03 Water Cooled Chillers
03 Water Cooled Chillers
03 Water Cooled Chillers
HVAC CHILLER
EQUIPMENT
Water-Cooled
Chillers
Technical Development Programs (TDP) are modules of technical training on HVAC theory,
system design, equipment selection and application topics. They are targeted at engineers and
designers who wish to develop their knowledge in this field to effectively design, specify, sell or
apply HVAC equipment in commercial applications.
Although TDP topics have been developed as stand-alone modules, there are logical group-
ings of topics. The modules within each group begin at an introductory level and progress to
advanced levels. The breadth of this offering allows for customization into a complete HVAC
curriculum – from a complete HVAC design course at an introductory-level or to an advanced-
level design course. Advanced-level modules assume prerequisite knowledge and do not review
basic concepts.
Water-cooled chillers range in size from small 20-ton capacity models that can fit in an eleva-
tor to several thousand-ton models that cool the world’s largest facilities such as airports,
shopping centers, skyscrapers, and other facilities. This TDP module will review all sizes of wa-
ter-cooled chillers, but will contain more information on the larger chillers in the range of 200-ton
and upward. Screw and centrifugal compressor water-cooled chillers tend to be the most popular
designs for larger commercial applications, while scroll and reciprocating compressor chillers are
used on the smaller ones. Air-cooled chillers are covered in a companion module, TDP-622.
Printed in Syracuse, NY
CARRIER CORPORATION
Carrier Parkway
Syracuse, NY 13221, U.S.A.
Table of Contents
Introduction...................................................................................................................................... 1
The First Centrifugal.................................................................................................................... 1
Water-Cooled versus Air-Cooled Chillers................................................................................... 2
Basic Refrigeration Cycle for Water-Cooled Chillers ..................................................................... 4
Subcooling Cycle..................................................................................................................... 5
Economizer Cycle.................................................................................................................... 6
Water-Cooled Chiller Components.................................................................................................. 7
Evaporator.................................................................................................................................... 7
Brazed Plate ............................................................................................................................. 7
DX Shell-and-Tube.................................................................................................................. 7
Flooded Shell-and-Tube........................................................................................................... 8
Evaporator Pros and Cons...................................................................................................... 10
Parallel and Series Chiller Evaporators ................................................................................. 10
Condenser .................................................................................................................................. 11
Compressors............................................................................................................................... 12
Reciprocating ......................................................................................................................... 12
Scroll...................................................................................................................................... 13
Screw ..................................................................................................................................... 13
Centrifugal ............................................................................................................................. 14
Refrigerant Metering – Expansion Device................................................................................. 16
Waterboxes ................................................................................................................................ 17
Purge .......................................................................................................................................... 18
Storage Tank and Transfer (Pumpout) Unit............................................................................... 19
Relief Valves.............................................................................................................................. 20
Chiller Controls.............................................................................................................................. 20
Compressor Starting Methods.................................................................................................... 21
Across-the-Line ..................................................................................................................... 21
Auto Transformer .................................................................................................................. 22
Primary Reactor ..................................................................................................................... 22
Part-Winding.......................................................................................................................... 22
Wye-Delta.............................................................................................................................. 23
Solid-State.............................................................................................................................. 23
Variable Frequency Drive...................................................................................................... 24
Energy Management .................................................................................................................. 25
Chilled Water Reset ............................................................................................................... 25
Demand Limit and Duty Cycling........................................................................................... 25
Screw Compressor Operational Details ......................................................................................... 26
Design and Off-Design Performance......................................................................................... 27
Centrifugal Compressor Operational Details................................................................................. 27
Head ........................................................................................................................................... 28
Lift ............................................................................................................................................. 28
Compressor Boundaries ............................................................................................................. 29
Compressor Stages..................................................................................................................... 31
Capacity Control Methods for Centrifugals and Screws ............................................................... 31
Inlet Guide Vanes ...................................................................................................................... 31
Screw Unloaders ........................................................................................................................ 32
Hot Gas Bypass.......................................................................................................................... 33
Speed Control ............................................................................................................................ 33
Refrigerant Related Topics ............................................................................................................35
Regulations ................................................................................................................................35
Chiller Construction...................................................................................................................36
Safety .........................................................................................................................................37
Heat Transfer .................................................................................................................................38
Heat Balance of Fluid ................................................................................................................39
Overall Heat Transfer.................................................................................................................40
Heat Transfer Coefficient...........................................................................................................41
Impact of Fouling Factor on (U) ................................................................................................42
Impact of Tube Velocity On (U)................................................................................................43
Impact of Tube Material On (U) ................................................................................................44
Evaporator and Condenser Tubing ............................................................................................44
Freezing of Fluids in Tubes .......................................................................................................45
Pass Arrangement ......................................................................................................................45
Variable Flow Operation............................................................................................................46
Codes and Standards ......................................................................................................................46
ARI Testing Standards ...............................................................................................................46
ASHRAE 90.1............................................................................................................................48
UL/CSA & ETL .........................................................................................................................48
ASHRAE Standard 15 ...............................................................................................................49
Selection Criteria ...........................................................................................................................50
Summary ........................................................................................................................................52
Work Session .................................................................................................................................53
Notes ..............................................................................................................................................56
Appendix........................................................................................................................................57
References..................................................................................................................................57
Work Session Answers ..............................................................................................................58
WATER-COOLED CHILLERS
Introduction
This TDP module on water-cooled chillers starts with a history of the first centrifugal chiller
and describes the first applications for early water-cooled chillers. After a discussion of the rela-
tive merits of water-cooled chillers, the refrigeration cycle for a water-cooled centrifugal chiller is
explained using pressure-enthalpy diagrams.
We will examine the major components used in water-cooled chillers such as evaporators,
condensers, compressors, and metering devices. The types of chiller starters and their applications
are also discussed.
A greater emphasis is placed on the larger screw and centrifugal types of water-cooled chill-
ers in this TDP module. A more detailed discussion of the screw and centrifugal compression
process and its characteristics is included. Current refrigerant issues, phase out dates, and appli-
cable codes and standards for water-cooled chillers are also examined.
Finally, computerized selection software for a centrifugal chiller is used to demonstrate the
required inputs and the selection process for a typical application.
Figure 3
Evolution of Centrifugal Chillers
Figure 4
Air-Cooled and Water-Cooled Chiller Benefits
A typical water-cooled chiller uses recirculating condenser water from a cooling tower to
condense the refrigerant. For a complete discussion on cooling towers, refer to TDP-641, Con-
densers and Cooling Towers.
Cost and efficiency are the important factors when
Absorption Chillers considering air or water-cooled chillers. Chilled-water
This TDP will cover water- systems with air-cooled chillers typically have lower in-
cooled chillers using the vapor- stalled and maintenance costs than water-cooled because
compression refrigeration cycle. a condenser water system using a cooling tower is not
Absorption chillers that use required. A condenser water pump and chemical treat-
water as the refrigerant will not ment for the condenser water loop adds to the
be covered in this TDP.
maintenance required with a water-cooled system. How-
ever, water-cooled chillers have higher efficiency and
therefore lower operational costs. Air-cooled chillers are chosen when it is impractical to use a
cooling tower, such as when little water is available or water is highly corrosive.
The refrigerant condensing temperature in an air-cooled chiller is dependent on the ambient
dry-bulb temperature. In a water-cooled chiller, refrigerant condensing temperature is dependent
upon the entering condenser water temperature (and flow rate), which is a function of the ambient
wet-bulb temperature. Since the wet-bulb temperature is always lower than the dry-bulb tempera-
ture, the refrigerant condensing
temperature (and pressure) in a
water-cooled chiller is often
significantly lower than in an
air-cooled chiller. This is why
water-cooled chillers are more
efficient.
