2.1 General Data For Indoor Units

This document provides general data for indoor and outdoor units of a split air conditioning system. For the indoor units, specifications are given for nominal cooling and heating capacity, sound levels, dimensions, weight and fan data for various ceiling cassette models. For the outdoor units, specifications include power supply, nominal cooling and heating capacity, dimensions, weight, refrigerant type, compressor details and condenser fan configuration for different models to pair with the indoor units. Notes provide additional information on capacity calculation conditions and external static pressure settings.

Uploaded by

brunorp3
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
104 views6 pages

2.1 General Data For Indoor Units

This document provides general data for indoor and outdoor units of a split air conditioning system. For the indoor units, specifications are given for nominal cooling and heating capacity, sound levels, dimensions, weight and fan data for various ceiling cassette models. For the outdoor units, specifications include power supply, nominal cooling and heating capacity, dimensions, weight, refrigerant type, compressor details and condenser fan configuration for different models to pair with the indoor units. Notes provide additional information on capacity calculation conditions and external static pressure settings.

Uploaded by

brunorp3
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

GENERAL DATA

2. GENERAL DATA
2.1 General Data for Indoor Units
In-the-Ceiling Type
Indoor Unit Type In-the-Ceiling Type
Model RPI-3.0FSN1SQ RPI-4.0FSN1SQ RPI-5.0FSN1SQ RPI-6.0FSN1SQ
Indoor Unit Power Supply AC 1, 220-240V/50Hz
Combined Outdoor Unit Model RAS-3HVRN RAS-4HVRN RAS-5HVRN RAS-6HVRN
Nominal Cooling kW 7.1 10.0 12.5 14.7
Capacity kcal/h 6,100 8,600 10,750 12,600
Btu/h 24,200 34,100 42,700 50,200
Nominal Heating kW 8.0 11.2 14.0 16.0
Capacity kcal/h 6,880 9,600 12,000 13,800
Btu/h 27,300 38,100 47,600 54,600
Sound Pressure Level
(Overall A Scale) (Hi/Me/Lo)
120Pa Setting dB 46/44/40 48/45/41 49/46/43 53/49/45
70Pa Setting dB 45/43/39 47/44/40 48/45/42 52/48/44
Outer Dimensions
Height mm 350 350 350 350
(in.) (13-3/4) (13-3/4) (13-3/4) (13-3/4)
Width mm 1,076 1,076 1,300 1,300
(in.) (42-3/8) (42-3/8) (51-3/16) (51-3/16)
Depth mm 800 800 800 800
(in.) (31-1/2) (31-1/2) (31-1/2) (31-1/2)
Net Weight kg 52 57 61 63
(lbs.) (115) (126) (134) (139)
Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate (Hi/Me/Lo)
120Pa Setting m3/min. 29/26/20 36/33/25 47/43/34 56/50/40
(l/s) (484/433/333) (600/550/417) (783/717/567) (933/833/667)
70Pa Setting m3/min. 29/26/20 36/29/25 47/39/36 56/48/42
(l/s) (484/433/333) (600/483/417) (783/650/600) (933/800/700)
External Pressure (*2) Pa 120 (70) 120 (70) 120 (70) 120 (70)
Motor W 250 300 500 550
Connections Flare-Nut Connection (with Flare Nuts)
Refrigerant Piping
Liquid Line mm 9.53 9.53 9.53 9.53
(in.) (3/8) (3/8) (3/8) (3/8)
Gas Line mm 15.88 15.88 15.88 15.88 or 19.05 (*1)
(in.) (5/8) (5/8) (5/8) (5/8) or (3/4)
Condensate Drain VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.49 0.49 0.573 0.573
(*1): When the pipe size of 19.05 is used, apply the reducer (field-supplied) to fit the 15.88 pipe for indoor unit,
branch pipe kit connection.
NOTES:
1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the
JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 or 2 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The data for external pressure (*2) indicates "High Pressure Setting (Standard Pressure Setting)"
values when a filter is not used.
The sound pressure level is based on the High Pressure Setting.

