Bare Aluminium Conductors AAC According To UNE 21018

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Conductor type Bare aluminium conductors AAC according to UNE 21018

Marking acc. to UNE 21018 L 28 L 40 L 56 L 80 L 110 L 145


Marking acc. to IEC 61089 28-A1-7 43-A1-7 55-A1-7 76-A1-19 117-A1-19 148-A1-19
Marking acc. to EN 50182 28-AL1 43-AL1 55-AL1 76-AL1 117-AL1 148-AL1
Design of conductor

Number of wires 7 7 7 19 19 19
Wire diameter mm 2,25 2,80 3,15 2,25 2,80 3,15
Strand direction of the last layer right (Z) right (Z) right (Z) right (Z) right (Z) right (Z)
Diameter of conductor mm 6,75 8,40 9,45 11,3 14,0 15,8
Computational cross-sectional area mm2 27,8 43,1 54,6 75,5 117,0 148,1
Weight of conductor kg/km 76,0 117,7 148,9 207,4 321,2 406,5

Conductor properties

Computational breaking force kN 5,01 7,33 9,00 13,60 19,89 24,43


Modulus of elasticity N/mm2 60 000 60 000 60 000 57 000 57 000 57 000
Linear expansion coefficient (1/ºK)*10-6 23,0 23,0 23,0 23,0 23,0 23,0
Computational resistance (20°C; DC) Ω/km 1,0269 0,6631 0,5239 0,3804 0,2457 0,1941
Current load capacity 1) A 155 205 235 290 385 450
Short-circuit current (1s; 200°C) kA 2,4 3,7 4,6 6,4 9,9 12,6

Standard packaging

Standard sections 2) m 5 000 4 000 5 000 5 000 3 500 2 500


Drum type 10 10 12 14 14 14
Gross weight kg 450 545 860 1200 1290 1180

1)
Load capacity calculated according to IEC 1597 standard for the following parameters:
- sun radiation intensity: 895 W/m2
- coefficient of sun radiation absorption: 0,5
- coefficient of emissivity in relation to complete radiator: 0,55
- wind velocity in lateral direction to the conductor: 0,6 m/s
- ambient temperature: 35 ºC
- conductor operating temperature: 80 ºC
2)
Delivery of conductors is possible in different sections after arrangements
Conductor type Bare aluminium conductors AAC according to UNE 21018
Marking acc. to UNE 21018 L 180 L 280 L 400 L 450 L 550 L 630
Marking acc. to IEC 61089 188-A1-19 279-A1-37 381-A1-61 454-A1-61 547-A1-61 638-A1-61
Marking acc. to EN 50182 188-AL1 279-AL1 381-AL1 454-AL1 547-AL1 638-AL1
Design of conductor

Number of wires 19 37 61 61 61 61
Wire diameter mm 3,55 3,10 2,82 3,08 3,38 3,65
Strand direction of the last layer right (Z) right (Z) right (Z) right (Z) right (Z) right (Z)
Diameter of conductor mm 17,8 21,7 25,4 27,7 30,4 32,9
Computational cross-sectional area mm2 188,1 279,3 381,0 454,5 547,3 638,3
Weight of conductor kg/km 516,3 769,3 1053 1256 1513 1764

Conductor properties

Computational breaking force kN 30,09 46,08 64,77 74,99 90,31 102,1


Modulus of elasticity N/mm2 57 000 57 000 57 000 57 000 57 000 57 000
Linear expansion coefficient (1/ºK)*10-6 23,0 23,0 23,0 23,0 23,0 23,0
Computational resistance (20°C; DC) Ω/km 0,1528 0,1033 0,0759 0,0637 0,0529 0,0453
Current load capacity 1) A 525 675 825 925 1040 1150
Short-circuit current (1s; 200°C) kA 16,0 23,7 32,3 38,6 46,5 54,2

Standard packaging

Standard sections 2) m 2 200 2 500 2 100 1 800 1 500 1 400


Drum type 14 16 18 18 20 20
Gross weight kg 1300 2160 2560 2610 2730 2930

1)
Load capacity calculated according to IEC 1597 standard for the following parameters:
- sun radiation intensity: 895 W/m2
- coefficient of sun radiation absorption: 0,5
- coefficient of emissivity in relation to complete radiator: 0,55
- wind velocity in lateral direction to the conductor: 0,6 m/s
- ambient temperature: 35 ºC
- conductor operating temperature: 80 ºC
2)
Delivery of conductors is possible in different sections after arrangements
Conductor type Bare alloy conductors AAAC according to UNE 21018
Marking acc. to UNE 21018 D 28 D 40 D 56 D 80 D 110 D 145
Marking acc. to IEC 61089 24-A2-7 37-A2-7 47-A2-7 65-A2-19 101-A2-19 128-A2-18
Marking acc. to EN 50182 28-AL2 43-AL2 55-AL2 76-AL2 117-AL2 148-AL2
Design of conductor