In terms of capacity, air-
cooled chillers are available in
packaged sizes ranging up to
approximately 500 tons, while
water-cooled chillers are typi-
cally available up to 3,000 tons, Figure 5
with limited custom designs
Typical Water-Cooled Chiller System
available up to 10,000 tons.
Water-cooled chillers typically last longer than air-cooled chillers. Air-cooled chillers may
last 20 years while water-cooled chillers may last 23 years or more. This may be attributable to
the fact that water-cooled chillers are installed indoors, and most air-cooled chiller configurations
spend their lives outdoors in the elements. Also, some of the larger water-cooled chillers are con-
structed with heavy duty, industrial-grade components.
In step 2 to 3, heat rejection takes place and the refrigerant transitions from superheated vapor
to saturated liquid. Step 3 to A is the refrigerant passing through the expansion device to reduce
pressure and temperature to the necessary conditions in the evaporator.
Subcooling Cycle
In the subcooler, the refrigerant is subjected to the coldest entering condenser water. The liq-
uid refrigerant is subcooled by 10º F to 15º F below the saturated condensing temperature. A
subcooler is an economical way to increase refrigeration cycle efficiency without adding work on
the compressor. It is ideal for use with
positive pressure refrigerants such as
HFC-134a and single-stage compres-
sors, which we will discuss later.
The typical method of subcooling
as described earlier simply cools the
liquid below its saturation temperature
in a tube bundle that cold condenser
water circulates through. This might
also be described as sensible subcool-
ing, because no refrigerant has flashed
or changed state (latent heat transfer).
Figure 9
Condenser Subcooler
Another method is called “flash subcooling.” In the flash subcooler a portion of the refriger-
ant is allowed to flash back into vapor further cooling the remaining refrigerant and effectively
lowering the saturated condensing temperature. The flash subcooler is not really a simple sub-
cooler but a lower saturation temperature condenser. Thermodynamically, the net effect of a
properly sized sensible subcooler can be the same as that of a flash subcooler in that the amount
of heat being rejected by the refrigerant to the condenser water is the same.
The “flash subcooler” has two cost advantages over a sensible subcooler:
1. It requires less refrigerant charge, since vapor is less dense than refrigerant and most of the
refrigerant side volume in a flash subcooler is vapor while it is liquid in a sensible sub-
cooler.
2. It has a very good refrigerant-side heat transfer coefficient (two-phase flow has a better
heat transfer coefficient than a pure liquid).
For example, it takes 71.22 Btu/lb to convert each pound of liquid R-134a to a gaseous form.
If the liquid refrigerant did not undergo a phase change, yet underwent 5° F temperature change,
the change in enthalpy is only 1.78 Btu/lb.
Economizer Cycle
Multiple-stage centrifugal and some screw chillers improve the cycle efficiency by using an
economizer, also known as a flash economizer. An economizer is a separate vessel after the con-
denser that improves the refrigeration cycle by allowing a small amount of gas to flash into vapor
after the condensing stage. This phase change decreases the temperature of the remaining liquid
refrigerant. The remaining vapor is then drawn back into the compressor at some secondary stage
of compression to be sent back through the cycle. Shown in Figure 10 is the increase in refrigera-
tion effect produced by the addition of an economizer to the centrifugal cycle.
This increase in refrigeration effect due to an economizer is shown by hfc – hfe.x
Pc = condensing pressure
Pe = pressure at economizer
P2 = pressure at stage 2
Ps = pressure at stage 1
hfe = enthalpy of liquid with
economizer
hfc = enthalpy of liquid without
economizer
h3 = enthalpy of mixture
hge = enthalpy of gas with
economizer
hgs = enthalpy of gas suction
inlet
Figure 10
Refrigeration Cycle with Economizer
Brazed-Plate
For smaller capacity chillers (15-60 tons), the brazed-plate evaporator is often used. These
evaporators consist of a series of plates brazed together with every second plate turned 180 de-
grees. This design creates two highly turbulent fluid channels that flow in opposite directions that
result in a high heat transfer coeffi-
cient over a small surface area. The
plates are stacked so they form a
multi-layered design for two inde-
pendent paths of fluid to travel. Each
layer or path is linked to an inlet and
outlet via a manifold at either end.
The design of a brazed-plate evapora-
tor maximizes heat transfer at an
attractive first cost for smaller chiller
designs. The waterside of a brazed-
plate evaporator must be kept free of
sediment and debris. Strainers are re-
quired. The brazed-plate evaporator
requires chemical cleaning since the Figure 11
waterside is not mechanically clean- Brazed-Plate Evaporator
able. Photo Courtesy of API Heat Transfer
DX Shell-and-Tube
Flooded Shell-and-Tube
Because refrigerant goes through a change of state from liquid to gas within the shell (refrig-
erant) side, some means of separating the vapor from the boiling liquid must be provided. This is
because liquid refrigerant droplets tend to become entrained in the flow of suction gas that is go-
ing to the compressor inlet. These liquid droplets that are “carried over” can be corrosive or
destructive to the centrifugal compressor. Space elimination is the preferred design method. The
cooler is designed with enough space between the top row of tubes and the compressor inlet to
ensure that the velocity of the refrigerant vapor is low enough to prevent entrainment of liquid
refrigerant droplets.
Other designs use eliminators to trap the liquid droplets before they reach the inlet of the
compressor. Eliminators are either a series of parallel plates bent in a Z-shape, or a wire mesh.
The disadvantages to eliminators are
that they can eventually fail, they in-
troduce a pressure drop, and they have
an upper limit on face velocity.
Eliminators work by converting mist
into large drops that fall back against
the oncoming vapor flow. If the ve-
locity of the refrigerant vapor is too
high, the liquid droplets that were
eliminated are re-entrained and car-
ried through the eliminator. The
allowable face velocity is a function
of the ratio of liquid to vapor densi-
ties.
Figure 15
Mechanical elimination Space Elimination of Refrigerant Droplets
requires approximately the Tube support sheets at intermediary points are criti-
same area as space elimination. cal to ensure that the tubes do not deflect due to the
boiling action that takes place around the tube bundle.
They also aid in the replacement of tubes, should that be
necessary. The end tube sheets form the ends of the heat exchanger, and tubes are sealed at the
end on these tube sheets to create the refrigerant to water boundary. Welding, chemically sealing,
or rolling the tubes into the grooved tube sheets can accomplish this sealing. Among these,
grooved tube sheets provide the best
seal, and with a double groove, the
seal is even better. To increase the
stability of the tubes, they can also be
swaged (expanded) at the intermediate
tube support sheets, a process that
expands the tube just enough to fill
the machined holes. This process en-
ables the tubes to be replaced by use
of a pulling tool that extracts the tube
from the tube support sheet.
Figure 16
Double Grooved Tube Sheet for Tight Seal
DX Shell-and-Tube Evaporator* Pro Cost effective for small and medium sizes
Pro Familiarity with customers/engineers
Design can accommodate heater cable on the shell to
Pro
prevent freezing of water
Condenser
Water-cooled chillers either use brazed-plate or shell-and-tube heat exchangers for the con-
denser. Since the focus of this TDP is on larger chillers, the shell-and-tube design will be
discussed further. As in the evaporator, the refrigerant is on the shell side, and the fluid is on the
tube side. The fluid is generally fresh
water, used with an open cooling
tower.
