Phase 1 Mechanical Addendum 1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

EXISTING WORK TO REMAIN

GENERAL 1. ALL WORK SHALL COMPLY WITH THE APPLICABLE SECTIONS OF THE 2014 BUILDING CODE, CITY OF NEW YORK, AND ALL AMENDMENTS X
EXISTING WORK TO BE REMOVED MAX MAXIMUM
AND RULES AND REGULATIONS OF THE DEPARTMENT OF BUILDINGS.
1. THE TERM "CONTRACTOR", "THIS CONTRACTOR", "HVAC CONTRACTOR" OR ANY TEXT AND DRAWINGS INCLUDED IN THIS MBH THOUSAND BTU PER HOUR
12x6
CONTRACT DOCUMENT (WHICH INCLUDES DRAWINGS AND SPECIFICATIONS) SHALL BE MEANT AND DIRECTED TO THE 2. SPECIAL INSPECTIONS ARE REQUIRED FOR MECHANICAL SYSTEMS IN ACCORDANCE WITH THE FOLLOWING CODE SECTIONS: 12"W x 6"H DUCT SIZE
CONTRACTOR PERFORMING THE HEATING, VENTILATING AND AIR CONDITIONING (HVAC) WORK IN THIS PROJECT. MC MECHANICAL CODE
2.1. MECHANICAL SYSTEMS BC 1704.16 CD CONDENSATE DRAIN
2. THE ARCHITECT/ENGINEER FOR THE PROJECT WHO WILL ALSO BE REFERRED TO AS THE ARCHITEDT/ENGINEER OF RECORD MCA MINIMUM CIRCUIT AMPACITY
2.2. MECHANICAL DEMOLITION BC 1704.20.4
WILL BE THE FIRM WHOSE NAME AND ADDRESS IS LISTED IN THE TITLE BLOCK OD THE DESIGN DOCUMENT. EXISTING PIPING GOING DOWN
2.3. FIRE-RESISTANT PENETRATIONS AND JOINTS BC 1704.27, BC 1704.25 MER MECHANICAL EQUIPMENT ROOM
3. ALL WORK SHOWN IN THE CONTRACT DRAWINGS AND INCLUDED IN THE SPECIFICATIONS SHALL BE CONSIDERED AS NEW
POINT OF CONNECTION MFS MAXIMUM FUSE SIZE
WORK TO BE PROVIDED (DEFINED AS FURNISHED AND INSTALLED) BY THE HVAC CONTRACTOR. ONLY ITEM SPECIFICALLY
INDICATED AS "EXISTING" OR "BY OTHERS" OR "BY OTHER TRADES" SHALL BE EXCLUDED FROM THE WORK PROVIDED BY THE
3. IN ADDITION TO SPECIAL INSPECTIONS, THE FOLLOWINGS PROGRESS INSPECTIONS ARE REQUIRED FOR MECHANICAL SYSTEMS IN MIN MINIMUM
HVAC CONTRACTOR. SYMBOL LIST SHOWING DIFFERENT LINE THICKNESS FOR EXISTING AND NEW COMPONENTS ARE MEANT POINT OF DISCONNECTION
ACCORDANCE WITH THE FOLLOWING SECTIONS:
ONLY FOR CLARITY. UNLESS SPECIFICALLY INDICATED AS "EXISTING" ALL COMPONENTS SHALL BE CONSIDERED TO BE NEW
MOP MAXIMUM OVERCURRENT PROTECTION D.O.B. DISCLAIMER:
TO BE PROVIDED BY THE HVAC CONTRACTOR.
3.1. ENERGY CODE COMPLIANCE INSPECTIONS BC 110.3.5 CEILING SUPPLY DIFFUSER
NC NOISE CRITERIA THIS PLAN IS APPROVED ONLY FOR WORK INDICATED ON
