UNIT 7:
Transducers: Classification and selection of transducers. Strain gauges. LVDT.
Measurement of temperature and pressure. Photo-conductive and photo-voltaic cells.
06 Hours
Nearly all engineering applications require some form of measuring, controlling, calculating,
communicating and recording of data. These operations, grouped or isolated, are inherent in
measurement instrumentation. If the equipment is to be used for the quantitative analysis of an
analogue signal, i.e., a naturally occurring signal, the following must be taken into consideration:
www.allsyllabus.com
Generally, the broad definition of a sensors/ transducers includes
devices which convert physical quantities (mechanical force) into
analogue electrical signal (in the range of millivolts or milliamps).
Classification of Transducers
The Classification of Transducers is done in many ways. Some of the criteria for the
classification are based on their area of application, Method of energy conversion, Nature of
vtu.allsyllabus.com
www.allsyllabus.com
Broadly one such generalization is concerned with energy considerations wherein they are
classified as active & Passive transducers.
A component whose output energy is supplied entirely by its input signal (physical
quantity under measurement) is commonly called a ‘passive transducer’. In other words the
passive transducers derive the power required for transduction from an auxiliary source.
www.allsyllabus.com
Active transducers are those which do not require an auxiliary power source to produce
their output. They are also known as self generating type since they produce their own
voltage or current output.
The table 1 & 2 list the principle of operation and applications of the resistance transducers
respectively.
vtu.allsyllabus.com
www.allsyllabus.com
www.allsyllabus.com
Table 1. Type & principle of operation of resistance transducers
vtu.allsyllabus.com
www.allsyllabus.com
Capacitance Transducers
Principle of operation: Distance between two parallel plates is varied by an externally applied
force
2. Capacitor microphone
Principle of operation: Sound pressure varies the capacitance between a fixed plate and a
movable diaphragm. Applications: Speech, music, noise
3. Dielectric gage
2. Reluctance pickup
3. Differential transformer
vtu.allsyllabus.com
www.allsyllabus.com
5. Magnetostriction gage
2. Ionization chamber
3. Photoemissive cell
4. Photomultiplier tube
vtu.allsyllabus.com
www.allsyllabus.com
2. Moving-coil generator
www.allsyllabus.com
3. Piezoelectric pickup
4. Photovoltaic cell
vtu.allsyllabus.com
www.allsyllabus.com
SELECTING A TRANSDUCER
In a measurement system the transducer is the input element with the critical
function of transforming some physical quantity to a proportional electrical signal. Selection
of the appropriate transducer is therefore the first and perhaps most
important step in obtaining accurate results. A number of elementary questions
should be asked before a transducer can be selected, for example,
www.allsyllabus.com
Which transducer principle can best be used?
An appropriate answer to the question requires that the input and output characteristic of the
transducer be compatible with the recording or measurement system.
In most cases, these two questions can be answered readily, implying that the proper
transducer is selected simply by the addition of an accuracy/ tolerance. In practice this is
rarely possible due to the complexity of the various transducer parameters that affect the
accuracy. The accuracy requirements of the total system determine the degree to which
individual factors contributing to accuracy must be considered. Some of the factors affecting
accuracy are:
vtu.allsyllabus.com
www.allsyllabus.com
The total measurement error in a transducer- activated system may be reduced to fall within
the required accuracy range by the following techniques:
Some individual errors are predictable and can be calibrated out of the system. When the
entire system is calibrated, these calibration data may then be used to correct the recorded
www.allsyllabus.com
data. Environmental errors can be corrected by data reduction if the environmental effects are
recorded simultaneously with the actual data. Then the data are corrected by using the known
environmental characteristics of the transducers. These two techniques can provide a
significant increase in system accuracy.
Another method to improve overall system accuracy is to control artificially the environment
of the transducer. If the environment of the transducer can be kept unchanged, these errors
are reduced to zero. This type of control may require either physically moving the transducer
to a more favorable position or providing the required isolation from the environment by a
heater enclosure.