Other condenser water sources
include lakes, rivers, or cooling
ponds. Use of these water sources
constitutes a once-thru system. Once-
thru condenser applications are very
limited compared to recirculating
cooling tower applications. That is
because they are often considered as a
source of thermal pollution. In coastal
areas, seawater may also be used;
however, appropriate materials, like
titanium, should be used to minimize Figure 18
tube and tube sheet corrosion. Large Chiller Shell-and-Tube Condenser
Figure 19
Large Chiller Condenser Cutaway
Figure 20
Refrigerant Path in a Shell-and-Tube Condenser
Compressors
There are several widely used compressors for water-cooled chillers. They are grouped into
two categories: positive displacement or dynamic compression (also called non-positive dis-
placement). Centrifugal compressors are the only type of non-positive displacement compressor.
Reciprocating
Reciprocating compres-
sors, like a reciprocating
engine, have pistons, rods,
discharge, and intake valves.
The valves operate on suc-
tion and discharge pressure.
Compression is achieved by
trapping a fixed amount of
refrigerant gas into a cham-
ber. For this reason,
reciprocating compressors
are positive displacement
type compressors as are
scrolls and screws.
Figure 21
Reciprocating Compressor
Scroll
Screw
Screw compressors are another version of positive displacement compression. As the screw
rotors turn, the gas is compressed. Screw compressors have one or more rotors to accomplish the
compression. Due to this characteristic, positive displacement compressors are best suited to han-
dle smaller volumes of refrigerant gas
over high compression ratios. The
HVAC industry is trending to phase
out reciprocating compressors, favor-
ing screw and scroll compressors.
Screw compressors are used in the 70
to 500-ton chiller range in multiples,
and are also used in both water-
cooled and air-cooled chillers. For an
in-depth discussion of screw com-
pressor operation, see the Screw
Compressor Operational Details sec-
tion (page 26). Figure 23
Screw Compressor
Centrifugal
Centrifugal compressors are dynamic compression, and they are water-cooled because their
efficiency is optimized at the lower condensing temperatures and pressures. As refrigerant mole-
cules are flung outward by centrifugal
force, new ones are drawn into the
compressor to replace them. The
overall effect is one of continuously
compressing the stream of refrigerant
gas. This process of compression al-
lows large volumes of refrigerant gas
to be compressed resulting in a rela-
tively compact size chiller. Thus,
centrifugal compressors are dominant
in larger capacities.
Note:
The break point from positive
displacement to centrifugal type
compression in air-conditioning Figure 24
chillers generally occurs Centrifugal Compressor
between 300 to 500 tons due to
design and capacity related
reasons.
As an alternative for larger capacity requirements, multiple chillers with positive displace-
ment compressors can be used to match the capacity of a single centrifugal chiller.
There are several possible drivers for refrigeration compressors. These include motors, steam
turbines, gas engines, and gas turbines. As electric motors are the most commonly used method
for driving a compressor, we will focus on these.
Centrifugal compressors fall into two broad categories: hermetic and open. The compressor
driven by these motors may be direct-drive, where the motor rotor and the impeller are on the
same shaft, or gear driven, where the rotor shaft and impeller shaft are coupled by a transmission.
In a direct-drive compressor, the impeller spins at the same speed as the motor (slightly below
3600 rpm for 60 Hz). In a gear-driven compressor, the gearing in the transmission is changed by
the manufacturer to meet different power frequency requirements or compression requirements.
Figure 25
Hermetic Centrifugal Compressor – Cutaway
Open-drive compressors have the compressor shaft extending through the casing to facilitate
connection to a number of different types of drives as discussed earlier. However, these machines
require shaft seals, which must
be replaced on a regular basis. By
design, shaft seals leak oil and
refrigerant to keep contaminants
out of the chiller. This oil and
refrigerant must be reclaimed,
typically in a separate container
outside the chiller. Additionally,
when routine preventive mainte-
nance is done, the compressor
and motor must be realigned. An
open drive motor also rejects its
heat directly into the
Figure 26
Open-Drive Centrifugal Compressor
Another benefit of the variable geometry orifice (float valve) on larger screw and centrifugal
chillers is that it can pass increased mass flow of refrigerant during periods of lower entering
condenser water temperature by increasing the area of the opening into the evaporator. More re-
frigerant flow will result in an approximate 15 percent increase in chiller capacity above the
design full load tons. This increase in capacity is called “maximum capacity.” Fixed orifice de-
signs cannot accomplish this feature.
Why might this be important? On multiple chiller projects, each chiller that can accomplish
maximum capacity will handle a larger portion of the total building load than a fixed orifice de-
sign chiller. This means the second (or third) chiller in a multi-chiller plant can remain inactive as
long as possible saving energy over designs that must run more than one chiller.
For a discussion on refrigerant metering devices used on the smaller chillers with reciprocat-
ing and scroll compressors (and some smaller screw compressors), refer to TDP-622, Air-Cooled
Chillers, and TDP-403, Expansion Devices & Refrigeration Specialties.
Waterboxes
Waterboxes are used to connect
the chiller waterside to the chilled or
condenser water loop piping. There
are two types of waterbox construc-
tion in common use on larger screw
and centrifugal chillers: “nozzle-in-
head” and “marine” type.
The most popular and economic
design is the “nozzle-in-head” type.
This design is a result of the industry
trend in air conditioning to make ma-
chines more compact and less costly.
The only drawback to nozzle in head
type waterboxes is that the piping Figure 28
connection must be undone, and the
Nozzle-in-Head Waterboxes
“heads” must be completely removed
to perform any tube maintenance.
The “marine” type waterbox is
larger and more costly. However, it
provides the ability to clean the tubes
without disturbing the piping external
to the machine. For this reason, the
marine waterboxes are generally used
in chillers above 700 tons. Moving the
piping is time consuming and expen-
sive, so making use of a marine type
waterbox offers owners an attractive
feature and reduced maintenance
costs. When available, marine water-
boxes with hinged waterbox covers Figure 29
eliminate rigging of heavy waterbox
Marine Waterboxes
covers.
Waterboxes are typically designed for 150 or 300 psig, the latter used for taller buildings,
where there may be a large water column in the water distribution piping system.
In a high-rise building, the static head imposes pressure on the chiller waterside components
if the chiller is located in the basement. Example: A 50-story building with 12 ft between floors
would be 600 ft high. Since 2.31 ft equals 1 psi, the pressure on the components at the lowest
level would be 600 ft/2.31 ft/psi = 260 psi. The hydronic system components in the basement
MER (mechanical equipment room) must be designed for this pressure. In this example, the
chiller “waterboxes” (area where piping connections are made to the chiller) would have to be
constructed to accommodate 260 psi. That means optional 300 psi waterboxes would have to be
specified.
Purge
Some refrigerants used in centrifugal water-cooled chillers, such as HFC-134a, are positive
pressure (operate above atmospheric pressure), and some are negative pressure, such as HCFC-
123, operating below atmospheric
pressure. Negative pressure centrifu-
gal chillers operate in a vacuum and
have gaskets and o-rings that can leak
which allows air to enter the chiller.
When air leaks in, some water vapor
comes with it. This air/water vapor
can displace some of the refrigerant in
the chiller causing a reduction in effi-
ciency.
A device called a purge is re-
quired to collect and expel the air and
the water vapor from the inside of the
chiller. When the air is expelled, some
Figure 30
refrigerant goes with it. A modern
high efficiency purge reduces the on- Purge on Negative Pressure Centrifugal Chiller
going loss of refrigerant to 0.5 lb for
every pound of air removed. Older purges lost from 3 to 5 lbs of refrigerant for every pound of air
removed. Air and non-condensables in the chiller causes the head pressure to rise. As a rule of
thumb, for every 2.5 psig increase in condenser (head) pressure, the chiller’s efficiency falls be-
tween 8-10 percent
The purge is continually sampling gas from the chiller condenser
and condensing the refrigerant and recirculating it back to the evapo- Note:
rator. Air and other non-condensables cannot be condensed. The The purge unit adds
purge will collect these non-condensables and eventually discharge maintenance and
them to the atmosphere. Purging to the atmosphere is in compliance electrical consumption
with EPA regulations. Water vapor from humid mechanical rooms is that is not required
also drawn into the chiller when there are leak areas in the chiller and with a positive
pressure chiller
must be condensed and collected in the purge then drained from the
design.
purge collection chamber.