4. IT SHALL BE EXPRESSLY UNDERSTOOD THAT ALL ITEMS INCLUDED IN THE CONTRACT DOCUMENTS ISSUED BY THE 3.2. SHUTOFF DAMPERS IB2, IIB2
THE APPLICATION SPECIFICATION SHEET. ALL OTHER
ARCHITEDT/ENGINEERS SHALL BE INCLUDED IN THE BID PRICE OF THE CONTRACTOR UNLESS OTHERWISE, SPECIFIC ADD CEILING RETURN / EXHAUST - GRILLE/REGISTER
3.3. HVAC AND SERVICE WATER HEATING EQUIPMENT IB3, IIB3 NO NUMBER MATTERS SHOWN ARE NOT TO BE RELIED UPON, OR TO
ALTERNATES ARE LISTED BY THE ARCHTIECT/ENGINEER IN THE DOCUMENTS.
BE CONSIDERED AS EITHER BEING APPROVED OR IN
3.4. HVAC AND SERVICE WATER HEATING SYSTEM CONTROLS IB4, IIB4 T THERMOSTAT
OA OUTSIDE AIR ACCORDANCE WITH APPLICABLE CODES.
5. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ASCERTAIN IN WRITING THAT HE HAS ALL THE CONTRACT
3.5. HVAC INSULATION AND SEALING IB5, IIB5
DOCUMENTS FOR THE PROJECT FORM THE ARCHTIECT/ENGINEER. NO CLAIMS FOR ANY MISSING DOCUMENTATION WILL BE SECTION DESIGNATION
ACCEPTABLE. 3.6. DUCT LEAKAGE TESTING IB6, IIB6 OAT OUTSIDE AIR TEMP
SHEET NO. WHERE SECTION IS SHOWN
3.7. ELECTRICAL MOTORS IIC6 OD OUTSIDE DIAMETER
6. WHERE INFORMATION IN DIFFERENT PARTS OF THE CONTRACT DOCUMENTS ARE INTERPRETED BY THE CONTRACTOR TO BE
A AMPERAGE
DUPLICATED, THE CONTRACTOR SHALL OBTAIN A WRITTEN APPROVAL OF HIS INTERPRETATION FROM THE OWNER BEFORE
DELETING THE SCOPE OF WORK HE INTERPRETS AS BEING A DUPLICATION. IN THE ABSENCE OF SUCH WRITTEN APPROVAL, 4. ALL INSPECTIONS AND TESTS SHALL BE MADE IN COMPLIANCE WITH BC 1704. PD PRESSURE DROP
A/C AIR CONDITIONING
THE CONTRACTOR SHALL NOT EXCLUDE ANY ITEM SHOWN IN DIFFERENT PARTS OF THE CONTRACT.
5. VENTILATION FOR ALL AREAS COMPLIES WITH THE MINIMUM CODE REQUIREMENTS OF MC 401 AND MC 402. PH PHASE
AC AIR CONDITIONER
7. FOR EITHER CONTRACTOR'S INTERPRETATION OF DUPLICATION OR CONTRADICTION AS INDICATED ABOVE, THE OWNER'S
DETERMINATION SHALL BE FINAL AND SHALL NOT ENTITLE THE CONTRACTOR TO ANY ADDITIONAL COMPENSATION. 6. CERTIFICATES OF COMPLIANCE (28-116.4) SHALL BE OBTAINED AND PAID FOR BY THE CONTRACTOR. PSI POUNDS PER SQUARE INCH
ACCU AIR COOLED CONDENSING UNIT
8. ALL WORK SHOWN ON THE CONTRACT DOCUMENTS ARE MEANT TO BE THE FINAL INTENT OF THE WORK. ANY WORK 7. ALL HVAC SYSTEMS AND EQUIPMENT COMPLY WITH THE REQUIREMENTS OF THE ENERGY CONSERVATION CONSTRUCTION CODE OF QTY QUANTITY
ACU AIR CONDITIONING UNIT
