GP Manual en
GP Manual en
GP Manual en
All of the following specified work must be carried out by knowledgeable personnel
experienced in installation and service of refrigeration systems. All personnel must
be familiar with the national legal requirements and safety regulations. All safety reg-
ulations and codes of practice concerning the use of refrigerants must be adhered
to, with special attention paid to protection clothing and wearing of safety glasses.
Service and maintenance only be carried out when the pump is stopped and the
power supply disconnected.
Important! The content of this manual must be adhered to. Deviation from the
specified conditions will make any claim for liability or warranty void.
3 - Introduction -
1.3 SAFETY ADVICE
The pump is designed for use in industrial refrigeration systems using primary refrigerants.
It is very important that everybody responsible for the safe operation and
maintenance of the plant reads this manual.
The coupling protection must be in place at all times! (see chapter 8.2.2)
If you have any problems please do not hesitate to call our service department, who will be
glad to assist you.
Make sure the ground area around the pump is clear, e.g. no incoming electric power cables.
If you cannot avoid such obstruction, they should be marked with two-coloured warning tape
(warning sign).
Correctly retighten all screw connections after mainte-nance and repair work.
If you have to disassemble any safety devices for maintenance and repair make sure that upon
completion of said work the re-assembly and correct functioning is checked.
When operating at low temperatures (< 0°C) freeze bites can occur when the surface is
touched. Therefore always wear appropriate protection clothing.
1.4 DISCLAIMER
Even when using the pump for the intended purpose it cannot be entirely excluded that a dan-
ger may remain during its working lifetime.
Translations have been made to the best of our knowledge. We are unable to accept any
liability for er-rors in translation.
We reserve the right to change descriptions, graphs and technical information due to future
development of the refrigerant pump.
- Introduction - 4
TERMS OF WARRENTY
In order to avoid accidents and ensure optimum performance, no modifications or conversions
may be carried out to the refrigerant pump without the explicit written approval by TH. WITT
KÄLTEMASCHINENFABRIK GMBH.
These instructions are based on internationally standardised SI units of measurements.
All data and information on the operation and maintenance of the refrigerant pump is provided
based on our extensive experience and to the best of our technical knowledge.
Our liability or warranty is excluded, if:
information and instructions in the operating manual are ignored,
the refrigerant pump including accessories is operated incorrectly or is installed contrary to
these installation instructions
the refrigerant pump is used for applications other than that for which it was intended,
safety devices are not used or disconnected
there have been modifications made without written approval
the safety regulations are not adhered to
the refrigerant pump including its filters and required safety devices has not been main-
tained or repaired correctly with respect to frequency or competence this includes the use
of approved spare parts.
Opening the pump within the warranty period will void all implied or explicit
guarantees!
It is recommended to return the pump to the supplier for repair or order an exchange pump.
When exchanging any parts respective spare parts only genuine spare parts are to be used.
Equipment must be used in accordance with the instructions in this manual.
5 - Terms of warrenty -
TECHNICAL INFORMATION
3.1 DESCRIPTION OF TYPES
Six WITT refrigerant pumps with flanged motor are available:
GP 41, GP 42, GP 51, GP 51a, GP 52 and GP82.
Pumps can be delivered with or without standard flange-motor. To select your model please
see table below.
Please specify for model 2 the motor size for correct selection of the motor
coupling (and if required to be supplied with the intermediate ring for the motor
flange).
The standard motor can be replaced by other sizes in accordance with the mo-
tor selec-tion data sheet.
Optional Equipment
Counter flange, suction side with screws, nuts and gasket
Counter flange, pressure side with screws, nuts and gasket
Shut off valve EA … suction side with counter flange, screws, nuts and gasket
Shut off valve EA … pressure side withcounter flange, screws, nuts, gasket and deaera-
tionvalve EA 10 GB (manometer connection)
Strainer KS .. P suction side, including shut-off device, with counter flange, screws, nuts
and gasket
Non return / shut off valve ERA ... pressure side, with counter flange, screws, nuts and
gasket and deaeration valve EA 10 GB (manometer connection) pipe Ø 17,2 and hand
regulating valve EE6 (loose)
NH3 manometer with stand B for 0 - 12,5 bar
NH3 manometer with stand B for 0 - 25 bar
Strainer KS ... L
- Technical Information - 6
3.3 ORDER INFORMATION
Please specify the following data when ordering a pump:
refrigerant
type GP 41, GP 42, GP 51, GP 51a, GP 52 or GP82
For models 2 the required coupling size (or motor size of the motor to be fitted later)
For models 4 the selected motor
Voltage and frequency.