The following is the summary of the factors influencing the choice of a transducer for
measurement of a physical quantity:
1. Operating principle
vtu.allsyllabus.com
www.allsyllabus.com
2. Sensitivity
3. Operating Range
4. Accuracy
5. Cross Sensitivity: Situations where the actual quantity is measured in one plane and the
transducer is subjected lo variations in another plane. More than one promising transducer
design has had to be abandoned because the sensitivity to variations of the measured quantity
in a plane perpendicular to the required plane has been such as to give completely erroneous
results when the transducer has been used in practice.
7. Transient and Frequency Response. The transducer should meet desired time
domain specifications like peak overshoot, rise time, settling time and small dynamic
error. It should ideally have a flat frequency response curve. In practice, however,
www.allsyllabus.com
there will be cutoff frequencies and higher cut off frequency should he high in order
to have a wide bandwidth.
8. Loading Effects. The transducer should have a high input impedance and a low output
impedance to avoid loading effects.
vtu.allsyllabus.com
www.allsyllabus.com
11. Usage and Ruggedness. The ruggedness both of mechanical and electrical intensities
of transducer versus its size and weight must be considered while selecting a suitable
transducer.
12. Electrical aspects. The Electrical aspects that need consideration while selecting a transducer
include the length and type of cable required. Attention also must be paid to signal to noise
ratio in case the transducer is to be used in conjunction
with amplifiers.
13. Stability and Reliability. The transducers should exhibit a high degree of stability during its
operation and storage life. Reliability should be assured in case of failure of transducer in
order that the functioning of the instrumentation system continues unaffected.
14. Static Characteristics. Apart from low static error, the transducers should have a low
nonlinearity, low hysteresis, high resolution and a high degree of repeatability. The
transducer selected should be free from load alignment effects. It should
not need frequent calibration, should not have any component limitations, and should be
www.allsyllabus.com
preferably small in size,
vtu.allsyllabus.com
www.allsyllabus.com
Resistive Transducers
The resistance of a metal conductor is expressed by a simple equation that involves a few
physical quantities. The relationship is R = ρL/A, where R = resistance Ω, L = length of
conductor m. A = cross-sectional area of conductor ; m2, and ρ = resistivity of conductor
material ; Ωm.
Any method of varying one of the quantities involved in the above relationship can be the
design basis of an electrical resistive transducer.
Strain gauges
Strain gauges work on the principle that the resistance of a conductor or a semiconductor
changes when strained. This property can be used for measurement of displacement, force
and pressure. The resistivity of materials also changes with change of temperature thus
causing a change of resistance. If a metal conductor is stretched or compressed, its resistance
changes on account of the fact that both length and diameter of conductor change. Also there
www.allsyllabus.com
is a change in the value of resistivity of the conductor when it is strained and this property is
piezoresistive effect. Therefore, resistance strain gauges are also known as piezoresistive
gauges.
The strain gauges are used for measurement of strain and associated stress in
experimental stress analysis. Secondly, many other detectors and transducers, notably the
load cells, torque meters, diaphragm type pressure gauges, temperature sensors,
accelerometers and flow meters, employ strain gauges as secondary transducers.
The change in the value of resistance by straining the gauge may be partly explained by the
normal dimensional behaviour of elastic material.
vtu.allsyllabus.com
www.allsyllabus.com
Fig. 1
In order to find how ∆R depends upon the material physical quantities, the expression
for R = ρL/A is differentiated with respect to stress s
+ www.allsyllabus.com
dR ρ ∂L L ∂ρ ρL ∂A
= −
dS A ∂s A ∂s A 2 ∂s
Dividing by R = ρL/A on both sides we get
dR 1 ∂L 1 ∂ρ 1 ∂A
= + −
dS L ∂s ρ ∂s A ∂s
Observe that per unit change in resistance is due to per unit change in length ∆L/L, per unit
change in area ∆A/A, per unit change in resistivity ∆ρ/ρ
dR 1 ∂L 1 ∂A 1 ∂ρ
now the equation = − + becomes
dS L ∂s A ∂s ρ ∂s
vtu.allsyllabus.com
www.allsyllabus.com
www.allsyllabus.com
Gauge factor
Gauge factor is defined as the ratio of per unit change in resistance to per unit change
in length
vtu.allsyllabus.com
www.allsyllabus.com
Where the term 1 => Resistance change due to change of length, 2ν => Resistance
change due to change in area , (∆ρ/ρ)/ε => Resistance change due to piezoresistive
effect
If the change in the value of resistivity of a material when strained is neglected, the
gauge factor is :
Gf = 1 + 2v
The common value for Poisson's ratio for wires is 0.3.This gives a gauge factor of 1.6
for wire wound strain gauges. Poisson's ratio for all metals is between 0 & 0.5.This
gives a value of 2
Example 1: A resistance wire strain gauge uses a soft iron wire of small diameter. The gauge
factor is + 4.2. Neglecting the piezoresistive effects, calculate the Poisson's ratio.
