1) The document presents an implementation of a single-phase solid-state transformer (SST) with ten cascaded subunits to interface a 13.2 kV medium voltage AC network and a 750 V bipolar DC distribution system. 2) Each subunit consists of an AC/DC stage using cascaded H-bridges to handle the medium voltage, and a DC/DC stage using a triple active bridge converter for the bipolar DC output. 3) A simple balancing controller is used at the AC/DC stage to prevent voltage unbalance across the cascaded DC links, while a current sharing controller at the DC/DC stage maintains equal current distribution.

Uploaded by

sanafayaz12
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
55 views19 pages

Electronics 07 00062

1) The document presents an implementation of a single-phase solid-state transformer (SST) with ten cascaded subunits to interface a 13.2 kV medium voltage AC network and a 750 V bipolar DC distribution system. 2) Each subunit consists of an AC/DC stage using cascaded H-bridges to handle the medium voltage, and a DC/DC stage using a triple active bridge converter for the bipolar DC output. 3) A simple balancing controller is used at the AC/DC stage to prevent voltage unbalance across the cascaded DC links, while a current sharing controller at the DC/DC stage maintains equal current distribution.

Uploaded by

sanafayaz12
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 19

electronics

Article
Implementation of a Single-Phase SST for the
Interface between a 13.2 kV MVAC Network and a
750 V Bipolar DC Distribution
Hyeok-Jin Yun 1,2 , Dong-Keun Jeong 1,2 , Ho-Sung Kim 2 , Myoungho Kim 2 , Ju-Won Baek 2 ,
Ju-Yong Kim 3 and Hee-Je Kim 1, *
1 Department of Electrical Engineering, Pusan National University, Busan 46241, Korea;
[email protected] (H.-J.Y.); [email protected] (D.-K.J.)
2 Power Conversion and Control Research Center, HVDC Research Division, KERI, Changwon 51543, Korea;
[email protected] (H.-S.K.); [email protected] (M.K.); [email protected] (J.-W.B.)
3 Smart Power Distribution Lab, Power Distribution ICT Group, Daejeon 305-760, KEPCO, Korea;
[email protected]
* Correspondence: [email protected]; Tel.: +82-51-510-2364

Received: 12 April 2018; Accepted: 30 April 2018; Published: 4 May 2018 

Abstract: This paper presents the implementation of a single-phase solid-state transformer (SST) for
the interface between a 13.2 kV medium voltage alternative current (MVAC) network and a 750 V
bipolar DC distribution. The SST has ten cascaded subunits in consideration of the device rating
and modulation index (MI). Each subunit consists of an AC/DC stage and a DC/DC stage with
a high frequency isolated transformer (HFIT). The AC/DC stage consists of cascaded H-bridges
(CHBs) to cope with the MVAC. The DC/DC stage employs a triple active bridge (TAB) converter
for bipolar DC distribution. Topology analysis and controller design for this specific structure are
discussed. In addition, the insulation of HFIT used in DC/DC converters is also discussed. A simple
balancing controller at the AC/DC stage and a current sharing controller at the DC/DC stage are
used to prevent DC-link voltage unbalance caused by the cascaded structure. The discussions are
validated using a 150 kW single-phase 21-level SST prototype at the laboratory level.

Keywords: balancing controller; CHB; DAB; SST

1. Introduction
In recent decades, DC distribution has received increased attention for many applications because
it is considered advantageous and superior to AC distribution in some cases, such as interfacing
between renewable energy sources and DC loads, lower line losses, and so on [1–5]. There are two
types of DC distribution systems: unipolar distribution and bipolar distribution. This paper focuses
on the bipolar system due to its prominent advantages. The bipolar DC system can provide different
voltage levels to loads, which allows connecting high- and low-power devices at a suited voltage level.
In addition, this concept reduces the voltage level with respect to ground, which makes the distribution
system safer for users [6]. To construct a bipolar DC distribution system with these many advantages,
there is a need for additional power conversion devices that can be connected to an already existing
AC grid.
The SST based on power electronics is a popular scheme to access to the AC grid and DC distribution
system. It decreases the size of the system and provides instantaneous voltage regulation, bidirectional
power flow, voltage sag and reactive power compensations, harmonic reduction, and so on [7–10].
Many researchers have developed some prototypes to implement SSTs. For example, Ref. [11]
introduced a 7.2 kV 20 kVA single-phase SST prototype with customized 6.5 kV 25 A dual insulated

Electronics 2018, 7, 62; doi:10.3390/electronics7050062 www.mdpi.com/journal/electronics


Electronics 2018, 7, 62 2 of 19

gate bipolar transistor (IGBT) packages for high-voltage and low-current application, and Ref. [12]
presented a 3.3 kV 300 kVA back-to-back three-phase SST prototype for universal and flexible power
management. In Ref. [13], a 15 kV 1.2 MVA single-phase SST prototype was designed for a railway
grid. These prototypes have different structures depending on the purpose of use. In other words,
the SST prototypes were designed to be suitable for specific applications.
This paper introduces a single-phase 150 kW prototype of an SST for the connection between a
13.2 kV MVAC grid and a bipolar 750 V DC distribution system. This SST prototype consists of an
AC/DC stage and a DC/DC stage. The AC/DC stage employs the CHB rectifiers and is responsible
for power factor control, voltage regulation, and the voltage balancing of DC-links. The DC/DC stage
employs a specially designed TAB converter for connecting to the bipolar DC distribution system.
In addition, it is responsible for voltage control, and current sharing in parallel-connected outputs.
This paper also discusses the insulation of the HFIT used in the TAB converter.
The rest of this paper is organized as follows: the overall structure of the SST system used in this paper
is briefly introduced in Section 2. Section 3 provides the details about the controller of AC/DC stage for
the voltage balancing of DC-links. In Section 4, the DC/DC stage is analyzed including the characteristics
of the topology, modeling, and controller design. In Section 5, the HFIT design for high-voltage insulation
is discussed. The simulations and experimental results using a 150 kW SST prototype are presented in
Sections 6 and 7, respectively. Finally, the conclusions are provided in Section 8.