(Special requirements if applicable, e.g. PN 65 for HRP 3232)
If you are unsure about the selection, please provide the following additional information:
evaporating temperature ....°C
volume flow .... m3/h or capacity and re-circulation rate
required pressure head …. m
7 - Technical Information -
TECHNICAL DATA
4.1 GENERAL INFORMATION
DESCRIPTION GP 41 GP 42 GP 51 GP 51a GP 52 GP 82
Volume refrigerant side [ltr.] 1,75 1,85 4,10 4,10 5,25 7,72
Reservoir oil content [ltr.] 1,70 1,70 2,00 2,00 2,00 2,00
Flange connection [DN] 40,00 40,00 50,00 50,00 50,00 50/80
Weight [kg] for
Model 1 41,00 45,00 63,00 63,00 73,00 91,00
Model 2 48,00 52,00 75,00 75,00 92,00 110,00
Model 4 dependent dependent dependent dependent dependent dependent
- Technical data - 8
4.2.2 Motor data for 50 Hz - 1.000 RPM
Density Power Voltage [V] Weight
Motor size Remark
[kg/dm3] [kW] Δ Y [kg]
< 0,7 (NH3)
< 1,4
GP 41 80 0,37 220 - 240 380 - 420 9
< 1,6
< 1,8
< 0,7 (NH3)
0,37 9
< 1,4
GP 42 80 220 - 240 380 - 420
< 1,6
0,55 11
< 1,8
< 0,7 (NH3)
< 1,4 100L 1,5 25
GP 51 220 - 240 380 - 420
< 1,6
< 1,8 112M 2,2 38
< 0,7 (NH3)
< 1,4
GP 51a 100L 1,5 220 - 240 380 - 420 26
< 1,6
< 1,8
< 0,7 (NH3) 100L 1,5 26
220 - 240 380 - 420
< 1,4 112M 2,2 38
GP 52
< 1,6 132S 3 220 - 240 380 - 420 66 Motor adapter ring ne-
< 1,8 132M 4 380 - 420 660 - 725 82 cessary
9 - Technical data -
4.2.4 Motor data for 60 Hz - 1.200 RPM
Density Power Voltage [V] Weight
Motor size Remark
[kg/dm3] [kW] Δ Y [kg]
< 0,7 (NH3)
0,44 9
< 1,4
GP 41 80 254 - 280 440 - 480
< 1,6
0,66 11
< 1,8
< 0,7 (NH3)
80 0,66 11
< 1,4
GP 42 254 - 280 440 - 480
< 1,6 90S 0,9 13
< 1,8 90L 1,3 16
< 0,7 (NH3)
100L 1,8 25
< 1,4
GP 51 254 - 280 440 - 480
< 1,6
112M 2,6 38
< 1,8
< 0,7 (NH3)
100L 1,8 26
< 1,4
GP 51a 254 - 280 440 - 480
< 1,6
112M 2,6 38
< 1,8
< 0,7 (NH3) 112M 2,6 254 - 280 38
< 1,4 132S 3,6 254 - 280 440 - 480 66
GP 52 Motor adapter ring ne-
< 1,6 4,8 460 82
132M cessary
< 1,8 6,6 460 --- 83
4.3 MATERIAS
Pump housing: EN-GJS-400-18-LT Motor flange: EN GJS-400-15
Coupling: Stahl Coupling bush: Kunststoff
Coupling protection: PVC Rohr transparent Ball bearings: Stahl
Shaft: C 35 Shaft seal: PTFE
Impellers: EN GJS-400-15 Main bolts 8.8
Counter flanges: P355NH Bolts for counter flanges: 8.8
Gaskets: Centellen NP Reservoir oil: MR 520
Painting system W 9.1 + W 9.2 *
* W9.1 + W9.2 = 2k epoxidy finish according DIN ISO 12944/5, RAL 7001
- Technical data - 10
4.5 DIMENSIONS
4.5.1 Dimensions GP 41 in mm
4.5.2 Dimensions GP 42 in mm
11 - Technical data -
4.5.3 Dimensions GP 51/ GP 51a in mm
4.5.4 Dimensions GP 52 in mm
- Technical data - 12
4.5.5 Dimensions GP 82 in mm
13 - Technical data -
4.5.6 Dimensions in mm Strainer KS + ERA and 2x EA
- Technical data - 14
4.6 SECTIONAL VIEWS
Figure 3a: GP 42
Figure 3b: GP 52
15 - Technical data -
Figure 3c: GP 82
- Technical data - 16
Figure 3e: Detail of coupling and motor connection
17 - Technical data -
4.7 PARTS LIST
Spare Parts
An overview of the available spare parts can be found in the WITT spare part cata-
logue and as a document in the download area at http://www.th-witt.com.