We have ∆R/R = Gf ε.
vtu.allsyllabus.com
www.allsyllabus.com
Strain gauges are broadly used for two major types of applications and they are :
(i) experimental stress analysis of machines and structures, and (ii) construction of force,
torque, pressure, flow and acceleration transducers.
www.allsyllabus.com
7. Diffused metal strain gauges.
An unbonded metal strain gauge is shown in Fig.2. This gauge consists of a wire stretched
between two points in an insulating medium such as air. The wires are of copper nickel,
chrome nickel or nickel iron alloys. The flexture element is connected via a rod to a
diaphragm which is used for sensing of pressure. The wires are tensioned to avoid buckling
when they experience a compressive force
vtu.allsyllabus.com
www.allsyllabus.com
Fig. 2
www.allsyllabus.com
The unbonded metal wire gauges, used almost exclusively in transducer applications,
employ preloaded resistance wires connected in a Wheatstone bridge as shown in
Fig.3.
Fig.3.
vtu.allsyllabus.com
www.allsyllabus.com
At initial preload, the strains and resistances of the four arms are nominally equal,
with the result the output voltage of the bridge, eo = 0. Application of pressure
produces a small displacement which is about 0.004 mm (full scale), the displacement
increases tension in two wires and decreases it in the other two thereby increasing the
resistance of two wires which are in tension and decreasing the resistance of the
remaining two wires. This causes an unbalance of the bridge producing an output
voltage which is proportional to the input displacement and hence to the applied
pressure. Electric resistance of each arm is 120 Ω to 1000Ω, the input voltage to the
bridge is 5 to 10 V, and the full scale output of the bridge is typically about 20 mV to
50 mV.
www.allsyllabus.com
Rosette
vtu.allsyllabus.com
www.allsyllabus.com
Torque gauge
Helical gauge
Fig. 4
www.allsyllabus.com
Bonded Metal Foil Strain Gauges
This class of strain gauges is only an extension of the bonded metal wire strain gauges. The
bonded metal wire strain gauges (Fig. 5) have been completely superseded by bonded metal
foil strain gauges
Advantages
The spreading of wire permits a uniform distribution of stress over the grid. The carrier is
bonded with an adhesive material to file specimen under study. This permits a good transfer
of strain from carrier to grid of wires. The wires cannot buckle as they are embedded in a
matrix of cement and hence faithfully follow both the tensile and compressive strains of the
specimen.
vtu.allsyllabus.com
www.allsyllabus.com
Fig. 5
Foil type gauges have a much greater heat dissipation capacity as compared with wire
www.allsyllabus.com
wound strain gauges on account of their greater surface area for the same volume. For this
reason, they can be used for higher operating temperature range. Also the large surface area
leads to better bonding. The sensing elements of foil gauges are formed from sheets less
than 0.005 mm thick by photocopying process, which allow greater flexibility with regard to
shape.