2. Structure of the SST Prototype


The upstream grid is a 13.2 kV single-phase MVAC network, but the loads work under the 750 V
bipolar DC distribution system. To meet this requirement, the SST prototype is assembled by several
subunits that are connected in a cascaded structure (as shown in Figure 1a). Figure 1b shows one
subunit consisting of one H-bridge rectifier and one TAB converter. The AC/DC stage is realized
using an interfacing inductor and several CHB rectifiers to support the 13.2 kV MVAC. The DC/DC
stage consists of three parts, which, organized from left to right, are the medium voltage direct current
(MVDC), HFIT, and low voltage direct current (LVDC). On the MVDC side, a neutral point clamped
(NPC) circuit is employed to handle a DC-link voltage higher than the rating of semiconductor devices.
The NPC generates a 3-level voltage to the HFIT, where the voltage applied to the semiconductor
devices is half of the DC-link. In addition, for application to bipolar DC distribution, the HFIT coupled
with three windings and the LVDC side is configured as a multi-terminal in which two half-bridge
circuits are connected in series. The outputs of the DC/DC stage are connected in parallel, and each
subunit has to be rated for only a fraction of the full power.

(a)

Figure 1. Cont.
Electronics 2018, 7, 62 3 of 19

(b)

Figure 1. Structure of the SST prototype system: (a) simplified structure of the overall SST prototype
system; (b) detailed structure of one subunit.

The voltage of the DC-link is controlled to 2.2 kV in consideration of the topology and the rating
of the semiconductor device. In this case, a minimum of ten modules are needed to take into account
the line voltage [14], the second harmonic ripple in the DC-link voltages, and the margin reserved for
the control strategy [15].

3. A Simple and Practical Voltage Balancing Controller for CHB


One of the main problems that arises when the AC/DC rectifier stage is configured as CHBs in a
SST system is the voltage imbalance between DC-links. This imbalance can be caused by unbalanced
load conditions, mismatch of the active and passive components, or the floating structure of the
high voltage DC-links [16–19]. This imbalance also increases the stress of the semiconductor device
and causes over-voltage or over-current problems that can lead to the collapse of the entire system.
The imbalance issue particularly worsens when the SST operates under no load or light load conditions
because a small power difference is a significant percentage of the real power and will result in a large
voltage imbalance.
To avoid this imbalance problem, an adequate control strategy should be needed to adjust the amount
of active power transferred to the individual DC-links. There are several references including control
strategies to solve the voltage imbalance of DC-links. In Ref. [20], based on a single-phase d–q control,
a voltage balancing controller that adjusts the individual modulation signals is proposed to balance the
DC-links. Ref. [21] presented an individual voltage balancing strategy for single-phase STATCOM devices
that is based on the CHB multi-level topology. This balancing technique achieves control and balance of
the individual DC-links, maintaining among them an equal distribution of the reactive power provided by
the H-bridges. In Ref. [22], a voltage balancing controller in the d–q coordinate is proposed to reduce the
coupling effect between the voltage balancing controller and the original system controller for the single
phase CHB multi-level topology. However, these conventional methods require additional balancing
controllers as many as the number of CHB modules. Therefore, as the number of modules increases,
the computation time of the additional balancing controllers increases.
In this paper, a simple and practical voltage balancing controller for DC-links is proposed.
The proposed balancing controller does not require additional sensors, and no additional control loops
required for module expansion. The entire control block diagram for an AC/DC stage is shown in
Figure 2. The controller is divided into three parts. The first part is the voltage error compensator
for total DC-links. This voltage error compensator is responsible for rectifying MVAC to MVDC.
In this process, the voltage error compensator only controls the voltage of the total DC-links, so an
additional controller is required for voltage balancing between individual DC-links. The second part is
Electronics 2018, 7, 62 4 of 19

the balancing controller for DC-links. The balancing controller monitors the voltage of all DC-links
and sorts them in order of magnitude. Through this sorting process, the maximum voltage and the
minimum voltage are obtained. A compensation value proportional to the difference between these
two values is generated for DC-link balancing, as shown in the following equations:

* *
IAC_max_mag = IAC_mag − Kp · (VO_max − VO_min ), (1)

* *
IAC_min_mag = IAC_mag + Kp · (VO_max − VO_min ). (2)

According to the Figure 2 and Equations (1) to (2), the balancing controller transfers more active
power to the DC-link with minimum voltage and less active power to the DC-link with maximum
voltage. The voltage deviation of the individual DC-links gradually converges to zero over the
processes of voltage sorting, detection of maximum and minimum values, and compensation of active
power. The last part is the current error compensator. The current error compensator is responsible for
power factor control between the grid voltage and current. The proportional-resonant (PR) controller
is used to improve the total harmonic distortion (THD) of the single-phase current and to reduce the
steady state error [23]. Finally, the AC current reference values from the current error compensator
were applied to the CHB by the phase shift pulse width modulation (PSPWM) scheme for ease of
expansion and implementation [24].

Figure 2. The entire control block diagram for AC/DC stage.