spring washer 17 Ø60 2161.001228 105 Ø73 2161.001267 127 Ø73 2161.001267 127
cylinder head screw with inner hex 25 M10 x 25 5112.BH71AO 25 M12 x 30 5112.BH81AT 39 M12 x 30 5112.BH81AT 39
cylinder head screw with inner hex 26b M10 x 35 5112.BH71AY 28 M12 x 50 5112.BH81BD 55 M12 x 50 5112.BH81BD 55
hex bolt 27a M16 x 55 5111.AHA1BI 110 M16 x 55 5111.AHA1BI 110 M16 x 65 5111.AHA1BS 126
hexagon socket screw (GP 41 & 51) 28 M16 x 100 5112.BHA1CR 186 M16 x 150 5112.BHA1E5 266 ---
hexagon socket screw (GP 42, 52 & 82) 28 M16 x 140 5112.BHA1DV 250 M16 x 220 5112.BHA1G3 320 M16 x 300 5112.BHA3IB 440
cylinder head screw with inner hex 29 M10 x 25 5112.BH71AO 25 M12 x 25 5112.BH81AO 36 M12 x 25 5112.BH81AO 36
gasket slide flange 35 30/40 x 0,5 5632.1ATB38 1 38/50 x 0,5 5632.1B1BD8 1 38/50 x 0,5 5632.1B1BD8 1
seal for stop valve 39 8/14 x 8 5643.ABAP01 1 8/14 x 8 5643.ABAP01 1 8/14 x 8 5643.ABAP01 1
rill ball bearing with steel cage 41 5341.000003 240 5341.000002 380 5341.000002 380
baring bush 42 Ø45 2161.001219 130 Ø55 2161.001256 220 Ø55 2161.001256 220
spring cage 44 Ø55 2161.001229 110 Ø62 2161.001268 130 Ø62 2161.001268 130
safety ring (2 resp. 4 pcs.) 45 22 x 1,2 5541.AAL120 2 28 x 1,5 5541.AAR150 3 28 x 1,5 5541.AAR150 3
impeller 47 Ø130 2161.001243 440 Ø165 2161.001285 1170 Ø165 2161.180101 1170
shaft GP 41 / GP 51 48 Ø23 x 370 2161.001210 1085 Ø30 x 400 2161.001251 1875 Ø30 x 400 --- 1875
shaft GP 42 / GP 52 / GP 82 49 Ø23 x 410 2161.001211 1180 Ø30 x 474 2161.001252 2180 Ø30 x 590 2161.182102 2660
- Technical data - 18
4.7.2 parts list for pump (part 2 of 2)
GP 41/ GP 42 GP 51/ GP 51a/ GP 52 GP82
oil MR 520 51 1 ltr. 9831.100001 872 1 ltr. 9831.100001 872 1 ltr. 9831.100001 872
sight glass 52 45 45 45
2161.002001 2161.002001 2161.002001
gasket for sight glass 56 30/40 x 2 2 30/40 x 2 2 30/40 x 2 2
oil-fill screw 57 M22 x 1,5 5116.OG4510 48 M22 x 1,5 5116.OG4510 48 M22 x 1,5 5116.OG4510 48
coupling protection (transp. PVC pipe) 59 BG 80/90 2161.001215 165 BG 100/112 2161.001217 210 ---
coupling protection (transp. PVC pipe) 59 BG 100 2161.001216 185 BG 132 2161.001218 210 BG 132 2161.001218 210
coupling, pump side 61 Ø16 2494.000011 330 Ø22 2494.000051 670 Ø22 2494.000051 670
coupling- motor side 62/2 BG 80 2494.000012 430 BG 100 2494.000052 600 ---
coupling- motor side 62/3 BG 90 2494.000013 430 BG 112 2494.000052 600 ---
coupling- motor side 62/4 BG 100 2494.000014 430 BG 132 2494.000053 460 BG 132 2494.000053 460
Intermediate piece
74 2161.001241 1260 --- ---
large (only GP 42)