REQUIRED TO MEET THE FINAL INTENT OF THE DESIGN DOCUMENTS, INCLUDING BUT NOT LIMITED TO THE FOLLOWING SHALL THE STATE OF NEW YORK (MC 301.2).
BE PROVIDED BY THE HVAC CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER: RD ROOF DRAIN
AD ACCESS DOOR
a. CUTTING AND PATCHING OF WALLS, FLOORS, CEILING, ROOFS, PARTITIONS; 8. THE FOLLOWING WORK ITEMS, COMPONENTS, MATERIALS, CAPACITIES, ETC. SHALL COMPLY WITH THE FOLLOWING CODE
b. REMOVAL AND REPLACEMENT OF SUSPENDED CEILINGS, ACCESS PANELS, ACCESS DOORS; REFERENCES: RG RETURN GRILLE
AFD ADJUSTABLE FLOW DEVICE
c. REMOVAL AND REPLACEMENT OF EXISTING ARCHITECTURAL, STRUCTURAL, PLUMBING, ELECTRICAL, FIRE
RH RELATIVE HUMIDITY NO. DATE DESCRIPTION
PROTECTION TRADES AND, TELECOMMUNICATION, COMPUTER, SECURITY, PUBLIC ADDRESS, INTERCOM SYSTEMS a. DUCT CONSTRUCTION MC 603
ASCS AIR SYSTEM CLEANING SPECIALIST
WHICH INTERFERE WITH THE FINAL INTENT OF THE HVAC WORK. b. AIR INTAKES AND OUTLETS MC 401
c. FILTERS MC 605 RLA RUNNING LOAD AMPS
BC BUILDING CODE
9. DETERMINE LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD. RELOCATE EXISTING WORK THAT INTERFERES WITH WORK d. FANS MC 503
OF THIS CONTRACT. UNLESS AND UNTIL SPECIFIC ITEMS ARE SHOWN IN OTHER TRADE DRAWINGS FOR REMOVAL AND e. ELECTRIC WIRING & EQUIPMENT MC 301.7 RPM REVOLUTIONS PER MINUTE
BTU BRITISH THERMAL UNIT
REPLACEMENT FOR THE AREA WHERE THE FINAL HVAC DESIGN INTENT IS SHOWN, ALL WORK REQUIRED FOR OTHER TRADES f. CONTROLS MC 405
RR RETURN REGISTER
TO PERFORM THEIR WORK TO ENABLE THE HVAC WORK SHOWN ON THESE DRAWINGS SHALL BE INCLUDED IN THE HVAC
CONTRACTOR'S BID.
g.
h.
HEATING CAPACITY MC 312
NOISE CRITERIA LEVELS BC 1207
CD CEILING DIFFUSER Ronnette Riley Architect
i. PIPING INSULATION MC 604 SR SUPPLY REGISTER
CFM CUBIC FEET PER MINUTE
10. ALL WORK SHOWN ON THE CONTRACT PLANS INCLUDING SCALED DRAWINGS ARE SCHEMATIC AND ARE INTENDED TO j. INTAKE, EXHAUSTS, RELIEFS MC 401
CONVEY GENERAL INFORMATION ON THE MAGNITUDE OF WORK AND TO PROVIDE GENERAL ARRANGEMENT OF EQUIPMENT. k. PLENUMS AND CORRIDORS MC 602, MC 601 SQFT SQUARE FEET
CLG CEILING
THE CONTRACT DRAWINGS ARE NOT MEANT TO CONVEY ALL THE FIELD CONDITIONS, ALL BENDS, OFFSETS, ELEVATIONS
TYP TYPICAL 494 Eighth Avenue, 15th Floor
ACCURATELY AND SHALL NOT BE USED AS THE BASIS TO ESTIMATE THE QUANTITY OF HVAC WORK. THE CONTRACTOR MAY 8. MINIMUM TEMPERATURE TO BE MAINTAINED DURING HEATING SEASON: BC 1204 - WHEN 13 DEG F OUTSIDE. D DEPTH New York, NY 10001