4. Analysis of the TAB Converter


The dual active bridge (DAB) converter has been widely used because of its various advantages
such as high power density, bidirectional power flow, galvanic isolation, and so on [25,26]. Most
DAB converters consist of half-bridge or full-bridge circuits, which produce 2-level square waves
across the HFIT. These 2-level DAB converters are usually cascaded for medium and high voltage
applications [27,28]. In this structure, the individual voltage of DC-links cannot be higher than the
voltage rating of the switching devices used in the 2-level DAB converters. Therefore, there is a
disadvantage in that the number of required subunits increases due to the voltage rating of the
switching devices when 2-level DAB converters are cascaded in an SST system.
Electronics 2018, 7, 62 5 of 19

The 3-level DAB converters can overcome this voltage constraint of semiconductor switches to a
great extent. Power converters synthesizing more than two voltage levels, such as NPC, and flying
capacitor converter (FCC), are traditionally known as 3-level converters. The FCC has a disadvantage
in that a complicated switching scheme is required to keep the flying capacitor voltage charged at the
appropriate constant level [29]. On the other hand, NPC has an advantage in that all of the switching
devices in a leg withstand only half of the individual DC-link voltage using simple switching scheme.
Therefore, in this paper, a 3-level NPC circuit is employed on the primary side of the DC/DC converter.
The loads of this DC/DC converter should work under a bipolar DC distribution system.
To simply meet this requirement, two 2-port DC/DC converters can be connected in parallel to
the individual DC-link. However, this structure has the disadvantage of increasing the number of
HFITs and converters. In addition, when a power transfer occurs between the two bipolar DC outputs,
the losses are increased because the circulating power is transmitted through two primary circuits.
Therefore, the TAB converter using a three windings coupled transformer is advantageous for bipolar
DC distribution. Studies have been conducted to expand to a TAB converter using 2-level DAB
converters [30,31].
However, unlike the conventional 2-level TAB, the TAB converter used in this paper is configured
as follows: a 3-level NPC circuit on the primary side, a three windings coupled transformer, and a
secondary side is configured as a multi-terminal in which two half-bridge circuits are connected in
series (as shown in Figure 1b). In addition, the outputs of the each TAB converter are connected in
parallel, and each subunit has to be rated for only a fraction of the full power.
This section discusses the modeling and controller design procedure of the TAB for this
particular structure.

4.1. Modeling of the Three Windings Coupled Transformer


Conceptually, the 2-port DAB converter can be viewed as an interfacing inductor driven at either
end by a controlled square-wave voltage source [32]. In the 2-port DAB converter, the interfacing
inductance is the sum of the transformer leakage inductance and the external inductance that is needed
in order to adjust the output power as well as to extend the zero-voltage switching operation [33].
The interfacing inductor between each port is a dominant parameter as the energy transfer component
in the DAB converter [32,33]. Therefore, interfacing inductances between each port should be obtained
for the power transfer modeling of the TAB converter.
Theoretically, the extended cantilever model (ECM) for the transformer is convenient in terms of
the parameter extraction, since each model parameter can be extracted from a single measurement
of an open-circuit voltage or a short-circuit current [34]. For this reason, the ECM is applied for the
three windings coupled transformer to extract interfacing inductances between each port, as shown in
Figure 3, where LW1 is the magnetizing inductance seen from the primary winding, W1 (Lij , i, j = 0∼2,
i 6= j) is the leakage inductance between each pair of windings, and n2 and n3 are turns ratios and have
the same value in this application.
The equivalent circuit of the TAB converter using an extended cantilever is shown in Figure 4,
0
where (Lij , i, j = 0∼2, i 6= j) is the leakage inductance between each pair of windings referred to
secondary and tertiary sides, the 3-level voltage at its primary NPC circuit is referred to secondary
and tertiary sides and it is denoted as V0 . V1 and V2 are the square-wave voltage at its secondary and
tertiary bridges, respectively, and P0 is the amount of power transferred from the DC-link to the input
port. P1 and P2 are the amount of power supplied to each load from the bipolar output ports.
Electronics 2018, 7, 62 6 of 19

Figure 3. Extended cantilever model for the three windings coupled transformer.

Figure 4. Equivalent circuit for the TAB converter.

4.2. Power Transfer Modeling of the TAB Converter


According to the equivalent circuit shown in Figure 4, it can be seen that the power flow paths
between any two of the three ports Pij (the power transferred from port i to port j; i, j = 0∼2, i 6= j).
P01 and P02 are the power flow from the primary side to each bipolar output, respectively. They can be
represented by the power flowing through the 2-port DAB converter, consisting of a primary NPC leg
and a secondary half-bridge leg. Figure 5a,b show the theoretical voltage and current waveforms of
this 2-port DAB converter, where Vac.P is the 3-level voltage produced by the primary NPC leg, α is
half of the angular distance for zero state, Vac.Sj is the 2-level voltage produced by the secondary or
tertiary half-bridge leg, φ0j is the phase-shift angle between the active bridges, and VL0j and IL0j are
the voltage and current of the interfacing inductor between port 0 and port j, respectively. Ioj is the
current of the each bipolar output.
The switching scheme for the 2-port DAB converter with a 3-level NPC topology was presented
in Refs. [35,36]. Based on the value of φ0j , there may be two cases such as Case I: 0 ≤ φ0j ≤ α, Case II:
α < φ0j ≤ π/2. Referring to Figure 5, the power equations for two cases can be obtained as follows:

nV0 Vj 2α
Case I : P0j = 0 φ0j · (1 − ), (3)
2ωL0j π

2
nV0 Vj φ0j α2
Case II : P0j = 0 · (φ0j − − ), ( j = 1, 2), (4)
2ωL0j π π

where ω is the switching angular frequency.


Electronics 2018, 7, 62 7 of 19

(a) (b)

Figure 5. Theoretical waveforms of the 2-port DC/DC converter: (a) Case I (0 ≤ φ0j ≤ α); (b) Case II
(α < φ0j ≤ π/2).