Intermediate piece without bore 75 2161.001240 1375 2161.001280 3800 2161.001280 3800
Intermediate piece
75 --- 2161.001283 ---
without bore (GP 51a)
bearing cover 76 2161.001306 2161.001307 2161.001307
spindle guide bushing 89.7 M16x1,5x18 2161.001201 15 M16x1,5x18 2161.001201 15 M16x1,5x18 2161.001201 15
19 - Technical data -
4.7.3 parts list for strainers
KS 40-P KS 50-P KS 80-P
hexagon socket screw 94 M10 x 30 5111.CL71AT 25 M12 x 35 5111.CL81AY 35 --- --- ---
- Technical data - 20
4.8 SPARE PART SETS
GP 41 GP 42 GP 51 / GP 51a GP 52 GP 82
21 - Technical data -
4.9 DESCRIPTION OF OPERATION
From the surge drum refrigerant liquid flows into the suc-tion chamber of the pump. A conical
filter is positioned in the suction connection. A special design of the suction chamber reduces
the inlet friction. The fluid pressure is increased by passing through one or two stage impellers
and intermediate piece(s).
Due to the lateral channels in the intermediate pieces the pump can deliver a gas/liquid mixture
without surging or reversing the flow.
The special double shaft seal with associated oil reservoir in the between ensures that no
refrigerant will escape outside the system.
During standstill any gas that evaporates must be able to leave the pump and vent to the surge
drum. If the pump can be isolated on the delivery side or if a return valve is mounted, a purge
line with a diameter of 10 mm (0.4”) must be installed between delivery flange and stop valve
and connected to the wet suction return line.
The WITT stop/return valve ERA is provided with a purge connection pipe DN 10 and a hand
regulating valve EE6, supplied loose. The EE6 should be fitted so that any gas may be purged
to the surge drum. The valve should be left ½ - ¼-turn open depending on the differential
pressure (see also fig. 6).
LIQUID NH3 R 22
HEAD
[m] EVAPORATING TEMPERATURE t0 GP 41 GP 42 GP 51A GP 51 GP 52 GP 82
25 1,42 1,69 2,78 3,46 1,4 2,1 6,3 9,8 15,1 17,8
30 1,7 2,03 3,33 4,15 - 1,9 5,5 7 14,2 16,6
35 1,99 2,37 3,89 4,84 - 1,6 4,5 3,6 13,5 15,5
40 2,27 2,71 4,45 5,54 - 1,3 - 0 12,5 14,3
45 2,56 3,05 5 6,23 - 1,1 - - 11,1 13
50 2,84 3,38 5,56 6,92 - 0,8 - - 10,4 11,6
55 3,12 3,72 6,11 7,61 - - - - 9,3 10
60 3,41 4,06 6,67 8,31 - - - - 8 8,4
65 3,69 4,4 7,22 9 - - - - 6,5 -
70 3,98 4,74 7,78 9,69 - - - - 5 -
1 m = 3.281 ft | 1 bar = 14.504 PSI | 1 m³/h = 4.403 gal/min
- Technical data - 22
APPLICATIONS
5.1 GENERAL
In industrial refrigeration systems pumps are used to deliver refrigerant to the evaporators.
WITT refrigerant pumps are designed especially for this purpose.