21
GENERAL DATA

2.2 General Data for Outdoor Units


Model RAS-3HVRN RAS-4HVRN RAS-5HVRN RAS-6HVRN
Power Supply AC 1φ, 220-240V/50Hz, 220V/60Hz AC 1φ, 240V/50Hz
Nominal Cooling kW 7.1 10.0 12.5 14.7
Capacity kcal/h 6,100 8,600 10,750 12,600
Btu/h 24,200 34,100 42,700 50,200
Nominal Heating kW 8.0 11.2 14.0 16.0
Capacity kcal/h 6,880 9,600 12,000 13,800
Btu/h 27,300 38,100 47,600 54,600
Cabinet Synthetic Resin Paint Baked on Galvanized Steel Plate
Sound Pressure Level
Cool (Night Shift)/Heat dB (A) 43(39)/45 45(41)/47 47(43)/49 48(44)/50
Outer Dimensions
Height mm 800 1,240 1,240 1,240
(in.) (31-1/2) (48-13/16) (48-13/16) (48-13/16)
Width mm 850 950 950 950
(in.) (33-7/16) (37-3/8) (37-3/8) (37-3/8)
Depth mm 315 315 315 315
(in.) (12-7/16) (12-7/16) (12-7/16) (12-7/16)
Net Weight kg 60 95 97 97
(lbs.) (132) (210) (214) (214)
Refrigerant R410A
Flow Control Micro-Computer Control Expansion Valve
Compressor Hermetic (Scroll)
Model 2YC45BXD E305AHD E405AHD E405AHD
Quantity 1 1 1 1
Motor Output (Pole) kW 1.38 (4) 2.2 (4) 3.0 (4) 3.0 (4)
Heat Exchanger Multi-Pass Cross-Finned Tube
Condenser Fan Propeller Fan
Quantity 1 2 2 2
Air Flow Rate m3/min. 45 80 90 90
(cfm) (1,589) (2,824) (3,177) (3,177)
Motor Output (Pole) kW 0.05(8) 0.03(8) + 0.05(8) 0.05(8) + 0.07(8) 0.05(8) + 0.07(8)
Refrigerant Piping Flare-Nut Connection (with Flare Nuts)
Liquid Line mm φ9.53 φ9.53 φ9.53 φ9.53
(in.) (3/8) (3/8) (3/8) (3/8)
Gas Line mm φ15.88 φ15.88 φ15.88 φ15.88 or φ19.05 (*1)
(in.) (5/8) (5/8) (5/8) (5/8) or (3/4)
Refrigerant Charge kg 2.4 3.6 3.6 3.6
Approximate
Packing Measurement m3 0.34 0.55 0.55 0.55
(*1): When the pipe size of φ19.05 is used, apply the reducer (field-supplied) to fit the φ15.88 pipe for indoor unit,
branch pipe kit connection.

NOTES:
1. The above cooling and heating capacities show the maximum capacities when the outdoor and indoor
temperature are below condition.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure is based on the following conditions.
1 Meter from the unit service cover surface, and 1.5 Meters from floor level.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The above data is based on the 4-Way Cassette Type indoor units. <RCI-**FSN>
(In case of 6HP, the data is based on the In-the-Ceiling Type indoor unit single connection. <RPI-6.0FSN1SQ>)

24
SELECTION DATA

4.3 Cooling Capacity


Cooling
RAS-3HVRN
Cooling Capacity Curve Correction Curve

Capacity Correction Factor


)
( DB
°C
Cooling Capacity (kW)

5 1.0
9.0 p. 2
em
nlet T 30°C
(0.98) (0.95)
rI
t doo
Ou 35°C
8.0
40°C
0.5

7.0
Nominal Compressor Frequency (Operation)

6.0 0
High Medium Low
12 14 16 18 19 20 22 24
Air Inlet Temp. (WB) Indoor Unit Air Flow
RAS-4HVRN
Cooling Capacity Curve
Correction Curve

Capacity Correction Factor


13.0 B)
D
5°C(
mp. 2 30°C
1.0
Cooling Capacity (kW)

t Te
12.0 nle 35°C (0.98)
o rI (0.95)
tdo 40°C
Ou
11.2
11.0
0.5

10.0
Nominal Compressor Frequency (Operation)

9.0 0
High Medium Low
12 14 16 18 19 20 22 24
Air Inlet Temp. (WB) Indoor Unit Air Flow
RAS-5HVRN
Cooling Capacity Curve

16.0 B)
(D
5°C
.2
mp 30°C Correction Curve
Te
15.0 let
Capacity Correction Factor

o r In 35°C
tdo
Ou
Cooling Capacity (kW)

40°C 1.0
14.0
(0.98) (0.95)

13.0
0.5
Nominal Compressor Frequency (Operation)
12.0

11.0 0
High Medium Low
12 14 16 18 19 20 22 24
Air Inlet Temp. (WB) Indoor Unit Air Flow
RAS-6HVRN
Cooling Capacity Curve

18.0 B)
(D
5°C
.2
mp 30°C Correction Curve
Te
17.0 et
Capacity Correction Factor

r Inl
oo 35°C
td
Ou
Cooling Capacity (kW)

40°C 1.0
16.0
(0.98) (0.95)

15.0
Nominal Compressor Frequency (Operation) 0.5
14.0

13.0 0
High Medium Low
12 14 16 18 19 20 22 24
Air Inlet Temp. (WB) Indoor Unit Air Flow

40
SELECTION DATA

4.4 Heating Capacity


Heating

RAS-3HVRN
Heating Capacity Curve
14.0
Correction Curve

Capacity Correction Factor


Heating Capacity (kW)