According to Equations (3) and (4), the smaller the value of α, the more power can be transferred
to the load. Therefore, α should theoretically have the minimum value for freewheeling. This means
that the 2-port DAB converter with a 3-level NPC topology works in Case I over a very short interval
in practice. In addition, the amount of power calculated by Equations (3) and (4) are almost the same
under light load conditions. Considering the above statements, the power equation of the 2-port DAB
converter with a 3-level NPC topology may be considered as the generalized equation and can be
rewritten as follows:
2
nV0 Vj φ0j
P0j ' 0 · (φ0j − π ),
2ωL0j
(5)
( j = 1, 2),
(0 ≤ φ0j ≤ π2 ).
Equation (5) is equivalent to the equation of a 2-level half-bridge DAB converter because the α
term that generates the zero-state in the NPC leg is removed. Therefore, P12 , which is another power
flow between two bipolar DC outputs, can also be obtained from Equation (5). As a result, in the TAB
converter, the amount of power between any two of the three ports can be obtained from Equation (5).
To reduce computing burden, (5) can be simplified as follows through the fundamental approximation
in Ref. [32]:
4V V
Pij ' 2 i j0 · φij ,
π ωLij
(i, j = 0 ∼ 2, i 6= j), (6)
(0 ≤ φij ≤ π2 ).
According to (6), the amount of power flowing through port 1 and port 2 are calculated as
follows, respectively:

4V0 V1 4V V 4V V
P1 = P01 + P21 = (
2 0 + 2 1 20 ) · φ01 − 2 1 20 · φ02 , (7)
π ωL01 π ωL12 π ωL12
4V1 V2 4V V 4V V
P2 = P02 + P12 = −
2 0 · φ01 + ( 2 0 20 + 2 1 20 ) · φ02 . (8)
π ωL12 π ωL02 π ωL12
Equations (7) and (8) can be rewritten in matrix form as follows:
! ! !
~ · ~φ, ~P =
~P = G p1 φ01 ~ = g11 g12
, ~φ = ,G , (9)
p2 φ02 g21 g22

~ is the transfer function matrix that describes the system parameters.


where G
Electronics 2018, 7, 62 8 of 19

As shown in (9), the TAB converter is a two-input and two-output (TITO) system. The TITO
system is characterized by significant interactions between their inputs and outputs. Because of
these interactions, a control action in one loop gets transmitted to the other loop as a disturbance.
Therefore, decoupling techniques are required to eliminate or minimize the interaction. The simplified
decoupling technique is most widely used in practice because of its robustness and simple decoupling
network for TITO systems [37]. Figure 6 shows the control block diagram with simplified decoupling.
The decoupler transfer function matrix D ~ and the decoupled transfer function matrix ~T can be given
as in (10) and (11), respectively:

− gg11
!
12
1
D ~ −1 · ~T =
~ =G , (10)
− gg21
22
1

g12 g21
!
g11 − g22 0
~T = g12 g21 . (11)
0 g22 − g11

Figure 6. Control block diagram with simplified decoupling.

4.3. Controller Design


After applying the simplified decoupling, the decoupled controller is represented by two
single-input and single-output (SISO) controllers as shown in Figure 7. Two SISO controllers hold
each bipolar DC output voltage at a set point by automatically adjusting control signals as follows.
The reference voltage and the measured voltage are given as inputs to the comparator, from which an
error signal is passed as input to the integral proportional (IP) controller. The use of the IP controller
enhances the system dynamic response and reduces undesirable peak overshoot compared to the
proportional integral (PI) controller [38]. The IP controller generates the control signal based on the
error signal. The output of the IP controller sets the output current of the converter required to keep
the output capacitor voltage at the appropriate constant level. In addition, a load current feedforward
is added into the controller to improve the dynamic response against the load changes [39].

Figure 7. Block diagram of the voltage controller converted to SISO system.


Electronics 2018, 7, 62 9 of 19

Using the formula of the IP controller and the mathematical relationship between the voltage and
current of the capacitor, the closed-loop transfer function is given by:

Ki
Voj Coj
H (s) = ∗ = Kp
, (12)
Voj s2 + Ki
Coj s + Coj

where Coj is the output capacitance, Kp and Ki , all non-negative, denote the coefficients for the
proportional and integral terms, respectively. To order the closed-loop system, it is necessary to choose
the coefficients Kp and Ki .
The transfer function of a second-order system in standard form is given by:

ωn2
F (s) = . (13)
s2 + 2ζωn s + ωn2

By comparing (12) and (13), the resulting IP controller parameters are obtained by:

Kp = 2ζωn2 Coj ,
(14)
Ki = Coj ωn2 ,

where ζ is the damping factor and ωn is the natural frequency.


The outputs of the DC/DC stage are connected in parallel, and each subunit has to be rated for
only a fraction of the full power. The primary goal of these parallel-connected converters is to share
the load current among the constituent converters. Improper load sharing can lead to the converter
overloading and overheating, which decreases the system reliability and can eventually lead to the
failure of the overall system [40]. Therefore, a robust control technique that ensures synchronizing and
proper load sharing is essential to ensure the stability and reliability of the system. Figure 8 shows the
control block diagram of the current-sharing controller based on the outer loop regulation (OLR) mode
studied in Ref. [41]. The OLR mode uses the current-sharing error signal to adjust the voltage reference
of the outer voltage loop until equal load current distribution is achieved. The current data of each
module is transmitted via the CAN protocol, and the average current value can be calculated based on
this information. The current-sharing error signal is processed through the average current method
(ACM), which compares the difference between the average current and the individual current. The
key features of the scheme, generally, are that the reference voltage, output voltage feedback, and the
voltage compensator of each converter module are independent.

Figure 8. Control block diagram of current sharing controller.