The principle of a pump re-circulation system is shown in fig. 4.
Long periods of cavitation must be avoided, as this will cause premature failure of
the pump. It is im-portant the installation instructions in chapter. 6 are correctly
understood and followed.
A horizontal separator is recommended: this gives great-er surface area for the settlement of
any oil and stable suction head conditions.
23 - Applications -
OPERATIONAL LIMITATIONS
GP refrigerant pumps are suitable for operation with all refrigerants.
GP 52 is only permitted for operation with higher density refrigerants (ρ > 800 kg/m³)
below 1200 RPM!
The max. allowable delivery head should never be exceeded, because otherwise the pump is
operated outside the permitted range and will see internal damages (see chap. 6.5)
A re-circulation factor of 4 means that 3 parts refrigerant are returned as liquid and 1 part is
evaporated.
The recirculation rate depends on the type of evaporator equipment and operation conditions.
The larger the duty, loading rate, the greater the recommended recirculation factor.
- Applications - 24
RECIRCULATION RATES AND PUMP CAPACITY
Liquid Chiller 1,2 – 1,5 1,2 – 1,5 1,2 – 1,5 1,4 – 1,6 0,6 1,7
V1 +V2 ≠ 2 x V1
Fig. 5, A-D
25 - Applications -
INSTALLATION REQUIREMENTS
To ensure trouble free operation some basic rules need to be applied to the installation
of the pumps.
Vertical distance between bottom of the separator to the pump centre shall be at
least 1 m. Greater distance will make the pump less sensitive to system pressure
fluctuations.
Therefore, it is recommended that the suction downleg protrude into the surge drum by 30 -
40 mm, depending on the vessel diameter (see fig. 6).
A standard short oil drainage dome is not suitable for connecting a pump suction down leg.
- Installation requirements - 26
Do not connect two or more pumps in operation by a single common pump suction line liquid
header.
27 - Installation requirements -
Shut off valves in the suction line shall be sized generously and without reducers to enable
degassing. Installation of full-bore ball valves are recommended. Straight through valves must
be installed with stem in horizontal position; ball valves should not have a reduced bore on the
pump side connection.
The installation of filters, dryers, etc. in the suction line is not permitted.
Under no circumstances should the maximum velocity in the downleg exceed 0.3
m/s (1 ft/s)!
The conical suction filter supplied with the pump must be installed at all times to protect the
pump from foreign material contamination!
The coarse-meshed strainer KS is intended to avoid contamination upon erection of the sys-
tem After approximately 2 weeks the strainer should be removed to avoid unnecessary pres-
sure drop.
- Installation requirements - 28
6.4 PUMP DISCHARGE LINE
The sizing of the discharge line is less critical to the sys-tem operation. A liquid velocity of 1.5
m/s is normally recommended.
A non-return valve (this is usually a combined stop/check valve type ERA) in the
discharge line is required when a backwards flow from the discharge to the suction
side is possible. This may be the case, when:
several pumps are connected to one discharge manifold.
the static head to the coolers is high.
A non-return valve should be mounted as close as possible to the discharge flange. If a larger
distance is required, an additional vent line should be installed to prevent a possible gas block-
age.
Vent line
To avoid backflow of refrigerant during stand-still it is important that each pump is individually
connected with a separate vent line immediately in front of the check valve on the delivery side
to the top of the surge drum.
It is important each pump gets its own vent line back to the surge drum to ensure the
pump can vent during stand-still!
The stop valve after the orifice shall be DN20 (3/4”) respective DN25 (1”) if installed in the part
of the vent line that can contain liquid.
If the valve is installed in the gas part of the vent line, immediately in front of the connection
point to the vessel a smaller valve is sufficient, e.g. DN10 (0.4”). The stop valve must be locked
in an open position and marked “do not close during normal operation”.
In application with a non-return valve or solenoid valve liquid may be trapped. When
this liquid is warmed up, the pressure increases rapidly to an unacceptable value
and the piping may fracture.
Adequate precautions must be taken by the installer to prevent any liquid from becoming
trapped.
29 - Installation requirements -
6.5.1 Safeguarding against too high pressure
Operating refrigerant pumps against too high pressure (e.g. against partially or fully
closed throttled condition) is not allowed and will damage the refrigerant pump!