MAKE CHANGES IN THE FORM OF SHOP DRAWINGS IF AND WHEN APPROVED IN WRITING BY THE ARCHITECT AT NO T 212 594 4015
ADDITIONAL COST TO THE OWNER. 9. EQUIPMENT SHALL BE LISTED AND APPROVED AS REQUIRED BY MC 107, MC 102. V VOLTAGE
dBA DECIBELS F 212 594 2868
www.ronnetteriley.com
11. THE CONTRACTOR SHALL SEEKING WRITTEN CLARIFICATIONS TO SCOPE OF WORK, VISIT AND CAREFULLY EXAMINE THE SITE VD VOLUME DAMPER
10. ALL BUILDING DEPARTMENT FORMS REQUIRED, INCLUDING THOSE REQUIRED FOR SPECIAL INSPECTIONS, PROGRESS INSPECTIONS, DC DIRECT CURRENT
OF THE PROPOSED WORK SO AS TO FAMILIARIZE HIMSELF OR HERSELF WITH EXISTING FIELD CONDITIONS, TO VERIFY CERTIFICATE OF COMPLIANCE, SERVICE EQUIPMENT PERMIT, EQUIPMENT USE PERMIT OR OTHER REASONS WITH REGARD TO THIS
DIMENSIONS AND TO VERIFY DIFFICULTIES THAT WILL BE ENCOUNTERED DURING THE EXECUTION OF THE WORK AND TO VFD VARIABLE FREQUENCY DRIVE
PROJECT SHALL BE COMPLETED AND FILED WITH THE NYC BUILDING DEPARTMENT BY THE CONTRACTOR. DH DEHUMIDIFICATION UNIT
VERIFY EXACT EXTENT OF WORK REQUIRED, PRIOR TO SUBMITTING HIS PROPOSAL. ANY CHANGES RESULTING FROM
W WIDTH
CONDITIONS ARISING IN THE FIELD ARE TO BE MADE BY THIS CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. 10. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER PROVIDED SPECIAL INSPECTORS. DN DOWN
12. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL HVAC/MECHANICAL DRAWINGS. W.M.S. WIRE MESH SCREEN
11. CONTRACTOR SHALL OBTAIN AND PROVIDE SERVICE EQUIPMENT PERMITS IN ACCORDANCE WITH SECTION 28-105.2 OF THE BUILDING DOAS DEDICATED OUTDOOR AIR SUPPLY
CODE. SERVICE EQUIPMENT PERMITS SHALL BE REQUIRED FOR THE USE AND OPERATION OF THE EXHAUST FANS.
YR YEAR
13. DIMENSIONS SHOWN ON PLAN ARE HORIZONTAL. DIMENSIONS SHOWN IN ELEVATION ARE VERTICAL EXCEPT IN WAY OF DOAU DEDICATED OUTDOOR AIR UNIT
STRUCTURAL STEEL, DIMENSIONS ARE MEASURED PERPENDICULAR TO FLANGE. 12. THESE PLANS ARE APPROVED ONLY FOR THE WORK INDICATED ON THE APPLICATION DRAWING. ALL OTHER MATTERS SHOWN ARE
Ø DIAMETER
NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OR IN ACCORDANCE WITH APPLICABLE CODES. DX DIRECT EXPANSION H RI
B
14. WHEREVER THE REQUIREMENTS AND REGULATIONS OF FEDERAL OR MUNICIPAL AUTHORITIES ARE MORE STRINGENT THAN

