General
a) Name of Manufacturer LS Cable India Pvt Ltd.
b) Applicable standard Generally to IS 7098 (Part-2)
c) Voltage grade kV(E) 1.9/3.3
0
d) Max. conductor temperature at rated
°C 90
current
e) Max. conductor temperature at the end of
°C 250
short circuit
Conductor
a) Material Plain annealed copper
1 c) Shape of conductor Stranded compacted circular
b) Nom. Cross sectional area Sq.mm. 240
0
d) Max. DC resistance of conductor at 20 C Ω/km 0.0754
Insulation
a) Material XLPE
2 b) Thickness
i) Nominal mm 2.2
ii) Minimum mm 1.88
Outer sheath
a) Material PVC ST-2
b) Thickness
3 i) Nominal mm 2.00
ii) Minimum mm 1.40
c) Colour Black
d) Overall diameter of cable mm 27.0 ± 2.0
Packing
4 a) Material/Type Wooden Drum
b) Standard drum length Mtr 1000 ± 5 %