Electronics 2018, 7, 62 10 of 19

5. Transformer
The primary windings of the HFIT are electrically connected to the 13.2 kV MVAC network,
as shown in Figure 1a. In addition, the secondary and tertiary windings of the HFIT are electrically
connected to the 750 V bipolar LVDC and are floated with respect to the ground of the MVAC network.
In this structure, the minimum requirement of dielectric strength between the primary and other
windings is 22 kV, which corresponds to the total DC-link voltage [42]. Similarly, the minimum
requirement of dielectric strength between the core and windings is 22 kV. The dielectric strength of
the HFIT was selected to be 50 kV, which is about 2.3 the former strength of 22 kV, according to the
IEEE standard in Ref. [43].
Figure 9 shows the guard and bobbin structure of the HFIT to ensure the high dielectric strength.
The guard provides an electrical insulation between the core and the windings. The bobbin provides an
electrical insulation between the windings through the section structure. Both guard and bobbin were
made of Teflon material considering processability, low permittivity, and high voltage insulation [44].
The thickness of the insulator was determined by electric field distribution and intensity, which is
difficult to calculate due to the nonuniform electric field. Therefore, to determine the thickness of
the guard and section layer, the electric field distribution and intensity were simulated via ElecNet
as shown in Figure 10. Based on the structure of Figure 9, the thickness of guard and section layer
was temporarily set to 5 mm and 50 kV is applied between the primary and other windings. It can be
seen that the maximum field strength induced in the guard and section layer was 17 kV/mm, while
the dielectric strength of Teflon material is usually 20 kV/mm in vacuum. Therefore, the thickness of
the guard and section layer was selected as 5 mm considering margin. In addition, the empty space
between the bobbin, guard, and windings was filled with molding fluid to prevent partial discharge
and surface discharge. SYLGARD 170 A/B was selected as the molding fluid, considering the thermal
conductivity, dielectric strength, viscosity [45].

Figure 9. Arrangement of windings and structure of bobbin.


Electronics 2018, 7, 62 11 of 19

Figure 10. Electric field simulation results of section bobbin structure.

6. Simulation
Figure 11 shows the simulation waveform employed to verify the DC-link voltage balancing
capability of the AC/DC stage. Simulation parameters are listed in Table 1. The AC/DC stage
was realized using an interfacing inductor and ten CHB rectifiers to support the 13.2 kV MVAC.
As mentioned in Section 3, this structure can cause the voltage imbalance between DC-links.
The simulation sequence is as follows. Initially, the active power flowing through all of the CHB
rectifiers is 150 kW (rated power) and the voltage imbalance is caused by unbalanced load conditions
(up to 20%). The voltage of DC-links remains unbalanced because the balancing algorithm is forcedly
deactivated until t = 0.4 s. The balancing algorithm is activated at t = 0.4 s, and the voltage of DC-links
gradually converges to 2.2 kV. At t = 0.6 s, the load of subunit10 is increases from 13.6 kW to 15.8 kW,
and the load of subunit6 is reduced from 16.6 kW to 14.4 kW. At t = 0.8 s, the CHB rectifiers act like an
inverter to transfer 150 kW of power from the DC-links to the MVAC. It can be seen that the DC-link
voltage is balanced in all sequences after the balancing algorithm is activated.
Figure 12 shows the simulation waveform used to verify the decoupling capability of the DC/DC
stage. Simulation parameters are also listed in Table 1. The simulation sequence is as follows.
At t = 0.1 s, the voltage reference of port 1 is changed from 720 to 750. At t = 0.14 s, the voltage
reference of port 2 is changed from 780 to 750. At t = 0.18 s, the load of port 1 is increased from no
load to full load (7.5 kW) in a stepwise manner. At t = 0.22 s, the load of port 2 is also increased from
no load to full load (7.5 kW). At t = 0.26 s, full power is injected into the power grid through port 1
(−7.5 kW). At t = 0.3 s, full power is injected into the power grid through port 2 (−7.5 kW). It can be
seen that two SISO controllers hold each bipolar DC output voltage at a set point in all sequences.
In addition, the results indicate that interactions between their inputs and outputs are well suppressed.
Figure 13 shows the simulation waveform employed to verify the current sharing controller of the
DC/DC stage. In the simulation, the number of output parallel-connected TAB converters is limited
to two because of the computing burden. At t = 0.06 s, the improper load-sharing is caused by the
non-identical voltage sensors (difference up to 2%). Initially, improper load-sharing occurs, but soon
all load currents gradually converge to their average value. In addition, at a random timing, the load
of each port is increased from no load to full load and full power is injected into the DC-links through
Electronics 2018, 7, 62 12 of 19

TAB converters. It can be seen that the load sharing is good in all sequences after the current sharing
controller is activated.

Table 1. System parameters.

Parameter Symbol Value Unit


Number of subunits 10
Line inductance Lin 40 mH
DC capacitance in DC-link Clink 370 uF
Rated DC voltage of DC-link Vlink 2.2 kV
Switching frequency of the AC/DC stage f sw.rec 1.8 kHz
DC capacitance in LVDC Co 1 mF
Rated DC voltage of LVDC Vo ±750 V
Switching frequency of the DC/DC stage f sw.conv 10 kHz
HFIT turn ratio n 0.34
Interfacing inductance between MVDC and LVDC L0j 140 uH

Figure 11. Simulation waveform to verify the voltage balancing capability of the AC/DC stage.

Figure 12. Simulation waveform to verify the decoupling capability of the DC/DC stage.
Electronics 2018, 7, 62 13 of 19

Figure 13. Simulation waveform to verify the current sharing controller.

7. Experiment
In order to test the hardware and software beyond the numerical simulations, a 150 kW
single-phase 21-level SST prototype was designed and assembled, and is shown in Figure 14.
As mentioned in Section 2, the AC/DC stage was realized using an interfacing inductor and ten CHB
rectifiers to support the 13.2 kV MVAC. In the DC/DC stage, for application to bipolar DC distribution,
the HFIT coupled with three windings and the LVDC side is configured as a multi-terminal in which
two half-bridge circuits are connected in series. The outputs of DC/DC stage are connected in parallel,
and ten subunits have to be rated for only a fraction of the full power. The entire operation of the
SST system was programmed by DSP and CPLD processors. The AC/DC stage and DC/DC stage
have its own DSP and CPLD controllers. The required data between them is shared by CAN protocol.
The parameters adopted in both simulation and experiment are the same.

Figure 14. Single-phase 21-level SST prototype.