Water mixed with refrigerant can also produce corrosive acids that break down the oil and at-
tack the internal metal parts of the machine.
Note:
A typical example of when the
operating charge must be
removed from the condenser is
when some of the condenser
tubes are being replaced.
Relief Valves
Refrigerant relief valves on either the condenser, the evaporator, or both, are provided as
safety devices in the event of overpressurization. Overpressurization might occur during a fire or
if hot water were run through the chiller tubes.
The standard pressure relief de-
vice on a negative pressure centrifugal
chiller is a carbon disk with a mem-
brane that shatters at 15 psig. Over-
pressurization results in total loss of
the refrigerant. Back-up relief valves
are available to minimize this loss in
the event of overpressurization. These
back-up devices contain non-
fragmenting disks with a reseating
plunger that will relieve the pressure
and then reseat. This saves a good
portion of the refrigerant that might Figure 33
otherwise be lost. Relief Valves
Positive pressure chiller designs typically use the reseatable valve design as standard. After a
release, the valve reseats, thus preventing a total loss of refrigerant.
Chiller Controls
All chillers need to be properly controlled for safe and efficient operation. Chiller designs
commonly use microprocessors, electronic sensors, and digital displays that have changed the
look of chiller equipment control sys-
tems. This technology is referred to a
Direct Digital Control (DDC).
DDC systems allow for the use of
digital display systems that give the
owner-operator and service technician
the ability to do a diagnostic evalua-
tion of the operation of the equipment
by way of equipment-mounted or
handheld user interfaces. In DDC sys-
tems, information is digital and can be
shared by other equipment to function
as a system. Most DDC systems will Figure 34
have a communication terminal that Water-Cooled Chiller Control Panel
allows for network communications
or the attachment of a PC for more detailed diagnostic capabilities. DDC systems are capable of
sharing information on a communication bus that can be viewed worldwide.
Across-the-Line
Across-the-line, also called full voltage, is the simplest and least expensive method. The mo-
tor locked rotor current is drawn directly from the line on starting, and is used when the power
system can withstand high inrush currents such as in a large industrial plant. With an across-the-
line starter, the inrush can be 6 to 8 times the motor rated full-load amp (FLA) value. Therefore,
this method is especially suited to the following motors:
1) low-voltage, single phase motors up to approximately 10 hp
2) low voltage, three phase motors up to approximately 25 hp
3) medium-voltage (over 600 volts) motors of any hp
Because full voltage is applied directly to the
Across-the-line starters motor terminals, this method also provides the
on large, single compressor chillers are quickest acceleration to running speed. This type
mostly used in the voltages (like 4160v) of starter is a common one used on smaller ton-
where the amp draw is low. On smaller nage chillers with multiple compressors. This is
multi compressor chillers, across-the- because the starting amps of the individual com-
line starters can be used for low voltage pressors are relatively low, and the compressors
applications because the inrush per
are staggered on startup.
compressor is manageable.
Auto Transformer
This method reduces inrush line current and motor starting Auto transformer starters
torque by limiting the voltage applied to the motor windings dur-
ing start-up. It is used typically for medium voltage applications. offer a soft start (relative
The torque is accomplished through a transformer within the to across-the-line) but the
starter with contacts configured to allow stepped acceleration to start is limited to discreet
full current. Changing incoming line voltage taps within the steps.
transformer varies the current drawn from the line, the voltage and current applied to the motor,
and the torque developed by the motor at startup. This tap is usually selected and then fixed at
installation, and is based on the application. For centrifugal chiller applications, the 65 percent tap
is the one that provides the required torque to start the motor compressor.
Primary Reactor
Like an auto transformer, this starter reduces inrush current by limiting the voltage applied to
the motor. A reactor, or resistor, is used to reduce the voltage to the compressor motor instead of
a transformer. Compared to an auto transformer, a primary reactor is the more economical
method for medium voltage. Primary reactor is not the most efficient starter type from an electri-
cal standpoint. A primary reactor starter uses the resistor in the circuit during starting. As the
resistor lowers that amp draw, there is some wasted energy. However, primary reactor starters
provide a smooth acceleration. This is because the starter adds resistance to reduce the voltages
and current at startup. The starter’s incoming line voltage taps may be changed at installation to
set the level of inrush voltage and current.
Part-Winding
Part-winding starters also produce a soft start. An electrical engineer typically determines if
soft starting is required based on an electrical system study that calculates voltage drop in the sys-
tem when a load is started. If the power supply is weak or the system is heavily loaded, the
system is more likely to be sensitive to motor starting, and soft starters are more likely to be re-
quired. It is more likely that 208V systems will require soft starters than 460V systems because of
the higher amp draw.
Part-winding starters are a cost effective means of providing a reduced current start where
smaller horsepower motors are used on water-cooled chiller designs using multiple compressors.
Part-winding starters can only be used with part-winding motors that have two sets of identi-
cal windings that are intended to be operated in parallel. During a part-winding start, only one
winding is energized, reducing the inrush current to 60-70 per-
cent of normal starting values with both windings energized. A part-winding starter
With only one winding in the circuit, a typical part-winding mo- is commonly used on re-
tor will not accelerate to more than half of the motor rated ciprocating compressors.
speed. Because the motor is operated with one winding only Availability varies from
during the initial acceleration period, after the transition from manufacturer to manu-
start to run mode, the current draw of the motor may be close to facturer based on the size
the rated locked rotor amps. A part-winding starter essentially of the compressor motor
provides a two-step start. Part-winding starters are not used on used.
centrifugal chiller compressors.
Wye-Delta
Wye-delta, also called Star-delta, starters reduce inrush line current and motor starting torque
by switching the motor winding connections. Three contactors and a timer change the winding
configuration to transition from around 33 percent current in the wye configuration to full current
in the delta configuration. Open transition wye-delta starters stop applying voltage to the motor in
the short transition between windings. A closed transition wye-delta
starter uses shunt resistors. Only closed transition wye-delta starters
Wye-delta starters
are now used in large chillers. Due to its relatively low cost when
compared to the reduced voltage type starters, wye-delta starting is are popular with
the most commonly used starter with hermetic centrifugals under technicians because of
600 volts. their familiarity with
wye-delta trouble
Wye-delta starters are used only on low-voltage applications. shooting procedures.
Solid-State
Solid-state starters are used for both low-voltage and medium-voltage applications although
they are not as common in medium voltage. They are popular for low voltage applications (≤600
volts) because they provide a programmable soft start.
Figure 37
Motor Starting Current as a Percent of Locked Rotor and Full Load Current
Energy Management
Use of energy management practices can significantly reduce operating costs, especially dur-
ing off-peak modes of operation. Demand limiting and chilled water temperature reset are two
techniques for accomplishing efficient energy management.
Chilled water reset means to change the chilled-water temperature leaving the chiller based
on some parameter. Increasing the leaving chilled-water temperature reduces compressor power
usage by reducing lift at both full and part-load conditions. However, at part-load conditions, de-
sign chilled-water temperature may not be necessary, especially
for comfort cooling applications, so reset is possible. However, Lift and Efficiency
increasing the chilled water temperature may result in greater
humidity levels in the conditioned spaces. Higher coil tempera- Lift refers to the difference
tures resulting from the increased chilled water temperature will between compressor
suction and condensing
reduce the latent heat capacity of the coils and the ability of the temperatures. Reducing lift
air distribution system to remove space humidity. increases efficiency.