Number of wires 7 7 7 19 19 19
Wire diameter mm 2,25 2,80 3,15 2,25 2,80 3,15
Strand direction of the last layer right (Z) right (Z) right (Z) right (Z) right (Z) right (Z)
Diameter of conductor mm 6,75 8,40 9,45 11,3 14,0 15,8
Computational cross-sectional area mm2 27,8 43,1 54,6 75,5 117,0 148,1
Weight of conductor kg/km 76,0 117,7 148,9 207,4 321,2 406,5

Conductor properties

Computational breaking force kN 9,05 14,01 17,73 24,55 38,02 48,12


Modulus of elasticity N/mm2 60 000 60 000 60 000 57 000 57 000 57 000
Linear expansion coefficient (1/ºK)*10-6 23,0 23,0 23,0 23,0 23,0 23,0
Computational resistance (20°C; DC) Ω/km 1,1931 0,7704 0,6087 0,4420 0,2854 0,2255
Current load capacity 1) A 145 190 220 275 360 420
Short-circuit current (1s; 200°C) kA 2,2 3,4 4,3 6,0 9,3 11,7

Standard packaging

Standard sections 2) m 5 000 4 000 5 000 5 000 3 500 2 500


Drum type 10 10 12 14 14 14
Gross weight kg 450 545 860 1200 1290 1180

1)
Load capacity calculated according to IEC 1597 standard for the following parameters:
- sun radiation intensity: 895 W/m2
- coefficient of sun radiation absorption: 0,5
- coefficient of emissivity in relation to complete radiator: 0,55
- wind velocity in lateral direction to the conductor: 0,6 m/s
- ambient temperature: 35 ºC
- conductor operating temperature: 80 ºC
2)
Delivery of conductors is possible in different sections after arrangements
Conductor type Bare alloy conductors AAAC according to UNE 21018
Marking acc. to UNE 21018 D 180 D 280 D 400 D 450 D 550 D 630
Marking acc. to IEC 61089 162-A2-19 240-A2-37 328-A2-61 391-A2-61 471-A2-61 549-A2-61
Marking acc. to EN 50182 188-AL2 279-AL2 381-AL2 454-AL2 547-AL2 638-AL2
Design of conductor

Number of wires 19 37 61 61 61 61
Wire diameter mm 3,55 3,10 2,82 3,08 3,38 3,65
Strand direction of the last layer right (Z) right (Z) right (Z) right (Z) right (Z) right (Z)
Diameter of conductor mm 17,8 21,7 25,4 27,7 30,4 32,9
Computational cross-sectional area mm2 188,1 279,3 381,0 454,5 547,3 638,3
Weight of conductor kg/km 516,3 769,3 1053 1256 1513 1764

Conductor properties

Computational breaking force kN 59,24 90,76 123,8 147,7 177,9 201,1


Modulus of elasticity N/mm2 57 000 57 000 57 000 57 000 57 000 57 000
Linear expansion coefficient (1/ºK)*10-6 23,0 23,0 23,0 23,0 23,0 23,0
Computational resistance (20°C; DC) Ω/km 0,1776 0,1200 0,0882 0,0740 0,0614 0,0527
Current load capacity 1) A 490 635 775 865 975 1080
Short-circuit current (1s; 200°C) kA 14,9 22,1 30,2 36,0 43,3 50,8