A by-pass valve (adjustable) has proven good practice to safeguard the pump against too
high pressure.
To set the by-pass valve select the pressure difference across the pump according table 1 for
the following de-livery head. (take into account the pressure losses in the pipework to the by-
pass valve)
- Installation requirements - 30
6.6 ELECTRICAL INFORMATION
Folgende Vorkehrungen im Steuerstromkreis sind zu berücksichtigen:
6.6.1 Overload protection
An overload protection switch shall protect the pump against too high current (amps) consump-
tion. Maximum setting must be less than max. allowable current Imax shown on the type plate.
6.6.2 Hand switch
It is recommended the control panel incorporates a H–0-A switch for use during commission-
ing and maintenance operations.
It is important to take care that during manual operation of the pump all safety
devices in the circuit are connected and in good working condition.
The length of the incoming power cables should be of sufficient length to enable the tilting and
moving of the pump during inspection and replacement of the conical strainer in the pump
suction connection.
Only qualified personnel must carry out installation work on the refrigerant pump!
The pumps have undergone a short mechanical test run at ambient temperature with
mineral refrigerant machine oil in the factory. If the pump is to be used in systems
where contamination with mineral oil is not allowed, i.e. in cases with ester oil in the
system, the residual oil must be removed and the pump cleaned by use of solvents.
When welding to WITT stop valves, the valves should be in a half open position with
wet cloths around the valve packing.
If the pump was not supplied with a motor you have to install a coupling protection
(see right photo).
The hand wheel (85) should always be turned fully open during operation!
When the pump operates normally, check after 2 hours, after 8 hours and later the pressure
difference and note the measured values.
After 1 to 2 weeks of trouble free operation you should inspect the conical filter for dirt
and contamination. Depending the degree of contamination the conical filter should be
regularly inspected and cleaned at planned intervals.
If the pump is fitted in an existing refrigeration system special attention has to be taken to drain
oil out of the the entire system within the first weeks.
If oil has collected in the pump, you can install an oil drain valve EA 10 GÜ/GB instead of plug
(58). With this valve in combination with a quick acting valve the pump may carefully drained
from oil by trained personnel (see chapter 9.6)
When the pump has been installed properly a long lifetime is ensured.
During periods of pump standstill, only one shut-off valve may be closed, preferably
the discharge valve. When the suction and discharge valves are closed at the same
time, the pressure of the trapped cold liquid in the pump will increase rapidly. As the
liquid warms up to an unacceptable high value, it can very quickly damage the pump.
The pump shaft should be rotated once a day to avoid the shaft seal sticking to the
shaft.
If there is oil contamination during standstill of the pump, the oil must be drained before re-
starting the pump. Otherwise, a malfunction may occur which can lead to pump failure, which
may lead to the failure of the pump.
Isolate the pump by switching off and locking off the electrical supply and the
electrical controls. A label should be fixed to control panel to indicate pumps are
switched off and are being worked on. Note the sequence of electrical connections
and disconnect the wiring.
Before moving or tilting the pump e.g. to access or to clean the conical suction filter, replace
the shaft seal or other parts, the refrigerant must be discharged. It is recommend-ed that the
refrigerant is purged to the dry gas side of the surge drum via the pressure gauge valve at the
base of the discharge valve. Hot water may be used on the outside of the pump to accelerate
the boiling off of the liquid refrigerant.
When there is no liquid refrigerant left in the pump, any remaining refrigerant gas can be
purged through the pressure gauge valve or, if installed, the drain valve EA10 GÜ/GB with
quick acting valve.
When there is no residual pressure inside the pump the flange bolts can be carefully un-
screwed. Be aware of any trapped liquid or leaking valves seats.
To fill oil carefully open the slotted screw (57) by hand ¼ turn. The surrounding of the screw
shall be covered with a wet cloth to dind any escaping refrigerant gas. (see first photo chapter
0). If liquid refrigerant has collected in the oil chamber (e.g. because of a leaking inner shaft
seal) it may take several hours until the chamber has depressurized.
Never open the slotted screw (57) completely if there is any residual pressure re-
maining!