Chilled water temperature can be reset as a function of:
• Ambient air temperature (most common) – used when the ambient temperature is the best
indication of load
• Return chilled water temperature – used when return water temperature is the best indica-
tion of load. This method is typically used when it is desired to maintain a fixed ∆t in the
chiller plant.
• Temperature within the building – used when space temperature is the best indication of
load on the chiller. This is used when there are critical areas in a building such as labs
that might require a specific temperature be maintained.
Reset doesn’t always mean an increase in water temperature. For example, space temperature
reset could actually lower the chilled water supply temperature, not raise it, in order to maintain
conditions.
Duty cycling will cycle selected electrical equipment in an installation (building, factory, etc.)
at regular intervals to limit the electrical demand, thereby lowering demand charges. However,
duty cycling is not recommended because constant cycling will cause increased stress and dam-
age to the motor windings, bearing, and controls. If demand must be controlled, the demand limit
sequence available from the manufacturer is recommended.
Head
Head can be visualized as the height (in feet) of an
imaginary column of refrigerant vapor, which, due to its Head pressure
weight, produces the same pressure as that developed
across the compres- is directly affected by entering
water temperature from the
sor (pressure at
cooling tower. The entering wet
discharge minus bulb temperature to the tower
pressure at suction). affects the tower’s ability to
Head has come to be cool the water.
synonymous with a
measure of the pressure rise developed by a centrifugal
compressor.
Variations in outside conditions result in different en-
tering condenser water temperatures at both full and part
load. This term for this is tower water relief and occurs
when the outside wet bulb temperature is below the cli-
matic design condition, increasing tower heat rejection and
Figure 40 lowering the condenser water temperature entering the
chiller.
Centrifugal Compressor Theory – Head
Lift
Another commonly used term is “lift.” The expression, “55º F of lift” refers to the difference
in saturated refrigerant temperature levels between which the compressor operates. To produce
44º F chilled water, a compressor draws in gas at a saturated suction temperature level of ap-
proximately 42º F and discharges gas at a saturated discharging temperature of approximately
97º F. This is for typical HVAC duty, with 85 to 95º F condenser water. The conditions described
here would produce 55º F of lift (97° F - 42° F). The following pressure enthalpy diagram dem-
onstrates that lift is the difference between saturated condensing and suction temperatures.
Compressor Boundaries
There are two important factors when discussing the operational envelope of a centrifugal
compressor. The first is stonewall, which describes the condition of maximum compression. As
the volume of gas increases, its velocity through the compressor also increases. When the velocity
of the gas exceeds the local sonic or acoustic velocity at the existing pressure, shock waves de-
velop. When this happens, high head losses occur and the compressor head output drops off
sharply. This is the “flow limitation,” and the resultant steep part of the compressor curve show-
ing this effect is referred to as “stonewall.” Centrifugal chiller software automatically keeps
selections the proper distance from this line.
The other limitation for the centrifugal compressor is surge. Surge occurs when the refriger-
ant pressure in the condenser is high enough that the impeller can no longer maintain the required
discharge gas flow. Stated another way, the required lift is too high for the compressor. This
higher condenser pressure results in
flow breakdown in the impeller pas-
sageways, and a partial or complete
flow reversal through the impeller
occurs. A lowering of the system
pressure should follow, and this al-
lows the impeller to function normally
again, and gas to flow in the correct
direction. The system pressure then
builds up again until it exceeds the
impeller capability, and the reversal of
flow repeats itself. This pulsing of
pressures is nearly instantaneous, and
continues until chiller controls take
corrective action to lower the con-
denser pressure, allowing proper flow Figure 43
of the refrigerant through the impeller, Centrifugal Chiller Compressor Map
diffuser, and volute. Surging is char-
acterized by an increase in the
operating noise level, and by wide fluctuations in discharge pressure and motor current. No det-
rimental mechanical effects are caused by periodic, short durations of surging. However,
prolonged periods of surging may damage the chiller.
Compressor Stages
In a centrifugal compressor, each impeller used is referred to as a stage. We have seen from
the ball and string example that a single-stage compressor with a large diameter impeller running
at a slow speed, or a single-stage
compressor with a small diameter
impeller running at a fast speed, can
produced the same amount of lift. A
two-stage compressor with even
smaller diameter wheels running at a
faster speed can also produce the
same amount of lift. Thus, there is a
design trade off between speed, stag-
ing, and impeller diameter to achieve
a desired result. For air-conditioning
duty (approximately 55º F of lift) ei-
ther one or two-stage compressors are Figure 44
used.
Centrifugal Compressor Stages
Screw Unloaders
For a screw chiller, either slide valves or solenoid actuated port valves are used to change the
volume ratio of the compression chamber.
A common means of capacity
control is changing the volume ratio
with slide valves. The slide valve
opens a passageway along the side of
the compression chamber, allowing a
portion of the gas to bypass the rotors.
This bypassed gas is recycled to the
suction cavity and is then compressed.
Essentially, a slide valve shortens the
length of the compression path, reduc-
ing the capacity of the screw
compressor. The slide valve offers
infinite volume ratio, and therefore Figure 47
infinite capacity control for screw Capacity Control – Slide and Port Valves
compressors.
Another means of reducing the volume by shortening the compression path is port valves.
Port valves are staged along the compression path, and the number of opened valves determines
the volume of gas compressed. These valves are less expensive, easier to control, and simpler to
maintain than slide valves, but they do not offer infinite control as they open in discrete steps, and
therefore reduce the volume of gas compressed in the same discrete steps.
Speed Control
Variable speed control provides the most efficient method to vary capacity, but in the past, it
has been expensive. Recent improvements in technology and the widespread acceptance of vari-
able frequency drives (VFD) have lowered the cost such that today’s VFD technology is often in
the 1-2 year payback period. Any time the lift requirements of a chilled water system are reduced,
a VFD applied to the compressor can realize power consumption savings that come from the
lower speeds required at the reduced lift. For a centrifugal compressor, a reduction in speed is
represented by the reduction in gas flow rate, lift capability, and input power as shown.
Figure 48
Laws for Centrifugal Loads
All of these centrifugal laws are based on how fast the im- is an increasingly popular
energy saving measure on
peller is spinning, and anytime there is a reduction in lift and
existing large chillers.
flow, the compressor speed can be reduced by a VFD, resulting
in energy savings.
Regulations
Recently, refrigerant selection has been driven by two international environmental agree-
ments, the Montreal Protocol on Substances that Deplete the Ozone Layer and the Kyoto
Protocol, which is focused in mini-
mizing the impact of climate change.
The Montreal Protocol mandates the
phase out of ozone depleting sub-
stances. The CFC’s, R-11, R-12, R-
113, R-114 and R-115, were phased
out on January 1, 1996. The HCFCs
(e.g. R-22 and R-123) will be phased
out on January 1, 2030 with interim
reductions taking place on January 1,
2004, January 1, 2010, January 1,
2015, and January 1, 2030. From
January 1, 2020 to January 1, 2030, Figure 51
consumption will be reduced to 0.5 Montreal Protocol Showing EPA Equipment Phaseout Dates
percent of the baseline and new
HCFCs may only be used to service existing equipment. The US and Europe, as well as a major-
ity of developed countries, have adopted the Montreal Protocol and in some cases have passed
regulations that accelerate the phase
Note: out of some or all HCFCs. In
Europe, most uses of HCFCs have
The Montreal Protocol treats HCFC-22 and HCFC-
already been banned.