Evaporation deposited thin film metal strain gauges are mostly used for the fabrication of
transducers. They are of sputter deposited variety. Both processes begin with a suitable
elastic metal element. The elastic metal element converts the physical quantity into a
strain. To cite an example of a pressure transducer, a thin, circular metal diaphragm is
formed. Both the evaporation and sputtering processes form all the strain gauge elements
directly on the strain surface, they are not separately attached as in the case of bonded strain
gauges.
vtu.allsyllabus.com
www.allsyllabus.com
For a high sensitivity, a high value of gauge factor is desirable. A high gauge factor means a
relatively higher change in resistance which can be easily measured with a good degree of
accuracy. Semiconductor strain gauges are used where a very high gauge factor and a small
envelope are required. They depend for their action upon piezo-resistive effect i.e. the
change in the value of the resistance due to change in resistivity. Semi-conducting materials
such as silicon and germanium are used as resistive materials
Fig. 6
www.allsyllabus.com
A typical strain gauge consists of a strain sensitive crystal material and leads that are
sandwiched in a protective matrix as shown in Fig.6. The production of these gauges
employs conventional semi-conductor technology using semi-conducting wafers or filaments
which have a thickness of 0.05 mm and bonding them on a suitable insulating substrates,
such as teflon. Gold leads are generally employed for making the contacts.
Advantages: high gauge factor of about 130. This allows measurement of very small strains
of the order of 0.01 microstrain. Hysteresis characteristics of semi-conductor strain gauges
are excellent. Some units maintain it to less than 0.05%. Fatigue life is in excess of 10 x 106
operations and the frequency response is upto 1012 Hz. Semi-conductor strain gauges can be
very small ranging in length from 0.7 to 7 mm. They are very useful for measurement of
local strains.
Disadvantages : The major and serious disadvantage of semiconductor strain gauges is that
they are very sensitive to changes in temperature, Linearity of the semi-conductor strain
gauge is poor , semi-conductor strain gauges are more expensive and difficult to attach to the
object under study
vtu.allsyllabus.com
www.allsyllabus.com
are primarily used in transducers. The diffusion process used in IC manufacture is employed.
In pressure transducers, for example, the diaphragm would be of silicon rather than metal
and the strain gauge effect would be realized by depositing impurities in the diaphragm to
form an intrinsic strain gauge. This type of construction may allow lower manufacturing
costs in some designs, as a large number of diaphragms can be made on a single silicon
wafer.
Rosettes
In addition to single element strain gauges, a combination of strain gauges called "Rosettes"
are available in many combinations for specific stress analysis or transducer applications. In
practical problems, an element may be subjected to stresses in any direction and hence it
is not possible to locate the direction of principle stress. Therefore, it is not possible to
orient the strain gauges along the direction of principle stress. Hence there is a necessity
to evolve a strain gauge measurement system which measures the values of principle
www.allsyllabus.com
strains and stresses without actually knowing their directions. The solution to the
problem lies in using three strain gauges to form a unit called a Rosette as shown in Fig.
7
vtu.allsyllabus.com
www.allsyllabus.com
www.allsyllabus.com
vtu.allsyllabus.com
www.allsyllabus.com
Fig. 7
www.allsyllabus.com
vtu.allsyllabus.com
www.allsyllabus.com
LVDT
DISPLACEMENT TRANSDUCERS
The concept of converting an applied force into a displacement is basic to many types of
transducers. The mechanical elements that are used to convert the applied force into a
displacement are called force-summing devices.
2) Bellows
4) Straight tube
Some of the Force-summing Devices Used in accelerometer and vibration pickups are
1)Mass cantilever, single or double suspension
www.allsyllabus.com
2)Pivot torque
The displacement created by the action of the force-summing device is converted into a
change of some electrical parameter.
The electrical principles commonly used in the measurement of displacement are Capacitive,
Inductive , Differential transformer, Ionization, Oscillation, Photoelectric, Piezoelectric,
Potentiometric
vtu.allsyllabus.com
www.allsyllabus.com
Diaphragm
www.allsyllabus.com
Bellows
Bourdon tube
vtu.allsyllabus.com
www.allsyllabus.com
Fig. 8
www.allsyllabus.com
vtu.allsyllabus.com
www.allsyllabus.com
The differential transformer transducer measures force in terms of the displacement of the
ferromagnetic core of a transformer. The basic construction of the LVDT is given in Fig, 9.