C
AO NA
< LESS THAN
THE REQUIREMENTS INDICATED ON THE DRAWINGS OR SPECIFICATIONS. THEN THESE MORE STRINGENT REQUIREMENTS

HE I L E
EA EXHAUST AIR
SHALL TAKE PRECEDENCE OVER THE DRAWINGS OR SPECIFICATIONS AND SHALL BE MADE PART OF THE CONTRACT AT NO
> GREATER THAN
ADDITIONAL COST TO THE OWNER. HOWEVER, WHERE THE DRAWING OR SPECIFICATIONS ARE MORE STRINGENT THAN EAT ENTERING AIR TEMPERATURE
FEDERAL OF LOCAL AUTHORITY REQUIREMENTS AND REGULATIONS, THE MORE STRINGENT SHALL APPLY AND THE WORK
# NUMBER
SHALL BE INCLUDED IN THE CONTRACT. EC ELECTRONICALLY COMMUTATED
SMOKE DETECTOR
15. THE CONTRACTOR SHALL PROVIDE PROTECTION FOR THE GENERAL PUBLIC AND CONSTRUCTION WORKERS IN AND AROUND
THE CONSTRUCTION AREA. ADEQUATE BARRIERS SHALL BE PROVIDED TO EXERCISE CONTROL OF SAFE INGRESS AND THERMOSTAT
SUPPLY DUCT GOING UP EF EXHAUST FAN
% PERCENT
CAMERON ENGINEERING &
°F DEGREES FAHRENHEIT
EGRESS OF PREMISES. FIRE EXITS SHALL AT NO TIME BE BLOCKED.
NEW PIPE WITH DIRECTION OF FLOW ESP EXTERNAL STATIC PRESSURE ASSOCIATES of NEW YORK, PLLC
1411 Broadway, Suite 610 New York, NY 10018 T: (212) 324-4000
16. ALL EXISTING CONSTRUCTION AND EQUIPMENT SHALL BE PROTECTED BY EACH CONTRACTOR DURING THE ENTIRE ECCENTRIC REDUCER SUPPLY DUCT GOING DOWN EXIST EXISTING 177 Crossways Park Drive Woodbury, NY 11797 T: (516) 827-4900
PERFORMANCE OF THEIR WORK. EXISTING AREAS DISTURBED OR DAMAGED BY CONTRACTORS SHALL BE REPAIRED OR 303 Tarrytown Road, 1st Floor, White Plains, NY 10603 T: (914) 721-8300

REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. PIPE DROP Corporate Seal Initiated 2012 State of New York
FC FLEXIBLE CONNECTION www.Cameronengineering.com COPYRIGHT

PIPE RISE
17. ALL UNUSED MATERIALS AND DEBRIS SHALL BE LEGALLY DISPOSED OF AWAY FROM THE PREMISES. FLEX FLEXIBLE
PITCH UP IN DIRECTION OF FLOW RETURN DUCT GOING UP
18. HVAC AND MECHANICAL SYSTEMS SHALL BE MAINTAINED FULLY OPERATIONAL IN AREAS/SPACES OUTSIDE OF AREA OF WORK FLA FULL LOAD AMPERAGE
DURING CONSTRUCTION. PITCH DOWN IN DIRECTION OF FLOW
FPM FEET PER MINUTE
19. COORDINATE ALL WORK WITH OTHER TRADES AND EXISTING CONDITIONS TO AVOID CONFLICTS. UNION RETURN DUCT GOING DOWN
FT FEET
20. WORK SHALL BE DONE IN ACCORDANCE WITH ALL APPLICABLE CODES INCLUDING THE CURRENT EDITION OF THE NEW YORK CONCENTRIC REDUCER
CITY CODES AND ALL LOCAL TOWNSHIP REQUIREMENTS. GA GAUGE
FLANGED CONNECTION ROOSEVELT ISLAND-
21. SCHEDULE WORK OF THIS SECTION TO AVOID INTERFERING WITH EXISTING OPERATIONS IN THE FACILITY.
GATE VALVE 3-WAY, 2-WAY CEILING SUPPLY DIFFUSER
GAL GALLON SPORTSPARK
22. CONTRACTOR TO CONTACT BUILDING MANAGEMENT AND TENANT REGARDING DUCTWORK REMOVAL SCOPE OF WORK TO
ANGLE GATE VALVE
GCHWS&R GLYCOL CHILLED WATER SUPPLY & RETURN RENOVATIONS
ENSURE THAT OTHER TENANTS THAT ARE TO STAY OPERATIONAL ARE NOT AFFECTED BY REMOVALS OF THE BASE BUILDING
DUCTWORK. FC GPM GALLONS PER MINUTE
GLOBE VALVE 250 Main St.
23. COORDINATE WITH BUILDING MANAGEMENT FOR ANY SERVICE INTERRUPTION OF EXISTING SYSTEMS AND GIVE NOTICE AS
DRAIN VALVE (TYPE AS SPECIFIED) FLEXIBLE CONNECTION HP HORSEPOWER Roosevelt Island, NY
REQUIRED BY BUILDING RULES AND REGULATIONS
. FC HV HEATING AND VENTILATING
10044
24. THE LOCATION AND ELEVATIONS OF ALL PIPING, PANELS, EQUIPMENT AND/OR DUCTWORK THAT IS IN OR PASSING THROUGH LOCK SHIELD VALVE
BASE BUILDING SPACES AND/OR TENANT SPACES ARE TO BE COORDINATED WITH BUILDING MANAGEMENT AND INDICATED ON KW KILOWATT
SHOP DRAWINGS BEFORE PROCEEDING WITH WORK CHECK VALVE, SWING OR LIFT
VD Sheet List Table
H HEIGHT
BALL VALVE Sheet Number Sheet Title