Standard packaging

Standard sections 2) m 2 200 2 500 2 100 1 800 1 500 1 400


Drum type 14 16 18 18 20 20
Gross weight kg 1300 2160 2560 2610 2730 2930

1)
Load capacity calculated according to IEC 1597 standard for the following parameters:
- sun radiation intensity: 895 W/m2
- coefficient of sun radiation absorption: 0,5
- coefficient of emissivity in relation to complete radiator: 0,55
- wind velocity in lateral direction to the conductor: 0,6 m/s
- ambient temperature: 35 ºC
- conductor operating temperature: 80 ºC
2)
Delivery of conductors is possible in different sections after arrangements
Conductor type Bare steel reinforced aluminium conductors ACSR according to UNE 21018
Marking acc. to UNE 21018 LA 30 LA 56 LA 78 LA 110 LA 145 LA 180
Marking acc. to IEC 61089 27-A1/S1A-6/1 47-A1/S1A-6/1 67-A1/S1A-6/1 94-A1/S1A-30/7 119-A1/S1A-30/7 147-A1/S1A-30/7
Marking acc. to EN 50182 27-AL1/4-ST1A 47-AL1/8-ST1A 67-AL1/11-ST1A 94-AL1/22-ST1A 119-AL1/28-ST1A 147-AL1/34-ST1A
Design of conductor
Galvanized steel core
Number of steel wires 1 1 1 7 7 7
Diameter of steel wires mm 2,38 3,15 3,78 2,00 2,25 2,50
Core diameter mm 2,38 3,15 3,78 6,00 6,75 7,50
Core cross-sectional area mm2 4,45 7,79 11,2 22,0 27,8 34,4
Core weight kg/km 34,7 60,7 87,4 172,1 217,9 269,0
Aluminium
Number of aluminium wires 6 6 6 30 30 30
Strand direction of the last layer right (Z) right (Z) right (Z) right (Z) right (Z) right (Z)
Diameter of aluminium wires mm 2,38 3,15 3,78 2,00 2,25 2,50
Cross-sectional area of aluminium part mm2 26,7 46,8 67,3 94,2 119,3 147,3
Weight of aluminium part kg/km 73,1 128,1 184,4 260,4 329,5 406,8
Conductor
Total number of wires 7 7 7 37 37 37
Diameter of conductor mm 7,14 9,45 11,3 14,0 15,8 17,5
Total cross-sectional area mm2 31,1 54,6 78,6 116,2 147,1 181,6
Conductor weight without grease kg/km 107,8 188,8 271,8 432,5 547,4 675,8
Grease weight 1) kg/km 0,7 0,9 1,1 3,5 4,5 5,5
Conductor properties
Computational breaking force kN 9,79 16,29 23,12 43,17 54,03 64,94
Modulus of elasticity N/mm2 81 000 81 000 81 000 82 000 82 000 82 000
Linear expansion coefficient (1/ºK)*10-6 19,2 19,2 19,2 17,8 17,8 17,8
Computational resistance (20°C; DC) Ω/km 1,0737 0,6129 0,4256 0,3067 0,2423 0,1963
Current load capacity 2) A 150 220 275 345 400 460
Short-circuit current (1s; 200°C) kA 2,3 4,0 5,7 8,0 10,1 12,5
Standard packaging
Standard sections 3) m 5 000 3 500 4 000 3 500 4 500 3 800
Drum type 10 10A 12 14 16 16
Gross weight kg 610 660 1210 1680 2690 2800
1)
Specified grease weight applies to steel core lubrication case
2)
Load capacity calculated according to IEC 1597 standard for the following parameters:
- sun radiation intensity: 895 W/m2
- coefficient of sun radiation absorption: 0,5
- coefficient of emissivity in relation to complete radiator: 0,55
- wind velocity in lateral direction to the conductor: 0,6 m/s
- ambient temperature: 35 ºC
- conductor operating temperature: 80 ºC
3)
Delivery of conductors is possible in different sections and on different drums after making arrangements with the manufacturer
Conductor type Bare steel reinforced aluminium conductors ACSR according to UNE 21018
Marking acc. to UNE 21018 LA 280 HAWK LA 380 GULL LA 455 CONDOR LA 545 CARDINAL LA 635 FINCH
Marking acc. to IEC 61089 242-A1/S1A-27/7 337-A1/S1A-54/7 405-A1/S1A-54/7 485-A1/S1A-54/7 565-A1/S1A-54/19
Marking acc. to EN 50182 242-AL1/39-ST1A 337-AL1/44-ST1A 402-AL1/52-ST1A 485-AL1/63-ST1A 565-AL1/72-ST1A
Design of conductor
Galvanized steel core
Number of steel wires 7 7 7 7 19
Diameter of steel wires mm 2,68 2,82 3,08 3,38 2,19
Core diameter mm 8,04 8,46 9,24 10,1 11,0
Core cross-sectional area mm2 39,5 43,7 52,2 62,8 71,6
Core weight kg/km 309,1 343 409 492 562
Aluminium
Number of aluminium wires 26 54 54 54 54
Strand direction of the last layer right (Z) right (Z) right (Z) right (Z) right (Z)
Diameter of aluminium wires mm 3,44 2,82 3,08 3,38 3,65
Cross-sectional area of aluminium part mm2 241,6 337,3 402,3 484,5 565,0