The transformer consists of a single primary winding and two secondary windings which are
placed on either side of the primary. The secondaries have an equal number of turns but they
are connected in series opposition so that the emfs induced in the coils OPPOSE each other.
The position of the movable core determines the flux linkage between the ac-excited primary
winding and each of the two secondary winding.
www.allsyllabus.com
vtu.allsyllabus.com
www.allsyllabus.com
Fig. 10
www.allsyllabus.com
Relative positions of the core generate the indicated output voltages as shown in Fig. 10. The
linear characteristics impose limited core movements, which are typically up to 5 mm from
the null position.
With the core in the center, (or reference position or Fig. 11,), the induced emfs in the
secondaries are equal, and since they oppose each other, the output voltage will be 0 V.
When an externally applied force moves the core to the left-hand position, more magnetic
flux links the left-hand coil than the right-hand coil and the Differential Output E0 = ES1 –
ES2 Is in-phase with Ei as ES1 > ES2 . The induced emf of the left hand coil is therefore larger
than the induced emf of the right-hand coil. The magnitude of the output voltage is then
equal to the difference between the two secondary voltages, and it is in phase with the
voltage of the left-hand coil.
Similarly, when the core is forced to move to the right, more flux links the right-hand
coil than the left-hand coil and the resultant output voltage is now in phase with the emf of
vtu.allsyllabus.com
www.allsyllabus.com
the right-hand coil, while its magnitude again equals the difference between the two induced
emfs.
www.allsyllabus.com
Fig. 11
vtu.allsyllabus.com
www.allsyllabus.com
www.allsyllabus.com
Fig. 12
Ideally the output voltage at the null position should be equal to zero. In actual practice there
exists a small voltage at the null position. (refer Fig. 12). This may be on account of
presence of harmonics in the input supply voltage and also due to harmonics produced
in the output voltage due to use of iron Displacement core. There may be either an
incomplete magnetic or electrical unbalance or both which result in a finite output voltage
at the null position. This finite residual voltage is generally less than 1% of the maximum
output voltage in the linear range. Other causes of residual voltage are stray magnetic fields
and temperature effects.
vtu.allsyllabus.com
www.allsyllabus.com
Example 1:
Solution:
www.allsyllabus.com
Minimum voltage that can be read on the voltmeter = (1/5) x 50 = 1mV
Applications of LVDT
Acting as a secondary transducer it can be used as a device to measure force, weight and
pressure etc. The force measurement can be done by using a load cell as the primary
transducer while fluid pressure can be measured by using Bourdon tube which acts as
primary transducer. The force or the pressure is converted into a voltage.
vtu.allsyllabus.com
www.allsyllabus.com
The electrical strain gauges attached to a diaphragm as shown in Fig.13 may be used for
measurement of pressure.
Fig. 13
www.allsyllabus.com
The output of these strain gauges is a function of the local strain, which in turn is a function
of the diaphragm deflection and the differential pressure.
P = P2 – P1 (when the deflection is less than one third of the diaphragm thickness.)
One of the disadvantages of the method is the small physical area is required for mounting
the strain gauges. Change in resistance of strain gauges on account of application of pressure
is calibrated in terms of the differential pressure. Gauges of this type are made in sizes
having a lower range of : 100 kN/m2 to 3 MN/m2 to an upper range of 100 kN/m2 to 100
MN/m2.
vtu.allsyllabus.com
www.allsyllabus.com
Inductive transducers have been used as secondary transducers along with a diaphragm for
measurement of pressure. Fig.14 shows an arrangement which uses two coils;
an upper and a lower coil which form the two arms of an a c. bridge.