1. ALL DEMOLITION WORK SHALL BE SCHEDULED AND PHASED SO AS NOT TO INTERFERE WITH THE OPERATION OF THE FACILITY.
THREE-WAY AUTOMATIC CONTROL VALVE
VOLUME DAMPER
HR HOUR M-001.00 MECHANICAL NOTES, SYMBOLS AND ABBREVIATIONS
MECHANICAL NOTES,
VD M-002.00 MECHANICAL SPECIFICATIONS 1 OF 4
2. WHEN DEMOLITION WORK REQUIRES TEMPORARY SHUT DOWN OF AN EXISTING OPERATING SYSTEM, THE DEMOLITION SHALL BE
"Y" TYPE STRAINER W.BLOW OFF VALVE AND CAP
HVAC HEATING, VENTILATION AND AIR CONDITIONING
M-003.00 MECHANICAL SPECIFICATIONS 2 OF 4
SYMBOLS AND
PERFORMED AT SUCH REGULAR TIME OR ON OVERTIME, WHEN DESIGNATED BY THE OWNER, AT NO ADDITIONAL COST.
MANUAL AIR VENT
HWS&R HOT WATER SUPPLY AND RETURN
M-004.00 MECHANICAL SPECIFICATIONS 3 OF 4 ABBREVIATIONS
W.M.S
3. THE OWNER SHALL BE NOTIFIED OF THE ESTIMATED DURATION OF THE SHUTDOWN PERIOD AT LEAST TEN (10) DAYS IN ADVANCE OF WIRE MESH SCREEN HZ HERTZ M-005.00 MECHANICAL SPECIFICATIONS 4 OF 4
THE DATE THE WORK IS TO BE PERFORMED. VIBRATION ISOLATOR IN HANGAR
ID INSIDE DIAMETER M-050.00 MECHANICAL DEMOLITION FIRST FLOOR EAST PLAN
4. WORK SHALL BE ARRANGED FOR CONTINUOUS PERFORMANCE, INCLUDING OVERTIME, WHEN APPROVED BY THE OWNER, IF M-051.00 MECHANICAL DEMOLITION SECOND FLOOR EAST PLAN
REQUIRED TO ENSURE EXISTING OPERATING SERVICES WILL BE SHUT DOWN ONLY IF ESSENTIAL AND NECESSARY FOR THE WORK. THERMOMETER WELL IN INCH OR INCHES
M-052.00 MECHANICAL DEMOLITION SECTIONS
5. PROVIDE ALL SCAFFOLDING, RIGGING, HOISTING AND SERVICES NECESSARY FOR REMOVAL OF ALL DEMOLISHED EQUIPMENT AND THERMOMETER END WELL INWG INCHES OF WATER GAUGE
M-100.00 MECHANICAL FIRST FLOOR EAST PLAN
MATERIALS FROM THE PREMISES.
L LENGTH M-102.00 MECHANICAL SECOND FLOOR EAST PLAN
6. THE CONTRACTOR SHALL NOT PERFORM ANY DEMOLITION AND REMOVAL WORK UNLESS A SCHEDULE HAS BEEN SUBMITTED AND PRESSURE GAUGE WITH SIPHON 06.10.2019
LAT LEAVING AIR TEMPERATURE M-300.00 MECHANICAL DETAILS SHEET No. 1
APPROVED.
M-301.00 MECHANICAL DETAILS SHEET No. 2
LBS POUNDS 19010
7. ALL DIMENSIONS SHOWN ON THE DRAWING SHALL BE VERIFIED IN FIELD BY THE CONTRACTOR.
M-302.00 MECHANICAL DETAILS SHEET No. 3
8. CONTRACTOR SHALL ASSURE THAT DEMOLITION AND INSTALLATION WORK WILL NOT CAUSE ANY DAMAGE TO EQUIPMENT, PRESSURE GAUGE ON TEE LF LINEAR FEET M-303.00 MECHANICAL DETAILS SHEET No. 4