Weight of aluminium part kg/km 666,9 932 1112 1339 1561
Conductor
Total number of wires 33 61 61 61 73
Diameter of conductor mm 21,8 25,4 27,7 30,4 32,9
Total cross-sectional area mm2 281,1 381,0 454,5 547,3 636,6
Conductor weight without grease kg/km 976,2 1275 1521 1831 2123
Grease weight 1) kg/km 6,3 7,0 8,3 10,0 12,7
Conductor properties
Computational breaking force kN 84,99 107,2 123,8 149,0 174,1
Modulus of elasticity N/mm2 77 000 70 000 70 000 70 000 68 000
Linear expansion coefficient (1/ºK)*10-6 18,9 19,3 19,3 19,3 19,4
Computational resistance (20°C; DC) Ω/km 0,1195 0,0857 0,0719 0,0597 0,0512
Current load capacity 2) A 630 775 870 980 1085
Short-circuit current (1s; 200°C) kA 20,5 28,6 34,2 44,1 48,0
Standard packaging
Standard sections 3) m 2 500 2 100 1 800 1 600 1 400
Drum type 16 18 18 20 20
Gross weight kg 2670 3020 3080 3390 3430
1)
Specified grease weight applies to steel core lubrication case
2)
Load capacity calculated according to IEC 1597 standard for the following parameters:
- sun radiation intensity: 895 W/m2
- coefficient of sun radiation absorption: 0,5
- coefficient of emissivity in relation to complete radiator: 0,55
- wind velocity in lateral direction to the conductor: 0,6 m/s
- ambient temperature: 35 ºC
- conductor operating temperature: 80 ºC
3)
Delivery of conductors is possible in different sections and on different drums after making arrangements with the manufacturer
Conductor type Bare steel reinforced alloy conductors AACSR according to UNE 21018
Marking acc. to UNE 21018 DA 30 DA 56 DA 78 DA 110 DA 145 DA 180 DA 280
Marking acc. to IEC 61089 23-A2/S1A-6/1 40-A2/S1A-6/1 58-A2/S1A-6/1 81-A2/S1A-30/7 103-A2/S1A-30/7 127-A2/S1A-30/7 195-A2/S1A-30/7
Marking acc. to EN 50182 27-AL2/4-ST1A 47-AL2/8-ST1A 67-AL2/11-ST1A 94-AL2/22-ST1A 119-AL2/28-ST1A 147-AL2/34-ST1A 226-AL2/53-ST1A
Design of conductor
Galvanized steel core
Number of steel wires 1 1 1 7 7 7 7
Diameter of steel wires mm 2,38 3,15 3,78 2,00 2,25 2,50 3,10
Core diameter mm 2,38 3,15 3,78 6,00 6,75 7,50 9,30
Core cross-sectional area mm2 4,45 7,79 11,2 22,0 27,8 34,4 52,8
Core weight kg/km 34,7 60,7 87,4 172,1 217,9 269,0 413
Aluminium
Number of aluminium wires 6 6 6 30 30 30 30
Strand direction of the last layer right (Z) right (Z) right (Z) right (Z) right (Z) right (Z) right (Z)
Diameter of aluminium wires mm 2,38 3,15 3,78 2,00 2,25 2,50 3,10
Cross-sectional area of aluminium part mm2 26,7 46,8 67,3 94,2 119,3 147,3 226,4
Weight of aluminium part kg/km 73,1 128,1 184,4 260,4 329,5 329,5 625
Conductor
Total number of wires 7 7 7 37 37 37 37
Diameter of conductor mm 7,14 9,45 11,3 14,0 15,8 17,5 21,7
Total cross-sectional area mm2 31,1 54,6 78,6 116,2 147,1 181,6 279,3
Conductor weight without grease kg/km 107,7 188,6 271,6 432,2 547,0 675,3 1038
Grease weight 1) kg/km 0,7 0,9 1,1 3,5 4,5 5,5 8,5
Conductor properties
Computational breaking force kN 13,75 23,77 33,55 56,36 71,33 87,03 131,7
Modulus of elasticity N/mm2 81 000 81 000 81 000 82 000 82 000 82 000 82 000
Linear expansion coefficient (1/ºK)*10-6 19,2 19,2 19,2 17,8 17,8 17,8 17,8
Computational resistance (20°C; DC) Ω/km 1,2474 0,7121 0,4945 0,3563 0,2815 0,2280 0,1483
Current load capacity 2) A 145 205 260 325 375 430 570
Short-circuit current (1s; 200°C) kA 2,1 3,7 5,3 7,5 9,4 11,7 17,9
Standard packaging
Standard sections 3) m 5 000 3 500 4 000 3 500 4 500 4 500 2 900
Drum type 10 10A 12 14 16 18 18
Gross weight kg 610 660 1210 1680 2640 2690 3360
1)
Specified grease weight applies to steel core lubrication case
2)
Load capacity calculated according to IEC 1597 standard for the following parameters:
- sun radiation intensity: 895 W/m2
- coefficient of sun radiation absorption: 0,5
- coefficient of emissivity in relation to complete radiator: 0,55
- wind velocity in lateral direction to the conductor: 0,6 m/s
- ambient temperature: 35 ºC
- conductor operating temperature: 80 ºC
3)
Delivery of conductors is possible in different sections and on different drums after making arrangements with the manufacturer