The coils have equal number of turns. The other two arms of the bridge are formed by two
equal resistances each of value R. The diaphragm is symmetrically placed with respect to the
coils when Pl = P2, the reluctances of the paths of magnetic flux for both the coils are equal
and hence the inductances of the coils are equal. Under this condition the bridge is balanced
and the output eo, of the bridge is zero. Suppose P2 is greater than Pl and the differential
pressure P = P2 - Pl deflects the diaphragm upwards through a distance d the reluctance of
the flux path of the upper and lower coils vary. The bridge becomes unbalanced and the
output voltage is directly proportional to displacement d.
www.allsyllabus.com
vtu.allsyllabus.com
www.allsyllabus.com
Measurement of Temperature
The principles used in the measurement of pressure are also applied in the measurement of
temperature, flow and liquid levels. Hence some of the working principles of the instruments
are repeated
Resistance Thermometers
Principle of working: The resistance of a conductor changes when its temperature is changed.
This property is utilized for measurement of temperature. The variation of resistance R with
temperature T (ºK) can be represented by the following relationship for most of the metals as:
www.allsyllabus.com
where Ro = resistance at temperature T= 0 and α1,α2,α3,αn are constants.
The resistance thermometer uses the change in electrical resistance of conductor to determine
the temperature. The resistivity of metals showing a marked dependence on temperature was
discovered by Sir Humphry Davy.
All metals produce a positive change in resistance with temperature. The requirements of
a conductor material to be used in RTDs are :
(i) The change in resistance of material per unit change in temperature should be as large as
possible. This implies a metal with a high value of resistivity should be used for RTDs.
ii) The material should have a high value of α so that minimum volume of material is used
Rt = Rref ( 1 + α ∆T)
vtu.allsyllabus.com
www.allsyllabus.com
This change in resistance (∆R) can be measured with a Wheatstone bridge which may be
calibrated to indicate the temperature that caused the resistance change rather than the
resistance itself.
Fig. 15 shows the variation of resistance with temperature for several commonly used
materials. The graph indicates that the resistance of platinum and copper increases almost
linearly with increasing temperature, while the characteristic for nickel is decidedly
nonlinear.
www.allsyllabus.com
Fig. 15
vtu.allsyllabus.com
www.allsyllabus.com
www.allsyllabus.com
Resistance thermometers are generally of the probe type (see Fig.16) for immersion in the
medium whose temperature is to be measured or controlled. A typical sensing element for a
probe-type thermometer is constructed by coating a small platinum, or silver tube with
ceramic material, winding the resistance wire over the coated tube, and coating the finished
winding again with ceramic. This small assembly is then fired at high temperature to assure
annealing of the winding and then it is placed at the tip of the probe, The probe is protected
by a sheath to produce the complete sensing element. Practically all resistance thermometers
for industrial applications are mounted in a tube or well to provide protection against
mechanical damage and to guard against contamination and eventual failure. Protecting
tubes are used at atmospheric pressure; when they are equipped with a pipe thread bushing,
they may be exposed to low or medium pressures. Metal tubes offer adequate protection to
vtu.allsyllabus.com
www.allsyllabus.com
the sensing element at temperatures to 2100 oF, although they may become slightly porous at
temperatures above 1,500oF and then fail to protect against contamination.
www.allsyllabus.com
Fig. 16
vtu.allsyllabus.com
www.allsyllabus.com
Fig. 17
The Wheatstone bridge has certain disadvantages when it is used to measure the resistance
variations of the resistance thermometer. These are the effect of contact resistances of
www.allsyllabus.com
connections to the bridge terminals, heating of the elements by the unbalance current, and
heating of the wires connecting the thermometer to the bridge. Slight modifications of the
Wheatstone bridge, such as the double slide-wire bridge, eliminate most of these problems.
To this day platinum is used as the primary element in all high accuracy resistance
thermometers. In fact, the platinum resistance temperature detector (PRTD) (see Fig. 17) is
used as an interpolation standard from oxygen point (-182.96) to antimony point (630.74 oC).
Platinum is especially suited for this purpose, as it can withstand high temperatures while
maintaining excellent stability. As a nobel metal, it shows limited susceptibility to
contamination.
vtu.allsyllabus.com
www.allsyllabus.com
www.allsyllabus.com
Fig. 17 Industrial Platinum Resistance Thermometer
vtu.allsyllabus.com
www.allsyllabus.com
Thermistors
Some materials, such as carbon and germanium, have a negative temperature coefficient of
resistance that implies that the resistance decreases with an increase in temperature.