A lack of oil normally indicates that the inner shaft seal has started to leak and needs
to be replaced. Particularly when the oil level drops after a short period of time(less
then 14 days) the inner shaft seal must be replaced.
If the shaft seal has been replaced and you ob-serve again a lack of oil, you should
check wheth-er hand wheel (85) is/was turned open the whole time, also when work-
ing on the pump side (except when filling oil).
If the hand wheel is closed, refrigerant is trapped in the chamber around the shaft.
Evaporating reber. When the pressure difference between oil chamber and pump
suction chamber reaches an unacceptable high value, the pressure-limitation valve
(19.1) will open and release an oil/refrigerant mixture to the pump suction side. In
such an event you should replace the pressure limitation valve (19.1) and safety
pressure limitation valve (19.2) and make sure the hand wheel (85) is turned open at
all times!
The oil level shall be below the bottom thread of the oil filler plug. The maximum oil filling is
for
GP 40 pumps 1,7 ltr. (0.45 Gal) and for
GP 50 pumps 2 ltr. (0.53 Gal).
Avoid an overfilling of oil. The inlet of the pressure limitation valve (19.1) should not
be covered with oil.
When recharging oil and tightening oil filler screw (57) the hand wheel (85) must be
turned open again!
If there is no significant oil consumption, the oil should be exchanged every 5 years.
1. Carefully open the oil filler plug (57) ¼ 2. The oil fill plug (57) is slotted to avoid a
turn and wait until the oil chamber is de- sudden escape of refrigerant. Never use
pressurized (this may take a while!) Use a power tool to open the plug!
a wet cloth to protect the plug.
3. The hand wheel (85) must be completely 4. Drain oil in a suitable container.
open to ensure that the pressure may
equalize between oil and pump chamber.
7. Outter sealing (motor side): 8. The O-ring must press the slide ring
Assemble spring (16) + pressure ring (15) tightly onto the shaft. Therefore, use the
and lightly oil the groove in the pressure loose slide flange (11) as an auxiliary tool.
ring. Protect the O-ring against the sharp
edges of the key bed. Assemble the slide
and lightly oil the entire shaft seal.
11. Fit for GP 50 pumps 1 felt ring respec- 12. Lightly oil the grooves of the intermediate
tive for GP 40 pumps 2 felt rings (78.5) rings.
and assemble part 78.
13.
14.
1. Loosen screws (21) in the tightening ring 2. You can only remove the snap (Seeger)
while holding against with the coupling. ring, if the screws in the tightening ring
are loose!
GP40 GP50
the internal sheet metal discs (18) have the purpose to reduce the turbulence of oil.
Checking the exact position is not required.
When too much oil flows into the pump from the separator, the pump will not
operate properly or may be damaged.
Oil can be removed through a WITT EA 10 GÜ/GB stop valve, which can be installed in place
of the lower 1/4"-screw plug in the discharge chamber. In addition, a quick closing action valve
must be installed be-hind the drain valve.
Oil from the suction chamber or in between the intermediate pieces can only be partly removed
from the pump.
Make sure drain and quick acting valve are in-stalled in a safe manner to
prevent accidents.
At low temperatures when oil removal is slow the pump should be closed at the inlet
and warmed up on the outside with warm water to lower the viscosity of the oil
making it flow more easily. The oil return system from the surge drum should be
checked or modified to prevent further oil contamination of the pump.
When operating the pump under vacuum condition the oil drainage cannot be easily
drained. Please ask for advise.
When a pump has to be returned to the supplier or the factory be sure the pump is
free of refrigerant, dirt and oil. The risk of damages to goods or the environment by
leaking oil during transport is at the senders risk. When returning the pump it is
important that full information is provided stating the reason and cause of failure.
Always return the conical suction filter, in condition found when the pump was
opened, with the pump.
Special attention must be paid to the national rules concerning the available
materials.
Pump should not be removed unless system has been evacuated to zero pressure.
All local rules to refrigeration systems, and electric control and installation systems
must complied with.
- Trouble shooting - 46
Lukasstraße 32, 52070 Aachen, Germany
Tel. +49 241 18208-0
[email protected]