Electronics 2018, 7, 62 14 of 19

Figure 15 shows a waveform used to verify the DC-link voltage balancing capability of the AC/DC
stage. Due to the limitations of the measuring equipment, only Vdclink1 ∼Vdclink3 was measured by
the oscilloscope. The remaining voltage of DC-links was monitored via software such as LabVIEW
(Ver 13.0, National Instrument, Austin, TX, USA). It can be seen that the voltage of DC-links was
initially unbalanced due to finite tolerances in the power stage and control parameters when the
balancing controller was deactivated. However, the voltage of DC-links started converging to set point
after the balancing controller was activated. This indicates that the balancing controller works properly.

Figure 15. DC-link voltage waveform when balancing controller is activated.

The steady-state waveform of a TAB converter in several load conditions are depicted as follows.
Figure 16a shows a waveform when the TAB converter is operating under no load conditions.
Figure 16b shows a waveform when the amount of power transferred from port 1 to load is 7.5 kW,
while port 2 has no load. Figure 16c shows a waveform when the amount of power transferred
from port 2 to load is 7.5 kW, while port 1 has no load. Figure 16d shows a waveform when the
amount of power transferred from each port to load is 7.5 kW (total 15 kW, rated power of one
subunit). The TAB converter holds each bipolar DC output voltage at a set point in several load
conditions. In addition, the experimental voltage and current waveforms have a close match with the
aforementioned analysis in Section 4.
Figure 17 shows a waveform used to verify the decoupling capability of the TAB converter.
The loads of each port are changed in a stepwise manner at a random timing. Due to the limitation
of the load device, the load that is changed stepwise on each port is limited to a maximum of 20 kW.
It can be seen that the result indicates that interaction between each port is well suppressed.
The paralleling experiment performed to verify the current-sharing controller of the DC/DC
stage is as follows. The number of output parallel-connected TAB converters was ten. However,
there are two limitations to measure the waveforms at the laboratory level. First, only the output
currents of five subunits are measured in the oscilloscope due to the limitations of the measuring
equipment. The remaining output currents were monitored via software such as LabVIEW. Second,
due to the limitation of the load device, the amount of power transferred from the ten subunits to
loads was limited to 50 kW, which corresponds to 1/3 of the rated power. The rated operation of the
SST prototype will be verified later through a field test. Figure 18a,b show the current waveforms of
the bipolar DC/DC output stage (denoted as Io_1y , Io_2y , y is the subunit index, y = 1∼5). It can be
seen that all output currents remain balanced under various load conditions.
Electronics 2018, 7, 62 15 of 19

(a) (b)

(c) (d)

Figure 16. Steady-state waveform of a TAB converter: (a) under the no load condition; (b) when the
amount of power transferred from port 1 to load is 7.5 kW; (c) when the amount of power transferred
from port 2 to load is 7.5 kW; (d) when the amount of power transferred from each port to load is
7.5 kW.

Figure 17. The decoupling waveform of the TAB converter when the loads of each port are changed at
a random timing (n is the subunit index, n = 1∼10).
Electronics 2018, 7, 62 16 of 19

(a)

(b)

Figure 18. Current sharing waveforms: (a) output currents corresponding to Port 1; (b) output currents
corresponding to Port 2.

8. Conclusions
This paper presents the implementation of a single-phase 150 kW prototype of an SST for
application between a 13.2 kV MVAC network and a 750 V bipolar DC distribution. The prototype
of the SST has ten cascaded subunits in consideration of the device rating and MI. Each subunit
consists of an AC/DC stage and a DC/DC stage. In the AC/DC stage, a simple balancing controller is
provided to prevent the voltage imbalance of DC-links due to the cascade structure. In the DC/DC
stage, a simplified decoupling technique is provided to suppress the interaction between bipolar DC
outputs. A paralleling scheme to ensure proper load sharing is provided for the parallel-connected
DC/DC stage. In addition, the design of the HFIT to ensure high dielectric strength is discussed.
All algorithms were validated through simulations and experiments.

Author Contributions: All the authors gave equal contributions in writing and revising the paper.
Acknowledgments: This research was supported by the KEPCO research institute.
Conflicts of Interest: The authors declare no conflict of interest.
Electronics 2018, 7, 62 17 of 19