Thermistors or thermal resistors, are semiconductor devices that behave as resistors with a
high, usually negative temperature coefficient of resistance.
In some cases, the resistance of a thermistor at room temperature may decrease as much as 6
per cent for each 1oC rise in temperature. This high sensitivity to temperature change makes
the thermistor extremely well suited to precision temperature measurement, control. and
compensation. Thermistors are widely used in applications, especially in the lower
temperature range of -100'C to 300 oC. Thermistors are composed of a sintered mixture of
metallic oxides, such as manganese, nickel, cobalt, copper, iron, and uranium. Their
resistances range from 0.5 Ω to 75 MΩ and they are available in a wide variety of shapes and
sizes. Smallest in size are the beads with a diameter of 0.15 mm to 1.25 mm.
www.allsyllabus.com
Beads may be sealed in the tips of solid glass rods to form probes that are somewhat easier
to mount than beads. Disks and washers are made by pressing thermistor material under high
pressure into flat cylindrical shapes with diameters from 2.5 mm to 25 mm. Washers can be
stacked and placed in series or in parallel for increased power dissipation.
vtu.allsyllabus.com
www.allsyllabus.com
A thermistor produces a large change of resistance with a small change in the temperature
being measured. This large sensitivity of thermistor provides good accuracy and resolution.
A typical industrial-type thermistor with a 2000 Ω resistance at 25oC and a resistance
temperature co-efficient of 3.9% per oC exhibits a change of 78 Ω per degree oC change in
temperature.
www.allsyllabus.com
Fig. 19 Measurement of temperature using a thermistor & a bridge circuit for getting higher
sensitivities
vtu.allsyllabus.com
www.allsyllabus.com
Thermocouples
In 1821 Thomas Seebeck' discovered that when two dissimilar metals were in
contact, a voltage was generated where the voltage was a function of temperature. The
device, consisting of two dissimilar metals joined together, is called a Thermocouple and the
voltage is called the Seebeck voltage. As an example, joining copper and Constantan
produces a voltage on the order of a few tens of milli-volts (see Fig. 20) with the positive
potential at the copper side. An increase in temperature causes an increase in voltage.
www.allsyllabus.com
Fig. 20
There are several methods of joining the two dissimilar metals. One is to weld the wires
together. This produces a brittle joint, and if not protected from stresses, this type of
thermocouple can fracture and break apart. During the welding process gases from the
welding can diffuse into the metal and cause a change in the characteristic of the
thermocouple.
vtu.allsyllabus.com
www.allsyllabus.com
Another method of joining the two dissimilar metals is to solder the wires together. This
has the disadvantage of introducing a third dissimilar metal. But if both sides of the
thermocouple are at the same temperature, the Seebeck voltage due to thermocouple action
between the two metals of the thermocouple and the solder will have equal and opposite
voltages and the effect will cancel.
More modern techniques use electronic reference junctions that are not necessarily at 0oC.
This junction is called the reference or cold junction due to the fact that this junction was in
the ice bath.
www.allsyllabus.com
Fig. 21
vtu.allsyllabus.com
www.allsyllabus.com
Decalibration. This error is a potentially serious fault, as it can cause more subtle errors that
may escape detection. Decalibration is due to altering the characteristics of the thermocouple
wire, thus changing the Seebeck Voltage. This can be caused by subjecting the wire to high
temperatures,diffusion of particles from the atmosphere into the wire, or by cold working the
wire. The last effect may be caused by straining the wire by drawing it through a long
conduit.
Insulation degradation. The thermocouple is often used at very high temperatures. In some
cases the insulation can break down and cause a significant leakage resistance which will
cause an error in the measurement of the Seebeck voltage. In addition, chemicals in the
www.allsyllabus.com
insulation can diffuse into the thermocoupe wire and cause decalibration
Galvanic action
Chemicals coming in contact with the thermocouple wire can cause a galvanic action. This
resultant voltage can be as much as 100 times the Seebeck effect, causing extreme errors.
