat and
valve opening position. Replace the valve
Low suction only if certain that the valve is not working.
pressure 5. Insufficient water flow to evaporator. 5. Check water pressure drop across the
evaporator and adjust the flow.
6. Water temperature leaving evaporator is 6. Adjust water temperature to higher value.
too low.
7. Evaporator head ring gasket slippage. 7. Low suction pressure and low superheat
both present may indicate an internal
problem. Consult factory.
1. Excessive load - high water temperature. 1. Reduce load or add additional equipment.
2. Compressor unloaders open. 2. See Corrective Steps below for failure of
High suction compressor to load.
pressure 3. Superheat is too low. 3. Check superheat on Microprocessor
display. Check suction line sensor
installation and the sensor itself.
1. “Q7” selector switch doesn’t work. 1. Replace the selector switch
2. No Heating load required. 2. Add additional equipment.
3. Flow switch not operating. 3. Check water pump.
4. 4-way solenoid valve not working. 4. Check the solenoid valve and if the 4-way
Unit doesn’t
valve is blocked. Replace the wrong
switch in Heat
components.
Recovery
5. “W10” sensor element not fixed in the well 5. Fix the element in the well pocket properly.
operation Mode
pocket.
6. “W10” sensor element gives wrong signal. 6. Replace the element.
7. “TC10” Microprocessor control doesn’t 7. Check the supply connections or replace
work. them.

D – 510 C – 07/02 E – EN pag. 47/48


We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding.

Air-cooled screw chillers


EWAD 650-C18BJYNN
EWAD 550-C12BJYNN/Q
EWAD 650-C21BJYNN/A
EWAD 600-C10BJYNN/Z

Daikin units comply with the European


regulations that guarantee the safety of
the product.

Daikin Europe N.V. is participating in the


EUROVENT Certification Programme.
Products are as listed in the EUROVENT
Directory of Certified Products.

Zandvoordestraat 300
B-8400 Ostend – Belgium
www.daikineurope.com

You might also like