123 the same, however, the U.S. has adopted
chemical-specific phase-out dates. HCFCs with
higher ODP (R-22)will be phased out first followed
by HCFCs with lower ODP. Therefore, in the U.S.,
HCFC-22 Is being phased out ahead of HCFC-123.
For example, as of 2010, no new R-22 equipment
can be produced, and as of 2020 no new R-123
equipment can be produced.
The Kyoto Protocol mandates the reduction of emissions of greenhouse gases (i.e. carbon di-
oxide, methane, nitrous oxide, HFCs). It does not call for the phase out of the chemicals. The
Kyoto Protocol has affected chiller design by influencing manufacturers to find more efficient
refrigerants, and therefore designing more efficient chillers to reduce the electrical consumption
of HVAC systems.
It is also important to note that any refrigerant for use in chillers must be on the EPA’s Sig-
nificant New Alternative Policy approved list, and in ASHRAE Standard 34 to ensure that it has
an “R” designation and is assigned a safety classification based on toxicity and flammability data.
If it is not, using it is a violation of the Clean Air Act, and is potentially hazardous. Several re-
frigerants that are described as drop-in replacements for HCFC chillers are considered dangerous
and are not approved by the EPA. In addition to this, the equipment that the substitute refrigerant
will go into must undergo design changes to ensure safe operation of the approved refrigerant
alternative. One significant reason for this is the different operating pressures of refrigerants. As
an example, R-22 replacement R-410A operates at about 30 percent higher pressure, and if the
original equipment is not designed to operate at that pressure, it would not be safe to apply R-
410A into the system without modifications. For complete discussion on this topic, refer to TDP-
402, Refrigerants.
Chiller Construction
The choice of refrigerant affects the
construction of the chiller as well. Dif-
ferent refrigerants have different
operating pressures, so various codes
dictate their construction. The cooler and
condenser may need to be constructed to
ASME pressure vessel standards as de-
fined in Section VIII, Division I of the
current ASME code. ASME stands for
the American Society of Mechanical
Engineers. A data report for each posi-
tive pressure centrifugal chiller is on file Figure 52
with the National Board of Boiler and Chiller Construction ASME “U” Stamp
Pressure Vessel Inspectors and is avail- Photo Courtesy of Honeywell Genetron Refrigerants
able for public review. In this report, an
authorized independent inspector will have approved the welds and verified the pressure tests.
These inspectors, working on behalf of ASME, not the chiller manufacturer, ensure that the posi-
tive pressure chillers are manufactured and tested in accordance with the strict standards of
ASME and will bear the “U” stamp indicating compliance with ASME. They provide third party
certification during the manufacturing process.
For large screw and centrifugal chillers, the quality of the construction enables hermetic posi-
tive pressure chillers to have approximately 0.1 percent annual refrigerant leak rate. ASME
currently requires that the refrigerant side (shells) of the R-134a chiller be pneumatically tested to
1.1 times the design pressure, a value typically around 200 psig. Negative pressure chillers are not
inspected by an ASME authority, and are tested to 30 psig as required by ANSI the American
National Standards Institute. Waterside testing of the tubes is typically 1.3 times the design pres-
sure of the water. This design pressure is usually 150 or 300 psig.
Safety
ASHRAE Standard 34 divides re-
frigerants into two groups, lower and
higher toxicity, designated by the let-
ters A and B, respectively.
Refrigerants with allowable exposure
limits (AEL) of 400 ppm or higher are
classified as group A (lower toxicity)
refrigerants, and those with AELs of
less than 400 ppm are group B (higher
toxicity). R-134a with an exposure
limit of 1000 ppm is classified as
Group A and R-123 with an exposure Figure 54
limit of 50 ppm is classified as
Allowable Exposure Limits
Group B.
Refrigerants are further classified by their degree of flammability: (1) no flame propagation,
(2) lower flammability, and (3) higher flammability. HFC-134a is a safe choice, because it has a
low toxicity and no flame propagation properties
Figure 55
Refrigerant Safety Groups
Heat Transfer
This section will look at the basic
heat transfer relationships of the heat
exchangers for a water-cooled chiller.
The information provided is general
in nature and should provide a basic
understanding of the heat transfer
principles associated with shell-and-
tube heat exchangers.
Shown is the longitudinal cross
section of a typical condenser and
evaporator together with their respec-
tive temperature profiles. The heat
transfer relationships of the evapora-
tor and condenser are similar. Figure 56
Heat Transfer – Condenser, Fluid Heated t1 –t2
In looking at the figure, it can be
observed that there are two basic heat
balances occurring in each heat ex-
changer. They are:
1. Heat given off or gained by the
fluid as it passed through the
tubes.
2. The overall transfer of heat be-
tween the fluid in the tubes and
the refrigerant in the shell.
.
Figure 57
Heat Transfer – Evaporator, Fluid Cooled t1 –t2
Heat transfer technology has improved to the point where the difference between the refriger-
ant temperature in a heat exchanger (evaporator or condenser) and the leaving fluid temperature
can be very low…in the range of 2-3 ºF. That means, for instance, if the saturated condensing
temperature is 97º F, the water returning to the cooling tower may be as high as 95º F. If the satu-
rated suction temperature is 42º F, the leaving chilled water may be as low as 44º F. Later in this
TDP module we will examine the components affecting heat transfer between the refrigerant and
water in the tubes as well as tubing technology that promotes increased heat transfer.
A heat balance is very useful in checking chiller selections for careless mistakes or verifying
chiller performance of an existing chiller. In using a heat balance on an existing chiller, it may be
difficult to predict the exact water flow.
Another equation that is useful in converting water flows into heat transfer is:
Btuh = 500 * (gpm) * ∆t, where 500 is a constant for fresh water.
Example: Heat balance for a centrifugal chiller selection.
Shown in the capacity printout:
Capacity 640 tons
Compressor kW 402
Condenser gpm 1393
Condenser rise °F 13
Let’s calculate the heat balance for the chiller:
Heat In = Heat Out
Chiller capacity + compressor kW = condenser heat rejection
640 tons ∗ 12,000 Btuh/ton + (402 kW ∗ 3413Btuh/kW) = 500 ∗ 1393 gpm ∗ 13° F
3413 converts Btuh to kW
9052 MBtuh is the evaporator and compressor heat
9054 MBtuh is the condenser total heat of rejection
This heat balance is basically equal at less than 1 percent difference. General industry prac-
tice is a balance within 5 percent is considered acceptable.
The LMTD of either heat exchanger can be calculated from an equation that takes into ac-
count the entering and leaving differences between fluid and refrigerant temperatures.
∆t F
LMTD =
Loge ∆tent
∆tlvg
Where:
∆tF = rise or drop in temperature of the fluid flowing through the tubes
∆tent = temperature difference (ºF) between the entering condenser fluid temperature and
the saturated condensing temperature, or the entering evaporator fluid temperature
and the evaporator suction temperature
∆tlvg = temperature difference (ºF) between the leaving condenser fluid temperature and the
saturated condensing temperature, or the leaving evaporator fluid temperature and
the evaporator suction temperature
This equation for overall heat transfer looks
familiar to us. The heat transfer through a wall Note
assembly when figuring heating and cooling loads This section on overall heat transfer is
is quite similar ( U * A * ∆t ). The heat transfer in included to establish a foundation on
a chiller involves both a sensible heat transfer the factors involved in heat transfer so
along with a phase change of the refrigerant; the that the reader may appreciate the
∆t is not a simple linear function, it is a logarith- impact of LMTD and U on chiller
efficiency and performance. These
mic function.
terms will be utilized in the next section.
The other three, RF, RW, and RM, are all variables (representing 75 to 80 percent of the total
resistance) and are within the control of those applying or selecting the heat exchangers. The im-
pact of these variables on the resultant refrigerant temperature (tR) is discussed below.