9.
DUCTWORK, PIPING, ELECTRICAL, PLUMBING OR ANY OTHER EXISTING SERVICES TO REMAIN.

CONTRACTOR SHALL COORDINATE ALL DEMOLITION WORK WITH NEW CONSTRUCTION DRAWINGS TO DETERMINE DIMENSIONS AND
LRA

NADCA
LOCKED ROTOR AMPS

NATIONAL AIR DUCT CLEANERS


M-400.00
M-500.00
MECHANICAL SCHEDULES
MECHANCIAL RISER DIAGRAM
M-001.00
SCOPE OF WORK TO INSURE THAT NO ITEMS OR SERVICES TO REMAIN ARE DISTURBED OR DAMAGED. HOSE BIB AND CAP
ASSOCIATION M-501.00 MECHANCIAL DUCT RISER DIAGRAM
DK 1 OF 18
10. CONTRACTOR SHALL PATCH TO MATCH CONSTRUCTION IN ALL AREAS WHERE REMOVALS ARE MADE. M-600.00 MECHANICAL SECTIONS

UNAUTHORIZED ALTERCATION OF ADDITION TO THIS DOCUMENT IS A VIOLATION OF SECTION 7209


OF THE NEW YORK STATE EDUCATION LAW.
THESE DOCUMENTS (OR COPIES OF ANY THEREOF) PREPARED BY OR BEARING THE SEAL OF THE
ENGINEER, SHALL NOT BE REUSED FOR ANY EXTENSIONS OF THE PROJECT OR ANY OTHER
PROJECT WITHOUT THE WRITTEN CONSENT OF THE ENGINEER.
D.O.B. DISCLAIMER:
THIS PLAN IS APPROVED ONLY FOR WORK INDICATED ON
THE APPLICATION SPECIFICATION SHEET. ALL OTHER
MATTERS SHOWN ARE NOT TO BE RELIED UPON, OR TO
BE CONSIDERED AS EITHER BEING APPROVED OR IN
ACCORDANCE WITH APPLICABLE CODES.

DUCT TRANSITION
(TYP.)

36x36 36x24 36x20 30x20 24x20 18x20 14x14 VD (TYP.)