References
1. Agelidis, V.G.; Demetriades, G.D.; Flourentzou, N. Recent Advances in High-Voltage Direct-Current Power
Transmission Systems. In Proceedings of the 2006 IEEE International Conference on Industrial Technology,
Mumbai, India, 15–17 December 2006; pp. 206–213.
2. Blaabjerg, F.; Ma, K. Future on Power Electronics for Wind Turbine Systems. IEEE J. Emerg. Sel. Top.
Power Electron. 2013, 1, 139–152. [CrossRef]
3. Kouro, S.; Malinowski, M.; Gopakumar, K.; Pou, J.; Franquelo, L.G.; Wu, B.; Rodriguez, J.; Perez, M.A.;
Leon, J.I. Recent Advances and Industrial Applications of Multilevel Converters. IEEE Trans. Ind. Electron.
2010, 57, 2553–2580. [CrossRef]
4. Flourentzou, N.; Agelidis, V.G.; Demetriades, G.D. VSC-Based HVDC Power Transmission Systems:
An Overview. IEEE Trans. Power Electron. 2009, 24, 592–602. [CrossRef]
5. Hammons, T.J.; Woodford, D.; Loughtan, J.; Chamia, M.; Donahoe, J.; Povh, D.; Bisewski, B.; Long, W. Role of
HVDC transmission in future energy development. IEEE Power Eng. Rev. 2000, 20, 10–25. [CrossRef]
6. Rodriguez-Diaz, E.; Savaghebi, M.; Vasquez, J.C.; Guerrero, J.M. An overview of low voltage DC distribution
systems for residential applications. In Proceedings of the 2015 IEEE 5th International Conference on
Consumer Electronics—Berlin (ICCE-Berlin), Berlin, Germany, 6–9 September 2015; pp. 318–322.
7. She, X.; Burgos, R.; Wang, G.; Wang, F.; Huang, A.Q. Review of solid state transformer in the distribution
system: From components to field application. In Proceedings of the 2012 IEEE Energy Conversion Congress
and Exposition (ECCE), Raleigh, NC, USA, 15–20 September 2012; pp. 4077–4084.
8. She, X.; Huang, A. Solid state transformer in the future smart electrical system. In Proceedings of the 2013
IEEE Power Energy Society General Meeting, Vancouver, BC, Canada, 21–25 July 2013; pp. 1–5.
9. Bignucolo, F.; Bertoluzzo, M.; Fontana, C. Applications of the solid state transformer concept in the electrical
power system. In Proceedings of the 2015 AEIT International Annual Conference (AEIT), Naples, Italy,
14–16 October 2015; pp. 1–6.
10. Shah, D.G.; Crow, M.L. Stability Design Criteria for Distribution Systems With Solid-State Transformers.
IEEE Trans. Power Deliv. 2014, 29, 2588–2595. [CrossRef]
11. Wang, G.; Baek, S.; Elliott, J.; Kadavelugu, A.; Wang, F.; She, X.; Dutta, S.; Liu, Y.; Zhao, T.; Yao, W.; et al.
Design and hardware implementation of Gen-1 silicon based solid state transformer. In Proceedings of the
2011 Twenty-Sixth Annual IEEE Applied Power Electronics Conference and Exposition (APEC), Fort Worth,
TX, USA, 6–11 March 2011; pp. 1344–1349.
12. Bifaretti, S.; Zanchetta, P.; Watson, A.; Tarisciotti, L.; Clare, J.C. Advanced Power Electronic Conversion and
Control System for Universal and Flexible Power Management. IEEE Trans. Smart Grid 2011, 2, 231–243.
[CrossRef]
13. Zhao, C.; Dujic, D.; Mester, A.; Steinke, J.K.; Weiss, M.; Lewdeni-Schmid, S.; Chaudhuri, T.; Stefanutti,
P. Power Electronic Traction Transformer-Medium Voltage Prototype. IEEE Trans. Ind. Electron. 2014,
61, 3257–3268. [CrossRef]
14. Dujic, D.; Zhao, C.; Mester, A.; Steinke, J.K.; Weiss, M.; Lewdeni-Schmid, S.; Chaudhuri, T.; Stefanutti, P.
Power Electronic Traction Transformer-Low Voltage Prototype. IEEE Trans. Power Electron. 2013, 28, 5522–5534.
[CrossRef]
15. Zhao, C.; Weiss, M.; Mester, A.; Lewdeni-Schmid, S.; Dujic, D.; Steinke, J.K.; Chaudhuri, T. Power electronic
transformer (PET) converter: Design of a 1.2 MW demonstrator for traction applications. In Proceedings of
the International Symposium on Power Electronics Power Electronics, Electrical Drives, Automation and
Motion, Sorrento, Italy, 20–22 June 2012; pp. 855–860.
16. Cecati, C.; Dell’Aquila, A.; Liserre, M.; Monopoli, V.G. A passivity-based multilevel active rectifier with
adaptive compensation for traction applications. IEEE Trans. Ind. Appl. 2013, 39, 1404–1413. [CrossRef]
17. Liu, Y.; Huang, A.Q.; Song, W.; Bhattacharya, S.; Tan, G. Small-Signal Model-Based Control Strategy for
Balancing Individual DC Capacitor Voltages in Cascade Multilevel Inverter-Based STATCOM. IEEE Trans.
Ind. Electron. 2009, 56, 2259–2269. [CrossRef]
18. Dell’Aquila, A.; Liserre, M.; Monopoli, V.G.; Rotondo, P. An energy-based control for an n-H-bridges
multilevel active rectifier. IEEE Trans. Ind. Electron. 2005, 52, 670–678. [CrossRef]
Electronics 2018, 7, 62 18 of 19

