The communications interface

1.1 Standard communications interface


1.1.1 RS232 interface definition

The RS232 interface shall be set as follows:

Interface cards Baud Rate


Data Length
9600 bps
8 bits
Stop Bit 1 bit

Installation Manual
Parity None
1.1.1.2 The Pin Assignments of true RS232 type. The pin assignments of
true RS232 type are illustrated as follows:

Pin 2: RS232 Rx
5 Pin 3: RS232 Tx
9 4
8 Pin 5: Ground
3
7 2
6
1

VERSION 1.0 1
2.2 Option communication card 2.2.2 RS-485 card
2.2.1 Hardware Installation Procedure

Open the top and sides of the cabinet

CN1 is for the function of the terminal resistor. Short pin1-2 to enable the
function and short pin2-3 to disable it.
CN2 is RS485 terminal, CN3 for remote power.

Put the communication card into the Definition


CN2
slot
1 2 3 1 Æ Ground
2 Æ A/Data+
3 Æ B/Data-
CN3
1 2 1 Æ AC+
2 Æ AC-

Screw back the side & top cover and


complete the installation

2 3
2.2.3 USB card 2.2.4 True Relay Contact Board (DCE-B card)

2.2.3.1 CN2 for USB. 2.2.4.1 The pin assignments of 10-Pin Terminal:
2.2.3.2 Definition
2.2.3.2.1 Comply with USB version 1.0 & 1.5Mbps. 1 2 3 4 5 6 7 8
2.2.3.2.2 Comply with USB HID Version 1.0.
2.2.3.2.3 The Pin Assignments of the USB card: Pin 1: Voltage of utility is abnormal.
Pin 2: PV strings voltage is normal.

1 Æ VCC (+5V) Pin 3: PV strings voltage is abnormal.

2 Æ D- Pin 4: Frequency of utility is abnormal.

3 Æ D+ Pin 5: Anti-islanding.

4 Æ Ground Pin 6: Output current of inverter is exceeds range.


Pin 7: Temperature of Heat-sink is too high.
Pin 8: Common.

2.2.4.2 The capacity of each relay contact is 40Vdc/25mA.

4 5
2.2.5 TCP/IP Cards

2.2.5.1 TCP/IP (Ethernet) card


2.2.5.2 For installation, please refer to the user’s manual attached with the card.