Figure 63
Tubing Materials Chart
Pass Arrangement
Pass arrangements are normally
related to maximum allowable tube
velocity or maximum allowable pres-
sure drop requirements. A general rule
of thumb is to use as high a pass ar-
rangement as possible, since leaving
temperature differences decrease with
larger pass arrangements. This has a
beneficial effect on compressor input
power. For example, based on a 10º F Figure 65
rise in the evaporator, the LTD for a
Pass Arrangements for Heat Exchangers with Water in the Tubes
one-pass and two-pass arrangement
would be 5º F and 2º F respectively. Using a one-pass arrangement would therefore require the
compressor to operate at a saturated suction temperature approximately 3º F lower than would be
possible with a two-pass.
Although higher pass arrangements tend to de- The most common method
crease compressor input power, this trend also
increases pumping horsepower for the chilled and of selecting of heat exchanger passes
condensing water circuits. This is a result of increas- is to specify reasonable pressure
ing tube velocities caused by increasing the number drop limits and allow the
manufacturer to recommend the
of passes. Thus, an economic balance must be struck
optimal pass arrangement for the load
between higher pumping horsepower and lower and application under consideration.
compressor input power.
Heat Exchanger Performance
It should be noted that centrifugal compressor performance and horsepower requirements will
be directly impacted by the choices made in applying the heat exchangers. The compressor oper-
ates between the pressure levels determined by the saturated suction and saturated condensing
temperatures. These temperatures are in turn directly related to the LTDs established for the
cooler and condenser. The higher the LTD, the greater will be the compressor head and horse-
power, and vice versa. High efficiency tubes can provide LTD approaches that are 1.5º F to 2º F.
Loading Rate
Each heat exchanger is designed by the manufacturer to transfer a nominal amount of heat.
For a given heat exchanger, the LTD will decrease as the load reduces below the nominal design
point. Thus, the LTD will decrease on a machine operating at part load causing the suction tem-
perature to rise or drop and the condensing temperature to drop. Or, for a given load, using larger
and more expensive heat exchangers initially, will require smaller LTD's and subsequently lower
compressor horsepower. This technique is commonly used today to select higher performance
(low kW/Ton) machines using standard heat exchangers and compressors.
IPLV is commonly expressed as either an IkW/ton value or in unites of EER. There is a fixed
relationship between IkW/ton and EER.
EER = 12(IkW/ton)
This relationship shows that EER increases as IkW/ton decreases, and vice versa. Therefore, a
“better” IPLV is shown as a lower value when the units are IkW/ton, and, due to the relationship
just described, a “better” IPLV is a higher value when the units are expressed in terms of EER.
The weightings derived by ARI are at
100, 75, 50, and 25 percent of full load. ARI
weights the part load values more, recogniz-
ing that chillers operate more at these
points. This weighting of part loads is also
evaluated with tower relief water, which
more accurately reflects the way chilled wa-
ter systems are operated. IPLV is only
appropriate for standard ARI conditions,
and NPLV is used when the conditions are
not identical to standard ARI conditions.
Figure 66
The standard ARI conditions for IPLV ARI Weighting Factors
for water-cooled chillers are:
• Leaving chilled water: 44º F
• Chilled water flow rate: 2.4
gpm/ton
• Cooler fouling factor: 0.0001 (ft2 ⋅ h ⋅ ºF)/Btu
• Entering condenser water temp: 85º F
• Condenser water flow rate: 3.0 gpm per ton
• Condenser fouling factor: 0.00025 (ft2 ⋅ h ⋅ ºF)/Btu
• Entering condenser water temperature: 85º F at 100 percent load, 75º F at 75 percent
load, 65º F at 50 percent and 25 percent load
IPLV is then calculated using the following formula:
1 Relief
IPLV =
⎛ 0.01 ⎞ ⎛ 0.42 ⎞ ⎛ 0.45 ⎞ ⎛ 0.12 ⎞ is defined as the natural
⎜ A ⎟+⎜ B ⎟+⎜ C ⎟+⎜ D ⎟ reduction in entering
⎝ ⎠ ⎝ ⎠ ⎝ ⎠ ⎝ ⎠
condenser water temperature
Where: made possible by a reduction
in ambient wet bulb
A = kW/ton at 100% load
temperature. For a complete
B = kW/ton at 75% load discussion on this topic, refer
C = kW/ton at 50% load to TDP-641, Condensers and
Cooling Towers.
D = kW/ton at 25% load
ARI also allows a tolerance to be applied to the run testing of chillers. These tolerances are
applied to power consumption and capacity, and are based on the full load temperature difference
across the evaporator. Tolerances increase as evaporator load decreases. These tolerances are
used every time a chiller is tested in a manufacturer’s ARI-certified test facility. Tolerances are
based on aggregate tolerances on instrumentation, as well as engineering and manufacturing
processes.
ASHRAE 90.1
The American Society of Heating, Refrigeration and Air Conditioning Engineers developed a
standard, ASHRAE 90.1, to require a minimum level of efficiency in water-cooled chillers. This
efficiency is based on the ARI 550/590 Standard, which uses 44º F leaving chilled water and 2.4
gpm/ton flow rate, and 85º F entering condenser water and 3 gpm/ton flow rate. As the design
conditions move away from this accepted, baseline rating point, the efficiency levels change to
account for the corresponding changes in lift conditions for the compressor. If the leaving chilled
water temperature is reduced, the lift therefore increases, and the efficiency level decreases.
When a lower entering condenser water temperature is used to rate the machine, the lift decreases
and the efficiency level is set higher. If the condenser flow rate is lowered, lift increases and the
efficiency level decreases.
ETL Testing Laboratories, like UL, conducts electrical performance and reliability testing.
OSHA (Occupation Safety and Health Administration) recognizes ETL as a nationally Recog-
nized Testing Laboratory as is Underwriters Laboratories. The ETL Listed Mark and Canadian-
ETL Listed Mark are accepted throughout the United States and Canada compliance with nation-
ally recognized standards such as ANSI (American National Standards Institute), UL, and CSA.
This certification mark indicates that the product has been tested to and has met the minimum
requirements of a widely recognized U.S. product safety standard, that the manufacturing site has
been audited, and that the applicant has agreed to a program of periodic factory follow-up inspec-
tions to verify continued conformance. If the mark includes a small “US” and/or “C,” it follows
product safety standards of United States and/or Canada respectively.
ASHRAE Standard 15
ASHRAE Standard 15, “Safety Standard for Refrigeration Systems,” has the primary goal of
mitigating safety risks to the environment, to mechanical room operators, and ultimately to the
public by incorporating specific design requirements for the safe installation and operation of me-
chanical refrigeration systems. Some of the design requirements of ASHRAE Standard 15 are:
• Location of refrigerant relief piping discharge
• Sizing of refrigerant pressure relief devices and piping per ASHRAE recommendation
• Restricting access to the mechanical room
• Providing sensors and a refrigerant monitor capable of detecting refrigerant leakage
• Installing a mechanical room ventilation system
• If the type of refrigerant in a chiller is changed, or if the chiller is replaced, then ASHRAE
15 will be applied.
Consulting engineers’ specifications and drawings incorporate ASHRAE 15 requirements
since it is has been adopted by building code authorities.
Figure 68
ASHRAE Standard 15 Requirements for a Typical Mechanical Room
Selection Criteria
Now that we have discussed all the items that go into chiller design, construction, and test-
ing/certification, let us look at the parameters that are used to select a centrifugal chiller using a
manufacturer’s ARI-certified selection program.
