Calculating Cable Fault Ratings
Calculating Cable Fault Ratings
When selecting a cable, the performance of the cable under fault conditions is an important consideration. It is important that
calculations be carried out to ensure that any cable is able to withstand the effects of any potential fault or short circuit. This
note looks at how to do this.
The primary concern with cables under a fault condition is the heat generated, and any potential negative effect this may have
on the cable insulation.
Calculation of fault rating is based on the principle that the protective device will isolate the fault in a time limit such that the
permitted temperature rise within the cable will not be exceeded.
Contents [hide]
1. The adiabatic equation
2. Derivation - Adiabatic Equation and k
1. Obtaining Values of k
3. Non-adiabatic effects
4. Other Cable Fault Issues
5. References
The normally used equation is the so-called adiabatic equation. For a given fault of I, which lasts for time t, the minimum
required cable cross sectional area is given by:
−−−
√ I 2t
A=
k
A=I2tk
Alternatively, given the cable cross section and fault current, the maximum time allowable for the protective device can be
found from:
https://myelectrical.com/notes/entryid/242/calculating-cable-fault-ratings 1/6
8/25/2021 Calculating Cable Fault Ratings
k 2 A2
t=
I2
t=k2A2I2
The factor k is dependant on the cable insulation, allowable temperature rise under fault conditions, conductor resistivity and
heat capacity. Typical values of k are:
Value of k
Temperature Conductor Material
Initial °C] Final [°C] Copper Aluminium Steel
Thermoplastic 70°C (PVC) 70 160/140 115/103 76/78 42/37
*where two values; lower value applied to conductor CSA > 300 mm2
* these values are suitable for durations up to 5 seconds, source: BS 7671, IEC 60364-5-54
Tip: for a better understanding of cable insulation and how it is categorised, refer to our Cable Insulation
Properties note .
Example
Consider a maximum fault current of 13.6 kA and the protective device trips in 2.6 s. The minimum safe cable cross sectional
area of a copper thermosetting 90°C cable (k=143) is:
−−−−−−−−−−
√ 136002 × 2.6
S= = 154mm 2
143
S=136002×2.6143=154mm2
Any selected cable larger than this will withstand the fault.
https://myelectrical.com/notes/entryid/242/calculating-cable-fault-ratings 2/6
8/25/2021 Calculating Cable Fault Ratings
The term adiabatic applies to a process where there is no heat transfer. For cable faults, we are assuming that all the heat
generated during the fault is contained within the cable (and not transmitted away). Obviously this is not fully true, but it is on
the safe side.
Q = cmΔT
Q=cmΔT
Q = I 2 Rt
Q=I2Rt
m = ρ cAl
m=ρcAl
ρr l
R=
A
and R=ρrlA
https://myelectrical.com/notes/entryid/242/calculating-cable-fault-ratings 3/6
8/25/2021 Calculating Cable Fault Ratings
I 2 Rt = cmΔT
I2Rt=cmΔT
ρr l
I 2t = cρ cAlΔT
A
I2tρrlA=cρcAlΔT
−−−
√ I 2t
S=
k
S=I2tk
−−−−−−
cρ cΔT
k=√
ρr
by letting k=cρcΔTρr
ΔT = θf − θi
ΔT=θf−θi
Units: are expressed in g (grams) and mm2, as opposed to kG and m. This is widely adopted by cable specifiers.
The equations can easily be redone in kG and m if required.
Obtaining Values of k
A more common approach for is to use the tabulated values for k, for example, from BS 7671[1].
https://myelectrical.com/notes/entryid/242/calculating-cable-fault-ratings 4/6
8/25/2021 Calculating Cable Fault Ratings
−−−−−−−−−−−−−−−−−−−−
Q c (β + 20) β + θf
k=√ ln ( )
ρ 20 β + θi
k=Qc(β+20)ρ20ln(β+θfβ+θi)
Substituting the above values and rearranging the IEC equation slightly, gives:
−−−−−−−−−−−−−−−−
θf − θi
k = 226√ ln (1 + )
234.5 + θi
k=226ln(1+θf−θi234.5+θi)
- copper conductors
−−−−−−−−−−−−−−−
θf − θi
k = 148√ ln (1 + )
228 + θi
k=148ln(1+θf−θi228+θi)
- aluminium conductors
−−−−−−−−−−−−−−−
θf − θi
k = 78√ ln (1 + )
202 + θi
k=78ln(1+θf−θi202+θi)
- steel
Non-adiabatic effects
https://myelectrical.com/notes/entryid/242/calculating-cable-fault-ratings 5/6
8/25/2021 Calculating Cable Fault Ratings
As mentioned, the adiabatic equation assumes no heat is dissipated from the cable during a fault. While putting the
calculation on the safe side, in some situations, particularly for longer fault duration there is the potential to be able to get
away with a smaller cross section. In these instances, it is possible to do a more accurate calculation.
Considering non-adiabatic effects is more complex. Unless there is some driver, using the adiabatic equations is just easier.
Software is available to consider non adiabatic effects, however, there is a cost, time and complexity associated with this.
The IEC also publish a standard which deals with non-adiabatic equations:
IEC 60949 "Calculation of thermally permissible short-circuit current, taking into account non-adiabatic heating
effects".
The method adopted by IEC 60949 is to use the adiabatic equation and apply a factor to cater for the non-adiabatic effects:
I = εI AD
I=εIAD
The bulk of the IEC 60949 standard is concerned with the calculation of ε.
electro-mechanical stress and fault levels large enough to cause cable failure
performance of joint and terminations under fault conditions
While in most cases the none heating effects are not serious, there may be situations where these could pose a risk to the
cable or equipment/personnel in the vicinity.
References
[1]. BS 7671 - Requirements for Electrical Installations. 17th ed. United Kingdom: IEE; 2008.
[2] IEC 60364-5-54 Low-voltage electrical installations - Part 5-54: Selection and erection of electrical equipment -
Earthing arrangements and protective conductors. 3rd ed. IEC; 2011.
https://myelectrical.com/notes/entryid/242/calculating-cable-fault-ratings 6/6