36x36
SD

14x14
20x18
EF-R-1 24x60 SA

14 Ø

14 Ø

14 Ø

14 Ø

14 Ø

14 Ø
DH-1 RR-3
DOAU-1
36x36 RA 28x28 (1600) 28x28
LOWER SECOND
ROOF EAST FD/AD FD/AD FD/AD FLOOR EAST
FD/AD NO. DATE DESCRIPTION

24x24
(1400) (1400) (1400) (1400) (1400) (1400)
VD (TYP.)
24x22 24x20 24x18 24x16 24x14

16x16 EA
RR-1 RR-1 RR-1 RR-1 RR-1 RR-1 RR-2
18x12

(500) (500) (500) (500) (500) (500) (2000)


8x6
Ronnette Riley Architect
14x8 SR-2 SR-2 SR-2 SR-2 SR-2 SR-2 SR-2
(100) (100) (100) (100) (100) (100) (100)
18x8 14x6
RR-4
(900)
14x8

14x6 14x8 16x16 494 Eighth Avenue, 15th Floor


New York, NY 10001
RR-4 T 212 594 4015
12x8

(900) F 212 594 2868


www.ronnetteriley.com
VD (TYP.)
10x6

14x8
8x6

8x6

8x6

8x6

8x6
RR-4

14x6
(900)

RR-4
8x6
(900)
8x6

RR-4
(900)

H RI
TRANSITION FROM B
RR-4

I
8x6 14x6 RECTANGULAR

C
AO NA
(900)

HE I L E
DUCT TO ROUND
(E) CONCRETE
DUCTWORK
28x28 RA

10x6
SR-1 SR-1 SR-1 SR-1 SR-1 SR-1 SR-1 SR-1 SR-1
(290) (290) (290) (290) (290) (290) (290) (290)
(290)
CAMERON ENGINEERING &
12x8
8x6

10x6
ASSOCIATES of NEW YORK, PLLC
10x6

20x18 26 Ø 26 Ø 24 Ø 22 Ø 22 Ø 20 Ø 20 Ø 16 Ø 12 Ø
8x6 1411 Broadway, Suite 610 New York, NY 10018 T: (212) 324-4000
177 Crossways Park Drive Woodbury, NY 11797 T: (516) 827-4900
303 Tarrytown Road, 1st Floor, White Plains, NY 10603 T: (914) 721-8300
12x6 (E)10x10 (E)10x6 Corporate Seal Initiated 2012 State of New York
VD (TYP.)
FD/AD www.Cameronengineering.com COPYRIGHT
8x6 8x6
8x6 8x6
SD-1 RR-5 RR-5 RR-7 RR-5 RR-7 RR-6 RR-6 RR-5 RR-5 14x14 14x14 14x12 14x10 14x10
(50) (30) (100) (200) (100) (180) (150) (120) (100) (100)
SD-6
(200) RR-5 RR-5
SD-1 SD-5 SD-7 SD-3 SD-1 RR-5 RR-5
(75) (75)
(50) (130) (400) (100) (70) (100) (100)
STORAGE EAST MAN'S FAMILY LIFEGUARD SD-6 POOL 121
CORRIDOR 119 115 LOBBY TOILET HOLD LOCKERS110 LOCKER 105 SHOWERS AREA 108 WOMEN'S LOCKER SHOWERS
(200) FIRST
FLOOR EAST
ROOSEVELT ISLAND-
SPORTSPARK
RENOVATIONS

250 Main St.


DUCT RISER DIAGRAM FOR SYSTEMS DH-1, DOAU-1 AND EF-R-1 Roosevelt Island, NY
10044

MECHANCIAL DUCT RISER


DIAGRAM

06.10.2019

19010

M-501.00
DK 17 OF 18

UNAUTHORIZED ALTERCATION OF ADDITION TO THIS DOCUMENT IS A VIOLATION OF SECTION 7209


OF THE NEW YORK STATE EDUCATION LAW.
THESE DOCUMENTS (OR COPIES OF ANY THEREOF) PREPARED BY OR BEARING THE SEAL OF THE
ENGINEER, SHALL NOT BE REUSED FOR ANY EXTENSIONS OF THE PROJECT OR ANY OTHER
PROJECT WITHOUT THE WRITTEN CONSENT OF THE ENGINEER.