13.0
Outdoor Inlet Temp. 15°C 1.0
12.0 (WB) (0.98) (0.97)
11.0 15oC
10oC
10.0
5oC 0.5
9.0
0oC
8.0 -5oC
7.0 -10oC
0
6.0 -15oC High Medium Low
5.0
8 10 12 14 16 18 20 22 24 26 28
Air Inlet Temp. (DB) Nominal Compressor Indoor Unit Air Flow
Frequency (Operation)

RAS-4HVRN
Heating Capacity Curve
18.0
17.0 Outdoor Inlet Temp. 15°C
(WB)
Heating Capacity (kW)

16.0 15oC Correction Curve

Capacity Correction Factor


15.0
10oC
14.0 1.0
5oC (0.98) (0.97)
13.0
o
12.0 0C

11.0 -5oC 0.5


10.0 -10oC
9.0 -15oC
8.0 0
-20oC High Medium Low
7.0
8 10 12 14 16 18 20 22 24 26 28
Air Inlet Temp. (DB) Nominal Compressor Indoor Unit Air Flow
Frequency (Operation)

RAS-5HVRN
Heating Capacity Curve
22.0
Outdoor Inlet Temp. 15°C (WB)
21.0
15oC
20.0
Heating Capacity (kW)

19.0 10oC Correction Curve


Capacity Correction Factor

18.0
5oC 1.0
17.0 (0.97)
(0.98)
16.0 0oC
15.0
-5oC 0.5
14.0
13.0 -10oC
12.0 -15oC
0
11.0 High Medium Low
-20oC
10.0
8 10 12 14 16 18 20 22 24 26 28
Air Inlet Temp. (DB) Nominal Compressor Indoor Unit Air Flow
Frequency (Operation)

RAS-6HVRN
Heating Capacity Curve
24.0
23.0 Outdoor Inlet Temp. 15°C (WB)
22.0 15oC
21.0
Heating Capacity (kW)

20.0 10oC Correction Curve


Capacity Correction Factor

19.4
19.0 o
5C
18.0 1.0
(0.98) (0.97)
17.0 0oC

16.0 -5oC
15.0 0.5
-10oC
14.0
13.0 -15oC
0
12.0
-20oC High Medium Low
11.0
8 10 12 14 16 18 20 22 24 26 28
Air Inlet Temp. (DB) Nominal Compressor Indoor Unit Air Flow
Frequency (Operation)

41
SELECTION DATA

4.5 Correction Factor According to Piping Length

Correction Factor for Cooling Capacity


According to Piping Length
The cooling capacity should be corrected according The correction factors are shown in the following
to the following formula: figure.
CCA=CCxF
CCA: Actual Corrected Cooling Capacity (kW)
CC: Cooling Capacity in the Performance
Table (kW)
F: Correction Factor Based on the
Equivalent Piping Length

RAS-3HVRN RAS-4HVRN
H(m)

H(m)
30 30
25 25

20 20
15
15

98%

96%

94%

92%

90%

88%

86%

84%

82%

80%

78%

76%
100%
10
10
Cooling

Cooling
5 EL(m)
5
EL(m) 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 -5
100%

-5 -10
99%

98%

97%

96%

95%

94%

93%

92%

91%

90%

-10 -15
-20
-15
-20

RAS-5HVRN RAS-6HVRN
H(m)

H(m)

30 30
25 25
20 20
15 15
98%
96%
94%
92%
90%
88%
86%
84%
82%
80%
78%
76%
74%
72%
70%
68%
66%
100%

98%
96%
94%
92%
90%
88%
86%
84%
82%
80%
78%
76%
74%
72%
70%
68%
66%
100%

10 10
Cooling

Cooling

5 EL(m) 5 EL(m)
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
-5 -5
-10 -10
-15 -15
-20 -20

42
SELECTION DATA

Correction Factor for Heating Capacity


According to Piping Length
The heating capacity should be corrected according The correction factors are shown in the following
to the following formula: figure.
HCA=HCxF
HCA: Actual Corrected Heating Capacity (kW)
HC: Heating Capacity in the Performance
Table (kW)
F: Correction Factor Based on the
Equivalent Piping Length

RAS-3HVRN RAS-4HVRN
H(m)

H(m)
30 30
25 25
20 20

99%

98%

97%

96%

95%
100%
15
15
10
10
Heating

Heating
5 EL(m)
100%

94%
96%

93%
95%

92%

91%
97%
98%
99%

5
EL(m) 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 -5
-5 -10
-10 -15
-20
-15
-20

RAS-5HVRN RAS-6HVRN
H(m)

H(m)

30 30
25 25
20 20
99%

98%

97%

96%
100%

99%

98%

97%

15 96%
100%

15
Heating

Heating

10 10
5 EL(m) 5 EL(m)
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
-5 -5
-10 -10
-15 -15
-20 -20

43