The first two pieces of information needed are the required capacity and efficiency. This
could be full load, IPLV, or ASHRAE 90.1 minimum efficiency requirements. Next, the stability
requirements of the chiller are selected. For humid regions, typical stability is chosen at approxi-
mately 50 percent of full load at design entering condenser water, to safeguard against surge
conditions.
Stability is a term that is used in evaluating the part load operating condition for a centrifugal
chiller. If the head pressure during part load operation is higher than the chiller was selected for,
the impeller may not be able to overcome the lift, and the chiller may enter an unstable opera-
tional condition causing the compressor to surge.
Centrifugal chillers are typically selected for full load and/or part load kW/ton targets. Then
they are checked for part load stability using software provided by the chiller manufacturer. A
typical part load stability check may involve running the chiller at part load points at entering
condenser water temperatures that follow a relief profile representative of the project geography.
For more information on the subject of cooling tower relief, refer to TDP-641, Condensers and
Cooling Towers.
Figure 69
Centrifugal Chiller Input Selection Screen 1
After that, the chilled and condenser fluid conditions are entered. These can be based on the
designer’s requirements, or at typical ARI conditions. For both the chilled and condenser water,
two of three inputs are required. For the chilled water, leaving chilled water temperature is typi-
cally set, and then either the flow rate or entering chilled water is entered. In the condenser, the
entering condenser water temperature at design is entered, and then either the leaving condenser
water temperature or the flow rate is entered.
Other parameters, such as the highest pressure drop allowed for the fluid, and the fouling fac-
tors, are also used here to help eventually determine the size of the heat exchangers and the size
of the compressor.
The next set of selection criteria is the type of starting equipment and the electrical require-
ments. These are typically determined by the site and designer or owner preference. The same is
true for the number of chiller passes, but this may also be dictated by the requirements of the
chiller capacity and water conditions.
Options that affect performance, and therefore the final chiller selection, are entered here.
Waterbox-type and waterside working pressure can be entered. Tubing material, wall thickness
and tube enhancements can be chosen as well, based on the application and design requirements.
Figure 70
Centrifugal Chiller Input Selection Screen 2
It is best to allow the program to select the cooler, condenser, compressor, and motor for ini-
tial selection. The program will pick the best options based on all the other inputs entered thus
far. However, these inputs may be entered manually at any time in the selection process. Once the
selection program has chosen an initial design, the user can go back and modify these inputs to
maximize the performance of the chiller. As an example, the compressor may be increased one
impeller size, or the condenser may be increased to improve performance.
These are the main inputs that determine the selected components of a water-cooled chiller
from a typical selection program. The format will vary among manufacturers, but the basic inputs
remain the same.
Summary
The intent of this TDP was to describe the water-cooled refrigeration cycle, as well as the de-
tails of the components, operation, and regulations that determine the chiller’s construction. From
reading this TDP, the student should be able to understand the main components in the centrifugal
refrigeration cycle, and be able to follow the path of water and refrigerant through the chiller. The
different types of compressors were described, so the reader should be familiar with the compres-
sion theories and have the ability to describe the differences in the compressor operating ranges
and chiller construction. The TDP then detailed the construction and uses of the components in a
water-cooled refrigeration cycle, and the student should be able to detail the differences and ad-
vantages to the various options.
Various starter types and were covered, and the TDP demonstrated the differences in starting
current and application for water-cooled chillers. The issue of refrigerants and the regulations
governing its usage, safety and chiller construction impacts was covered to allow the reader to
make informed decisions on what refrigerant should be used in a water-cooled chiller. The TDP
defined different capacity control methods, and the affects on efficiency should be recognized.
Heat transfer theory for heat exchangers provided the basic concepts for shell-and-tube heat trans-
fer and the process used to determine the heat exchanger construction and performance. The TDP
briefly outlined the different standards that relate to water-cooled chiller performance, construc-
tion, and installation. From this section, the student should now understand the agencies and
organizations that rate and certify water-cooled chillers. Finally, the TDP covered the necessary
selection inputs for a centrifugal chiller.
Work Session
____________________________ ___________________________
____________________________ ___________________________
____________________________
5. Describe the two types of compressor motor designs used in centrifugal chillers.
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
____________________________ __________________________
____________________________ __________________________
____________________________ __________________________
____________________________
_________________________________________________________________________
_________________________________________________________________________
9. What are two operation envelope limits for the centrifugal compressor?
_________________________________________________________________________
_________________________________________________________________________
11. Name three important effects refrigerant has on the construction of a chiller?
________________________________________
________________________________________
________________________________________
13. List three testing agencies that certify water-cooled chiller electrical code compliance.
________________________________________
________________________________________
________________________________________
___________________________________________________________________________
___________________________________________________________________________
15. List four reasons for the attraction of VFDs on centrifugal chillers.
________________________________________
________________________________________
________________________________________
________________________________________
Notes
Appendix
References
API Heat Transfer, Buffalo, NY. http://www.apiheattransfer.com/
ARI Standard 550/590, “Water Chilling Packages Using the Vapor Compression Guide.”
http://www.ari.org/std
ASHRAE Standard 90.1, “Energy Efficient Design of New Buildings Except Low-Rise
Residential Buildings
2. subcooling, economizer
5. hermetic motors, which are sealed to the atmosphere and utilize refrigerant cooling
open-drive motors, which are coupled to the compressor through a shaft seal and exposed to
the mechanical room atmosphere.
6. Hermetic motors are smaller, run cooler, and have lower inrush current. Open drive motors
offer flexibility of motor size and types of drivers that can be applied to the compressor.
7. across the line, auto-transformer, primary reactor, part winding, wye-delta, solid state, vari-
able frequency drives
8. Head is the measure of the pressure rise developed in the compressor, and lift is the differ-
ence between the saturated suction and condensing temperatures.
10. refrigerant flow control, hot gas bypass, and speed control combined with flow control
11. design working pressure and construction certification, physical size of chiller, and ability to
store refrigerant in chiller
12. refrigerant film resistance, tube wall metal resistance, fouling deposits resistance, fluid film
resistance
14. ASHRAE 15 will help you determine if you need a separate mechanical room. If you do, then
you should provide a tight fitting access door, a refrigerant monitor, an alarm system to notify
operators if there is a refrigerant leak, a mechanical room ventilation fan, and properly sized
relief lines. There are other requirements in addition to these listed in the standard.
15. high power factor, low inrush current, increased part load efficiency, low sound levels at part
load
Learning Objectives:
After reading this module, participants will be able to:
• Compare the advantages of water-cooled versus air-cooled chillers.
• Identify and diagram the different components of a basic refrigeration cycle as it applies to
as water-cooled chiller.
• Compare and describe the differences among scroll, reciprocating, centrifugal, and screw
compressors.
• Discuss the differences in construction of water-cooled chillers of various sizes.
• Identify the standards that relate to water-cooled chillers.
• Understand the typical inputs required to select a water-cooled chiller.
Supplemental Material:
Book Instructor Presentation
Form No. Cat. No. Cat. No. Title
TDP-622 796-054 797-054 Air-Cooled Chillers
TDP-705 796-070 797-070 Chilled Water Systems
Instructor Information
Each TDP topic is supported with a number of different items to meet the specific needs of the
user. Instructor materials consist of a CD-ROM disk that includes a PowerPoint™ presentation
with convenient links to all required support materials required for the topic. This always includes:
slides, presenter notes, text file including work sessions and work session solutions, quiz and
quiz answers. Depending upon the topic, the instructor CD may also include sound, video,
spreadsheets, forms, or other material required to present a complete class. Self-study or student
material consists of a text including work sessions and work session answers, and may also
include forms, worksheets, calculators, etc.
Carrier Corporation
Technical Training
800 644-5544
www.training.carrier.com