Thermal conduction.
The thermocouple wire will shunt heat energy away from the source to be measured. For
small masses to be measured, small-diameter thermocouple wire could be used. However, the
smaller-diameter wire is more susceptible to the effects described previously . if a reasonable
compromise between the degrading effects of small thermocouple wire and the loss of
thermal energy and the resultant temperature error cannot be found, thermocouple extension
wire can be used. This allows the thermocouple to be made of small-diameter wire, while the
extension wire that covers the majority of the connecting distance is of a much larger
diameter and not as susceptible to the degrading effects.
vtu.allsyllabus.com
www.allsyllabus.com
Photosensitive elements are versatile tools for detecting radiant energy or light. They
exceed the sensitivity of the human eye to all the colors of the spectrum and
operate even into the ultraviolet and infrared regions.
The photosensitive device has found practical use in many engineering applications.
Vacuum-type phototubes
Gas-type phototubes
Multiplier phototubes
Photovoltaic cells
semiconductor junction devices used to convert radiation energy into electrical power
vtu.allsyllabus.com
www.allsyllabus.com
Photoconductive Cells
www.allsyllabus.com
The essential elements of a photoconductive cell are the ceramic substrate, a layer of
photoconductive material, metallic electrodes to connect the device into a circuit, and a
moisture-resistant enclosure.(refer Fig. 22)
vtu.allsyllabus.com
www.allsyllabus.com
www.allsyllabus.com
Fig. 22
vtu.allsyllabus.com
www.allsyllabus.com
www.allsyllabus.com
Fig. 23
Fig. 24
vtu.allsyllabus.com
www.allsyllabus.com
Fig. 24 uses the electrical resistance of the material varies with the amount of light energy
striking it. When the photo-cell has the appropriate light incident upon it, its resistance is
low and the current through the relay is consequently high to operate the relay. When the
light is interrupted or shut off partially or completely, the resistance of the photocell
increases thereby reducing the current and switching off the relay The low resistance of
photo-conductive cells when they are exposed lo light means that they can and are designed
to carry moderate currents, such as are capable of operating a relay coil directly without any
amplification. They can be designed to operate upon low voltages and are thus used in
industrial control equipments. For example they can be used for counting packages moving
on a conveyor belt, in burglar alarm circuits, wherein the interception of light actuates an
alarm circuit. The devices used would be sensitive in the infra-red region, so that the burglar
cannot see the beam of light .
When the cell is kept in darkness, its resistance is called dark resistance. The dark
resistance may be as high as 10 x 1012 Ω. If the cell is illuminated its resistance decreases.
www.allsyllabus.com
vtu.allsyllabus.com
www.allsyllabus.com
Photovoltaic Cells
They generate a voltage which is proportional to EM radiation’s Intensity. They are called
photovoltaic cells because of their voltage generating characteristics. They, in fact, convert
the EM energy into electrical energy. They are active transducers i.e they do not need an
external source to power them.
Photovoltaic cells may be used in a number of applications. The silicon solar cell converts
the radiant energy of the sun into electrical power. The solar cell consists of a thin slice of
single crystal p-type silicon, up to 2 cm square into which a very thin (0.5 micron) layer of
n-type material is diffused. The conversion efficiency depends on the spectral content and
the intensity of the illumination.
www.allsyllabus.com
conduction holes and electrons causing a difference of potential to develop across the
junction.
Advantages of the photovoltaic cell, is its ability to generate a voltage without any form of
bias and its extremely fast response..This means that it can be used as an energy converter
directly. One use of this is in photographic exposure meters which require no battery. The
cell voltage operates the meter directly, or may be directly linked to the iris to control the
aperture .
Multiple-unit silicon photovoltaic devices may be used for sensing light in applications such
as reading punched cards in the data-processing industry. Used to sense the pattern of holes
in the card tapes. The size of the transducer may be an advantage if the holes are closely
spaced .Gold-doped germanium cells with controlled spectral response characteristics act
as photovoltaic devices in the infrared region of the spectrum and may be used as infrared
detectors.