19. Zhao, T.; Wang, G.; Zeng, J.; Dutta, S.; Bhattacharya, S.; Huang, A.Q. Voltage and power balance control
for a cascaded multilevel solid state transformer. In Proceedings of the 2010 Twenty-Fifth Annual IEEE
Applied Power Electronics Conference and Exposition (APEC), Palm Springs, CA, USA, 21–25 February 2010;
pp. 761–767.
20. Zhao, T.; Wang, G.; Bhattacharya, S.; Huang, A.Q. Voltage and Power Balance Control for a Cascaded
H-Bridge Converter-Based Solid-State Transformer. IEEE Trans. Power Electron. 2013, 28, 1523–1532.
[CrossRef]
21. Barrena, J.A.; Marroyo, L.; Vidal, M.Á.R.; Apraiz, J.R.T. Individual Voltage Balancing Strategy for PWM
Cascaded H-Bridge Converter-Based STATCOM. IEEE Trans. Ind. Electron. 2008, 55, 21–29. [CrossRef]
22. She, X.; Huang, A.Q.; Zhao, T.; Wang, G. Coupling Effect Reduction of a Voltage-Balancing Controller in
Single-Phase Cascaded Multilevel Converters. IEEE Trans. Power Electron. 2012, 27, 3530–3543. [CrossRef]
23. Wang, H.; Cheng, Q.; Li, M.; Chen, G.; Deng, L. The study of single-phase PWM rectifier based on PR control
strategy. In Proceedings of the 26th Chinese Control and Decision Conference (2014 CCDC), Changsha,
China, 31 May–2 June 2014; pp. 3818–3823.
24. Park, Y.M.; Yoo, J.Y.; Lee, S.B. Practical Implementation of PWM Synchronization and Phase-Shift Method
for Cascaded H-Bridge Multilevel Inverters Based on a Standard Serial Communication Protocol. IEEE Trans.
Ind. Appl. 2008, 44, 634–643. [CrossRef]
25. Kheraluwala, M.N.; Gascoigne, R.W.; Divan, D.M.; Baumann, E.D. Performance characterization of a
high-power dual active bridge DC-to-DC converter. IEEE Trans. Ind. Appl. 1992, 28, 1294–1301. [CrossRef]
26. Zhao, B.; Song, Q.; Liu, W.; Sun, Y. Overview of Dual-Active-Bridge Isolated Bidirectional DC-DC Converter
for High-Frequency-Link Power-Conversion System. IEEE Trans. Power Electron. 2014, 29, 4091–4106.
[CrossRef]
27. Bhattacharya, S.; Zhao, T.; Wang, G.; Dutta, S.; Baek, S.; Du, Y.; Parkhideh, B.; Zhou, X.; Huang, A.Q.
Design and development of Generation-I silicon based Solid State Transformer. In Proceedings of the 2010
Twenty-Fifth Annual IEEE Applied Power Electronics Conference and Exposition (APEC), Palm Springs,
CA, USA, 21–25 February 2010; pp. 1666–1673.
28. Engel, S.P.; Stieneker, M.; Soltau, N.; Rabiee, S.; Stagge, H.; de Doncker, R.W. Comparison of the Modular
Multilevel DC Converter and the Dual-Active Bridge Converter for Power Conversion in HVDC and MVDC
Grids. IEEE Trans. Power Electron. 2015, 30, 124–137. [CrossRef]
29. Da Silva, M.M.; Pinheiro, H. Voltage balancing in flying capacitor converter multilevel using space vector
modulation. In Proceedings of the 2017 IEEE 8th International Symposium on Power Electronics for
Distributed Generation Systems (PEDG), Florianopolis, Brazil, 17–20 April 2017; pp. 1–5.
30. Zhao, C.; Round, S.D.; Kolar, J.W. An Isolated Three-Port Bidirectional DC-DC Converter With Decoupled
Power Flow Management. IEEE Trans. Power Electron. 2008, 23, 2443–2453. [CrossRef]
31. Baek, S.; Roy, S.; Bhattacharya, S.; Kim, S. Power flow analysis for 3-port 3-phase dual active bridge dc/dc
converter and design validation using high frequency planar transformer. In Proceedings of the 2013 IEEE
Energy Conversion Congress and Exposition, Denver, CO, USA, 15–19 September 2013; pp. 388–395.
32. De Doncker, R.W.A.A.; Divan, D.M.; Kheraluwala, M.H. A three-phase soft-switched high-power-density
DC/DC converter for high-power applications. IEEE Trans. Ind. Appl. 1991, 27, 63–73. [CrossRef]
33. Zhang, Z.; Andersen, M.A.E. High frequency AC inductor analysis and design for dual active bridge (DAB)
converters. In Proceedings of the 2016 IEEE Applied Power Electronics Conference and Exposition (APEC),
Long Beach, CA, USA, 20–24 March 2016; pp. 1090–1095.
34. Shah, M.; Ngo, K.D.T. Parameter extraction for the extended cantilever model of magnetic component
windings. IEEE Trans. Aerosp. Electron. Syst. 2000, 36, 260–266. [CrossRef]
35. Moonem, M.; Pechacek, C.; Hemandez, R.; Krishnaswami, H. Analysis of a Multilevel Dual Active Bridge
(ML-DAB) DC-DC Converter Using Symmetric Modulation. Electronics 2015, 4, 239–260. [CrossRef]
36. Moonem, M.A.; Krishnaswami, H. Analysis and control of multi-level dual active bridge DC-DC converter.
In Proceedings of the 2012 IEEE Energy Conversion Congress and Exposition (ECCE), Raleigh, NC, USA,
15–20 September 2012; pp. 1556–1561.
37. Wu, Z.; Xue, Y.; Pan, L.; Li, D.; He, T.; Sun, L.; Yang, Y. Active disturbance rejection control based simplified
decoupling for two-input-two-output processes. In Proceedings of the 2017 36th Chinese Control Conference
(CCC), Dalian, China, 26–28 July 2017; pp. 399–404.
Electronics 2018, 7, 62 19 of 19

38. Vasanthakumar, D.; Srikanth, V. DC-DC converter control using IP controller. In Proceedings of the 2014
International Conference on Computation of Power, Energy, Information and Communication (ICCPEIC),
Chennai, India, 16–17 April 2014; pp. 245–249.
39. Segaran, D.; Holmes, D.G.; McGrath, B.P. Enhanced Load Step Response for a Bidirectional DC-DC Converter.
IEEE Trans. Power Electron. 2013, 28, 371–379. [CrossRef]
40. Huang, Y.; Tse, C.K. Circuit Theoretic Classification of Parallel Connected DC-DC Converters. IEEE Trans.
Circuits Syst. I Regul. Pap. 2007, 54, 1099–1108. [CrossRef]
41. Luo, S.; Ye, Z.; Lin, Ra.; Lee, F.C. A classification and evaluation of paralleling methods for power supply
modules. In Proceedings of the 30th Annual IEEE Power Electronics Specialists Conference, Charleston, SC,
USA, 1 July 1999; pp. 901–908.
42. Du, S.B.Y.; Wang, G.; Bhattacharya, S. Design considerations of high voltage and high frequency transformer
for solid state transformer application. In Proceedings of the IECON 2010–36th Annual Conference on IEEE
Industrial Electronics Society, Glendale, AZ, USA, 7–10 November 2010; pp. 421–426.
43. IEEE Standard for General Requirements for Dry-Type Distribution and Power Transformers; IEEE Std
C57.12.01-2015 (Revision of IEEE Std C57.12.01-2005); IEEE: Piscataway, NJ, USA, 2015; pp. 1–52.
44. Schwodiauer, R.; Neugschwandtner, G.; Bauer-Gogonea, S.; Bauer, S.; Heitz, J.; Bauerle, D. Dielectric and
electret properties of novel Teflon PTFE and PTFE-like polymers. In Proceedings of the10th International
Symposium on Electrets (ISE 10), Athens, Greece, 22–24 September 1999; pp. 313–316.
45. Dowcorning. Sylgard 170 Silicone Elastomer. In Sylgard Datasheet; Dowcorning: Midland, MI, USA, 2015.

c 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).

You might also like